Contents
Page
Transducer Survey. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
General description and technical data . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Transducers DU for AC voltage. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Transducers DI for AC current. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Transducers DUD for DC voltage and DID for DC current. . . . . . . . . 19
Transducers DF for frequency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Transducers for power factor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Transducers DP, DQ and DPQ for active and reactive power. . . . . . . 26
Transducers DP for active power. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Transducers DQ for reactive power . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Transducers DPQ for active and reactive power. . . . . . . . . . . . . . . . . . 43
Transducers DR for resistance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Dimensions and weights. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Transducer Survey
Type Function Output config. Auxiliary Case Page
AC Voltage
DU 120 AC voltage A Utan hjlpspnning C1 13
DU 121 AC voltage A, B, C, D 92 138 V AC C1 13
DU 122 AC voltage A, B, C, D 184 276 V AC C1 13
AC current
DI 120 AC current A Utan hjlpspnning C1 17
DI 121 AC current A, B, C, D 92 138 V AC C1 17
DI 122 AC current A, B, C, D 184 276 V AC C1 17
DC Voltage
DUD 124 DC voltage A, B, C, D, I, K, L 18 80 V AC/DC C3 20
DUD 125 DC voltage A, B, C, D, I, K, L 80 276 V AC/DC C3 20
DC Curren
DID 124 DC current A, B, C, D, I, K, L 18 80 V AC/DC C3 20
DID 125 DC current A, B, C, D, I, K, L 80 276 V AC/DC C3 20
Frequency
DF 03-04 2-wire, ph/n or ph/ph A, B 19 58 V AC/DC C3 22
88 264 V AC/DC
Power Factor
24
4
Transducer Survey
Type Function Output config. Auxiliary Case Page
Active Power
DP 124 1E, 1-phase/2-wire, (ph/n) A, B, I, K, L 18 80 V AC/DC C3 29
DP 125 1E, 1-phase/2-wire, (ph/n) A, B, I, K, L 80 276 V AC/DC C3 29
Reactive Power
DQ 134 1E, 3-wire, balanced load A, B, I, K, L 18 80 V AC/DC C3 38
DQ 135 1E, 3-wire, balanced load A, B, I, K, L 80 276 V AC/DC C3 38
5
Transducer Survey
Type Function Output config. Auxiliary Case Page
DPQ 334 3E, 3- or 4-wire, unbalanced load , without connected neutral A, B, I, K, L 18 80 V AC/DC C4 48
DPQ 335 3E, 3- or 4-wire, unbalanced load, without connected neutral A, B, I, K, L 80 276 V AC/DC C4 48
6
Transducer Survey
Type Function Output config. Auxiliary Case Page
Resistance/Temperature
DR 134 Pot A, B, C, D 18 80 V AC/DC C3 51
DR 135 Pot A, B, C, D 80 276 V AC/DC C3 51
7
General description and technical data
In this catalogue, Cewe Instrument presents BLUE MO- an explanation of working principle, block diagram, and
DULE, a wide range of Transducers for DIN-rail and general data.
panel mounting. The output from our transducers are within certain limits
Thanks to high performance and high reliability e. g. a independent of load. The load limits are given in a data
MTBF of 40 years for current transducers, Cewe Instru- sheets. The load independence is obtained by a certain
ment transducers have obtained a wide clientele. The feedback of the output signal to the amplifier. These trans-
transducers are used by industries and power companies in ducer charactaristics give great advan-tages among which
around 40 countries in Europe as well as in all parts of the the most important are mentioned below.
world. Cewe Instruments transducer are also produced on 1. Measuring values can be transmitted over relatively long
licence in China. distances.
Below follows general information on electrical measur- 2. Within the framework of the permitted output signal
ing transducers with examples of application, definition loadings, several measuring or registration units can be
of terms and some common data for Cewe Instrument connected simultane-ously to the same transducer. No
transducers. For each group of transducers then follows special tuning is required.
P~
Computer
dP 134
Cl 48
B0086 GB
Cl 96
3. No adjustment for wire resistance need to be made in 5. Individual instruments or other measuring or registration
connected instruments. units can be disconnected from a circuit after short-circui-
4. The actual wiring is simple and inexpensive in that thin ting their connection wires. The signal and the remaining
wires can be used for output signals. units in the circuit remain unaffected which simplifies
service.
P~
Computer
dP 134
Cl 48
B0087 GB
Cl 96
6. Maximum open circuit output voltage is low, 20 V, Certain A/D-converters and controllers require a positive
which means that the output circuit can be opened without input signal. For this purpose it is useful to have a zero
any precautions. displacement in power measurements with both positive
7. They have a wide range of applications because of their and negative power. Cewe Instruments transducers can be
high accuracy and the fact that they are approved in ac- produced with zero displacement up to 50 % of the mea-
cordance wit interference tests IEC 255 -5 and -6, for input suring range.
and output signals.
Example: Measuring range 100-0-100 kW, output signal 4 12 20 mA where 4 mA = 100 kW,
12 mA = 0 kW and 20 mA = +100 kW.
See page 11 output signal L.
Example:
Connection to a
P~
computer.
R Computer
dP 135
B0088GB
Cl 48
8
General description and technical data
Addition or subtraction of outputs Cewe Instruments power transducers are adapted for
both summation and different measurements. Other Cewe
Summation or different measurements are made by con-
Instrumenttransducers can be used for summation measu-
necting the outputs according to the figures below. This is
rements.
possible because the outputs are potential free.
P~ + + P~ P2
P1
- P1 P2 -
Summation
P1 + P2
P~ + + P~ P2
P1
- P1 P2 -
Difference
P1 P2
B0089
Live-Zero output Response time
Using a measuring transducer with a nominal output of 0 The standard response time is 300 ms. A response time of
20 mA, there can be an uncertainty when the output is 50 ms is available as an option. (Except for DF and DPF)
zero, whether the in-put quantity is zero or there is a faulty Other response times on request.
transformer, transducer or connector. To avoid this we In this catalogue the concept response time is used to
produce transducers with a live zero out-put. This output characterize the time performance of the transducer. Time
is normally 4 20 mA for an input of 0 100 %. These constant is often used in other cases. The diagram below
live zero output transducers are frequently used in process makes clear the difference between response time and time
technology, but could also be used in power distribution constant.
instrumentation.
constant time
cally linear from 20 to 100 %. If a good A.C. measurement
in the range 0 20 % is needed, the combination transdu-
cer moving-coil instrument is a suitable choice. Ripple
The maximum ripple on the output is < 1 % of the output
signal (fs) for transducers in class 0.5. The max. ripple for
transducers in class 0.2 is < 0,5 %.
A
I~ 50
25
0
B0825
9
General description and technical data
Linearity Casing
A transducer is linear when the output is proportional to the The casing is made of self-extinguishing polycarbonate.
input. A deviation from a linear function is called a non-li-
nearity error and is expressed as a percentage of a range in Tropical design
our data sheets. In environments with a high temperature, high relative hu-
Output
midity and corrosive atmosphere the tropical design gives
a good protection.
I max
Ideal
function
Standard design Tropical design
I
True function Relative humidity max 85% Relative humidity max 95%
for max 60 days per year. for max 30 days per year.
Input Otherwise max 75% Otherwise max 85%
B0100
10
General description and technical data
Standards
Cewe Instrument measurement transducers are tested ac-
cording to the standards of the EMC Directive and accor-
ding to IEC 60255-5 and -6 Interference environ-mental
classes and test regulations for electronic apparatuses in
control equipment for power stations.
The transducers are manufactured to IEC 60688-2.2.
EMC directives
IEC 61000-6-3 Emissions light industry
IEC 61000-6-4 Emissions heavy industry
IEC 61000-6-1 Immunity light industry
IEC 61000-6-2 Immunity heavy industry
LVD directive
IEC 61010-1 Safety
IEC 60664-1 Safety
Output signals
*) Normally the knee
a Output B Output C*) Output d*) Output point should not be
closer than 20 % to
the end value.
Compressed lower region Compressed lower region Compressed upper region Compressed upper region
0 1 10 mA live Zero 0 16 20 mA live zero
corresponding to 4 6 20 mA corresponding to 4 17 20 mA
0 8 12 kV corresponding to 0 200 800 A corresponding to
0 8 12 kV 0 200 800 A
100 0 100 kW
11
Transducers DU for AC voltage
Transducers type DU transforms sinusoidal AC voltage Dimensions and weights
to a proportional load independent DC signal. The input
See page 58
signal can be connected either directly to the transducer, or
via a transformer (VT).
Transducer type DU 120 does not require auxiliary supply.
Uaux.~
~ UN~
~ +
= = - Output
B0692GB
T2
+
UN~
~ Output
= -
B0110GB
Output
Accuracy class 0.5 0.2*) (Option) *)
Not DU 120
General data
Working temp. range -10 +55C
Function temp. range -20 +65C
Storage temp. range -65 +80C
Test voltage 3.7 kV at UN 300 V
5.55 kV at 300 V < UN < 600 V
Overload 1.2 x UN continuosly, varistor protection 1.5 x UN
Output signals**)
**) The availability
a Output B Output C Output d Output of output signal
per type, see
page 13 and 14
Input Input Input Input
12
Transducers DU for AC voltage
DU 120
DU 120
Utgng/Output/Ausgang
Input
+ - Input voltage (UN) 0 40525 V 1)
15 16 Burden < 1.2 VA
Frequency 50 or 60 Hz
Kpa 1
Casing size 1 Does not require auxiliary supply.
Gehuse 1
Output Output signal Load resistance RL
2 5 rated value 1)
U~ 1 mA A 0 15 k
Ingng/Input/Eingang
2.5 mA A 0 6.0 k
B0819A
5 mA A 0 3.0 k
Connection 10 mA A 0 1.5 k
20 mA A 0 750
1)
Other values on request.
DU 121 to 122
DU 121 - 122
Hjlpspnning Input
Uaux. supply
Hilfsspannung Input voltage (UN) 0 40600 V 1)
Utgng Burden 1 mA x UN
Output
Ausgang Frequency 16/, 50/60, 400 Hz
+ -
14 15 16 Output Output signal Load resistance RL
Kpa 1 rated value 1)
Casing size 1
Gehuse 1
1 mA A, B, C, D 0 15 k
2.5 mA A, B, C, D 0 6.0 k
13 2 5 5 mA A, B, C, D 0 3.0 k
U~
10 mA A, B, C, D 0 1.5 k
Ingng/Input/Eingang 20 mA A, B, C, D 0 750
Hjlpspnning: Vxelspnning
Auxiliary supply: AC voltage
5 V A, C > 2 k
B0818A
1)
Other values on request.
2)
Third digit in the type designition, shows type of auxiliary supply.
13
Transducers DU for AC voltage
DU 124 to 125
Hjlpspnning Utgng
Uaux. supply Output Input
Hilfsspannung Ausgang
+ - Input voltage (UN) 0 40600 V 1)
Burden 1 mA x UN
13 14 15 16 Measuring range 0.2 0.99 x UN
Frequency 16/, 50/60, 400 Hz
DU 124 - 125
Kpa 3/Casing size 3/Gehuse 3 Output Output signal 2) Load resistance RL
rated value 1)
2 5
1 mA A, B, C, D, E, F, G, H 0 15 k
U~ 2.5 mA A, B, C, D, E, F, G, H 0 6.0 k
Ingng/Input/Eingang 5 mA A, B, C, D, E, F, G, H 0 3.0 k
10 mA A, B, C, D, E, F, G, H 0 1.5 k
Hjlpspnning: Lik-/vxelspnning
Auxiliary supply: AC/DC voltage 20 mA A, B, C, D, E, F, G, H 0 750
B0817F
Hilfsspannung: Gleich-/Wechselspannung
5 V A, C, E, G > 2 k
Connection 10 V A, C, E, G > 2 k
Auxiliary voltage
3)
Unit Voltage Frequency Burden
4 18 80 V AC/DC 45 65 HzorDC 4 VA/2.5 W
5 80 276 V AC/DC 45 65 HzorDC 4 VA/2.5 W
1)
Other values on request.
2)
Curve E, F: Min. supressed lower region is
0-20% of max input value.
Curve G, H: Max. supressed upper region is
80-100% of max input.
3)
Third digit in the type designition, shows type of
auxiliary supply value.
14
Transducers DU for AC voltage
Ordering form DU
DU (Voltage AC) Default Example 1 Example 2
15
Transducers DI for AC current
Transducers type DI transform sinusoidal AC current to a Dimensions and weights
proportional load independent DC signal. The input signal
See page 58
can be connected either directly to the transducer, or via a
transformer.
Transducer DI 11 does not require auxiliary supply.
Uaux.~
~ IN~
~ +
Output
= = -
B0425GB
T2
+
IN ~
~ Output
= -
B0115GB
Output
Accuracy class 0.5 0.2*) (Option)
*)
Not DI 120
General data
Working temp. range -10 +55C
Function temp. range -20 +65C
Storage temp. range -65 +80C
Test voltage 3,7 kV Standard (UN < 300 V),
5,55 kV, Option (300 V < UN < 600 V)
Overload 2 x IN continuosly, 10 x IN during 10 s, 40 x IN during 1 s
Output signals**)
**) The availability
a Output B Output C Output d Output of output signal
per type, see
page 17 and 18
16
Transducers DI for AC current
DI 120
DI 120
Utgng/Output/Ausgang
Input
+ - Input current (IN) 1.0, 1.2, 5.0, 6.0 A 1)
15 16 Burden < 0,25 to < 1.2 VA
Frequency 50/60 Hz at Class 0.5
Kpa 1
Casing size 1 Does not require auxiliary supply.
Gehuse 1
Output Output signal Load resistance RL
1 3 rated value 1)
I~ 1 mA A 0 15 k
Ingng/Input/Eingang
B0823A
2.5 mA A 0 6.0 k
5 mA A 0 3.0 k
Connection
10 mA A 0 1.5 k
20 mA A 0 750
1)
Other values on request.
Hilfsspannung: Wechselspannung
10 V A, C > 2 k
Connection
Auxiliary voltage
2)
Unit Voltage Frequency Burden
1 92 138 V AC 45 65 Hz 2 VA
2 184 276 V AC 45 65 Hz 2 VA
1)
Other values on request.
2)
Third digit in the type designition, shows type of auxiliary supply.
17
Transducers DI for AC current
DI 124 to 125
Hjlpspnning Utgng
Uaux. supply Output Input
Hilfsspannung Ausgang
+ - Input current (IN) 1.0, 1.2, 2.0, 2.4, 5.0, 6.0 A 1)
Burden < 0.04 to < 0.2 VA
13 14 15 16 Frequency 16/, 50/60, 400 Hz
1 3 1 mA A, B, C, D, E, F, G, H 0 15 k
2.5 mA A, B, C, D, E, F, G, H 0 6.0 k
I~
Ingng/Input/Eingang 5 mA A, B, C, D, E, F, G, H 0 3.0 k
10 mA A, B, C, D, E, F, G, H 0 1.5 k
Hjlpspnning: Lik-/vxelspnning
Auxiliary supply: AC/DC voltage
20 mA A, B, C, D, E, F, G, H 0 750
Hilfsspannung: Gleich-Wechelspannung 5 V A, C, E, G > 2 k
B0821B
10 V A, C, E, G > 2 k
Connection
Auxiliary voltage
2)
Unit Voltage Frequency Burden
4 18 80 V AC/DC 45 65 HzorDC 4 VA/2.5 W
5 80 276 V AC/DC 45 65 HzorDC 4 VA/2.5 W
1)
Other values on request.
2)
Third digit in the type designition, shows type of auxiliary supply.
Ordering form DI
DI (Current AC) Default Example 1 Example 2
18
Transducers DUD for DC VOLTAGE AND diD for DC CURRENT
Transducers type DUD and DID are used to measure DC Dimensions and weights
voltage and DC current that are converted into a proportio-
See page 58
nal load-independent galvanic isolated DC voltage or DC
current signal.
T1
~
UAUX
~
Type dud
+
UN= Output/
-
T1
~
UAUX
~
Type did
+
IN= Output/
B0730GB
Output data
Accuracy class 0.5 0.2 (Option)
Linearity error < 0.2 % <0.1 %
Load-dependence <0.05 % <0.05 %
Response time (0-99%) 50 100 ms 50 100 ms
Auxiliary voltage dependence < 0.1 % < 0.1 %
Temperature dependence < 0.1 %/10 C < 0.06 %/10 C
Max voltage with open output 20 V 20 V
Max output signal with over-driven input signal <125 % <125 %
Ripple (peak-to-peak) <1.0 % <0.5 %
General data
Working temp. range -10 +55 C
Function temp. range -20 +65 C
Storage temp. range -65 +80 C
Test voltage 5.55 kV, 50 Hz
Output signals
a Output B Output C Output d Output
19
Transducers DUD for DC VOLTAGE AND diD for DC CURRENT
4 20 mA A, B, C, D, I, K, L 0 750
Connection 0 1 V A, B, C, D, I, K, L > 2 k
0 2 V A, B, C, D, I, K, L > 2 k
0 5 V A, B, C, D, I, K, L > 2 k
0 10 V A, B, C, D, I, K, L > 2 k
Auxiliary voltage
2)
Unit Voltage Frequency Burden
1)
Other values on request.
2)
Third digit in the type designition, shows type of
4 18 80 V AC/DC 45 65 HzorDC 4 VA/2.5 W
auxiliary supply. 5 80 276 V AC/DC 45 65 HzorDC 4 VA/2.5 W
0 1 V A, B, C, D, I, K, L > 2 k
0 2 V A, B, C, D, I, K, L > 2 k
Connection
0 5 V A, B, C, D, I, K, L > 2 k
0 10 V A, B, C, D, I, K, L > 2 k
Auxiliary voltage
2)
Unit Voltage Frequency Burden
1)
Other values on request.
4 18 80 V AC/DC 45 65 HzorDC 4 VA/2.5 W
2)
Third digit in the type designition, shows type of
auxiliary supply. 5 80 276 V AC/DC 45 65 HzorDC 4 VA/2.5 W
20
Transducers DUD for DC VOLTAGE AND diD for DC CURRENT
DUD 125
Type:
Accuracy: cl. 0.5 0.5
Input signal: 0-60 mV
Output:
0-20 mA
Output curve: A
Response time: 300 ms 300 ms
Auxiliary supply: 80-276 V AC/DC
21
Transducers DF for frequency
Transducers type DF are used for the measurement of the Dimensions and weights
frequency of an AC voltage and transforms it into a pro-
See page 58
portionally load independent DC signal. The input can be
connected directly or via a transformer.
Uaux.~
+
Micro- Output 1
UN~
processor -
B1040GB
+
Output 2
-
Output
Accuracy class 0.1
Non-linearity < 0.05 %
Load dependence < 0.05 % (within load limits)
Response time < 300 ms
Aux. supply dependence < 0.05 % for Uaux. 20 %
Temperature coefficient < 0.1 %/ 10C
Max open circuit output voltage 20 V
General data
Working temp. range -10 +50C
Function temp. range -10 +50C
Storage temp. range -20 +60C
Test voltage 3.75 kV, 50 Hz
Overload capacity Uin x 2, rated for 1 sec
Output signals
a Output B Output
Input Input
B0855GB
22
Transducers df for frequency
45 55 Hz
1)
Other values on request.
Ordering form DF
DF (Frequency) Default Example
Type: DF 125
Accuracy: cl. 0.1 0.1
Measuring range: 48-52 Hz
Voltage: 110 V
Output 1: 0-10 mA
Output curve 1: A
Output 2:
Output curve 2:
Auxiliary supply: 110 V DC
23
Transducers for power factor
24
Transducers for power factor
Brief description
The Programmable Transducer type DPT has in a fully equipped version; four analogue channels for any in-
stantaneous measured value, with a output signal of mA or V, galvanic insulated from each other and from the
input signals , two digital pulse outputs for energy and a Modbus RTU with all measured values available.
Easy programmed with the belonging software CofigView connected with a standard USB cable. Available as
ConfigView or as a ConfigView kit, software and USB cable.
The Transducer is meant for DIN rail mounting and has the dimensions 71x101,4x113,8mm (h x w x d)
The Transducer is designed according to the standard IEC 60688 and reaches the accuracy class 0.2 or 0.5 as
per your order.
All essential measuring values can be programmed to the outputs and are available through Modbus commu-
nication, the connection of the input signals can be freely programmed for single phase, 3 phase 3 wire as well
as 3 phase 4 wire and for both balanced and unbalanced load.
Both input voltage and input current as well as auxiliary supply are of wide range type.
See separate product presentation.
25
Transducers DP, DQ and DPQ for active and reactive power
Transducer type DP, DQ and DPQ measures the active T1
(P) and reactive (Q) A.C.-power and converts these into dP, dq
UAux
proportional load-independent DC current signals. The =
measurement principle for multiplication of the current
T2
and the voltage is based on the TDM (Time-Division-Mul- +
tiplication) method. The measurement principle also takes UN ~
- Output
account of the curve form error and the phase angle diffe-
rence ( = 0 360) between the current and the voltage T3
and gives the true power value (true RMS) as its result. In
transducer DPQ the signal outputs (P) and (Q) are galvani- IN ~
B0768GB
The measurement voltage and measurement current can be
connected directly to the transducer or via measurement T1
dPq
transformers. The permitted value for the scale factor shall UAux
lie within the range 0.3 1.8 and shall be defined by the =
scale factor formula. The current may not exceed 10 A. T2
+
Scale Measuring range [W or Var] UN ~ Output P
(Normally 0.3 1.8) -
factor = Nominal apparent power [VA]
T3
+
IN ~ Output Q
-
General data
B0850GB
Working temp. range -10 +55C
Fundamental circuit
Function temp. range -20 +65C
Storage temp. range -65 +80C
Test voltage 5.55 kV, 50 Hz (measurement input signal/outputs)
3.7 kV, 50 Hz (auxiliary voltage input signal/outputs)
1.5 kV, 50 Hz (signal output (P) signal output (Q)
Overload 1.2 x UN continuous, varistor protection 1.5 x UN
2 x IN continuous, 10 x IN during 10 s, 40 x IN during 1 s
Output data
Linearity Output
Iout max
26
Transducers DP for active power
Auxiliary voltage
Unit*) Voltage Frequency Burden
4 18 80 V AC/DC 45 65 HzorDC 4 VA/2.5 W
5 80 276 V AC/DC 45 65 HzorDC 4 VA/2.5 W
*) Third digit in the type designition, shows type of auxiliary supply.
27
Transducers DP for active power
Output signals
K Output l Output
Input Input
B0809GB
28
Transducers DP for active power
Hjlpspnning Utgng
DP 124 to 125
Uaux. supply Output
Hilfsspannung Ausgang Input data
+ - Measurement voltage (UN) 40 to 600 V 1)
Internal consumption 1 mA per phase x UN
13 14 15 16
Measurement current (IN) 1, 2, 5 A 1)
DP 124 - 125 Internal consumption <0.1 VA per phase
Kpa 3/Casing size 3/Gehuse 3 Frequency 16/, 50, 60, 400 Hz
Niederspannungssystem
Output Output signal Load resistance RL
Connection rated value 1)
1 mA A, B, I, K, L 0 15 k
Hjlpspnning Utgng
2 mA A, B, I, K, L 0 7,5 k
Uaux. supply Output 2,5 mA A, B, I, K, L 0 6 k
Hilfsspannung Ausgang
+ - 5 mA A, B, I, K, L 0 3 k
10 mA A, B, I, K, L 0 1.5 k
13 14 15 16
20 mA A, B, I, K, L 0 750
DP 124 - 125 1 V A, I, K > 2 k
Kpa 3/Casing size 3/Gehuse 3 2 V A, I, K > 2 k
5 V A, I, K > 2 k
1 2 3 11
10 V A, I, K > 2 k
u v k l 1)
Other values on request.
U V K L
L1
x
N
Hgspnningssystem
High voltage system
B0793B
Hochspannungssystem
Connection
29
Transducers DP for active power
Hjlpspnning Utgng
DP 134 to 135
Uaux. supply Output
Hilfsspannung Ausgang Input data
+ - Measurement voltage (UN) 40 to 600 V 1)
Internal consumption 1 mA per phase x UN
13 14 15 16
Measurement current (IN) 1, 2, 5 A 1)
DP 134 - 135 Internal consumption <0.1 VA per phase
Kpa 3/Casing size 3/Gehuse 3 Frequency 16/, 50, 60, 400 Hz
Niederspannungssystem
Connection
Output Output signal Load resistance RL
Hjlpspnning Utgng rated value 1)
Uaux. supply Output
Hilfsspannung Ausgang 1 mA A, B, I, K, L 0 15 k
+ - 2 mA A, B, I, K, L 0 7,5 k
13 14 15 16 2,5 mA A, B, I, K, L 0 6 k
5 mA A, B, I, K, L 0 3 k
DP 134 - 135 10 mA A, B, I, K, L 0 1.5 k
Kpa 3/Casing size 3/Gehuse 3
20 mA A, B, I, K, L 0 750
1 2 3 5 8 1 V A, I, K > 2 k
2 V A, I, K > 2 k
u v u v k l 5 V A, I, K > 2 k
U
L1
V U VK L 10 V A, I, K > 2 k
x
L2 x
x 1)
Other values on request.
L3
Hgspnningssystem
High voltage system
B0797B
Hochspannungssystem
Connection
30
Transducers DP for active power
Hjlpspnning Utgng
DP 144 to 145
Uaux. supply Output
Hilfsspannung Ausgang Input data
+ - Measurement voltage (UN) 40 to 600 V 1)
Internal consumption 1 mA per phase x UN
13 14 15 16
Measurement current (IN) 1, 2, 5 A 1)
DP 144 - 145 Internal consumption <0.1 VA per phase
Kpa 3/Casing size 3/Gehuse 3 Frequency 16/, 50, 60, 400 Hz
Niederspannungssystem
Output Output signal Load resistance RL
Connection
rated value 1)
1 mA A, B, I, K, L 0 15 k
Hjlpspnning Utgng
2 mA A, B, I, K, L 0 7,5 k
Uaux. supply Output 2,5 mA A, B, I, K, L 0 6 k
Hilfsspannung Ausgang
+ - 5 mA A, B, I, K, L 0 3 k
10 mA A, B, I, K, L 0 1.5 k
13 14 15 16
20 mA A, B, I, K, L 0 750
DP 144 - 145 1 V A, I, K > 2 k
Kpa 3/Casing size 3/Gehuse 3 2 V A, I, K > 2 k
5 V A, I, K > 2 k
1 2 3 11
10 V A, I, K > 2 k
u v k l 1)
Other values on request.
U VK L
L1
x
L2
x
L3
x
N
Hgspnningssystem
High voltage system
B0795B
Hochspannungssystem
Connection
31
Transducers DP for active power
DP 234 to 235
Hjlpspnning Utgng
Uaux. supply Output
Hilfsspannung Ausgang
Input data
+ - Measurement voltage (UN) 40 to 600 V 1)
Internal consumption 1 mA per phase x UN
13 14 15 16 Measurement current (IN) 1, 2, 5 A 1)
Internal consumption <0.1 VA per phase
DP 234 - 235
Frequency 16/, 50, 60, 400 Hz
Kpa 3/Casing size 3/Gehuse 3
Lgspnningssystem
Low voltage system
Niederspannungssystem
B0798B
Connection
32
Transducers DP for active power
Hjlpspnning Utgng
DP 334 to 335
Uaux. supply Output
Hilfsspannung Ausgang Input data
+ - Measurement voltage (UN) 40 to 600 V 1)
Internal consumption 1 mA per phase x UN
13 14 15 16
Measurement current (IN) 1, 2, 5 A 1)
DP 334 - 335 Internal consumption <0.1 VA per phase
Kpa 4/Casing size 4/Gehuse 4
Frequency 16/, 50, 60, 400 Hz
u v u v
1)
Other values on request.
k l k l k l
U V U V
K L
L1 x
K L
L2 x
K L x
L3
N
Hgspnningssystem
High voltage system
B0852B
Hochspannungssystem
Connection
33
Transducers DP for active power
DP 344 to 345
Hjlpspnning Utgng
Uaux. supply Output Input data
Hilfsspannung Ausgang
+ - Measurement voltage (UN) 40 to 600 V 1)
Internal consumption 1 mA per phase x UN
13 14 15 16 Measurement current (IN) 1, 2, 5 A 1)
Internal consumption <0.1 VA per phase
DP 344 - 345 Frequency 16/, 50, 60, 400 Hz
Kpa 4/Casing size 4/Gehuse 4
k l 15 [V]
K L k l k l RL max [k] =
L1 x Output current [mA]
K L
L2 x
K L x
L3
xx
N
Lgspnningssystem
Low voltage system
Niederspannungssystem Output Output signal Load resistance RL
rated value 1)
B0800B
1 mA A, B, I, K, L 0 15 k
Connection
2 mA A, B, I, K, L 0 7,5 k
2,5 mA A, B, I, K, L 0 6 k
H lpspnning Utgng
Uaux supply Output 5 mA A, B, I, K, L 0 3 k
Hil sspannung Ausgang 10 mA A, B, I, K, L 0 1.5 k
+ -
20 mA A, B, I, K, L 0 750
13 14 15 16 1 V A, I, KL > 2 k
2 V A, I, K > 2 k
DP 344 - 345
Kpa 4/Casing size 4/Gehuse 4
5 V A, I, K > 2 k
10 V A, I, K > 2 k
1 2 3 4 5 6 7 8 9 11 1)
Other values on request.
u u u
x x x
k l k l k l
X X X
U U U
K L
L1 x
K L
L2 x
K L x
L3 xx
N
Hgspnningssystem
High voltage system
B0801B
Hochspannungssystem
Connection
34
Transducers DP for active power
Ordering form DP
DP (Active power) Default Example
Type: DP 235
Accuracy: cl. 0.5 0.5
Transf. ratio voltage: 11000/110 V
Transf. ratio current: 100/5 A
Frequency: 50 Hz 50 Hz
Measuring range (P): 0-2 MW
Output (P): 4-20 mA
Output curve: B
Response time: 300 ms 300 ms
Auxiliary supply: 80 - 276 V AC/DC
35
Transducers DQ for reactive power
Auxiliary voltage
Unit*) Voltage Frequency Burden
4 18 80 V AC/DC 45 65 HzorDC 4 VA/2.5 W
5 80 276 V AC/DC 45 65 HzorDC 4 VA/2.5 W
*) Third digit in the type designition, shows type of auxiliary supply.
36
Transducers DQ for reactive power
Output signals
K Output l Output
Input Input
B0809GB
37
Transducers DQ for reactive power
DQ 134 to 135
Hjlpspnning Utgng
Uaux. supply
Hilfsspannung
Output
Ausgang
Input data
+ - Measurement voltage (UN) 40 to 600 V 1)
Internal consumption 1 mA per phase x UN
13 14 15 16 Measurement current (IN) 1, 2, 5 A 1)
Internal consumption <0.1 VA per phase
DQ 134 - 135 Frequency 16/, 50, 60, 400 Hz
Kpa 3/Casing size 3/Gehuse 3
k l 15 [V]
RL max [k] =
L1 K L Output current [mA]
x x
L2
x
L3
Lgspnningssystem
Low voltage system Output Output signal Load resistance RL
Niederspannungssystem
rated value 1)
B0802B
1 mA A, B, I, K, L 0 15 k
Connection
2 mA A, B, I, K, L 0 7,5 k
2,5 mA A, B, I, K, L 0 6 k
Hjlpspnning Utgng
5 mA A, B, I, K, L 0 3 k
Uaux. supply Output 10 mA A, B, I, K, L 0 1.5 k
Hilfsspannung Ausgang
+ - 20 mA A, B, I, K, L 0 750
1 V A, I, K > 2 k
13 14 15 16 2 V A, I, K > 2 k
DQ 134 - 135 5 V A, I, K > 2 k
Kpa 3/Casing size 3/Gehuse 3 10 V A, I, K > 2 k
1)
Other values on request.
1 3 5 8
u v k l
U VK L
L1
x
L2 x
x
L3
Hgspnningssystem
High voltage system
Hochspannungssystem
B0803B
Connection
38
Transducers DQ for reactive power
DQ 234 to 235
Hjlpspnning Utgng
Uaux. supply Output Input data
Hilfsspannung Ausgang
+ - Measurement voltage (UN) 40 to 600 V 1)
Internal consumption 1 mA per phase x UN
13 14 15 16 Measurement current (IN) 1, 2, 5 A 1)
Internal consumption <0.1 VA per phase
DQ 234 - 235 Frequency 16/, 50, 60, 400 Hz
Kpa 3/Casing size 3/Gehuse 3
1 mA A, B, I, K, L 0 15 k
Connection 2 mA A, B, I, K, L 0 7,5 k
2,5 mA A, B, I, K, L 0 6 k
5 mA A, B, I, K, L 0 3 k
Hjlpspnning Utgng
Uaux. supply Output 10 mA A, B, I, K, L 0 1.5 k
Hilfsspannung Ausgang
+ - 20 mA A, B, I, K, L 0 750
1 V A, I, K > 2 k
13 14 15 16 2 V A, I, K > 2 k
5 V A, I, K > 2 k
DQ 234 - 235
Kpa 3/Casing size 3/Gehuse 3 10 V A, I, K > 2 k
1)
Other values on request.
1 2 3 5 7 8 9
u v u v
k l k l
U V U VK L
L1
x
L2 x
K L x
L3
Hgspnningssystem
High voltage system
B0805B
Hochspannungssystem
Connection
39
Transducers DQ for reactive power
DQ 334 to 335
Hjlpspnning Utgng
Uaux. supply Output Input data
Hilfsspannung Ausgang
+ - Measurement voltage (UN) 40 to 600 V 1)
Internal consumption 1 mA per phase x UN
13 14 15 16 Measurement current (IN) 1, 2, 5 A 1)
Internal consumption <0.1 VA per phase
DQ 334 -335 Frequency 16/, 50, 60, 400 Hz
Kpa 4/Casing size 4/Gehuse 4
K
k l
L k l k l 15 [V]
L1 RL max [k] =
K L x Output current [mA]
L2 x
K L x
L3
N
Lgspnningssystem
Low voltage system
Niederspannungssystem
Output Output signal Load resistance RL
B0853B
rated value 1)
Connection 1 mA A, B, I, K, L 0 15 k
2 mA A, B, I, K, L 0 7,5 k
Hjlpspnning Utgng
2,5 mA A, B, I, K, L 0 6 k
Uaux. supply Output 5 mA A, B, I, K, L 0 3 k
Hilfsspannung Ausgang
+ - 10 mA A, B, I, K, L 0 1.5 k
20 mA A, B, I, K, L 0 750
13 14 15 16
1 V A, I, K > 2 k
DQ 334 -335 2 V A, I, K > 2 k
Kpa 4/Casing size 4/Gehuse 4 5 V A, I, K > 2 k
10 V A, I, K > 2 k
1 2 3 4 5 6 7 8 9
1)
Other values on request.
u v u v
k l k l k l
U V U V
K L
L1 x
K L
L2 x
K L x
L3
N
Hgspnningssystem
High voltage system
B0854B
Hochspannungssystem
Connection
40
Transducers DQ for reactive power
DQ 344 to 345
Hjlpspnning Utgng
Uaux. supply Output Input data
Hilfsspannung Ausgang
+ - Measurement voltage (UN) 40 to 600 V 1)
Internal consumption 1 mA per phase x UN
13 14 15 16 Measurement current (IN) 1, 2, 5 A 1)
Internal consumption <0.1 VA per phase
DQ 344 -345 Frequency 16/, 50, 60, 400 Hz
Kpa 4/Casing size 4/Gehuse 4
1 2 3 4 5 6 7 8 9
The maximum load resistance (at current output) is cal-
culated from the formula:
k l 15 [V]
K L k l k l RL max [k] =
L1 Output current [mA]
K L x
L2 x
K L x
L3
xx
N
Lgspnningssystem
Low voltage system Output Output signal Load resistance RL
Niederspannungssystem rated value 1)
B0806B
1 mA A, B, I, K, L 0 15 k
Connection 2 mA A, B, I, K, L 0 7,5 k
2,5 mA A, B, I, K, L 0 6 k
5 mA A, B, I, K, L 0 3 k
H lpspnning Utgng
Uaux supply utput 10 mA A, B, I, K, L 0 1.5 k
Hil sspannung usgang
+ - 20 mA A, B, I, K, L 0 750
1 V A, I, K > 2 k
13 14 15 16
2 V A, I, K > 2 k
DQ 344 -345 5 V A, I, K > 2 k
Kpa 4/Casing size 4/Gehuse 4 10 V A, I, K > 2 k
1)
Other values on request.
1 2 3 4 5 6 7 8 9
u u u
x x x
k l k l k l
X X X
U U U
K L
L1 x
K L
L2 x
K L x
L3
xx
N
Hgspnningssystem
High voltage system
B0807B
Hochspannungssystem
Connection
41
Transducers DQ for reactive power
Ordering form DQ
DQ (Reactive power) Default Example
Type: DQ 235
Accuracy: cl. 0.5 0.5
Transf. ratio voltage: 11000/110 V
Transf. ratio current: 100/5 A
Frequency: 50 Hz 50 Hz
Measuring range (Q): 0-2 Mvar
Output (Q): 4-20 mA
Output curve: B
Response time: 300 ms 300 ms
Auxiliary supply: 80 - 276 V AC
42
Transducers DPQ for active and reactive power
Auxiliary voltage
Unit*) Voltage Frequency Burden
4 18 80 V AC/DC 45 65 HzorDC 4 VA/2.5 W
5 80 276 V AC/DC 45 65 HzorDC 4 VA/2.5 W
*) Third digit in the type designition, shows type of auxiliary supply.
43
Transducers DPQ for active and reactive power
Output signals
K Output l Output
Input Input
B0809GB
44
Transducers DPQ for active and reactive power
Hjlpspnning Utgng
DPQ 134 to 135
Uaux. supply Output
Hilfsspannung Ausgang Input data
P Q Measurement voltage (UN) 40 to 600 V 1)
+ - + -
Internal consumption 1 mA per phase x UN
13 14 15 16 17 18 Measurement current (IN) 1, 2, 5 A 1)
Internal consumption <0.1 VA per phase
DPQ 134 - 135
Kpa 4/Casing size 4/Gehuse 4
Frequency 16/, 50, 60, 400 Hz
Connection 1 mA A, B, I, K, L 0 15 k
2 mA A, B, I, K, L 0 7,5 k
2,5 mA A, B, I, K, L 0 6 k
Hjlpspnning Utgng
Uaux. supply Output 5 mA A, B, I, K, L 0 3 k
Hilfsspannung Ausgang
P Q
10 mA A, B, I, K, L 0 1.5 k
+ - + - 20 mA A, B, I, K, L 0 750
13 14 15 16 17 18 1 V A, I, K > 2 k
2 V A, I, K > 2 k
DPQ 134-135
5 V A, I, K > 2 k
Kpa 4/Casing size 4/Gehuse 4
10 V A, I, K > 2 k
1 2 3 5 8 1)
Other values on request.
u v u v
k l
U V U V L
K
L1
L2
x
x
L3
x
Hgspnningssystem
High voltage system
Hochspannungssystem
B0753B
Connection
45
Transducers DPQ for active and reactive power
Hjlpspnning
DPQ 144 to 145
Utgng
Uaux. supply Output
Hilfsspannung Ausgang Input data
P Q Measurement voltage (UN) 40 to 600 V 1)
+ - + -
Internal consumption 1 mA per phase x UN
13 14 15 16 17 18 Measurement current (IN) 1, 2, 5 A 1)
Internal consumption <0.1 VA per phase
DPQ 144-145
Frequency 16/, 50, 60, 400 Hz
Kpa 4/Casing size 4/Gehuse 4
Niederspannungssystem
rated value 1)
Connection 1 mA A, B, I, K, L 0 15 k
2 mA A, B, I, K, L 0 7,5 k
Hjlpspnning Utgng 2,5 mA A, B, I, K, L 0 6 k
Uaux. supply Output
Hilfsspannung Ausgang 5 mA A, B, I, K, L 0 3 k
P Q
+ - + - 10 mA A, B, I, K, L 0 1.5 k
20 mA A, B, I, K, L 0 750
13 14 15 16 17 18
1 V A, I, K > 2 k
DPQ 144-145 2 V A, I, K > 2 k
Kpa 4/Casing size 4/Gehuse 4 5 V A, I, K > 2 k
1 2 3 11 8
10 V A, I, K > 2 k
u u u
1)
Other values on request.
x x x
k l
X X X
U U U V
L1 K L
L2
x
L3
x
x
N
Hgspnningssystem
High voltage system
B0755B
Hochspannungssystem
Connection
46
Transducers DPQ for active and reactive power
Hjlpspnning Utgng
DPQ 234 to 235
Uaux. supply Output
Hilfsspannung Ausgang Input data
P Q Measurement voltage (UN) 40 to 600 V 1)
+ - + -
Internal consumption 1 mA per phase x UN
13 14 15 16 17 18 Measurement current (IN) 1, 2, 5 A 1)
Internal consumption <0.1 VA per phase
DPQ 234-235
Frequency 16/, 50, 60, 400 Hz
Kpa 4/Casing size 4/Gehuse 4
rated value 1)
Connection 1 mA A, B, I, K, L 0 15 k
2 mA A, B, I, K, L 0 7,5 k
Hjlpspnning Utgng 2,5 mA A, B, I, K, L 0 6 k
Uaux. supply Output
Hilfsspannung Ausgang 5 mA A, B, I, K, L 0 3 k
+
P
- +
Q
- 10 mA A, B, I, K, L 0 1.5 k
20 mA A, B, I, K, L 0 750
13 14 15 16 17 18
1 V A, I, K > 2 k
DPQ 234-235 2 V A, I, K > 2 k
Kpa 4/Casing size 4/Gehuse 4 5 V A, I, K > 2 k
10 V A, I, K > 2 k
1 2 3 5 7 8 9
1)
Other values on request.
u v u v
k l k l
U V U VK L
L1
L2
x
x
L3
K L x
Hgspnningssystem
High voltage system
B0757B
Hochspannungssystem
Connection
47
Transducers DPQ for active and reactive power
rated value 1)
Connection 1 mA A, B, I, K, L 0 15 k
2 mA A, B, I, K, L 0 7,5 k
2,5 mA A, B, I, K, L 0 6 k
Hjlpspnning Utgng
Uaux. supply Output 5 mA A, B, I, K, L 0 3 k
Hilfsspannung Ausgang
P Q
10 mA A, B, I, K, L 0 1.5 k
+ - + - 20 mA A, B, I, K, L 0 750
13 14 15 16 17 18 1 V A, I, K > 2 k
2 V A, I, K > 2 k
DPQ 334-335
5 V A, I, K > 2 k
Kpa 4/Casing size 4/Gehuse 4
10 V A, I, K > 2 k
1 2 3 4 5 6 7 8 9 1)
Other values on request.
u v u v
k l k l k l
U V U V L
K
L1
K L x
L2 x
L3
K L x
N
Hgspnningssystem
High voltage system
B0759B
Hochspannungssystem
Connection
48
Transducers DPQ for active and reactive power
rated value 1)
Connection
1 mA A, B, I, K, L 0 15 k
2 mA A, B, I, K, L 0 7,5 k
H lpspnning tgng 2,5 mA A, B, I, K, L 0 6 k
aux supply utput
Hil sspannung usgang 5 mA A, B, I, K, L 0 3 k
- - 10 mA A, B, I, K, L 0 1.5 k
13 14 15 16 17 18 20 mA A, B, I, K, L 0 750
1 V A, I, K > 2 k
DPQ 344-345 2 V A, I, K > 2 k
Kpa 4/Casing size 4/Gehuse 4
5 V A, I, K > 2 k
1 2 3 4 11 6 7 8 9 10 V A, I, K > 2 k
u u u
1)
Other values on request.
x x x
k l k l k l
K L
L1
K L x
L2 x
L3
K L x
xx
N
Hgspnningssystem
High voltage system
B0761B
Hochspannungssystem
Connection
49
Transducers DPQ for active and reactive power
Ordering form DPQ
DPQ (Active and reactive power combined) Default Example
50
Transducers Dr for resistanCE
relative to Rx.
Potentiometer circuit: Used in conjunction with mechanical 3
1
3
Linearity error < 0.2 % <0.1 % Rx (3-wire)
B0732GB
C (3-wire)
Max output signal with
over-driven input signal <125 % <125 %
Ripple (peak-to-peak) <1.0 % <0.5 %
Dimensions and weights
General data See page 58
Working temp. range -10 +55 C
Function temp. range -20 +65 C
Storage temp. range -65 +80 C
Test voltage 5.55 kV, 50 Hz
Output signals
51
Transducers Dr for resistanCE
Hjlpspnning
DR 134 to 435
Utgng
Uaux. supply
Hilfsspannung
Output
Ausgang
Input data
+ - Measuring range (RX) 0 100 , ..... 0 10 k
15 16 Measuring current (I RX) 0,2 10 mA (measuring range 0 10 k)
13 14
10 mA (measuring range 0 100 )
DR 134-135 3.5 5 mA (PT 100 sensor)
Kpa 3/Casing size 3/Gehuse 3
Output Output signal Output signal Load
1 2 3 rated value1) DR 134-335 DR 434-435 resistance RL
1 mA A, B, C, D A, B, C, D, I, K, L 0 15 k
Rx 2 mA A, B, C, D A, B, C, D, I, K, L 0 7.5 k
Potentiometerkoppling
Potentiometer circuit 2,5 mA A, B, C, D A, B, C, D, I, K, L 0 6.0 k
B0858B
Potentiometerschaltung 5 mA A, B, C, D A, B, C, D, I, K, L 0 3.0 k
10 mA A, B, C, D A, B, C, D, I, K, L 0 1.5 k
Connection
20 mA A, B, C, D A, B, C, D, I, K, L 0 750
20 mA A, B, C, D A, B, C, D, I, K, L 0 750
Hjlpspnning Utgng
1 V A, B, C, D A, B, C, D, I, K, L > 2 k
Uaux. supply
Hilfsspannung
Output
Ausgang
2 V A, B, C, D A, B, C, D, I, K, L > 2 k
+ - 5 V A, B, C, D A, B, C, D, I, K, L > 2 k
13 14 15 16 10 V A, B, C, D A, B, C, D, I, K, L > 2 k
DR 224-225 1)
Other values on request.
Kpa 3/Casing size 3/Gehuse 3
Auxiliary voltage
1 3 2)
Unit Voltage Frequency Burden
4 18 80 V AC/DC 45 65 HzorDC 4 VA/2.5 W
Rx 5 80 276 V AC/DC 45 65 HzorDC 4 VA/2.5 W
Tvtrdskoppling
Two-wire circuit 2) Third digit in the type designition, shows type of auxiliary supply.
B0859B
Zweidrahtschaltung
Connection
DR 334-335 DR 434-435
Kpa 3/Casing size 3/Gehuse 3 Kpa 3/Casing size 3/Gehuse 3
1 2 3 1 2 3
C
Rx Rx
Tretrdskoppling Temperaturgivare
Three-wire circuit Temperature sensors
B0861B
B0860B
Dreidrahtschaltung Temperaturmessgeber
Connection Connection
52
Transducers Dr for resistanCE
Ordering form DR
DR (Resistance DC) Default Example
Type: DR 134
Measurment principle Potentiometer
Accuracy: cl. 0.5 0.5
Input 15x20 ohm
Measuring range:
Output: 0-20 mA
Output curve: A
Response time: 300 ms 300 ms
Auxiliary supply: 18-80 V AC/DC
Type: DR 435
Measurment principle Temperature
Accuracy: cl. 0.5 0.5
Sensor: PT 100 ohm/0C
Measuring range: 0-100C
Output: 0-10 mA
Output curve: C
Response time: 300 ms 300 ms
Auxiliary supply: 80-276 V AC/DC
53
Dimensions and weights
1 73 77*
75
* With terminal protection
= Casing size
73
3
100
73
4
B1038GB
54
Dimensions and weights
Type Weight g
DU 120 280
DU 121, DU 122 260
DU 124 DU 125 340
DI 120 210
DI 121, DI 122 250
DI 124 DI 125 450
55
Cewe Instrument AB
Box 1006 SE-611 29 Nykping SWEDEN
Tel: +46 155 775 00 Fax: +46 155 775 97
e-mail: info@ceweinstrument.se www.ceweinstrument.com
A0140e-9