Vous êtes sur la page 1sur 6

2RMLG Test Blocks

For internal use only / Siemens


Protection
AG 2009.
noticeAll
/ Copyright
rights reserved.
notice
2RMLG Test Blocks

Allows monitoring and secondary injection testing of


protection schemes
Usually panel mounted alongside Relay to be tested
No need to disturb wiring on Relay terminals
Re-designed RMLG to use Epsilon E2 enclosure

14 spring loaded normally-closed


contacts linked to pairs of terminals on
rear terminal block

Insertion of RMLB test plugs open


contacts and break connection
between terminal pairs

Protection notice / Copyright notice


Page 2 Jul-12 Mike Holden Reyrolle Protection Devices
RMLB Test Plugs

RMLB 01, 07 and 08 are multi-fingered test


plugs

Once spring loaded contacts have been


opened, plug-in leads allow direct connection
to rear terminals or shorting of contacts

CB SECONDARY CONNECTIONS MUST


BE SHORT-CIRCUITED ON TEST PLUG

RMLB 02 is single fingered test plug


available for monitoring current flow
through individual pair of terminals

Protection notice / Copyright notice


Page 3 Jul-12 Mike Holden Reyrolle Protection Devices
Typical Connections
2RMLG 01 / 2RMLG 02 Test Socket and RMLB 01 Test Plug

RMLB 01 TEST PLUG


(FRONT VIEW)

* 2RMLG 01 has a metallic probe attached to the front cover assembly


which when withdrawn open circuits the 2 contacts at position 13 and 14

Protection notice / Copyright notice


Page 4 Jul-12 Mike Holden Reyrolle Protection Devices
Typical Connections
2RMLG 07 Test Socket and RMLB 07 Test Plug

Protection notice / Copyright notice


Page 5 Jul-12 Mike Holden Reyrolle Protection Devices
Typical Connections
2RMLG 08 Test Socket and RMLB 08 Test Plug

Protection notice / Copyright notice


Page 6 Jul-12 Mike Holden Reyrolle Protection Devices