Académique Documents
Professionnel Documents
Culture Documents
and Maintenance
SAFETY WARNING
Only qualified personnel should install and service the equipment. The installation, starting up, and
servicing of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific
knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could
result in death or serious injury. When working on the equipment, observe all precautions in the literature
and on the tags, stickers, and labels that are attached to the equipment.
Important
Environmental Concerns!
Scientific research has shown that certain man-made
WARNING
chemicals can affect the earths naturally occurring Personal Protective Equipment (PPE)
stratospheric ozone layer when released to the Required!
atmosphere. In particular, several of the identified
Installing/servicing this unit could result in exposure to
chemicals that may affect the ozone layer are refrigerants electrical, mechanical and chemical hazards.
that contain Chlorine, Fluorine and Carbon (CFCs) and
those containing Hydrogen, Chlorine, Fluorine and Before installing/servicing this unit, technicians
Carbon (HCFCs). Not all refrigerants containing these MUST put on all Personal Protective Equipment (PPE)
compounds have the same potential impact to the recommended for the work being undertaken.
environment.Trane advocates the responsible handling of ALWAYS refer to appropriate MSDS sheets and OSHA
all refrigerants-including industry replacements for CFCs guidelines for proper PPE.
such as HCFCs and HFCs. When working with or around hazardous chemicals,
ALWAYS refer to the appropriate MSDS sheets and
Responsible Refrigerant Practices! OSHA guidelines for information on allowable
Trane believes that responsible refrigerant practices are personal exposure levels, proper respiratory
important to the environment, our customers, and the air protection and handling recommendations.
conditioning industry. All technicians who handle
If there is a risk of arc or flash, technicians MUST put
refrigerants must be certified.The Federal Clean Air Act
on all Personal Protective Equipment (PPE) in
(Section 608) sets forth the requirements for handling,
accordance with NFPA 70E or other country-specific
reclaiming, recovering and recycling of certain
requirements for arc flash protection, PRIOR to
refrigerants and the equipment that is used in these
servicing the unit.
service procedures. In addition, some states or
municipalities may have additional requirements that Failure to follow recommendations could result in death
or serious injury.
WARNING
Hazardous Service Procedures!
The maintenance and troubleshooting procedures
recommended in this manual could result in exposure
to electrical, mechanical or other potential safety
hazards. Always refer to the safety warnings provided
throughout this manual concerning these procedures.
Unless specified otherwise, disconnect all electrical
power including remote disconnect and discharge all
energy storing devices such as capacitors before
servicing. Follow proper lockout/tagout procedures to
ensure the power can not be inadvertently energized.
When necessary to work with live electrical
components, have a qualified licensed electrician or
other individual who has been trained in handling live
electrical components perform these tasks. Failure to
follow all of the recommended safety warnings
provided, could result in death or serious injury.
Introduction
Overview
This manual covers the installation, operation and
maintenance of the CGAM units.
Revision Summary
CG-SVX17E-EN
The following points describe the changes to this revision
of the manual:
High ambient option added
Copper fin option added
Seismically rated isolator option added
No Freeze Protection option added
Pump package option pressure drop information
revised
Maximum loop volume for pump package expansion
tank added
Diagnostics tables updated
Trademarks
Trane, CompleteCoat,Tracer and theTrane logo are
trademarks ofTrane in the United States and other
countries. All trademarks referenced in this document are
the trademarks of their respective owners.
CG-SVX17E-EN 3
4 CG-SVX17E-EN
CG-SVX17E-EN 5
The unit nameplate provides the following information: Model Number Coding System
Unit model and size descriptor.
The model numbers for the unit and the compressors are
Unit serial number. comprised of numbers and letter which represent features
Identifies unit electrical requirements. of the equipment.
Lists correct operating charges of R-410A and See Unit Model Number Description, p. 7 and
refrigerant oil. Compressor Model Number Description, p. 8 for details.
Lists unit design pressures. Each position, or group of positions, in a number or letter
Identifies installation, operation and maintenance and is used to represent a feature. For example, from the chart,
service data literature. we can determine that the letter F in digit 8 of the unit
model number indicates unit voltage is 460/60/3.
Lists drawing numbers for unit wiring diagrams.
6 CG-SVX17E-EN
CG-SVX17E-EN 7
8 CG-SVX17E-EN
CG-SVX17E-EN 9
Accessory/Options Information
Figure 6. V 40-70 ton - ship with location - isolator and
Check all the accessories and loose parts which are prop rod
shipped with the unit against the original order. Included
in these items will be water vessel drain plugs, rigging
diagrams, electrical diagrams, and service literature,
which are placed inside the control panel and/or starter
panel for shipment. Also check for optional components,
such as isolators.
The unit isolators and fan prop rod ship on brackets
attached to the frame of the unit.The location varies by
unit tonnage.The following figures show the location of
these ship with items for the different sizes.
Elastomeric
Isolators Prop Rod
Elastomeric
solators
Prop Rod
Seismic Isolators
Seismic Isolators
10 CG-SVX17E-EN
Prop Rod
Elastomeric Isolators
Seismic Isolators
CG-SVX17E-EN 11
General Data
12 CG-SVX17E-EN
CG-SVX17E-EN 13
14 CG-SVX17E-EN
CG-SVX17E-EN 15
Fan
Control
panel Chilled water
84.7 in inlet
(2151 mm)
1 More clearance may be needed for airflow Total of four mounting locations.
depending on the installation.
CG-SVX17E-EN 17
Fan
Control
panel Chilled water
84.7 in inlet
(2151 mm)
Compressor
Wire 20.3 in (516 mm)
connection
9.7 in (246 mm)
21.3 in (541 mm)
50.4 in Chilled water 16.9 in
(1279 mm) 128.4 in (3263 mm) outlet (429 mm)
149.8 in (3804 mm)
Figure 11. CGAM 30 and 35 ton - service clearances and mounting locations
1 More clearance may be needed for airflow Total of four mounting locations.
depending on the installation.
18 CG-SVX17E-EN
Wire
Control panel Fan Compressor
connection
Chilled water
84.8 in inlet
(2155 mm)
Chilled water
outlet
25.8 in
(656 mm)
Note: When facing the control panel, circuit 1 is on the right side of unit.
Figure 13. CGAM 40 and 52 ton- service clearances and mounting locations
85.4 in
(2164 mm) Chilled water
Door
swing connection side
Control
panel side
1 More clearance may be needed for airflow Total of four mounting locations.
depending on the installation.
CG-SVX17E-EN 19
Chilled water
inlet
84.8 in
(2155 mm) Chilled water
outlet
31.1 in
(790 mm)
7.9 in
23.8 in (603 mm)
88.4 in 125.8 in (3196 mm) (199 mm)
(2245 mm)
149.8 in (3804 mm) 14.4 in
(367 mm)
The number of fans shown does not represent Water connections are even with unit end.
the number of fans installed.
Note: When facing the control panel, circuit 1 is on the right side of unit.
Figure 15. CGAM 60 and 70 ton - service clearances and mounting locations
85.4 in
(2169 mm)
Door Chilled water
swing Control connection side
panel side
20 CG-SVX17E-EN
Fan Compressor
Chilled water
92.6 in inlet
Control (2352 mm)
panel Chilled water
outlet
Wire
connection
31.1 in (790 mm)
29.6 in (751 mm) 7.9 in (200 mm)
88.9 in
(2257 mm)
89.2 in (2265 mm)
Note: When facing the control panel, circuit 1 is on the right side of unit.
Figure 17. CGAM 80 and 90 ton - service clearances and mounting locations
CG-SVX17E-EN 21
Fan Compressor
Chilled water
92.5 in inlet
Control (2349 mm)
panel Chilled water
outlet
Wire
connection 31.1 in
(790 mm)
29.6 in (751 mm)
88.9 in
(2257 mm) 11.5 in 7.9 in
111.7 in (2837 mm) (292 mm) (199 mm)
165.9 in (4214 mm)
Water connections are 5.4 in (139 mm)
The number of fans shown does not represent the
from unit end.
number of fans installed.
Note: When facing the control panel, circuit 1 is on the right side of unit.
Figure 19. CGAM 100, 110 and 120 ton- service clearances and mounting locations
85.9 in
Door (2181 mm) Chilled water
swing connection side
Control
panel side
1 More clearance may be needed for airflow Total of six mounting locations.
depending on the installation.
22 CG-SVX17E-EN
Compressor Fan
Chilled water
inlet
Control 92.5 in
Panel (2349 mm) Chilled water
outlet
31.1 in
Wire (790 mm)
Connection
Note: When facing the control panel, circuit 1 is on the right side of unit.
Figure 21. CGAM 130 ton- service clearances and mounting locations
85.2in
Door (2174 mm) Chilled water
Swing connection side
Control
panel side
CG-SVX17E-EN 23
Unit Dimensions - Optional Pump Package, Buffer Tank, Partial Heat Recovery
Figure 22. Sizes 20 and 26 ton pump package, buffer tank, partial heat recovery
Fan
Control Panel
84.7 in
(2151 mm)
Pump Package
Wire BufferTank
Connection
Compressor
Pump Package
VFD 20.8 in (529 mm)
Figure 23. Sizes 30 and 35 ton pump package, buffer tank, partial heat recovery
Fan
Control Panel
84.7 in
(2151 mm)
Pump Package
Wire BufferTank
Connection
Compressor
Pump Package
VFD 21.0 in (534 mm)
Lifting
Locations 128.2 in (3256 mm)
50.6 in
(1285 mm)
150.0 in (3809 mm)
170.0 in (4318 mm)
24 CG-SVX17E-EN
Figure 24. Sizes 40 and 52 ton pump package, buffer tank, partial heat recovery
Pump 84.8 in
Package (2155 mm)
VFD
Figure 25. Sizes 60 and 70 ton pump package, buffer tank, partial heat recovery
Pump 84.8 in
Package (2155 mm)
VFD
Lifting
23.7 in (602 mm)
88.6 in (2250 mm) Locations
125.8 in (3196 mm)
150.4 in (3820 mm)
170.7 in (4336 mm)
CG-SVX17E-EN 25
Figure 26. Sizes 80 and 90 ton pump package, buffer tank, partial heat recovery
Fan
Compressors
Buffer Tank
Control
Panel
92 in (2337 mm)
Pump Package
Wire
Connection
Figure 27. Sizes 100, 110 and 120 ton pump package, buffer tank, partial heat recovery
Fan
Compressors
Buffer Tank
Control
Panel
92 in (2337 mm)
Pump Package
Wire
Connection
26 CG-SVX17E-EN
Figure 28. Size 130 ton pump package, buffer tank, partial heat recovery
Control Panel
92 in (2337 mm)
Wire
Connection
CG-SVX17E-EN 27
Pump Package, Partial Heat Recover and Buffer Tank - Water Connections
Figure 29. CGAM 20 and 26 ton - pump package, buffer tank, partial heat recovery unit water connections
Chilled Chilled
water water
inlet outlet
Chilled
water outlet 15.2 in
12.8 in (385 mm)
(325 mm)
22.4 in 22 in
9.7 in (569 mm) (559 mm) 6.9 in
(246 mm)
Chilled (176mm)
water 12.5 in (317 mm) 20.9 in Heating 67.4 in (1712 mm)
inlet (531mm) outlet Heating
39.8 in 29.8 in inlet
(1011 mm) (757 mm)
Water connections are recessed Partial heat recovery connections are even with unit edge.
1.3 in (33 mm) from unit end. Water connections are recessed
from unit end. The chilled water inlet and outlet connections are the same
Outlet is 14.8 in (377 mm) and as the standard unit unless pump package or buffer tank
inlet is 0.3 in (7.8 mm) are ordered.
Figure 30. CGAM 30 and 35 ton - pump package, buffer tank, partial heat recovery unit water connections
Chilled Chilled
water water
inlet outlet
Chilled
water outlet 15.2 in
12.9 in (385 mm)
(327 mm)
22.2 in 22 in
9.7 in (564 mm) (559 mm) 7.2 in
(246 mm)
Chilled (182mm)
water 12.3 in (313 mm) 20.9 in Heating 67.4 in (1712 mm)
inlet (531mm) outlet Heating
39.9 in 29.8 in inlet
(1012 mm) (757 mm)
Water connections are recessed Partial heat recovery connections are even with unit edge.
1.3 in (33 mm) from unit end. Water connections are recessed
from unit end. The chilled water inlet and outlet connections are the same
Outlet is 14.8 in (377 mm) and as the standard unit unless pump package or buffer tank
inlet is 0.3 in (7.8 mm) are ordered.
28 CG-SVX17E-EN
Figure 31. CGAM 40 and 52 ton- pump package, buffer tank, partial heat recovery unit water connections
Chilled
Chilled water water
inlet inlet
Chilled
Chilled water
outlet water
outlet 54.8in
(1392mm)
19.7in 19.7in
19.7in (500mm) (500mm) 45.4in
9.2 in (499mm) (1153mm)
(474mm) 18.7in
(234mm) 18.7in (474 mm)
70.4 in (1788 mm)
66.8 in (1696 mm) 44.2in
(1122mm)
Water inlet connect is even with unit end,
outlet is recessed 14.8 in (376 mm) from unit end.
Water outlet connection is even with unit end, Partial heat recovery connections are even with unit end.
inlet is 6.1 in (154 mm) from unit end. The chilled water connections are the same as the standard
unit unless pump package or buffer tank are ordered.
Figure 32. CGAM 60 and 70 ton- pump package, buffer tank, partial heat recovery unit water connections
Chilled
Chilled water water
inlet inlet
Chilled
Chilled water
outlet water
outlet 55.2in
(1402mm)
19.7in 19.7in
19.7in (500mm) (500mm) 45.6in
9.2 in (499mm) (1158mm)
(474mm) 18.7in
(234mm) 18.7in (474 mm)
70.4 in (1788 mm)
66.8 in (1696 mm) 44.2in
(1122mm)
Water inlet connect is even with unit end,
outlet is recessed 14.8 in (376 mm) from unit end.
Water outlet connection is even with unit end, Partial heat recovery connections are even with unit end.
inlet is 6.1 in (154 mm) from unit end. The chilled water connections are the same as the standard
unit unless pump package or buffer tank are ordered.
CG-SVX17E-EN 29
Figure 33. CGAM 80 and 120 ton- pump package, buffer tank, partial heat recovery unit water connections
Pump Package
(with or without buffer tanks) Partial Heat Recovery
Chilled water
11.5 in (292 mm)
outlet
Water connections are .7 in (18 mm) from unit end.
22.6 in (575 mm)
Water connections are 5.9 in (151 mm) from unit end.
Figure 34. CGAM 130 ton- pump package unit water connections
Pump Package
(with or without buffer tanks) Partial Heat Recovery
Chilled water
11.5 in (292 mm)
outlet
22.6 in (575 mm) Water connections are .7 in (18 mm) from unit end.
30 CG-SVX17E-EN
Weights
Table 5. Weights - 60 Hz
Base Unit Base Unit Base Unit Partial Heat
Without Pump With Pump With Pump and Buffer Tank Recovery - add
Copper -
Tons
Shipping Operating Shipping Operating Shipping Operating Shipping Operating add
lb kg lb kg lb kg lb kg lb kg lb kg lb kg lb kg lb kg
20 2185 991 2207 1002 2726 1236 2814 1277 3253 1475 3964 1799 39 18 24 11 258 117
26 2249 1020 2278 1034 2790 1265 2891 1311 3317 1504 4035 1830 39 8 31 14 258 117
30 2846 1291 2879 1306 3388 1537 3496 1586 3915 1776 4636 2103 47 21 36 16 360 163
35 2878 1305 2919 1325 3420 1551 3545 1608 3947 1790 4676 2121 47 21 44 20 360 163
40 3666 1663 3696 1677 4285 1944 4382 1988 4876 2212 5524 2506 94 43 34 15 515 234
52 3761 1706 3805 1726 4379 1986 4505 2044 4970 2254 5633 2555 94 43 49 22 515 234
60 4978 2258 5032 2283 5814 2637 5984 2715 6405 2905 7102 3222 111 50 59 27 719 326
70 5045 2289 5119 2323 5881 2668 6092 2764 6472 2936 7190 3262 111 50 80 36 719 326
80 5607 2543 5691 2582 6486 2942 6788 3080 7077 3210 7969 3615 170 77 90 41 1270 576
90 5859 2658 5959 2704 6738 3056 7073 3209 7329 3324 8237 3737 170 77 109 49 1270 576
100 6646 3015 6757 3066 7549 3424 7907 3587 8265 3749 9419 4273 178 81 120 54 1511 686
110 6724 3050 6844 3105 7627 3460 8003 3631 8343 3785 9506 4313 178 81 129 59 1511 686
120 6762 3067 6882 3122 8018 3637 8393 3808 8734 3962 9896 4490 178 81 131 60 1511 686
130 7753 3517 7898 3583 9006 4085 9427 4277 9722 4410 10905 4947 178 81 156 71 1889 857
Notes:
1. Weights based on aluminum fins, refrigerant charge, isolators, circuit breakers and louvers.
2. Base unit weights are shown above on the left side for units without a pump package, units with a pump package and units with both pump package
buffer tank options. The partial heat recovery and copper weights are in addition to the base unit weights.
3. All weights 3%.
Table 6. Weights - 50 Hz
Base Unit Partial Heat Recovery - add
Tons Shipping Operating Shipping Operating Copper - add
lb kg lb kg lb kg lb kg lb kg
20 2187 992 2209 1002 39 18 24 11 258 117
26 2249 1020 2278 1034 39 18 31 14 258 117
30 2845 1291 2879 1306 47 21 36 16 360 163
35 2877 1305 2919 1325 47 21 44 20 360 163
40 3665 1663 3696 1677 94 43 34 15 515 234
52 3760 1706 3805 1726 94 43 48 22 515 234
60 4977 2258 5032 2283 111 50 59 27 719 326
70 5044 2289 5119 2323 111 50 79 36 719 326
80 5606 2543 5691 2582 170 77 90 41 1270 576
90 5857 2657 5958 2703 170 77 107 49 1270 576
100 6628 3007 6741 3059 178 81 118 54 1511 686
110 6711 3045 6833 3100 178 81 129 59 1511 686
120 6756 3065 6878 3121 178 81 129 59 1511 686
Notes:
1. Weights based on aluminum fins, refrigerant charge, isolators, circuit breakers and louvers.
2. The partial heat recovery and copper weights are in addition to the base unit weights.
3. All weights 3%.
CG-SVX17E-EN 31
Provide enough space around the unit to allow the Important: The center of gravity (CG) is never at the
installation and maintenance personnel unrestricted midpoint of the base rail lifting strap holes.
access to all service points. Refer to submittal drawings for A level unit lift is required for a safe lift and
the unit dimensions, to provide sufficient clearance for the to prevent unit damage.
opening of control panel doors and unit service. Refer to Lifting a unit with equal length straps will NOT produce a
the chapter on Unit Dimensions/Weights for minimum level unit during the lift because the CG will not be at the
clearances. In all cases, local codes which require midpoint between the base lifting holes.The following
additional clearances will take precedence over these adjustments must be made to produce a level lift:
recommendations.
Single spreader bar lifting method
If the unit CG is closer to the control panel, the
Rigging straps on the control panel side of the spreader bar
Refer to Unit Dimensions/Weights section for typical unit must be adjusted to be shorter than those on the
lifting weights. Refer to the rigging label attached to the opposite side of the spreader bar, allowing the
unit for further details. spreader bar to move toward the control panel and
over the unit CG. Several adjustments of the strap
length may be required to produce a level unit
during lift.
H-type spreader bar lifting method
If the straps from the H bar to the unit base are the
same length, the crane lifting point on the center
web of the H bar must be adjusted to produce a level
unit lift. See Figure 35, p. 33 for illustration.
32 CG-SVX17E-EN
Figure 35. H-type spreader bar adjustment for level unit Figure 37. CGAM V 40-70 Ton Rigging
lift
Lifting Straps to unit base Figure 38. CGAM W 80-130 Ton Rigging
Y
X
CG-SVX17E-EN 33
34 CG-SVX17E-EN
CG-SVX17E-EN 35
W
D Table 10. CGAM seismically rated isolator
C
36 CG-SVX17E-EN
Figure 40. MSSH seismically rated isolator Figure 41. M2SS seismically rated isolator
1 1/2 11 1/4
8 1 1/8 5/8 EQUIPMENT
5/8 EQUIPMENT CLAMP DOWN NUT
13/16 DIA HOLE FOR
CLAMP DOWN NUT
ATTACHMENT TO 13/16 DIA HOLE FOR
CONCRETE (4 TYP) ATTACHMENT TO
CONCRETE (4 TYP)
2 1/4
2 1/4 (BASE PLATE) 6 1/4
3/4 DIA HOLE FOR
2
6 1/4 ATTACHMENT TO
STEEL (4 TYP)
(VIEW CUT AWAY FOR CLAR
2 7/8
(BASE PLATE)
3/4 DIA HOLE FOR
2 7/8 7/8
ATTACHMENT TO
STEEL (4 TYP)
7/8 (VIEW CUT AWAY FOR CLARITY
7 1/8
1 1/2 7 1/4
CUSTOMER
STEEL SHIM EQUIPMENT CUSTOMER STEEL SHIM
ELASTOMERIC 5/8 ADJUSTING NUT
(REMOVE AFTER EQUIPMENT (REMOVE AFTER
5/8 ADJUSTING (2 TYP)
SPRING ADJUSTMENT) SNUBBER 3/8 GAP SPRING ADJUSTMENT)
NUT
3/8 GAP ELASTOMERIC
SNUBBER
1/4 - 3/8
1/4 - 3/8
PVC
PVC 7 1/4
BUSHING
FREE &
BUSHING TOP
OPERATING
HEIGHT COMPRESSION CUP
8
TOP (2 TYP)
FREE &
OPERATING COMPRESSION ELASTOMERIC
HEIGHT CUP CUP
ELASTOMERIC
CUP 14 1/4
4 3/4
CUSTOMER
10 1/4 EQUIPMENT
(1/2)
CUSTOMER
EQUIPMENT
5 3/4
(3/8)
CG-SVX17E-EN 37
Screw
Nut
("F")
Washer
Doubler
G rail Plate
Isolator
("C") ("D") ("C")
(top
Figure 43. M2SS Seismic isolator installation reference panel)
("H")
("I") CUSTOMER
("A")
EQUIPMENT
("E") ("E")
("G") ("G")
GROMMET
Important: The following adjustment process can only
begin after the equipment or machine is at
1/4 - 3/8
its full operating weight.
WASHER
("F") 6. Back off each of the (2) or (4) limit stop locknuts (F) per
isolator 1/4-3/8.
7. Adjust each isolator in sequence by turning adjusting
nut(s) (G) one full clockwise turn at a time. Repeat this
procedure on all isolators, one at a time. check the limit
("H")
("B")
stop locknuts (F) periodically to ensure that clearance
("I") CUSTOMER
EQUIPMENT between the washer and rubber grommet is
("A")
("E")
maintained. Stop adjustment of an isolator only when
the top plate (A) has risen just above the shim (E).
8. Remove all spacer shims (E).
9. Fine adjust isolators to level equipment.
("F")
10. Adjust all limit stop locknuts (F) per isolator to obtain 3/
8 gap. the limit stop nuts must be kept at this 3/8 gap
to ensure uniform bolt loading during uplift.
38 CG-SVX17E-EN
4 4 6
Control Panel
2
Control Panel
2
1 3 1 3 5
4 6 8
Control Panel
1 3 5 7
Table 11. Elastomeric isolator locations - base unit - with or without partial heat recovery
Location
Size (ton) 1 2 3 4 5 6 7 8
RDP-3 RDP-3 RDP-3 RDP-3
20-26 - - - -
Grey 60 Grey 60 Grey 60 Grey 60
RDP-4 RDP-4 RDP-3 RDP-3
30-35 - - - -
Brown 61 Brown 61 Grey 60 Grey 60
RDP-4 RDP-4 RDP-4 RDP-4
40-52 - - - -
Red 62 Red 62 Red 62 Red 62
RDP-4 RDP-4 RDP-3 RDP-4 RDP-3 RDP-3
60-70 - -
Red 62 Red 62 Gray 60 Brown 61 Gray 60 Gray 60
RDP-4 RDP-4 RDP-4 RDP-4 RDP-3 RDP-3
80-120 - -
Red 62 Green 63 Red 62 Red 62 Gray 60 Gray 60
RDP-4 RDP-4 RDP-4 RDP-4 RDP-4 RDP-4 RDP-3 RDP-3
130
Red 62 Red 62 Red 62 Red 62 Red 62 Red 62 Grey 60 Grey 60
Table 12. Elastomeric isolator locations - with pump package- with or without partial heat recovery
Location
Size (ton) 1 2 3 4 5 6 7 8
RDP-3 RDP-3 RDP-3 RDP-3
20-26 - - - -
Brown 61 Grey 60 Grey 60 Grey 60
RDP-4 RDP-4 RDP-4 RDP-4
30-35 - - - -
Brown 61 Brown 61 Brown 61 Brown 61
RDP-4 RDP-4 RDP-4 RDP-4
40-52 - - - -
Red 62 Red 62 Red 62 Red 62
RDP-4 RDP-4 RDP-4 RDP-4 RDP-4 RDP-4
60-90 - -
Red 62 Red 62 Red 62 Red 62 Red 62 Red 62
RDP-4 RDP-4 RDP-4 RDP-4 RDP-4 RDP-4
100-120 - -
Green 63 Green 63 Green 63 Green 63 Green 63 Green 63
RDP-4 RDP-4 RDP-4 RDP-4 RDP-4 RDP-4 RDP-4 RDP-4
130
Red 62 Red 62 Red 62 Red 62 Red 62 Red 62 Red 62 Red 62
CG-SVX17E-EN 39
Table 13. Elastomeric isolator locations - with pump package and buffer tank option - with or without partial heat
recovery
Location
Size (ton) 1 2 3 4 5 6 7 8
RDP-3 RDP-3 RDP-4 RDP-4
20-35 - - - -
Grey 60 Grey 60 Green 63 Green 63
RDP-4 RDP-4 RDP-4 RDP-4
40-52 - - - -
Brown 61 Brown 61 Grey 64 Grey 64
RDP-4 RDP-4 RDP-4 RDP-4 RDP-4 RDP-4
60-70 - -
Brown 61 Brown 61 Green 63 Green 63 Green 63 Green 63
RDP-4 RDP-4 RDP-4 RDP-4 RDP-4 RDP-4
80-90 - -
Green 63 Green 63 Red 62 Red 62 Red 62 Red 62
RDP-4 RDP-4 RDP-4 RDP-4 RDP-4 RDP-4
100-120
Grey 64 Grey 64 Green 63 Green 63 Green 63 Green 63
RDP-4 RDP-4 RDP-4 RDP-4 RDP-4 RDP-4 RDP-4 RDP-4
130
Green 63 Green 63 Green 63 Green 63 Green 63 Green 63 Green 63 Green 63
Locations
Size
(ton) 1 2 3 4 5 6 7 8
MSSH-1E-825N MSSH-1E-825N MSSH-1E-530N MSSH-1E-530N
20
Red/Dk Blue Red/Dk Blue Black/Dk Blue Black/Dk Blue
MSSH-1E-1000 MSSH-1E-825N MSSH-1E-530N MSSH-1E-530N
26
Tan Red/Dk Blue Black/Dk Blue Black/Dk Blue
M2SS-1E-1300 M2SS-1E-1060N M2SS-1E-800 M2SS-1E-800
30
Red Black/Dk Blue Black Black
M2SS-1E-1300 M2SS-1E-1060N M2SS-1E-800 M2SS-1E-800
35
Red Black/Dk Blue Black Black
M2SS-1E-1300 M2SS-1E-1300 M2SS-1E-800 M2SS-1E-1060N
40
Red Red Black Black/Dk Blue
M2SS-1E-1300 M2SS-1E-1650N M2SS-1E-1060N M2SS-1E-1060N
52
Red Red/Dk Blue Black/Dk Blue Black/Dk Blue
M2SS-1E-
M2SS-1E-1650N M2SS-1E-1060N M2SS-1E-1060N M2SS-1E-800 M2SS-1E-800
60 1650N Red/Dk
Red/Dk Blue Black/Dk Blue Black/Dk Blue Black Black
Blue
M2SS-1E-
M2SS-1E-1650N M2SS-1E-1060N M2SS-1E-1060N M2SS-1E-800 M2SS-1E-800
70 1650N Red/Dk
Red/Dk Blue Black/Dk Blue Black/Dk Blue Black Black
Blue
M2SS-1E-2000 M2SS-1E-2000 M2SS-1E-1060N M2SS-1E-1300 M2SS-1E-800 M2SS-1E-800
80
Tan Tan Black/Dk Blue Red Black Black
M2SS-1E-2000 M2SS-1E-2000 M2SS-1E-1060N M2SS-1E-1650N M2SS-1E-800 M2SS-1E-800
90
Tan Tan Black/Dk Blue Red/Dk Blue Black Black
M2SS-1E-2000 M2SS-1E-2000 M2SS-1E-1300 M2SS-1E-1650N M2SS-1E-800 M2SS-1E-800
100
Tan Tan Red Red/Dk Blue Black Black
M2SS-1E-2000 M2SS-1E-2000 M2SS-1E-1300 M2SS-1E-1650N M2SS-1E-800 M2SS-1E-800
110
Tan Tan Red Red/Dk Blue Black Black
M2SS-1E-2000 M2SS-1E-2000 M2SS-1E-1300 M2SS-1E-2000 M2SS-1E-800 M2SS-1E-800
120
Tan Tan Red Tan Black Black
M2SS-1E-
M2SS-1E-1650N M2SS-1E-1300 M2SS-1E-1650N M2SS-1E-1060N M2SS-1E-1300 M2SS-1E-800 M2SS-1E-1060N
130 1650N Red/Dk
Red/Dk Blue Red Red/Dk Blue Black/Dk Blue Red Black Black/Dk Blue
Blue
40 CG-SVX17E-EN
Isolator location
Aluminum Fins Copper Fins
Size
(tons) 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8
Without partial heat recovery
20 706 645 408 365 - - - - 822 648 425 487 - - - -
26 792 614 369 420 - - - - 808 716 486 443 - - - -
30 887 858 627 425 - - - - 1027 882 673 574 - - - -
35 894 862 645 436 - - - - 1035 884 690 587 - - - -
40 1152 1036 611 811 - - - - 1198 1246 823 858 - - - -
52 1081 1156 714 769 - - - - 1210 1283 844 898 - - - -
60 1130 1198 771 821 493 527 - - 1252 1319 900 949 603 637 - -
70 1118 1210 781 849 511 558 - - 1239 1330 911 978 622 668 - -
80 1435 1662 774 886 396 449 - - 1796 1835 863 1203 581 594 - -
90 1508 1763 802 927 406 466 - - 1872 1931 888 1249 591 611 - -
100 1640 1587 847 1120 608 866 - - 1771 1993 1195 1342 886 995 - -
110 1673 1634 851 1134 602 863 - - 1803 2038 1200 1356 878 993 - -
120 1691 1651 854 1138 600 861 - - 1821 2055 1204 1360 876 990 - -
130 1284 1273 910 1229 861 852 569 826 1270 1749 1301 1197 990 1246 1009 933
With partial heat recovery
20 708 661 414 382 - - - - 773 713 482 453 - - - -
26 793 630 375 437 - - - - 752 789 550 402 - - - -
30 891 882 633 439 - - - - 1032 905 677 590 - - - -
35 955 829 593 507 - - - - 1041 908 694 603 - - - -
40 1062 1111 749 785 - - - - 1191 1239 879 914 - - - -
52 1073 1148 770 825 - - - - 1202 1276 900 954 - - - -
60 1111 1179 802 851 539 573 - - 1232 1299 931 980 650 683 - -
70 1098 1190 812 880 558 604 - - 1311 1280 917 895 600 858 - -
80 1529 1756 780 891 384 437 - - 1889 1926 872 1213 568 580 - -
90 1602 1858 808 933 394 454 - - 1966 2023 896 1260 577 596 - -
100 1732 1680 860 1138 596 848 - - 1862 2083 1213 1361 870 978 - -
110 1765 1726 864 1152 589 846 - - 1935 1895 1210 1775 830 810 - -
120 1784 1745 867 1156 588 843 - - 1953 1913 1214 1780 827 807 - -
130 1129 1587 1144 1072 855 803 589 812 1589 1476 1146 1605 938 1204 990 935
CG-SVX17E-EN 41
Isolator location
Aluminum Fins Copper Fins
Size
(tons) 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8
Without partial heat recovery
20 875 612 603 619 - - - - 802 803 809 552 - - - -
26 910 630 614 624 - - - - 834 825 823 555 - - - -
30 939 892 940 609 - - - - 1173 822 892 853 - - - -
35 946 897 958 620 - - - - 1182 824 908 866 - - - -
40 1214 1109 1009 932 - - - - 1336 1244 1146 1054 - - - -
52 1225 1146 1030 972 - - - - 1349 1279 1165 1096 - - - -
60 1275 1196 890 832 852 794 - - 1287 1340 1227 938 863 901 - -
70 1265 1209 897 855 870 829 - - 1292 1239 1233 1181 869 830 - -
80 1296 1663 922 1070 901 763 - - 1637 1812 1190 1307 927 1012 - -
90 1556 1616 816 1152 857 887 - - 1712 1910 1217 1349 934 1031 - -
100 1278 1684 1330 1175 1013 1226 - - 1562 1736 1653 1828 1162 1278 - -
110 1306 1733 1339 1189 1006 1221 - - 1594 1778 1661 1846 1152 1275 - -
120 1276 1623 1280 1630 1285 1091 - - 1742 1721 1721 1700 1133 1679 - -
130 835 1195 1150 1206 1168 1224 1177 1233 1341 1335 1253 1247 1116 1665 1565 1556
With partial heat recovery
20 877 626 609 636 - - - - 802 819 817 568 - - - -
26 852 706 681 581 - - - - 835 841 831 571 - - - -
30 944 916 944 624 - - - - 1181 843 894 871 - - - -
35 1025 846 889 710 - - - - 1190 846 910 884 - - - -
40 1118 1190 1154 899 - - - - 1329 1236 1202 1110 - - - -
52 1128 1229 1177 938 - - - - 1342 1272 1222 1152 - - - -
60 1259 1180 912 854 903 845 - - 1284 1211 1252 1180 899 846 - -
70 1249 1192 919 878 922 880 - - 1273 1221 1261 1209 917 879 - -
80 1570 1609 804 1123 832 852 - - 1728 1903 1203 1320 911 996 - -
90 1649 1707 827 1166 842 871 - - 1804 2001 1231 1362 918 1015 - -
100 1584 1635 1178 1212 951 1331 - - 1648 1823 1680 1855 1141 1257 - -
110 1616 1681 1183 1226 943 1329 - - 1680 1865 1688 1873 1131 1254 - -
120 1586 1562 1136 1679 1212 1196 - - 1828 1809 1748 1730 1114 1653 - -
130 1067 1199 1089 1221 1124 1256 1143 1275 1381 1115 1359 1638 1324 1586 1305 1558
42 CG-SVX17E-EN
Table 17. Point weights (lbs) - 60 Hz - with pump package and buffer tank options
Isolator location
Aluminum Fins Copper Fins
Size
(tons) 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8
Without partial heat recovery
20 617 413 1728 1650 - - - - 610 538 1867 1650 - - - -
26 650 434 1741 1653 - - - - 640 562 1884 1650 - - - -
30 860 552 1885 1782 - - - - 858 718 2074 1789 - - - -
35 868 556 1903 1794 - - - - 865 722 2092 1801 - - - -
40 838 790 2266 2136 - - - - 967 918 2396 2264 - - - -
52 856 820 2279 2182 - - - - 985 948 2410 2311 - - - -
60 882 838 1205 1146 1810 1721 - - 1007 963 1325 1265 1926 1836 - -
70 878 848 1208 1166 1826 1763 - - 1004 972 1328 1285 1942 1878 - -
80 1868 2086 1234 1379 899 1005 - - 1892 2452 1703 1650 1040 1005 - -
90 1873 2145 1281 1657 957 828 - - 2169 2400 1565 1738 1012 1128 - -
100 1681 2251 1789 1796 1263 1267 - - 2292 2524 1638 1812 1559 1734 - -
110 1710 2298 1797 1810 1255 1263 - - 2324 2568 1645 1828 1549 1732 - -
120 1862 2235 1856 1671 1234 1666 - - 2314 2562 1710 1896 1685 1871 - -
130 1210 1223 1148 1742 1580 1599 1504 1523 1110 1688 1706 1728 1768 1791 1801 1824
Without partial heat recovery
20 624 423 1729 1672 - - - - 616 549 1870 1671 - - - -
26 585 516 1813 1604 - - - - 646 574 1886 1671 - - - -
30 872 569 1883 1805 - - - - 867 738 2074 1810 - - - -
35 880 572 1900 1817 - - - - 874 742 2092 1821 - - - -
40 831 783 2322 2191 - - - - 959 911 2452 2320 - - - -
52 849 813 2336 2238 - - - - 977 941 2466 2367 - - - -
60 870 827 1218 1159 1866 1777 - - 841 928 1732 1273 1742 1920 - -
70 866 836 1222 1179 1883 1819 - - 837 937 1737 1294 1758 1962 - -
80 1823 2358 1285 1248 980 953 - - 2217 2293 1679 1736 827 1165 - -
90 1959 2243 1296 1667 945 809 - - 2293 2389 1710 1782 832 1183 - -
100 1762 2347 1817 1815 1247 1245 - - 2380 2613 1661 1836 1540 1715 - -
110 1791 2394 1825 1829 1239 1241 - - 2413 2657 1668 1851 1530 1713 - -
120 1941 2333 1885 1694 1220 1639 - - 2403 2651 1733 1919 1666 1852 - -
130 1158 1611 1132 1573 1639 1514 1607 1482 1476 1637 1559 1720 1688 1849 1757 1918
CG-SVX17E-EN 43
44 CG-SVX17E-EN
Table 20. Point Weights (lbs) - 50 Hz - with pump package and buffer tank options
Isolator location
Aluminum Fins Copper Fins
Size (tons) 1 2 3 4 5 6 1 2 3 4 5 6
Without partial heat recovery
20 616 419 1637 1585 - - 609 544 1778 1584 - -
26 637 430 1662 1596 - - 628 558 1804 1593 - -
30 853 554 1801 1719 - - 850 721 1990 1726 - -
35 862 557 1835 1743 - - 859 724 2025 1750 - -
40 735 882 2280 2010 - - 954 920 2321 2229 - -
52 843 822 2204 2146 - - 972 950 2335 2275 - -
60 881 842 1196 1143 1788 1709 1006 966 1316 1262 1905 1824
70 877 851 1200 1164 1804 1750 1003 975 1320 1283 1921 1865
80 1872 2089 1224 1369 884 991 2131 2206 1654 1710 829 1168
90 1876 2150 1271 1643 943 814 2206 2301 1684 1756 834 1185
100 1700 2273 1774 1778 1230 1233 2309 2542 1627 1801 1524 1698
110 1713 2300 1786 1798 1238 1246 2325 2569 1636 1818 1531 1713
120 1872 2259 1809 1631 1165 1569 2330 2575 1673 1857 1600 1784
With partial heat recovery
20 623 429 1639 1607 - - 614 555 1780 1604 - -
26 573 511 1733 1548 - - 633 569 1806 1614 - -
30 865 571 1798 1742 - - 859 740 1990 1746 - -
35 874 574 1833 1766 - - 868 744 2025 1770 - -
40 818 784 2247 2155 - - 946 912 2377 2284 - -
52 836 814 2260 2202 - - 964 942 2391 2331 - -
60 869 830 1209 1156 1845 1765 994 954 1329 1275 1961 1880
70 866 839 1213 1177 1861 1806 991 964 1333 1296 1977 1921
80 1827 2361 1274 1237 966 938 2221 2298 1667 1724 815 1150
90 1961 2247 1285 1652 931 796 2295 2393 1697 1770 820 1167
100 1780 2368 1801 1797 1215 1212 2467 2452 1851 1840 1234 1840
110 1794 2396 1813 1817 1222 1224 2484 2479 1861 1858 1240 1856
120 1951 2356 1837 1653 1151 1543 2418 2664 1696 1880 1581 1765
CG-SVX17E-EN 45
4 6
7 2
5 3
8
1
B
A
6
3 2
5
46 CG-SVX17E-EN
Evaporator Label
The BPHE evaporator label, including barcode, is located
under the insulation, in the locations shown in Figure 47,
p. 48. Insulation backing over this area has not been
removed, so that it can be rolled back to access BPHE label.
CG-SVX17E-EN 47
BPHE LABEL
LOCATION
BARCODE
BPHE LABEL
LOCATION
ADDITIONAL BARCODE
INSULATION
TAP
ADDITIONAL
INSULATION
TAP
BPHE LABEL
LOCATION
BPHE LABEL
BARCODE LOCATION
BARCODE
ADDITIONAL
INSULATION ADDITIONAL
TAP INSULATION
TAP
48 CG-SVX17E-EN
+]
040 120
40 030 070 080 100 130
P R E S S UR E D R OP ( F t.of H 2O)
052
20
10
5
020 035 060 110
026 090
1
10 50 100 200 400
F L O W ( G P M)
50Hz
040 120
40 060 080 100
030 130
PRESSURE DROP (Ft.of H2O)
20
10
5
052
020 070 090 110
026 035
1
10 50 100 200 400
FLOW (GPM)
CG-SVX17E-EN 49
Freeze Protection OR
Depending on the ambient temperature the unit may be 3. Freeze inhibitor
exposed to, there are up to four different options for freeze
Freeze protection can be accomplished by adding
protection.They are listed in order of highest ambient
sufficient glycol to protect against freezing below
(least freeze protection) to lowest ambient (most freeze
the lowest ambient expected.
protection).
See Low Evap Refrigerant Cutout/Percent Glycol
1. Water pump (for protection with ambient
Recommendations, p. 50.
temperatures down to 0F)
a. CH530 controller can start the pump when the OR
ambient temperatures drops to prevent freezing. 4. Drain water circuit (for protection with ambients below
For this option the pump must to be controlled by -20F)
the CGAM unit and this function must be validated.
a. Shut off the power supply to the unit and to all
b. Water circuit valves need to stay open at all times. heaters.
Note: If dual high head pump package option is b. Purge the water circuit.
selected, the chiller MUST control the
c. Blow out the evaporator to ensure no liquid is left in
pumps.
the evaporator.
OR Note: By default the CH530 freeze protection control is
2. Heaters (for protection with ambient temperatures enabled and will request the start of the chilled
down to -20F) water pump with ambient temperatures less than
the evaporator low leaving water temperature
Note: This option is not applicable for units ordered
setpoint.The pump remains ON until the minimum
with No Freeze Protection (model number
evaporator water temperature is greater than low
digit 18 is X). Factory mounted heaters are
leaving water temperature setpoint plus 7C.The
NOT installed on these units, and one of the
minimum on time for the pump is 5 minutes. If you
other forms of freeze protection must be used.
do NOT want the CH530 to start the pump when the
a. For units with freeze protection selected (model ambient temperature drops to freezing, disable this
number digit 18 is 1), heaters are factory-installed freeze protection control.
on the evaporator and water piping and will protect
them from freezing in ambient temperatures down
to -20F (-29C). Low Evap Refrigerant Cutout/Percent
b. Install heat tape on all water piping, pumps, and Glycol Recommendations
other components that may be damaged if exposed
The table below shows the low evaporator temperature
to freezing temperatures. Heat tape must be
cutout for different glycol levels.
designed for low ambient temperature
applications. Heat tape selection should be based Additional glycol beyond the recommendations will
on the lowest expected ambient temperature. adversely effect unit performance.The unit efficiency will
be reduced and the saturated evaporator temperature will
be reduced. For some operating conditions this effect can
NOTICE: be significant.
Equipment Damage! If additional glycol is used, then use the actual percent
All heaters have separate power from the unit. All glycol to establish the low refrigerant cutout setpoint.
heaters must be energized or the CH530 must control
the pumps when the unit is off (unless the water circuit
is drained). In the event of power loss, neither heaters
nor CH530 control of the pumps will protect the
evaporator from catastrophic damage. In order to
provide freeze protection in the event of a power loss
you MUST drain the evaporator or use sufficient freeze
inhibitor in the evaporator.
50 CG-SVX17E-EN
Table 22. Low Evap Refrigerant Temp Cutout and Low Water Temp Cutout
CG-SVX17E-EN 51
Table 22. Low Evap Refrigerant Temp Cutout and Low Water Temp Cutout (continued)
52 CG-SVX17E-EN
Figure 50. Ethylene - compressor power adjustment Figure 53. Propylene - GPM adjustment
0.999 1.06
0.9985
1.05
50 Hz
0.998 60 Hz
1.04
0.9975
Adjustment Factor
Adjustment Factor
0.997 1.03
0.9965
1.02
0.996
50 Hz 1.01
0.9955
0.995
1.00
0.9945
60 Hz 0.99
0.994 0 5 10 15 20 25 30 35 40 45 50
0 5 10 15 20 25 30 35 40 45 % Ethylene Glycol by Weight
% Ethylene Glycol by Weight
Figure 51. Propylene - compressor power adjustment Figure 54. Ethylene - capacity adjustment
0.999 0.996
0.998 0.994
0.997
0.992
0.996
0.990
Adjustment Factor
Adjustment Factor
0.995
0.988
0.994
0.986
0.993
0.984
0.992
50 Hz
0.982
0.991
50 Hz
60 Hz
0.99 0.980
60 Hz
0.989 0.978
0.998 0.976
0 5 10 15 20 25 30 35 40 45 50
0 5 10 15 20 25 30 35 40 45
% Ethylene Glycol by Weight % Ethylene Glycol by Weight
Figure 52. Ethylene - GPM adjustment Figure 55. Propylene - capacity adjustment
1.14 0.995
50 Hz
1.12 0.990
60 Hz 0.985
1.10
Adjustment Factor
0.980
Adjustment Factor
1.08
0.975
1.06
50 Hz
0.970
1.04
0.965
1.02 60 Hz
0.960
1.00
0 5 10 15 20 25 30 35 40 45
0.955
% Ethylene Glycol by Weight 0 5 10 15 20 25 30 35 40 45 50
% Ethylene Glycol by Weight
CG-SVX17E-EN 53
NOTICE:
Equipment Damage!
If the partial heat recovery heat exchanger is drained
the heater must be turned off to avoid damaging the
partial heater recovery heat exchanger. The heater
should only be on when the heat recovery heat
exchanger has water in it.
54 CG-SVX17E-EN
CGAM Unit
Note: In addition to those recommended for field piping, the CGAM unit includes factory installed manual air vent and
water drain valve with partial heat recovery option. See Figure 81, p. 96 through Figure 83, p. 97 for partial heat
recovery component locations.
OR
Add freeze inhibit fluid to the partial heat recovery
water loop.
CG-SVX17E-EN 55
Figure 57. Partial heat recovery pressure drop curve Figure 58. Partial heat recovery pressure drop curve
60 Hz 50 Hz
8 12
90/100/110 120/130
7 80/90/100
80 10
PHR Water Pressure Drop (psid)
2
1
0 0
0 20 40 60 80 100 0 20 40 60 80 100 120
PHR Water Flow Rate (gpm) PHR Water Flow Rate (gpm)
Note: Partial heat recovery may function at flow rates near zero. However, heat transfer performance is severely reduced
and water flow distribution is poor.
56 CG-SVX17E-EN
INLET
CONNECTIONS TO UNIT
C
OUTLET
CG-SVX17E-EN 57
58 CG-SVX17E-EN
CG-SVX17E-EN 59
Unit Component Pressure Drop. Figure 65 shows the pressure drop values for unit components.
100
PRESSURE HEAD (Ft. of H2O)
10
070
040 130
080
020 035 110/120
052 060 100
026/030 090
1
10 100 1000
FLOW RATE (GPM)
System Head Pressure. See Figure 66 for the system head pressure available.
Figure 66. CGAM pump package available head pressure - water only
140
120
PRESSURE HEAD (Ft. of H2O)
100
80
60
020
080
40 090
026/030 130
035 100
110 120
20
040 070
052 060
0
0 50 100 150 200 250 300 350 400 450 500
FLOW RATE (GPM)
60 CG-SVX17E-EN
CG-SVX17E-EN 61
62 CG-SVX17E-EN
CG-SVX17E-EN 63
WARNING
Hazardous Voltage!
Disconnect all electric power, including remote
disconnects before servicing. Follow proper lockout/
tagout procedures to ensure the power can not be
inadvertently energized. Failure to disconnect power
before servicing could result in death or serious injury.
NOTICE:
Use Copper Conductors Only!
Unit terminals are not designed to accept other types of
conductors. Failure to use copper conductors could
result in equipment damage.
NOTICE:
Equipment Damage!
Do not allow conduit to interfere with other
components, structural members or equipment.
Control voltage (115V) wiring in conduit must be
separate from conduit carrying low voltage (<30V)
wiring. To prevent control malfunctions, do not run low
voltage wiring (<30V) in conduit with conductors
carrying more than 30 volts.
64 CG-SVX17E-EN
CG-SVX17E-EN 65
66 CG-SVX17E-EN
No Pump Pump
Terminal Std Fault High Fault Terminal Std Fault High Fault
Unit Size Rated Power Blocks Ckt Breaker Ckt Breaker Blocks Ckt Breaker Ckt Breaker
208/60/3 #6 - 350 MCM #14 - 1/0 #14 - 1/0 #6 - 350 MCM #6 - 350 MCM #6 - 350 MCM
230/60/3 #6 - 350 MCM #14 - 1/0 #14 - 1/0 #6 - 350 MCM #6 - 350 MCM #6 - 350 MCM
20 380/60/3 #6 - 350 MCM #14 - 1/0 #14 - 1/0
460/60/3 #6 - 350 MCM #14 - 1/0 #14 - 1/0 #6 - 350 MCM #14 - 1/0 #14 - 1/0
575/60/3 #6 - 350 MCM #14 - 1/0 n/a #6 - 350 MCM #14 - 1/0 n/a
208/60/3 #6 - 350 MCM #6 - 350 MCM #6 - 350 MCM #6 - 350 MCM #6 - 350 MCM #6 - 350 MCM
230/60/3 #6 - 350 MCM #6 - 350 MCM #6 - 350 MCM #6 - 350 MCM #6 - 350 MCM #6 - 350 MCM
26 380/60/3 #6 - 350 MCM #14 - 1/0 #14 - 1/0 n/a n/a n/a
460/60/3 #6 - 350 MCM #14 - 1/0 #14 - 1/0 #6 - 350 MCM #14 - 1/0 #14 - 1/0
575/60/3 #6 - 350 MCM #14 - 1/0 n/a #6 - 350 MCM #14 - 1/0 n/a
208/60/3 #6 - 350 MCM #6 - 350 MCM #6 - 350 MCM #6 - 350 MCM #6 - 350 MCM #6 - 350 MCM
230/60/3 #6 - 350 MCM #6 - 350 MCM #6 - 350 MCM #6 - 350 MCM #6 - 350 MCM #6 - 350 MCM
30 380/60/3 #6 - 350 MCM #14 - 1/0 #14 - 1/0 n/a n/a n/a
460/60/3 #6 - 350 MCM #14 - 1/0 #14 - 1/0 #6 - 350 MCM #14 - 1/0 #14 - 1/0
575/60/3 #6 - 350 MCM #14 - 1/0 n/a #6 - 350 MCM #14 - 1/0 n/a
208/60/3 #6 - 350 MCM #6 - 350 MCM #6 - 350 MCM #6 - 350 MCM #6 - 350 MCM #6 - 350 MCM
230/60/3 #6 - 350 MCM #6 - 350 MCM #6 - 350 MCM #6 - 350 MCM #6 - 350 MCM #6 - 350 MCM
35 380/60/3 #6 - 350 MCM #14 - 1/0 #14 - 1/0 n/a n/a n/a
460/60/3 #6 - 350 MCM #14 - 1/0 #14 - 1/0 #6 - 350 MCM #14 - 1/0 #14 - 1/0
575/60/3 #6 - 350 MCM #14 - 1/0 n/a #6 - 350 MCM #14 - 1/0 n/a
208/60/3 #4 - 500 MCM 3/0 - 500 MCM 3/0 - 500 MCM #4 - 500 MCM 3/0 - 500 MCM 3/0 - 500 MCM
230/60/3 #4 - 500 MCM 3/0 - 500 MCM 3/0 - 500 MCM #4 - 500 MCM 3/0 - 500 MCM 3/0 - 500 MCM
40 380/60/3 #4 - 500 MCM #6 - 350 MCM #6 - 350 MCM n/a n/a n/a
460/60/3 #4 - 500 MCM #6 - 350 MCM #6 - 350 MCM #4 - 500 MCM #6 - 350 MCM #6 - 350 MCM
575/60/3 #4 - 500 MCM #6 - 350 MCM n/a #4 - 500 MCM #6 - 350 MCM n/a
208/60/3 #4 - 500 MCM 3/0 - 500 MCM 3/0 - 500 MCM #4 - 500 MCM 3/0 - 500 MCM 3/0 - 500 MCM
230/60/3 #4 - 500 MCM 3/0 - 500 MCM 3/0 - 500 MCM #4 - 500 MCM 3/0 - 500 MCM 3/0 - 500 MCM
52 380/60/3 #4 - 500 MCM #6 - 350 MCM #6 - 350 MCM n/a
460/60/3 #4 - 500 MCM #6 - 350 MCM #6 - 350 MCM #4 - 500 MCM #6 - 350 MCM #6 - 350 MCM
575/60/3 #4 - 500 MCM #6 - 350 MCM n/a #4 - 500 MCM #6 - 350 MCM n/a
208/60/3 #4 - 500 MCM 3/0 - 500 MCM 3/0 - 500 MCM
230/60/3 #4 - 500 MCM 3/0 - 500 MCM 3/0 - 500 MCM n/a
60 380/60/3 #4 - 500 MCM #6 - 350 MCM #6 - 350 MCM
460/60/3 #4 - 500 MCM #6 - 350 MCM #6 - 350 MCM #4 - 500 MCM #6 - 350 MCM #6 - 350 MCM
575/60/3 #4 - 500 MCM #6 - 350 MCM n/a #4 - 500 MCM #6 - 350 MCM n/a
208/60/3 #4 - 500 MCM 3/0 - 500 MCM 3/0 - 500 MCM
230/60/3 #4 - 500 MCM 3/0 - 500 MCM 3/0 - 500 MCM n/a
70 380/60/3 #4 - 500 MCM 3/0 - 500 MCM 3/0 - 500 MCM
460/60/3 #4 - 500 MCM #6 - 350 MCM #6 - 350 MCM #4 - 500 MCM #6 - 350 MCM #6 - 350 MCM
575/60/3 #4 - 500 MCM #6 - 350 MCM n/a #4 - 500 MCM #6 - 350 MCM n/a
1. Optional circuit breaker and high fault circuit breaker.
2. Will accept two conduits per phase in this size.
3. Copper wire only, based on nameplate Minimum Circuit Ampacity (MCA).
4. Data shown for circuit one. The second circuit is always the same.
5. n/a - not available
CG-SVX17E-EN 67
No Pump Pump
Terminal Std Fault High Fault Terminal Std Fault High Fault
Unit Size Rated Power Blocks Ckt Breaker Ckt Breaker Blocks Ckt Breaker Ckt Breaker
208/60/3 #4 - 500 MCM 3/0 - 500 MCM 3/0 - 500 MCM #4 - 500 MCM 3/0-500 MCM 3/0-500 MCM
230/60/3 #4 - 500 MCM 3/0 - 500 MCM 3/0 - 500 MCM #4 - 500 MCM 3/0-500 MCM 3/0-500 MCM
80 380/60/3 #4 - 500 MCM 3/0 - 500 MCM 3/0 - 500 MCM n/a
460/60/3 #4 - 500 MCM #6 - 350 MCM #6 - 350 MCM #4 - 500 MCM 3/0-500 MCM 3/0-500 MCM
575/60/3 #4 - 500 MCM #6 - 350 MCM n/a #4 - 500 MCM #6 - 350 MCM n/a
208/60/3 #4 - 500 MCM 3/0 - 500 MCM 3/0 - 500 MCM #4 - 500 MCM 3/0-500 MCM 3/0-500 MCM
230/60/3 #4 - 500 MCM 3/0 - 500 MCM 3/0 - 500 MCM #4 - 500 MCM 3/0-500 MCM 3/0-500 MCM
90 380/60/3 #4 - 500 MCM 3/0 - 500 MCM 3/0 - 500 MCM n/a
460/60/3 #4 - 500 MCM 3/0 - 500 MCM 3/0 - 500 MCM #6 - 350 MCM 3/0 - 500 MCM 3/0 - 500 MCM
575/60/3 #4 - 500 MCM #6 - 350 MCM n/a #6 - 350 MCM #6 - 350 MCM n/a
208/60/3 #4 - 500 MCM 3/0 - 500 MCM 3/0 - 500 MCM #6 - 350 MCM 3/0-500 MCM 3/0-500 MCM
230/60/3 #4 - 500 MCM 3/0 - 500 MCM 3/0 - 500 MCM #6 - 350 MCM 3/0-500 MCM 3/0-500 MCM
100 380/60/3 #4 - 500 MCM 3/0 - 500 MCM 3/0 - 500 MCM n/a
460/60/3 #4 - 500 MCM 3/0 - 500 MCM 3/0 - 500 MCM #6 - 350 MCM 3/0 - 500 MCM 3/0 - 500 MCM
575/60/3 #4 - 500 MCM 3/0 - 500 MCM n/a #6 - 350 MCM 3/0 - 500 MCM n/a
208/60/3 #4 - 500 MCM 3/0 - 500 MCM 3/0 - 500 MCM #6 - 350 MCM 3/0-500 MCM 3/0-500 MCM
230/60/3 #4 - 500 MCM 3/0 - 500 MCM 3/0 - 500 MCM #6 - 350 MCM 3/0-500 MCM 3/0-500 MCM
110 380/60/3 #4 - 500 MCM 3/0 - 500 MCM 3/0 - 500 MCM n/a
460/60/3 #4 - 500 MCM 3/0 - 500 MCM 3/0 - 500 MCM #6 - 350 MCM 3/0 - 500 MCM 3/0 - 500 MCM
575/60/3 #4 - 500 MCM 3/0 - 500 MCM n/a #6 - 350 MCM 3/0 - 500 MCM n/a
208/60/3 #4 - 500 MCM 3/0 - 500 MCM 3/0 - 500 MCM n/a
230/60/3 #4 - 500 MCM 3/0 - 500 MCM 3/0 - 500 MCM #6 - 350 MCM 3/0-500 MCM 3/0-500 MCM
120 380/60/3 #4 - 500 MCM 3/0 - 500 MCM 3/0 - 500 MCM n/a
460/60/3 #4 - 500 MCM 3/0 - 500 MCM 3/0 - 500 MCM #6 - 350 MCM 3/0 - 500 MCM 3/0 - 500 MCM
575/60/3 #4 - 500 MCM 3/0 - 500 MCM n/a #6 - 350 MCM 3/0 - 500 MCM n/a
208/60/3 #4 - 500 MCM 3/0 - 500 MCM 3/0 - 500 MCM n/a
230/60/3 #4 - 500 MCM 3/0 - 500 MCM 3/0 - 500 MCM #4 - 500 MCM 3/0 - 500 MCM 3/0 - 500 MCM
130 380/60/3 #4 - 500 MCM 3/0 - 500 MCM 3/0 - 500 MCM n/a
460/60/3 #4 - 500 MCM 3/0 - 500 MCM 3/0 - 500 MCM #4 - 500 MCM 3/0 - 500 MCM 3/0 - 500 MCM
575/60/3 #4 - 500 MCM 3/0 - 500 MCM n/a #4 - 500 MCM 3/0 - 500 MCM n/a
1. Optional circuit breaker and high fault circuit breaker.
2. Will accept two conduits per phase in this size.
3. Copper wire only, based on nameplate Minimum Circuit Ampacity (MCA).
4. Data shown for circuit one. The second circuit is always the same.
5. n/a - not available
68 CG-SVX17E-EN
Unit Rated Number Qty Qty Fan Motor Cond Fan Compressor Compressor
Size Power Circuits Comp Fans Power (kW) FLA RLA LRA MCA MOPD
20 400/50/3 1 2 2 1 2.4 17-17 142-142 46 60
26 400/50/3 1 2 2 1 2.4 21-21 158-158 55 70
30 400/50/3 1 2 3 1 2.4 27-27 160-160 71 90
35 400/50/3 1 2 3 1 2.4 27-33 160-215 79 110
40 400/50/3 2 4 4 1 2.4 17-17/17-17 142-142/142-142 85 100
52 400/50/3 2 4 4 1 2.4 21-21/21-21 158-158/158-158 102 110
60 400/50/3 2 4 6 1 2.4 27-27/27-27 160-160/160-160 133 150
70 400/50/3 2 4 6 1 2.4 27-33/33-27 160-215/215-160 147 175
80 400/50/3 2 4 6 1 2.4 33-33/33-33 215-215/215-215 160 175
90 400/50/3 2 4 6 1 2.4 33-43/43-33 215-260/260-215 181 200
100 400/50/3 2 4 8 1 2.4 43-43/43-43 260-260/260-260 204 225
110 400/50/3 2 4 8 1 2.4 43-47/47-43 260-320/260-320 214 250
120 400/50/3 2 4 8 1 2.4 47-47/47-47 320-320/320-320 223 250
1. RLA - Rated Load Amps - Rated in accordance with UL Standard 1995.
2. LRA - Locked Rotor Amps - Based on full winding starts.
3. MCA - Minimum Circuit Ampacity - 125 percent of largest compressor RLA plus 100 percent of all other loads.
4. MOPD or Max fuse size - 225 percent of the largest compressor RLA plus all other loads.
5. Local codes may take precedence.
6. Voltage Utilization Range: +/- 10% of rated voltage
Rated voltage (use range): 400/50/3 (360-440)
7. One separate 120/50/1, 15 amp customer provided power connection is required to power the heaters.
8. n/a - not available
9. Pump package not available with 50 Hz units.
CG-SVX17E-EN 69
70 CG-SVX17E-EN
V Configuration 40-70Ton
Low Incoming
Slant Configuration 20-35Ton Voltage Power
Power
Low
Voltage Incoming
Power Power
W Configuration 80-130Ton
Incoming
Low Voltage Power
Power
Partial Heat Recovery Power Supply Note: If partial heat recovery heat exchanger is drained,
the heater must be turned off in order to avoid
The partial heat recover heat exchanger is insulated from damaging the partial heat recovery heat exchanger.
ambient air and protected from freezing temperatures by The heater should only be on when the heat
an immersion heater. When the ambient air temperature recovery heat exchanger has water in it.
drops to approximately 37F (2.8C) the thermostat
energizes the heaters.The heaters will provide protection Water Pump Power Supply
from ambient temperatures down to -20F (-29C).
Provide power supply wiring with disconnect for the
It is required to provide an independent power source chilled water pump(s).
(115V 60-Hz-20 amp, 50Hz-15 amp), with a fused-
disconnect to the heater.The heaters are factory-wired
back to the unit control panel.
CG-SVX17E-EN 71
Interconnecting Wiring
Chilled Water Flow (Pump) Interlock EWP relay and generates a non-latching diagnostic. If flow
returns (e.g. someone else is controlling the pump), the
All CGAM model chillers have a factory-installed flow diagnostic is cleared, the EWP relay is re-energized, and
switch. In addition, it is recommended to use an additional normal control resumed.
field-supplied control voltage contact input through an
auxiliary contact to prove flow. Connect the auxiliary If evaporator water flow is lost once it has been
contact to 1X5-3 and 1X5-9. Refer to the field wiring for established, the EWP relay remains energized and a non-
details.The auxiliary contact can be a BAS signal, starter latching diagnostic is generated. If flow returns, the
contactor auxiliary or any signal which indicates the pump diagnostic is cleared and the chiller returns to normal
is running. operation.
72 CG-SVX17E-EN
Description
This output is true whenever there is any active diagnostic that requires a manual reset to clear, that affects either the
Alarm - Latching
Chiller, the Circuit, or any of the Compressors on a circuit. This classification does not include informational diagnostics.
This output is true whenever there is any active diagnostic that could automatically clear, that affects either the Chiller,
Alarm - Auto Reset
the Circuit, or any of the Compressors on a circuit. This classification does not include informational diagnostics.
This output is true whenever there is any diagnostic affecting any component, whether latching or automatically clearing.
Alarm
This classification does not include informational diagnostics
This output is true whenever there is any diagnostic effecting Refrigerant Circuit 1, whether latching or automatically
Alarm Ckt 1
clearing, including diagnostics affecting the entire chiller. This classification does not include informational diagnostics.
This output is true whenever there is any diagnostic affecting Refrigerant Circuit 2 whether latching or automatically
Alarm Ckt 2
clearing, including diagnostics effecting the entire chiller. This classification does not include informational diagnostics.
Chiller Limit Mode (with This output is true whenever the chiller has been running in one of the Unloading types of limit modes (Condenser,
a 20 minute filter) Evaporator, Current Limit or Phase Imbalance Limit) continuously for the last 20 minutes.
This output is true whenever any compressor is running (or commanded to be running) on Refrigerant Circuit 1, and false
Circuit 1 Running
when no compressors are commanded to be running on that circuit.
This output is true whenever any compressor is running (or commanded to be running) on Refrigerant Circuit 2, and false
Circuit 2 Running
when no compressors are commanded to be running on that circuit.
This output is true whenever any compressor is running (or commanded to be running) on the chiller and false when
Chiller Running
no compressors are commanded to be running on the chiller.
Maximum Capacity This output is true whenever the chiller has all compressors on. The output is false once one compressor is shut off.
CG-SVX17E-EN 73
74 CG-SVX17E-EN
Connect leads from 6K6 to the proper terminals of 1A16. 2-10 VDC and 4-20 mA shall each correspond to an EDLS
Refer to the field diagrams which are shipped with the unit. range with a minimum of 0% and a maximum of 100%.The
Silver or gold-plated contacts are recommended.These following equations exist.
customer furnished contacts must be compatible with 24
VDC, 12 mA resistive load. Global Scroll Voltage Signal Current Signal
As generated from
External Chilled Water Setpoint (ECWS) Vdc = 8*(EDLS) + 2 mA = 16*(EDLS) + 4
external source
Option As processed by
EDLS = (Vdc - 2)/8 EDLS = (mA - 4)/16
CH530
The CH530 provides inputs that accept either 4-20 mA or 2-
10 VDC signals to set the external chilled water setpoint The minimum EDLS will be clamped at the front panel
(ECWS).This is not a reset function.The input defines based on 100% /Total number of Compressors. For input
the set point.This input is primarily used with generic BAS signals beyond the 2-10VDC or 4-20mA range, the end of
(building automation systems).The chilled water setpoint range value shall be used. For example, if the customer
set via the DynaView or through digital communication inputs 21 mA, the EDLS shall limit it self to the
withTracer. corresponding 20 mA EDLS.
The chilled water setpoint may be changed from a remote ECWS and EDLS Analog Input Signal
location by sending either a 2-10 VDC or 4-20 mA signal to Wiring Details:
the 1A14, J2-1 and 2.The 2-10 VDC and 4-20 mA each
correspond to a 10 to 65F (-12 to 18C) external chilled Both the ESWS and EDLS can be connected and setup as
water setpoint. either a 2-10 VDC (factory default), 4-20 mA, or resistance
input (also a form of 4-20 mA) as indicated below.
The following equations apply:
Depending on the type to be used, theTechView Service
Tool must be used to configure the LLID and the MP for the
Voltage Signal proper input type that is being used.This is accomplished
VDC = by a setting change on the CustomTab of the
(8*ECWSF + 2*ECWSmax - 10*ECWSmin)/(ECWSmax - ECWSmin) Configuration View withinTechView.
The J2-3 and J2-6 terminal is chassis grounded and
Current Signal terminal J2-1 and J2-4 can be used to source 12 VDC.The
mA = ECLS uses terminals J2-2 and J2-3. EDLS uses terminals
(16*ECWSF + 4*ECWSmax - 20*ECWSmin)/ (ECWSmax - ECWSmin) J2-5 and J2-6. Both inputs are only compatible with
Note: To convert ECWS values to F, use the following high-side current sources.
formula: F = 1.8*(C) + 32 Figure 67. Wiring Examples for ECLS and EDLS
If the ECWS input develops an open or short, the LLID will
report either a very high or very low value back to the main
processor.This will generate an informational diagnostic
and the unit will default to using the Front Panel
(DynaView) Chilled Water Setpoint.
TechView ServiceTool is used to set the input signal type
from the factory default of 2-10 VDC to that of 4-20 mA.
TechView is also used to install or remove the External
ChilledWater Setpoint option as well as a means to enable
and disable ECWS.
CG-SVX17E-EN 75
Chilled Water Reset (CWR) the same as the Return Reset equation except on selection
of Constant Return Reset, the MP will automatically set
CH530 resets the chilled water temperature set point Ratio, Start Reset, and Maximum Reset to the following.
based on either return water temperature, or outdoor air
temperature. RATIO = 100%
One of three ResetTypes: None, Return Water MAXIMUM RESET = Design DeltaTemp.
Temperature Reset, Outdoor AirTemperature Reset, or The equation for Constant Return is then as follows:
Constant Return WaterTemperature Reset. CWS' = CWS + 100% (Design DeltaTemp. - (TWE -TWL))
Reset Ratio Set Points. and CWS' > or = CWS
For outdoor air temperature reset there shall be both and CWS' - CWS < or = Maximum Reset
positive and negative reset ratio's.
When any type of CWR is enabled, the MP will step the
Start Reset Set Points. Active CWS toward the desired CWS' (based on the above
Maximum Reset Set Points. equations and setup parameters) at a rate of 1 degree F
The equations for each type of reset are as follows: every 5 minutes until the Active CWS equals the desired
CWS'.This applies when the chiller is running.
Return
When the chiller is not running the CWS is reset
CWS' = CWS + RATIO (START RESET - (TWE -TWL)) immediately (within one minute) for Return Reset and at a
and CWS' > or = CWS rate of 1 degree F every 5 minutes for Outdoor Reset.The
chiller will start at the Differential to Start value above a
and CWS' - CWS < or = Maximum Reset
fully reset CWS or CWS' for both Return and Outdoor
Outdoor Reset.
CWS' = CWS + RATIO * (START RESET -TOD)
Percent Capacity Output Option
and CWS' > or = CWS
CH530 provides an optional percent capacity output for
and CWS' - CWS < or = Maximum Reset
those customers without a communicating BAS interface.
where The active unit capacity (AUC) is provided through a 2-10
CWS' is the new chilled water set point or the "reset CWS" VDC analog output at 1A25 terminals J2-4 and J2-6 (GND).
The active unit capacity value (in %) can be derived from
CWS is the active chilled water set point before any reset the 2-10 VDC output voltage (OV) using the following
has occurred, e.g. normally Front Panel,Tracer, or ECWS calculation:
RESET RATIO is a user adjustable gain
START RESET is a user adjustable reference AUC = 100*(OV - 2.0V)/(10.0V - 2.0V)
TOD is the outdoor temperature Note: The percent capacity output is based on the
TWE is entering evap. water temperature number and size of compressors energized, and is
not adjusted for operating conditions.This value
TWL is leaving evap. water temperature
cannot be used as an accurate measure of total unit
MAXIMUM RESET is a user adjustable limit providing the current, power or cooling capacity.
maximum amount of reset. For all types of reset, CWS' -
CWS < or = Maximum Reset.
76 CG-SVX17E-EN
CG-SVX17E-EN 77
BACnet protocol: data link layers, device address Alarm and Event-Information-B (AE-INFO-B)
binding, networking options, and character sets
Alarm and Event-Notification Internal-B (AE-N-I-B)
Object data points and configurations
Supported
BACnet Protocol Implementation Trending Description BIBB
Segmentation Capability
Supported
Segmentation Description Segment
Segmented Requests/ Window Size: 1
Segmented Responses/ Window Size: 1
78 CG-SVX17E-EN
Object Types
Table 41. Descriptions and configurations
CG-SVX17E-EN 79
80 CG-SVX17E-EN
CG-SVX17E-EN 81
82 CG-SVX17E-EN
Character Sets
Indicates support for multiple characters sets, but does not Table 43. Analog Input
imply that all character sets are supported simultaneously. Object
Maximum supported string length is 64 bytes (any Identifier Object Name Description Units
character set).
Active Cool/Heat Active chiller
Degrees-
Analog Input, 1 Setpoint water or hot
Fahrenheit (64)
Temperature water setpoint.
Character Set Descriptions Supported Active capacity
Active Current
ANSI X3.4 Analog Input, 2 current limit Percent (98)
Limit Setpoint
setpoint.
IBM/Microsoft DBCS
Level of
ISO 10646 (UCS-4) capacity that
Actual Running
ISO 10646 (UCS2) Analog Input, 5 the chiller is Percent (98)
Capacity
currently
ISO 8859-1 running at.
JIS C 6226 Circuit 1
Suction
Analog Input, 7 suction PSI
Pressure- Ckt 1
pressure.
Object Data Points and Diagnostic Circuit 2
Suction
Analog Input, 10 suction PSI
Data Points with Corresponding Pressure- Ckt 2
pressure.
Chiller Models Evaporator
Circuit 2
Saturated
evaporator Degrees-
Analog Input, 12 Refrigerant
For quick reference, the following tables are listed two refrigerant Fahrenheit (64)
Temperature-
different ways. Table 42 through Table 47 are listed by temperature.
Ckt 1
input/output type and sorted by object identifier.These Evaporator
tables provide the user with the units type for each object Circuit 2
Saturated
evaporator Degrees-
type. Table 48 is sorted by object name and provides a Analog Input, 14 Refrigerant
refrigerant Fahrenheit (64)
complete list of object names, types, values/ranges, and Temperature-
temperature.
Ckt 2
descriptions. Not all points are available to the user.The
Circuit 1
available data points are defined during self-configuration Condenser
condenser
and are dependent on the type of equipment Analog Input, 16 Refrigerant PSI
refrigerant
Pressure- Ckt 1
pressure.
.
Circuit 2
Table 42. Analog Output Condenser
condenser
Analog Input, 18 Refrigerant PSI
refrigerant
Object Object Valid Relinq Pressure- Ckt 2
pressure.
Identifier Name Description Units Range Default
Condenser
Desired leaving Circuit 1
Saturated
Chilled water condenser Degrees-
Analog F 0F to Analog Input, 20 Refrigerant
Water temperature if 44F refrigerant Fahrenheit (64)
Output 1 (64) 75F Temperature-
Setpoint chiller is in temperature.
Ckt 1
cooling mode.
Condenser
Sets the Circuit 2
Current Perce Saturated
Analog maximum 0% to condenser Degrees-
Limit nt 100% Analog Input, 22 Refrigerant
Output 2 capacity that the 120% refrigerant Fahrenheit (64)
Setpoint (98) Temperature-
chiller can use. temperature.
Ckt 2
Desired leaving The power
water Unit Power being
Analog Hot Water F 80F to Analog Input, 24 Kilowatts
temperature if 120F Consumption consumed by
Output 4 Setpoint (64) 140F
chiller is in the chiller.
heating mode.
Local Local
Analog Input, 25 Atmospheric atmospheric PSI
Pressure pressure.
Number of
Starts- starts for
Analog Input, 26 None
Compressor 1A compressor
1A.
Number of
Starts- starts for
Analog Input, 27 None
Compressor 1B compressor
1B.
CG-SVX17E-EN 83
Table 43. Analog Input (continued) Table 43. Analog Input (continued)
Object Object
Identifier Object Name Description Units Identifier Object Name Description Units
Number of Pressure of the
Starts- starts for High Side Oil oil at the high
Analog Input, 28 None
Compressor 2A compressor Analog Input, 51 Pressure- side of PSI
2A. Compressor 2B compressor
2B.
Number of
Starts- starts for Temperature of
Analog Input, 29 None
Compressor 2B compressor Refrigerant the refrigerant
Degrees-
2B. Analog Input, 56 Disch Temp- Ckt being
Fahrenheit (64)
1 discharged
Total run time
Run Time- from Ckt 1.
Analog Input, 34 of compressor Hours
Compressor 1A
1A. Outdoor Air Outdoor air Degrees-
Analog Input, 57
Temperature temperature. Fahrenheit (64)
Total run time
Run Time-
Analog Input, 35 of compressor Hours Percentage of
Compressor 1B
1B. condenser
Condenser water flow
Total run time Analog Input, 58 Percent (98)
Run Time- Control Output being
Analog Input, 36 of compressor Hours
Compressor 2A requested by
2A.
the chiller.
Total run time
Run Time- Phase AB
Analog Input, 37 of compressor Hours Phase AB
Compressor 2B voltage,
2B. Analog Input, 59 Voltage- Volts
compressor
Compressor 1A
Approximate 1A.
Airflow
airflow
Analog Input, 42 Percentage- Percent (98) Phase BC
percentage of Phase BC
Circuit 1 voltage,
circuit 1. Analog Input, 60 Voltage- Volts
compressor
Compressor 1A
Approximate 1A.
Airflow
airflow
Analog Input, 43 Percentage- Percent (98) Phase CA
percentage of Phase CA
Circuit 2 voltage,
circuit 2. Analog Input, 61 Voltage- Volts
compressor
Compressor 1A
Temperature of 1A.
Evaporator
the water Degrees-
Analog Input, 44 Entering Water Phase AB
entering the Fahrenheit (64) Phase AB
Temp voltage,
evaporator. Analo5 Input, 62 Voltage- Volts
compressor
Compressor 1B
Temperature of 1B.
Evaporator
the water Degrees-
Analog Input, 45 Leaving Water Phase BC
leaving the Fahrenheit (64) Phase BC
Temp voltage,
evaporator. Analog Input, 63 Voltage- Volts
compressor
Compressor 1B
Temperature of 1B.
Condenser
the water Degrees-
Analog Input, 46 Entering Water Phase CA
entering the Fahrenheit (64) Phase CA
Temp voltage,
condenser. Analog Input, 64 Voltage- Volts
compressor
Compressor 1B
Temperature of 1B.
Condenser
the water Degrees-
Analog Input, 47 Leaving Water Phase AB
leaving the Fahrenheit (64) Phase AB
Temp voltage,
condenser. Analog Input, 65 Voltage- Volts
compressor
Compressor 2A
Pressure of the 2A.
High Side Oil oil at the high
Phase BC
Analog Input, 48 Pressure- side of PSI Phase BC
voltage,
Compressor 1A compressor Analog Input, 66 Voltage- Volts
compressor
1A. Compressor 2A
2A.
Pressure of the
Phase CA
High Side Oil oil at the high Phase CA
voltage,
Analog Input, 49 Pressure- side of PSI Analog Input, 67 Voltage- Volts
compressor
Compressor 1B compressor Compressor 2A
2A.
1B.
Phase AB
Pressure of the Phase AB
voltage,
High Side Oil oil at the high Analog Input, 68 Voltage- Volts
compressor
Analog Input, 50 Pressure- side of PSI Compressor 2B
2B.
Compressor 2A compressor
2A. Phase BC
Phase BC
voltage,
Analog Input, 69 Voltage- Volts
compressor
Compressor 2B
2B.
84 CG-SVX17E-EN
Table 43. Analog Input (continued) Table 43. Analog Input (continued)
Object Object
Identifier Object Name Description Units Identifier Object Name Description Units
Phase CA Phase CA Line 2 Current Line 2 Current
Analog Input, 70 Voltage- voltage, Volts Analog Input, 90 (%RLA)- (%RLA)- Percent (98)
Compressor 2B compressor 2B Compressor 2A Compressor 2A
Line 1 Current Line 1 Current Line 3 Current Line 3 Current
Analog Input, 71 (in Amps)- (in Amps)- Amps Analog Input, 91 (%RLA)- (%RLA)- Percent (98)
Compressor 1A Compressor 1A Compressor 2A Compressor 2A
Line 2 Current Line 2 Current Line 1 Current Line 1 Current
Analog Input, 72 (in Amps)- (in Amps)- Amps Analog Input, 92 (%RLA)- (%RLA)- Percent (98
Compressor 1A Compressor 1A Compressor 2B Compressor 2B
Line 3 Current Line 3 Current Line 2 Current Line 2 Current
Analog Input, 73 (in Amps)- (in Amps)- Amps Analog Input, 93 (%RLA)- (%RLA)- Percent (98)
Compressor 1A Compressor 1A Compressor 2B Compressor 2B
Line 1 Current Line 1 Current Line 3 Current Line 3 Current
Analog Input, 74 (in Amps)- (in Amps)- Amps Analog Input, 94 (%RLA)- (%RLA)- Percent (98)
Compressor 1B Compressor 1B Compressor 2B Compressor 2B
Line 2 Current Line 2 Current Number of Number of
Analog Input, 95 None
Analog Input, 75 (in Amps)- (in Amps)- Amps Circuits Circuits
Compressor 1B Compressor 1B
Number of Number of
Line 3 Current Line 3 Current Analog Input, 96 Compressors, Compressors, None
Analog Input, 76 (in Amps)- (in Amps)- Amps Ckt 1 Ckt 1
Compressor 1B Compressor 1B
Number of Number of
Line 1 Current Line 1 Current Analog Input, 97 Compressors, Compressors, None
Analog Input, 77 (in Amps)- (in Amps)- Amps Ckt 2 Ckt 2
Compressor 2A Compressor 2A
Line 2 Current Line 2 Current
Analog Input, 78 (in Amps)- (in Amps)- Amps Table 44. Multistate Output
Compressor 2A Compressor 2A
Line 3 Current Line 3 Current Object Object Relinq
Analog Input, 79 (in Amps)- (in Amps)- Amps Identifier Name Description Default Object States
Compressor 2A Compressor 2A 1 = HVAC _Heat
Chiller Mode of
Line 1 Current Line 1 Current Multi-State 2 = HVAC_Cool
Mode operation of 1 = Cool
Analog Input, 80 (in Amps)- (in Amps)- Amps Output, 1 3 = HVAC_Ice
Command the chiller.
Compressor 2B Compressor 2B 4 = Not Used
Line 2 Current Line 2 Current
Analog Input, 81 (in Amps)- (in Amps)- Amps Table 45. Multistate Input
Compressor 2B Compressor 2B
Line 3 Current Line 3 Current
BCI-C
Analog Input, 82 (in Amps)- (in Amps)- Amps Object Object
Compressor 2B Compressor 2B Identifier Name Description Object States
Line 1 Current Line 1 Current 1 = Chiller Off
Analog Input, 83 (%RLA)- (%RLA)- Percent (98) Indicates the 2 = Chiller in Start Mode
Compressor 1A Compressor 1A Multi-State Running primary running 3 = Chiller in Run Mode
Input, 1 Mode mode of the 4 = Chiller in Pre-shutdown
Line 2 Current Line 2 Current chiller. Mode
Analog Input, 84 (%RLA)- (%RLA)- Percent (98 5 = Chiller in Service Mode
Compressor 1A Compressor 1A
Indicates the 1 = HVAC_Heat
Line 3 Current Line 3 Current Multi-State Operating primary 2 = HVAC_Cool
Analog Input, 85 (%RLA)- (%RLA)- Percent (98) Input, 2 Mode operating mode 3 = HVAC_Ice
Compressor 1A Compressor 1A of the chiller. 4 = Not Used
Line 1 Current Line 1 Current 1 = R-22
Analog Input, 86 (%RLA)- (%RLA)- Percent (98) MP 2 = Communication
Compressor 1B Compressor 1B Multi-State Communication
Comm. 3 = Communication Lost
Input, 3 status.
Line 2 Current Line 2 Current Status 4 = Failed to Established
Analog Input, 87 (%RLA)- (%RLA)- Percent (98) 5 = Waiting to Establish
Compressor 1B Compressor 1B 1 = R-11
Line 3 Current Line 3 Current 2 = R-12
Analog Input, 88 (%RLA)- (%RLA)- Percent (98) 3 = R-22
Multi-State Refrigeran Refrigerant 4 = R-123
Compressor 1B Compressor 1B
Input, 4 t Type type.
5 = R-134A
Line 1 Current Line 1 Current
6 = R407C
Analog Input, 89 (%RLA)- (%RLA)- Percent (98)
7 = R-410A
Compressor 2A Compressor 2A
CG-SVX17E-EN 85
BCI-C Object
Object Object Identifie Object
Identifier Name Description Object States r Name Description Object States
1 = RTA Indicates if the chiller is
Binary Run Inactive = Stop
2 = CVH available to run or is
Input, 1 Enabled Active = Auto
3 = CVG currently running.
4 = CVR
Indicates if the chiller is Inactive =Remote
5 = CDH Local
Binary being controlled by local Control
6 = RTH Setpoint
Input, 2 setpoints instead of BAS Active = Local
7 = CGW Control
setpoints. Control
Indicates the 8 = CGA
Multi-State
Model model type of Indicates if conditions
Input, 5 9 = CCA Inactive = Not
the chiller. Binary Capacity may exist that prevent
10 = RTW Limited
Input, 3 Limited the chiller from reaching
11 = RTX Active = Limited
setpoint.
12 = RTU
13 = CCU Chiller
Binary Indicates if the chiller is Inactive = Off
Running
14 = CXA Input, 4 running or stopped. Active = On
State
15 = CGC
16 = RAU Condenser
Binary Condenser water flow Inactive = No Flow
Water Flow
Multi-State Cooling Cooling type of 1 = Water Cooled Input, 5 status. Active = Flow
Status
Input, 6 Type the condenser. 2 = Air Cooled
Indicates if all available
1 = Field Applied Binary Maximum Inactive = Off
chiller capacity is being
2 = La Crosse Input, 6 Capacity Active = On
used.
3 = Pueblo
4 = Charmes Indicates if the chiller is
5 = Rushville asking an outside
Binary Head Relief Inactive = Off
system to provide more
6 = Macon Input, 7 Request Active = On
heat rejection from the
7 = Waco condenser water loop.
8 = Lexington
Location where 9 = Forsyth Compresso
Multi-State Manuf. Binary Indicates if compressor Inactive = Off
chiller was r 1A
Input, 7 Location 10 = Clarksville Input, 9 1A is running. Active = Running
manufactured. Running
11 = Ft. Smith
12 = Penang Compresso Indicates if compressor
Binary Inactive = Off
13 = Colchester r 1B 1B is running.
Input, 10 Active = Running
14 = Curitiba Running
15 = Taicang Compresso Indicates if compressor
Binary Inactive = Off
16 = Taiwan r 2A 2A is running.
Input, 11 Active = Running
17 = Epinal Running
18 = Golbey
Compresso Indicates if compressor
Binary Inactive = Off
r 2B 2B is running.
Input, 12 Active = Running
Table 46. Binary Output Running
Evaporator Indicates a request
Object Object Relinq Object
Binary Water from the chiller to turn Inactive = Off
Identifier Name Description Default States Input, 17 Pump on the evaporator water Active = On
Allows the Request pump.
Chiller chiller to run if Condenser Indicates a request
Binary Inactive = Stop
Auto Stop conditions for True Binary Water from the chiller to turn Inactive = Off
Output, 1 Active = Auto
Command running are Input, 19 Pump on the condenser water Active = On
met. Request pump.
Resets
Remote Inactive = No Noise Indicates if the chiller is
remotely Binary Inactive = Off
Binary Diagnosti Reset Request Reduction in a state where noise is
diagnostics False Input, 20 Active = On
Output, 2 c Reset Active = Reset Active being reduced.
that can be
Command Request
reset. Evaporator Indicates if water is
Binary Inactive = No Flow
Water Flow flowing through the
Requests Inactive = Input, 22 Active = Flow
Noise Status evaporator.
Binary chiller to enter Normal
Reduction False
Output, 4 mode to Active = Inactive = No
Request Binary Alarm Indicates if an alarm is
reduce noise. Reduced Noise Alarm
Input, 23 Present active.
Active = Alarm
Shutdown Inactive = No
Binary Indicates if a shutdown
Alarm Alarm
Input, 24 alarm is active.
Present Active = None
Binary Last Indicates last diagnostic Inactive = Off
Input, 25 Diagnostic for the chiller. Active = On
86 CG-SVX17E-EN
Table 48. All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects)
CG-SVX17E-EN 87
Table 48. All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)
88 CG-SVX17E-EN
Table 48. All Object Types Sorted by Object Name (Refer to previous tables for detailed descriptions of objects) (continued)
BCI-C Alarming
The BCI-C unit has three binary input points that are used Note: Not all diagnostics are able to be reset remotely.
for communicating alarms and one binary output point Some will require local reset at the chiller front
that is used to reset alarms remotely.Those inputs and panel.
output points are:
BI 23; Alarm PresentThis object indicates if any
alarms are active regardless of severity. A notification
will be sent to any recipients of the Information
Notification Class object when the point transitions
from No Alarm to Alarm.
BI 24; Shutdown Alarm PresentThis object
indicates if any alarms that result in the shutdown of
the chiller are active. A notification will be sent to any
recipients of the Critical Notification Class object when
the point transitions from No Alarm to Alarm.
BI 25; Last DiagnosticThe active text of this object
will reflect the description of the last diagnostic to
occur on the chiller.
BO 2; Remote Diagnostic Reset CommandThis
object is used to remotely reset diagnostics on the
chiller. Immediately after commanding this point value
to 1, the BCI-C will send the reset command to the
chiller and set this point value back to 0 and clear the
priority array.
CG-SVX17E-EN 89
Discharge line
Drain
Service valves Vent valve
Ball valve High pressure side High pressure side Flow
Low pressure side valve switch
Schrader Schrader
Schrader
90 CG-SVX17E-EN
Flow Vent
switch Drain
valve valve Service Discharge line Low pressure side High pressure side
valves ball valve Schrader Schrader
CG-SVX17E-EN 91
Expansion tank
Pump
Gauge
Pressure port
Butterfly Valve
Pressure port
Strainer
Thermostat
92 CG-SVX17E-EN
Junction
Temperature sensor
box
Thermostat
Thermostat
Immersion
heaters
Temperature
sensor
Flow switch
Drain valve
Pressure port
Butterfly valve
Junction
box
Drain Valve
Immersion
Heater
Expansion tank
Handle Pressure port
Gauge Thermostat
pressure Flexible hose Blow down valve
port
CG-SVX17E-EN 93
Immersion
Heaters
Victaulic
coupling
Strainer Temp
sensor
Butterfly
valve
Pressure port
Pressure port
Immersion
Flow switch Heater
94 CG-SVX17E-EN
Immersion
heater
Victaulic coupling
Butterfly valve
Thermostat Immersion
heater
Strainer
Gauge
Blow down valve pressure port
Handle Junction box
Relief Valve
Victaulic
coupling
Immersion
heater
Victaulic
coupling
Temperature
sensor
Immersion
heater
Temperature
Manual sensor
air bleed
Pressure port
Drain valve
Butterfly valve
Flow switch
Pressure port
CG-SVX17E-EN 95
Figure 80. Buffer tank components slant 20-35 ton & V 40-70 ton
Thermostat
Pressure
port
Victaulic
coupling
Junction box
Immersion heater
Temperature Sensor
Schrader
Valve
Temperature
Sensor
Immersion
Heater
96 CG-SVX17E-EN
HPC
Schrader Valve
Immersion Heater
BPHE
Drain Valve
HPC
Temperature Sensor
Temperature Sensor
CG-SVX17E-EN 97
Refrigerant Cycle
Figure 84. CGAM refrigerant circuit
SERVICE VALVE
T P SCHRADER VALVE
ANGLE VALVE
DISCHARGE LINE
EXV
HPC P SCHRADER VALVE
The refrigeration cycle of the Model CGAM chiller is modules (TraneTracerCH530) provide accurate chilled
conceptually similar to otherTrane air-cooled chiller water control and provide monitoring, protection and
products.The CGAM chiller uses a brazed plate evaporator adaptive limit functions.The adaptive nature of the
and an air-cooled condenser.The compressors use suction controls intelligently prevent the chiller from operating
gas cooled motors and an oil management system to outside of its limits, or compensates for unusual operating
provide almost oil-free refrigerant to the condenser and conditions while keeping the chiller running rather than
evaporator for maximum heat transfer while lubricating simply shutting off the chiller. If problems do occur, the
and sealing compressor bearings.The lubrication system CH530 controls provide diagnostic messages to help the
helps to assure long compressor life and contributes to operator in troubleshooting.
quiet operation.
Refrigerant Cycle Description
Refrigerant condensers in the air-cooled heat exchanger
which is available in three configurationsslant, V and The CGAM refrigeration cycle is described using the
Wbased on the CGAM nominal tonnage cooling pressure-enthalpy chart shown in Figure 84 Key State
capacity. Liquid refrigerant is metered into the brazed plate Points 1 through 5 are indicated on the chart. A schematic
evaporator using an electronic expansion valve to showing refrigerant components throughout the system
maximize chiller efficiency at full and part load operation. is shown in Figure 85.
The CGAM chiller is equipped with a unit-mounted starter Refrigerant evaporation occurs in the brazed plate
and control panel. Microprocessor-based unit control evaporator. Metered refrigerant vaporizes as it cools the
chilled water or liquid flowing through the evaporator
98 CG-SVX17E-EN
passages.The refrigerant vapor leaves the evaporator as Figure 85. Pressure/Enthalpy Curve
superheated gas. State Point 1.
Refrigerant vapor generated in the evaporator flows to the
compressor suction manifold where it enters and flows
across the compressor motor windings to provide cooling. Liquid
Pressure
between the compressor scrolls. Refrigerant vapor is
discharged to the air-cooled condenser at State Point 2. 1
5
After the refrigerant vapor condenses into liquid (State
Gas
Points 3 and 4) it is returned to the evaporator (State Point
5) where the refrigerant again flashes into vapor and the
refrigeration cycle repeats. Enthalpy
CG-SVX17E-EN 99
100 CG-SVX17E-EN
CG-SVX17E-EN 101
Display Screens The AUTO and STOP keys, take precedence over the Enter
and Cancel keys. (While a setting is being changed, AUTO
and STOP keys are recognized even if Enter or Cancel has
Basic Screen Format not been pressed.)
The basic screen format appears as: The ALARMS button appears only when an alarm is
present, and blinks (by alternating between normal and
File folder tabs Tab navigator reverse video) to draw attention to a diagnostic condition.
Pressing the ALARMS button takes you to the
corresponding tab for additional information.
102 CG-SVX17E-EN
operator that a diagnostic exists.The second purpose is to Run Inhibit, etc.).The additional info icon will present a
provide navigation to a diagnostic display screen. subscreen that lists in further detail the subsystem modes.
Diagnostic Screen
CG-SVX17E-EN 103
Touching the double arrow to the left of the Active Chilled place of the Auxiliary source. Front Panel Demand Limit
Water Setpoint will take the user to the active chilled water Setpoint will provide navigation to its setpoint change
setpoint arbitration sub-screen. screen.
The chilled water reset status area in the right most column
will display one of the following messages
Return
Constant Return
Outdoor
Disabled
The left column text Front Panel, BAS or Schedule,
External, Auxiliary, Chilled Water Reset, and Active Settings Sub-Screens - Table of Text, Data,
Chilled Water Setpoint will always be present regardless Ranges, etc.
of installation or enabling those optional items. In the Below is the table of text, resolution, field size, enumerated
second column ----- will be shown if that option is Not selections, and data for Settings subscreens. See the
Installed, otherwise the current setpoint from that source functional specification CGAM Settings and Setpoints
will be shown. for further information such as ranges and operation.
Setpoints that are adjustable from the DynaView (Front
Panel Chilled Water Setpoint, Auxiliary Chilled Water
Setpoint) will provide navigation to their respective Table 50. Unit
setpoint change screen via a double-arrow to the right of
Resolution or
the setpoint source text.The setpoint change screen will Description (Enumerations) Units
look identical to the one provided in the Chiller Setpoints
Front Panel Cool Cool Enum
screen.The Back button on the setpoint change screen
Front Panel Chilled Water Setpt: + or - XXX.X Temperature
provides navigation back to the setpoint arbitration
screen. Auxiliary Chilled Water Setpt: + or - XXX.X Temperature
Front Panel Demand Limit Setpt: XXX Percent
The Back button on the setpoint arbitration screen
provides navigation back to the chiller screen. Front Panel Ice Build Cmd: On/Auto Enum
Front Panel Ice Term Setpt: + or - XXX.X Temperature
Other Active Setpoints Front Panel Noise Stb Cmd: On/Auto Enum
The Active Demand Limit Setpoint will behave the same (BAS/Ext/FP, Ext/
was as the Active Chilled Water Setpoint, except that its Setpoint Source: Front Panel, Front Enum
Panel), BAS/Ext/FP
units are in percent and there is an Ice Building source in
104 CG-SVX17E-EN
Resolution or
Table 56. Circuit Manual Control Settings
(Enumerations
Description ), Default Units
Resolution or
(Const Return, (Enumerations), Monitor
Chilled Water Reset: Outdoor, Return, Enum Description Default Units Value
Disable), Disable
(Not Locked Out,
Return Reset Ratio: XXX Percent
Front Panel Ckt Lockout Locked Out), Not Enum
Return Start Reset: XXX.X Temperature Locked Out
Return Maximum Reset: XXX.X Temperature (Not Locked Out,
Cprsr A Lockout Locked Out), Not Enum
Outdoor Reset Ratio: XXX Percent Locked Out
Outdoor Start Reset: XXX.X Temperature (Not Locked Out,
Outdoor Maximum Reset: XXX.X Temperature Cprsr B Lockout Locked Out), Not Enum
Locked Out
CG-SVX17E-EN 105
Table 56. Circuit Manual Control Settings (continued) This screen shows the overall feature enable/disable
setting, plus a listing of all 10 events, including their event
Resolution or time and active days of the week.
(Enumerations), Monitor
Description Default Units Value
(Not Locked Out,
Cprsr C Lockout Locked Out), Not Enum
Locked Out
Manual EXV Control: (Auto, Manual), Auto Enum
EXV
Status
Manual EXV Position Cmd: XXX Percent
Suction
Pressure
Cooling EXV Manual Ctrl: (Auto, Manual), Auto Enum
EXV
Cooling EXV Manual Status
XXX Percent
Position Cmd: Suction
Pressure
Status: (Avail, Not
Avail, Pumpdown) Local Settings Event Screen
Override Subscreen This screen displays the details for a particular event,
command buttons: Suction
Cprsr A Pumpdown Enum including the active days, event time, and the Local
(Abort, Pumpdown) - Pressure
button is either Schedule arbitrated setpoints. Selecting a given item will
grayed out or not allow the user to modify it.
shown if not available
Status: (Avail, Not
Avail, Pumpdown)
Override Subscreen
command buttons: Suction
Cprsr B Pumpdown Enum
(Abort, Pumpdown) - Pressure
button is either
grayed out or not
shown if not available
Status: (Avail, Not
Avail, Pumpdown)
Override Subscreen
command buttons: Suction
Cprsr C Pumpdown Enum
(Abort, Pumpdown) - Pressure
button is either
grayed out or not
shown if not available
106 CG-SVX17E-EN
CG-SVX17E-EN 107
Date/Time Subscreen
All setpoint subscreens will execute the equivalent of a The setpoint screen for setting up the CH530 date is shown
Cancel key if any display activities cause the subscreen to below:The user must select Day, Month, orYear and then
be left before a new setpoint is entered. E.g. If Alarms key use the up/down arrows to adjust.
is pressed before a new setpoint is entered, new setpoint
will be cancelled.The same applies to any time-outs.
Pressing the Auto or Stop keys will not cause a cancel
since the setpoint subscreen is not left on this action.
108 CG-SVX17E-EN
Lockout Screen
Table 58. Report name: System Evaporator
The DynaView Display andTouch Screen Lock screen is
Description Resolution Units
shown.This screen is used if the Display andTouch Screen
Lock feature is Enabled.Thirty minutes after the last key Evap Entering Water Temp: + or - XXX.X Temperature
stroke this screen will be displayed and the Display and Evap Leaving Water Temp: + or - XXX.X Temperature
Touch Screen will be locked out until 159 Enter is Evap Pump Inverter 1 Run Cmd: On, Off Enumeration
entered. Evap Pump 1 Command: On, Off Enumeration
Until the proper password is entered there will be no Evap Pump 2 Command: On, Off Enumeration
access to the DynaView screens including all reports, all Evap Water Flow Switch Status: Flow, No Flow Enumeration
setpoints, and Auto/Stop/Alarms/Interlocks.The
password 159 is not programmable from either Table 59. Report name: Circuit Evaporator
DynaView orTechView.
Description Resolution Units
Suction Pressure XXX.X Pressure
Suction Saturated Rfgt Temp: + or - XXX.X Temperature
Suction Temperature: + or - XXX.X Temperature
Evap Approach Temp: + or - XXX.X Temperature
EXV Position Status: XXX.X Percent
Heating EXV Position Status: XXX.X Percent
CG-SVX17E-EN 109
110 CG-SVX17E-EN
CG-SVX17E-EN 111
point name, value and unit of measure. It reflects active CGAM Unit View is shown below:
setpoints and allows you to make changes.
Unit View also displays, in real time, all non-setpoint data Circuit/Compressor Lockout
organized by tabs. As data changes on the chiller it is
In order to lock out a circuit the user must go to the Unit
automatically updated in the Unit View.
View/Circuit 1 Manual OverridesTab and then select the
Figure 90. Unit view tabs Front Panel Lockout for circuit 1 and/or circuit 2. It is also
possible to lockout individual compressors from the same
Circuit 1 Manual OverridesTab in this view.
112 CG-SVX17E-EN
CG-SVX17E-EN 113
114 CG-SVX17E-EN
CG-SVX17E-EN 115
The items that can be modified show up in white.The To change the setpoint enter a new value for the setpoint
items that cannot be modified show up in gray. into the text field.
Figure 91. Fields in white Figure 92. Change setpoint
116 CG-SVX17E-EN
If the value entered is not valid, an error message will Diagnostics View
display and the change will not occur.
This window lists the active and inactive (history)
Figure 94. Setpoint change failed
diagnostics.There can be up to 60 diagnostics, both active
and historic. For example, if there were 5 active
diagnostics, the possible number of historic diagnostics
would be 55.You can also reset active diagnostics here,
(i.e., transfer active diagnostics to history and allow the
chiller to regenerate any active diagnostics).
Resetting the active diagnostics may cause the chiller to
resume operation.
The Active and History diagnostics have separate tabs. A
button to reset the active diagnostics displays when either
tab is selected.
Configuration View connection and since the last time the Load Configuration
button was selected.
This view is under the CH530 tab and displays the active
configuration and allows you to make changes to the unit
configuration. ConfigurationView allows you to define the
chiller's components, ratings, and configuration settings.
These are all values that determine the required installed
devices, and how the chiller application is run in the main
processor. For example, a user may set an option to be
installed with Configuration View, which will require
devices to be bound using Binding View. And when the
main processor runs the chiller application, the
appropriate steps are taken to monitor required inputs and
control necessary outputs.
Any changes made in the ConfigurationView, on any of the
tabs, will modify the chiller configuration when you click
on the Load Configuration button (located at the base of
the window).The Load Configuration button uploads the
new configuration settings into the main processor.
Selecting the Undo All button will undo any configuration
setting changes made during the presentTechView
CG-SVX17E-EN 117
118 CG-SVX17E-EN
Software view allows you to verify the version of chiller You can also add up to two available languages to load into
software currently running on the EasyView or DynaView the DynaView. Loading an alternate language file allows
the DynaView to display its text in the selected alternate
language, English will always be available.
Figure 99. Software view
CG-SVX17E-EN 119
Binding View and categories. Binding View allows you to add, remove,
modify, verify, and reassign devices and options in order
Binding View allows you to assess the status of the to match the configuration requirements.
network and all the devices connected as a whole, or the
status of individual devices by using status icons and Whenever a device is installed, it must be correctly
function buttons. configured to communicate and to function as intended.
This process is called binding. Some features of Binding
Binding View is essentially a table depicting what devices View are intended to serve a second purpose; that is
and options are actually discovered on the network bus diagnosing problems with communication among the
(and their communication status) versus what is required devices.
to support the configuration defined by the feature codes
Figure 100. Binding view
120 CG-SVX17E-EN
Verify that the compressor oil sump heaters are Start the chilled water pump to begin circulation of the
installed tightly around the compressor. Energize and water. Inspect all piping for leakage and make any
verify heaters are operational using a temperature necessary repairs.
probe. See Table 68, p. 121.
With water circulating through the system, adjust
Table 68. Compressor oil sump heater summary(a) water flow and check water pressure drop through the
Heater Grp Heater Description Heater Designation(s) evaporator.
Compr 1A, Ckt 1 3M1E1 Prove all Interlock and InterconnectingWiring Interlock
Compr 1B, Ckt 1 3M2E1 and External.
Compressor Compr 1C, Ckt 1 3M3E1
Check and set, as required, all CH530 Menu Items.
Oil Sump Compr 2A, Ckt 2 4M1E1
Compr 2B, Ckt 2 4M2E1 Stop the chilled water pump.
Compr 2C, Ckt 2 4M3E1
(a) Not all heaters are present on all unit configurations. See schematics and
component locations in sectionUnit Wiring, p. 151.
CG-SVX17E-EN 121
NOTICE:
This exceeds the maximum allowable (2%) by 0.2 percent. Equipment Damage!
Do not interchange any load leads that are from the
unit contactors or the motor terminals.
122 CG-SVX17E-EN
WARNING
Hazardous Voltage!
Disconnect all electric power, including remote
disconnects before servicing. Follow proper lockout/
tagout procedures to ensure the power can not be
inadvertently energized. Failure to disconnect power
before servicing could result in death or serious injury.
Water System
Flow Rates
NOTICE:
Equipment Damage!
Establish a balanced chilled water flow through the
evaporator. The flow rates should fall between the
minimum and maximum values. Flow rates outside the
recommended range could cause evaporator failure.
Pressure Drop
Measure water pressure drop through the evaporator at
the field-installed pressure taps on the system water
piping. Use the same gauge for each measurement.
Measure flow at the field-installed supply and return.This
will include valves, strainers, and fittings in the pressure
drop readings.
Pressure drop readings should be approximately those
shown in the Pressure Drop Charts in the Installation-
Mechanical section.
CG-SVX17E-EN 123
***This checklist is not intended to be a substitution for the contractors installation instruction.
This checklist is intended to be a guide for the Trane technician just prior to unit start-up. Many of the recommended checks and actions could expose the
Pre-Start Checkout
1.) Unit clearances adequate for service and to avoid air recirculation etc.
2.) Unit exterior inspected
3.) Compressor oil sump heaters connected tightly a n d working properly for 24 hours prior to arrival of Trane technician performing start up
4.) Correct voltage supplied to unit and electric heaters (imbalance not to exceed 2%)
5.) Unit power phasing (A-B-C sequence) proper for compressor rotation and pump rotation.
6.) Copper power wiring meets sizing requirement in job submittal
7.) Unit properly grounded
8.) All automation and remote controls installed/wired
9.) All wiring connections tight
10.) Prove chilled water side Interlock and Interconnecting Wiring Interlock and externals (chilled water pump)
11.) Field installed control wiring landed on correct terminals (external start/stop, emergency stop, chilled water reset)
12.) Verify all refrigerant and oil valves are open/back seated
13.) Pump Package (if installed)
a.) Pump shaft able to rotate freely
b.) Full of working fluid
c.) Shutoff valve in open position .Flush line valves in open position .
d.) Automatic air bleed functioning properly
e.) Relief valve functioning properly
CG-SVX17E-EN
14.) Compressor oil levels (1/2 -3/4 high in glass) proper
CG-SVX17E-EN
15.) Verify chilled water strainer is clean and free of debris and evaporator chilled water circuits are filled
16.) Close the fused-disconnect switch(es) that supplies power to the chilled water pump starter
17.) Start the chilled water pump to begin circulation of the water. Inspect piping for leaks and repair as necessary
Pre-Start Checkout
18.) With water circulating through the system, adjust water flow and check water pressure drop through
evaporator
19.) Adjust the chilled water flow switch for proper operation
20.) Return chilled water pump to auto
125
Unit Start-Up Procedures
Sequence of Operation
Power Up software model will always transition through the
'Stopped' Software state independent of the last mode. If
The Power up chart shows the respective DynaView
the last mode before power down was 'Auto', the
screens during a power up of the main processor.This
transition from 'Stopped' to 'Starting' occurs, but it is not
process takes from 30 to 45 seconds depending on the
apparent to the user.
number of installed Options. On all power ups, the
Figure 101. Power up
Last Mode
Apply
i.e. Auto
Control Self Test Starting Application
or Stopped
Power
as Shown
Note: The variation in DynaView Power up time is
dependent on the number of installed options.
Last Mode Was Auto Call for Cooling: Differential to Start is met
Auto Auto
Power Run
(Waiting for Evaporator (Waiting for Waiting to Start Waiting to Start
Power Up Inhibited
Water Flow) a Need to Cool) Start
Applied CH530 Command
Enforce Power Up Confirm Evaporator EXV stroke to Wait for Pressure
Boot Time Start Delay Timer Water Flow Waiting for Stabilization to Lead
(30 to 40 Sec) Differential to Start Preposition Cprsr*
(adj 0 to 10 mins) (10 Second Filter) (3 Seconds)
Energize Evaporator
Water Pump Relay
Pre-Position EXV
of Lead Circuit*
Confirm Evaporator Water
Flow Within 20 minutes
Fan Pre-Start
(10 Sec Filter)
of Lead Circuit*
126 CG-SVX17E-EN
Stopped to Starting:
The stopped to starting diagram shows the timing from a NOTICE:
stopped mode to energizing the compressor.The shortest
allowable time would be under the following conditions: Compressor Damage!
6. No motor restart inhibit Use only refrigerant specified on the unit nameplate (R-
410A) and OIL00080 (1 gallon). Failure to do so may
7. Evaporator Water flowing cause compressor damage and improper unit
8. Power up Start DelayTimer has expired operation.
9. Adjustable Stop to StartTimer has expired
10. Need to cool
The above conditions would allow the compressor to start NOTICE:
in 60 seconds. Equipment Damage!
Important: If both suction and discharge pressures are Ensure that the oil sump heaters have been operating
low but sub-cooling is normal, a problem for a minimum of 24 hours before starting. Failure to do
other than refrigerant shortage exists. Do so may result in equipment damage.
not add refrigerant, as this may result in
overcharging the circuit.
Figure 103. Chiller state chart
Power Up
CGAM Sequence of Operation:
Chiller State Chart
Boot and
Stopped Self Test
or
Run Inhibit
ed Co Auto
rm mm
nfi wn
Co utdo an
d
Sh
Re
of leas
Inh e
ibi
t
Auto
Shutting Down or
Stop Command or Diagnostic Waiting to Start
Sto
pC
om
m art
Di an
d St
ag ed
no rm Check for
sti Running nfi Differential
c Co
or to Start
Running Limit
Check for
Differential
to Stop
Equipment Damage! 3. Close the fused-disconnect switch for the chilled water
pump. Energize the pump(s) to start water circulation.
Ensure that the oil sump heaters are connected
properly and are operating properly for a minimum of 4. Check the service valves on the discharge line, suction
24 hours before starting. Failure to do so may result in line, oil line and liquid line for each circuit.These valves
equipment damage. must be open (backseated) before starting the
compressors.
If pre-start checkout has been completed, unit is ready to
start.
CG-SVX17E-EN 127
128 CG-SVX17E-EN
Local Stop
Normal Shutdown Diagnostic*, Latched
Normal Shutdown Diagnostic*, Non-Latched
BAS Stop
External Auto-Stop
Local Schedule Stop
Shutting Down Stopped
Shutting Down Shutting Down
Running (Evaporator Water or
(Operational Pumpdown) (Operational Pumpdown)
Pump Off Delay) Run Inhibit
Waiting for EXV to Close Waiting for Saturated Suction Time out Evap Pump Off Delay
(0 to 10 Seconds) Temperature to fall to 0 Degrees F (adj 0-30 minutes) De-Energize Evaporator
(Less than 30 Seconds)
Water Pump
Close EXV
De-Energize Pumpdown
Confirm Pumpdown Compressors
Termination. See Note***
*** If normal pumpdown termination does not occur within the Pumpdown Timeout
CG-SVX17E-EN 129
130 CG-SVX17E-EN
CG-SVX17E-EN 131
Monthly Maintenance Clean the condenser coils. Refer to Coil Cleaning in this
manual.
Complete all weekly maintenance procedures.
Measure and record the evaporator superheat. Refer to WARNING
Evaporator Superheat. Rotating Components!
Measure and record the system subcooling. Refer to The following procedure involves working with
System Subcooling. rotating components. Disconnect all electric power,
Manually rotate the condenser fans to ensure that there is including remote disconnects before servicing. Follow
proper lockout/ tagout procedures to ensure the power
proper clearance on the fan shroud openings.
can not be inadvertently energized. Failure to
disconnect power before servicing could result in
WARNING rotating components cutting and slashing technician
Rotating Components! which could result in death or serious injury.
The following procedure involves working with
rotating components. Disconnect all electric power, Clean the condenser fans. Check the fan assemblies for
including remote disconnects before servicing. Follow proper clearance in the fan shroud openings and for motor
proper lockout/ tagout procedures to ensure the power shaft misalignment or abnormal end-play, vibration and
can not be inadvertently energized. Failure to noise.
disconnect power before servicing could result in
rotating components cutting and slashing technician
which could result in death or serious injury.
Compressor Service Information
Compressor Electrical Connections
Annual Maintenance
It is very important that CSHD compressors used inTrane
Complete all weekly and monthly maintenance checks. Model CGAM chillers are wired correctly for proper
Check the oil level and refrigerant charge. Routine rotation.These compressors will not tolerate reverse
changing of oil is not required. rotation. Verify correct rotation/phasing using a rotation
Have a qualified laboratory perform a compressor oil meter. Proper phasing is clockwise, A-B-C. If wired
analysis to determine system moisture content and acid incorrectly a CSHD compressor will make excessive noise,
level.This analysis is a valuable diagnostic tool. will not pump and will draw about half the normal current.
It will also become very hot if allowed to run for an
Contact a qualified service provider to leak test the chiller, extended period.
check operating and safety controls, and to inspect
electrical components for proper operation. Leak testing NOTICE:
my be accomplished using soap solution or with electronic
or ultrasonic leak detectors. Compressor Failure!
Inspect all piping components for leaks and damage. Do not bump the compressor to check rotation as
incorrect rotation could cause compressor motor failure
Clean all water strainers.
in as little as 4 to 5 seconds!
NOTICE:
It is also very important that CSHN compressors used in
Equipment Damage! Trane Model CGAM chillers are wired correctly for proper
If the CGAM chiller evaporator or evaporator water rotation. Correct rotation of CSHN compressors is also
piping is drained of water, the evaporator immersion clockwise, with A-B-C phasing. Improper rotation of the
heater must be de-energized. Failure to de-energize the CSHN compressors is indicated by a compressor module
heater will cause it to burn out. trip, noisy operation, no pressure difference on manifold
gauges and low amp draw.
Clean and repaint any components that show corrosion.
Motor Protection
Internal motor protection is provided on model CSHN
compressors (15, 20, 25 and 30T sizes). LED indicators are
as follows:
Green No Fault
Red Fault
See Table 73, p. 133 for fault diagnostic indications on the
protection module. Manual reset is required at the
module.
132 CG-SVX17E-EN
CG-SVX17E-EN 133
Note: The service pumpdown algorithm expects the compressor. If the oil is drained below the level of the oil
liquid line service valve to be closed during service level sight glass, it will be below the oil equalizer line level.
pumpdown.The EXV will open, allowing the Pressurize the low side of the compressor using nitrogen
refrigerant between the liquid line service valve to help drain the oil. No more than 10 psig of pressure will
and EXV to be pumped out. be needed.
Service pump down is complete when: CSHD Compressors
Service pump down time expires (60 x (100/circuit CSHD compressors do not have an oil drain valve.
capacity %)) Therefore, before removing the oil equalizer line, the
Saturated evaporator pressure falls below Low system refrigerant charge must be recovered before
Pressure Cutout x1.15 for one second draining the oil. Use a catch pan to catch the oil when the
After pump down terminates, the MP automatically puts compressor oil equalizer line is loosened to ensure that oil
circuit into lockout. Pump down can also be terminated by does not spill out of the compressor when the equalizer
Abort Pump down in service tool, an immediate line is removed.The torque value for the Rotolock fitting
shutdown diagnostic occurs or a pressure transducer fails. on CSHD compressors is 64 ft.-lbs., plus or minus 2 ft.-lbs.
W Unit
Slant Unit V Unit
2C 1C
2B 1B
1B
2B 1B
1A 2A 1A
2A 1A
134 CG-SVX17E-EN
CG-SVX17E-EN 135
Compressor oil sump heaters must be energized at least Note: Strainer maintenance is critical to proper operation
24 hours before starting the CGAM chiller.This is required and reliability. Any particles larger than 1mm
to boil refrigerant out of the oil before startup. Ambient entering the BPHE evaporator may cause the
temperature is not a factor and the oil sump heaters must evaporator to fail, requiring replacement.
always be energized prior to startup. Acceptable BPHE evaporator water flow rate is 1.5 to 3.6
GPM per nominal unit ton capacity.To maintain 54-44 F in/
Condenser Maintenance out chilled water temperatures, the nominal water flow
rate is 2.4 GPM per ton.
Condenser Coil Cleaning Minimum water flow rate must be maintained to avoid
laminar flow, potential evaporator freezing, scaling and
WARNING poor temperature control.The microprocessor and
capacity control algorithms are designed to take a 10
Hazardous Chemicals! percent change in water flow rate per minute while
Coil cleaning agents can be either acidic or highly maintaining a 2F (1.1C) leaving water temperature
alkaline and can burn severely if contact with skin control accuracy.The chiller tolerates up to 30 percent per
occurs. Handle chemical carefully and avoid contact minute water flow variation as long as the flow is equal to
with skin. ALWAYS wear Personal Protective Equipment or greater than minimum flow requirements.
(PPE) including goggles or face shield, chemical
resistant gloves, boots, apron or suit as required. For Maximum water flow is 18 feet per second. Flow rates
personal safety refer to the cleaning agent greater than this will cause excessive erosion.
manufacturers Materials Safety Data Sheet and follow
The BPHE evaporator is difficult to clean should it become
all recommended safe handling practices. Failure to
follow all safety instructions could result in death or plugged with debris. Indications of a plugged BPHE
serious injury. evaporator include wet suction due to lack of heat
exchange, loss of superheat control, depressed discharge
Clean the condenser coils at least once a year or more superheat (<63F), compressor oil dilution and/or
frequently if the unit is in a dirty environment. A clean starvation and premature compressor failure.
condenser coil will help to maintain chiller operating
efficiency. Follow the detergent manufacturer's Evaporator Replacement
instructions to avoid damaging the condenser coils. If the CGAM evaporator requires replacement, it is very
To clean the condenser coils use a soft brush and a sprayer important that the new evaporator be replaced correctly
such as a garden pump type or a high-pressure type. A and with the correct refrigerant and water piping
high quality detergent such asTrane Coil Cleaner (Part No. connections.The refrigerant inlet/liquid connection is at
CHM-00255) is recommended. the bottom of the evaporator and the refrigerant outlet/
suction connection is at the top of the evaporator and both
Refer to RTAC-SVG01B-EN for maintenance and cleaning
are on the same side. Pay particular attention to
procedures.
evaporators with dual circuits. Avoid cross-circuiting
Note: If detergent mixture is strongly alkaline (pH value when installing the new evaporator.
greater than 8.5, an inhibitor must be added).
136 CG-SVX17E-EN
CG-SVX17E-EN 137
138 CG-SVX17E-EN
CG-SVX17E-EN 139
Evaporator Water Flow Lost Immediate After the pump request was activated, water
and flow was established and then lost. Special
Evaporator Water Flow Lost Chiller NonLatch All Remote
Special action is to keep the evap pump request
Evap Water Flow Lost Action active in a diagnostic override mode.
Evaporator Water Flow Lost Pump 1 Warning For dual evaporator pump configurations
and only. Evaporator Water Flow Lost diagnostic
Evaporator Water Flow Lost Pump 1 Chiller NonLatch All Remote
Special occurred while Pump 1 was the selected
Evap Water Flow Lost Action pump.
140 CG-SVX17E-EN
Evaporator Water Flow Lost Pump 2 Warning For dual evaporator pump configurations
and only. Evaporator Water Flow Lost diagnostic
Evaporator Water Flow Lost Pump 2 Chiller NonLatch All Remote
Special occurred while Pump 2 was the selected
Evap Water Flow Lost Action pump.
Evaporator Water Flow Lost Lockout Four (4) water flow loss events occurred in
a moving 4 day time window. Corrective
Evaporator Water Flow Lost Lockout Chiller Immediate Latch All Local
action is needed to identify and eliminate the
Evap Water Flow Lost Lockout cause.
After the pump request was activated, the
Evaporator Water Flow Overdue Immediate evaporator water flow overdue wait time
and elapsed before water flow was established.
Evaporator Water Flow Overdue Chiller NonLatch All Remote
Special Special action is to keep the evap pump
Evap Water Flow Overdue Action request active in a diagnostic override
mode.
Evaporator Water Flow Overdue Pump 1 Warning For dual evaporator pump configurations
and only. Evaporator Water Flow Overdue
Evaporator Water Flow Overdue Pump 1 Chiller NonLatch All Remote
Special diagnostic occurred while Pump 1 was the
Evap Water Flow Overdue Action selected pump.
Evaporator Water Flow Overdue Pump 2 Warning For dual evaporator pump configurations
and only. Evaporator Water Flow Overdue
Evaporator Water Flow Overdue Pump 2 Chiller NonLatch All Remote
Special diagnostic occurred while Pump 2 was the
Evap Water Flow Overdue Action selected pump.
Evaporator Water Flow Too Low Cooling Mode Refrigerant side to water side heat balance
Evaporator Water Flow Too Low Chiller Immediate Latch [Not Cooling indicates that water flow has dropped below Local
Evap Water Flow Too Low Mode] allowable manufacturer limits.
a. Function Not Enabled: no diagnostics.
B. Enabled : Out-Of-Range Low or Hi or
External Chilled/Hot Water Setpoint bad LLID, set diagnostic, default CWS/HWS
External Chilled/Hot Water Setpoint Chiller Warning NonLatch All to next level of priority (e.g. Front Panel Remote
Ext Chilled/Hot Water Setpt SetPoint). This Warning diagnostic will
automatically reset if the input returns to the
normal range.
a. Function Not Enabled: no diagnostics.
B. Enabled : Out-Of-Range Low or Hi or
External Demand Limit Setpoint bad LLID, set diagnostic, default DLS to next
External Demand Limit Setpoint Chiller Warning NonLatch All level of priority (e.g. Front Panel SetPoint). Remote
External Demand Limit Setpt This Warning diagnostic will automatically
reset if the input returns to the normal
range.
Fan Fault
Fan Fault Circuit Warning Latch All The fan deck is indicating a fault. Local
Fan Fault
Fan Inverter Fault Ckt Energized The fan inverter fault input is ignored for the
Fan Inverter Fault Circuit Warning NonLatch [Ckt Not first 5 seconds of start up to allow variable Local
Fan Inverter Fault Energized]All speed drives to power up.
For systems with no evaporator pump, a
single evaporator pump, or a single inverter
driving dual evaporator pumps, an
immediate shutdown shall be performed.For
multiple pump systems, detection of a pump
Normal fault will generally cause pump control to
Fault Detected: Evaporator Water Pump 1 Immediate switch to the redundant pump. For single
or Warning inverter, dual pump configuration, switching
Fault Detected: Evaporator Water Pump 1 Chiller NonLatch All Remote
and to the redundant pump can only happen
Fault: Evap Water Pump Special after the fault is cleared. For systems with
Action no evaporator pump or a single evaporator
pump, a normal shutdown shall be
performed. For multiple pump systems,
detection of a pump fault will generally
cause pump control to switch to the
redundant pump.
CG-SVX17E-EN 141
142 CG-SVX17E-EN
Low Differential Refrigerant Pressure The system differential pressure for the
Ckt Energized
respective circuit was below 90 psid for more
Low Differential Refrigerant Pressure Circuit Normal Latch [Ckt Not Local
than 4000 psid-sec, with a 2.5 minute ignore
Low Differential Rfgt Press Energized]
time from the start of the circuit.
The discharge saturated temperature for the
Low Discharge Saturated Temperature Ckt Energized respective circuit was below 20 C for more
Low Discharge Saturated Temperature Circuit Normal Latch [Ckt Not than 3750 C-sec, with a 10 minute ignore Local
Low Discharge Sat Temp Energized] time from the start of the circuit. Integration
starts after the ignore time is completed.
The leaving chilled water temperature fell below
the leaving water temp cutout setting for 30 degree
F seconds while the Chiller is in the Stop mode, or
in Auto mode with no compressors running.
Energize Evap Water pump Relay until diagnostic
Unit in Stop auto resets, then return to normal evap pump
Low Evap Leaving Water Temp: Unit Off Chiller Warning Mode, or in Auto control. Automatic reset occurs when the temp
and Mode and No rises 2qF above the cutout setting for 30 minutes.
Low Evap Leaving Water Temp: Unit Off or NonLatch Remote
Special Ckt(s) Energized When this diagnostic is active AND Leaving Water
Low Evap Leav Wtr Temp: Off Circuit
Action [Any Ckt Temperature sensor diagnostic (loss of comm or
Energized] out of range) the Evap Water pump relay shall be
de-energized.
If evaporator protection temperature
sensors are installed, the effect is on the
appropriate circuit. Else, the effect is on the
chiller.
CG-SVX17E-EN 143
MP: Could not Store Starts and Hours MP has determined there was an error with
the previous power down store. Starts and
MP: Could not Store Starts and Hours Platform Warning Latch All Remote
Hours may have been lost for the last 24
MP: Starts and Hours Failure hours.
MP: Non-Volatile Block Test Error MP has determined there was an error with
MP: Non-Volatile Block Test Error Platform Warning Latch All a block in the Non-Volatile memory. Check
MP: NV Block Test Error settings.
MP: Non-Volatile Memory Reformatted MP has determined there was an error in a
MP: Non-Volatile Memory Reformatted Platform Warning Latch All sector of the Non-Volatile memory and it was Remote
MP: NV Memory Reformatted reformatted. Check settings.
The main processor has successfully come
out of a reset and built its application. A
MP: Reset Has Occurred reset may have been due to a power up,
MP: Reset Has Occurred Chiller Warning NonLatch All installing new software or configuration. NA
MP: Reset Has Occurred This diagnostic is immediately and
automatically cleared and thus can only be
seen in the historic diagnostic list.
No Partial Heat Recovery Ckt Energized PHR entering water temperature is greater than
No Partial Heat Recovery Circuit Warning NonLatch [Ckt Not the discharge temperature by 1.11qC for 30
No Partial Heat Recovery Energized] continuous minutes.
This diagnostic is only effective if all the following
requirements are met: 1) Unit is running. 2) THR
Control is enabled. 3) THR entering water
temperature is less than 4qC, or discharge
temperature integral is greater than Discharge
Temperature Integral Limit in all the energized
circuits.
Unit energized
It shall be de-activated when any one of the
No Total Heat Recovery and THR control
Heat Normal following requirement is met: 1) THR entering
No Total Heat Recovery NonLatch enabled [Unit Remote
Recovery Warning water temperature is greater than 5qC., and the
No Total Heat Recovery de-energized or
discharge saturated temperature is greater than
THR disabled]
minimum discharge saturated temperature in at
least one energized circuit, see Total Heat
Recovery Control Algorithm specification for
details. 2) THR entering water temperature is
invalid (comm loss or sensor diagnostic). 3) Total
Heat Recovery Control disabled. 4) No
compressor energized.
144 CG-SVX17E-EN
CG-SVX17E-EN 145
146 CG-SVX17E-EN
Communication Diagnostics
Note: The following communication loss diagnostics will functional output associated with it. A comm loss
not occur unless that input or output is required to with such a multiple function board, will generate
be present by the particular configuration and multiple diagnostics. Refer to the Chillers wiring
installed options for the chiller. 2. Communication diagrams to relate the occurrence of multiple
diagnostics (with the exception of Excessive Loss communication diagnostics back to the physical
of Comm are named by the Functional Name of llid boards that they have been assigned to
the input or output that is no longer being heard (bound).
from by the Main Processor. Many LLIDs, such as
the Quad Relay LLID, have more than one
Table 80. Communication diagnostics
Activ
e
Mode
s [In-
active
Persis Mode Reset
Diagnostic Name Affects Severity - tence s] Criteria Level
Comm Loss: Anti-Freeze Heater Relay Warning
Continual loss of communication between the MP and
and
Comm Loss: Anti-Freeze Heater Relay Chiller Latch All the Functional ID has occurred for a 35-40 second Remote
Special
Comm: Anti-Freeze Heater Rly period.
Action
Continual loss of communication between the MP and
Comm Loss: Auxiliary Setpoint Command Warning
the Functional ID has occurred for a 35-40 second
and
Comm Loss: Auxiliary Setpoint Command Chiller Latch All period. Chiller shall discontinue use of the Auxiliary Remote
Special
Comm: Auxiliary Setpt Cmd Setpoint and revert to the Chilled Water Setpoint
Action
based on setpoint arbitration
Comm Loss: Compressor Fault Input Continual loss of communication between the MP and
Comm Loss: Compressor Fault Input Cprsr Immediate Latch All the Functional ID has occurred for a 35-40 second Remote
Comm: Compressor Fault Input period.
Comm Loss: Compressor Run Command Continual loss of communication between the MP and
Comm Loss: Compressor Run Command Cprsr Immediate Latch All the Functional ID has occurred for a 35-40 second Remote
Comm: Cprsr Run Command period.
Comm Loss: Cooling EXV Continual loss of communication between the MP and
Comm Loss: Cooling EXV Circuit Immediate Latch All the Functional ID has occurred for a 35-40 second Remote
Comm: Cooling EXV period.
Comm Loss: Discharge Pressure Transducer Continual loss of communication between the MP and
Comm Loss: Discharge Pressure Transducer Circuit Immediate Latch All the Functional ID has occurred for a 35-40 second Remote
Comm: Discharge Press Xdcr period.
Comm Loss: Discharge Temperature Sensor Continual loss of communication between the MP and
Comm Loss: Discharge Temperature Sensor Circuit Immediate Latch All the Functional ID has occurred for a 35-40 second Remote
Comm: Discharge Temp Sensor period.
Comm Loss: Electronic Expansion Valve Continual loss of communication between the MP and
Comm Loss: Electronic Expansion Valve Circuit Immediate Latch All the Functional ID has occurred for a 35-40 second Remote
Comm: EXV period.
Comm Loss: Emergency Stop Continual loss of communication between the MP and
Comm Loss: Emergency Stop Chiller Normal Latch All the Functional ID has occurred for a 35-40 second Remote
Comm: Emergency Stop period.
Comm Loss: Evap Entering Water Temp Continual loss of communication between the MP and
Comm Loss: Evap Entering Water Temp Chiller Normal Latch All the Functional ID has occurred for a 35-40 second Remote
Comm: Evap Ent Water Temp period.
Comm Loss: Evap Leaving Water Temp Continual loss of communication between the MP and
Comm Loss: Evap Leaving Water Temp Chiller Normal Latch All the Functional ID has occurred for a 35-40 second Remote
Comm: Evap Leav Water Temp period.
Comm Loss: Evap Pump Inverter 1 Fault Input Continual loss of communication between the MP and
Comm Loss: Evap Pump Inv 1 Fault Input Chiller Normal Latch All the Functional ID has occurred for a 35-40 second Remote
Comm: Evap Pmp Inv 1 Flt Inp period.
Comm Loss: Evap Pump Inverter 1 Frequency
Feedback Continual loss of communication between the MP and
Chiller Normal Latch All the Functional ID has occurred for a 35-40 second Remote
Comm Loss: Evap Pump Inv 1 Freq Feedback
period.
Comm: Evap Pmp Inv 1 Freq
Comm Loss: Evap Pump Inverter 1 Run Command Continual loss of communication between the MP and
Comm Loss: Evap Pump Inverter 1 Run Cmd Chiller Normal Latch All the Functional ID has occurred for a 35-40 second Remote
Comm: Evap Pmp Inv 1 Run Cmd period.
CG-SVX17E-EN 147
Comm Loss: External Heat Recovery Input Warning Continual loss of communication between the MP and
Heat
and the Functional ID has occurred for a 35-40 second
Comm Loss: External Heat Recovery Input Recover Latch All Remote
Special period. External input is excluded from arbitration
Comm: Ext Heat Recovery Inp y
Action logic per standard arbitration rules.
Comm Loss: External Ice Building Control Input Continual loss of communication between the MP and
the Functional ID has occurred for a 35-40 second
Comm Loss: Ext Ice Building Ctrl Input Chiller Warning Latch All Remote
period. Chiller shall revert to normal (non-ice
Comm: Ext Ice Building Ctrl building) mode regardless of last state.
Comm Loss: External Night Noise Setback Input Warning Continual loss of communication between the MP and
and the Functional ID has occurred for a 35-40 second
Comm Loss: Ext Night Noise Setback Input Chiller Latch All Remote
Special period. External input is excluded from arbitration
Comm: Ext Night Noise Inp Action logic per standard arbitration rules.
Comm Loss: Fan Control Relays Continual loss of communication between the MP and
Comm Loss: Fan Control Relays Circuit Immediate Latch All the Functional ID has occurred for a 35-40 second Remote
Comm: Fan Control Relays period.
Comm Loss: Fan Fault Continual loss of communication between the MP and
Comm Loss: Fan Fault Circuit Warning Latch All the Functional ID has occurred for a 35-40 second Remote
Comm: Fan Fault period.
Comm Loss: Fan Inverter Fault Warning Continual loss of communication between the MP and
and the Functional ID has occurred for a 35-40 second
Comm Loss: Fan Inverter Fault Circuit Latch All Remote
Special period. Revert to fixed-speed fan algorithm using
Comm: Fan Inverter Fault Action remaining fans.
Comm Loss: Fan Inverter Speed Command Warning Continual loss of communication between the MP and
and Non the Functional ID has occurred for a 35-40 second
Comm Loss: Fan Inverter Speed Command Circuit All Remote
Special Latch period. Revert to fixed-speed fan algorithm using
Comm: Fan Inverter Speed Cmd Action remaining fans.
Comm Loss: Heat Recovery Entering Water Continual loss of communication between the MP and
Temperature Sensor Heat
Warning or the Functional ID has occurred for a 35-40 second
Recover Latch All Remote
Comm Loss: HR Entering Water Temperature Normal period. Warning for Partial Heat Recovery. Normal
y
Comm: HR Entering Water Temp shutdown for Total Heat Recovery.
Comm Loss: Heat Recovery Leaving Water
Temperature Sensor Heat Continual loss of communication between the MP and
Recover Warning Latch All the Functional ID has occurred for a 35-40 second Remote
Comm Loss: HR Leaving Water Temperature
y period.
Comm: HR Leaving Water Temp
Comm Loss: Heat Recovery Three Way Valve Heat Continual loss of communication between the MP and
Comm Loss: Heat Recovery Three Way Valve Recover Normal Latch All the Functional ID has occurred for a 35-40 second Remote
Comm: HR Three Way Valve y period.
Comm Loss: Heat/Cool Switch Continual loss of communication between the MP and
Comm Loss: Heat/Cool Switch Chiller Normal Latch All the Functional ID has occurred for a 35-40 second Remote
Comm: Heat/Cool Switch period.
148 CG-SVX17E-EN
CG-SVX17E-EN 149
150 CG-SVX17E-EN
CG-SVX17E-EN 151
Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice.