Vous êtes sur la page 1sur 6

ANSI/ASAE S362.

2 JAN1983 (R2009)
Wiring and Equipment for Electrically Driven or Controlled
Irrigation Machines

S
T ASABE is a professional and technical organization, of members worldwide, who are dedicated to advancement of

A
engineering applicable to agricultural, food, and biological systems. ASABE Standards are consensus documents
developed and adopted by the American Society of Agricultural and Biological Engineers to meet standardization
needs within the scope of the Society; principally agricultural eld equipment, farmstead equipment, structures, soil
and water resource management, turf and landscape equipment, forest engineering, food and process engineering,
electric power applications, plant and animal environment, and waste management.

N
NOTE: ASABE Standards, Engineering Practices, and Data are informational and advisory only. Their use by
anyone engaged in industry or trade is entirely voluntary. The ASABE assumes no responsibility for results attrib-
utable to the application of ASABE Standards, Engineering Practices, and Data. Conformity does not ensure
compliance with applicable ordinances, laws and regulations. Prospective users are responsible for protecting

D
themselves against liability for infringement of patents.

ASABE Standards, Engineering Practices, and Data initially approved prior to the society name change in July of
2005 are designated as ASAE, regardless of the revision approval date. Newly developed Standards, Engineering
Practices and Data approved after July of 2005 are designated as ASABE.

A
Standards designated as ANSI are American National Standards as are all ISO adoptions published by ASABE.
Adoption as an American National Standard requires verication by ANSI that the requirements for due process,
consensus, and other criteria for approval have been met by ASABE.

R
Consensus is established when, in the judgment of the ANSI Board of Standards Review, substantial agreement has
been reached by directly and materially affected interests. Substantial agreement means much more than a simple
majority, but not necessarily unanimity. Consensus requires that all views and objections be considered, and that a
concerted effort be made toward their resolution.

D
CAUTION NOTICE: ASABE and ANSI standards may be revised or withdrawn at any time. Additionally, procedures
of ASABE require that action be taken periodically to reafrm, revise, or withdraw each standard.

Copyright American Society of Agricultural and Biological Engineers. All rights reserved.

ASABE, 2950 Niles Road, St. Joseph, MI 49085-9659, USA ph. 269-429-0300, fax 269-429-3852, hq@asabe.org
ANSI/ASAE S362.2 JAN1983 (R2009)
Approved April 1988; reaffirmed January 2010 as an American National Standard

Wiring and Equipment for Electrically Driven or Controlled


Irrigation Machines

Developed by a standards subcommittee of the ASAE Agricultural Wiring subpanels or numerous other devices, gaining access to hidden nuts, or
and Utilization Committee; approved by the Electric Power and removing a rear enclosure cover.
Processing Division Standards Committee; adopted by ASAE June 1973; 2.2.4 front-wired: Mounting of replaceable devices so that they may be
revised April 1978, January 1983; reconfirmed December 1987; individually wired from the front of an enclosure without removing the
approved as an American National Standard April 1988; revised device, subpanels, or rear enclosure covers to gain access to electrical
editorially July 1989; reaffirmed by ASAE December 1992; reaffirmed by connections.
ANSI July 1993; revised editorially June 1997; reaffirmed by ASAE
December 1997, December 1998; reaffirmed by ANSI December 1999; 2.2.5 grounded: Connected to earth or to some conducting body which
reaffirmed by ASAE December 1999; revised editorially March 2000; serves in place of earth.
reaffirmed by ASAE February 2005; reaffirmed by ANSI March 2005; 2.2.6 grounded conductor: A circuit conductor which is intentionally
reaffirmed by ASABE December 2009; reaffirmed by ANSI January 2010. grounded.
Keywords: Definitions, Electrical, Irrigation, Safety, Safety signs, 2.2.7 grounding conductor: The conductor used to connect
Sprinkler, Wiring noncurrent-carrying metal parts of a machine to a service-grounded
conductor and/or a grounding electrode conductor.
2.2.8 machine disconnect: A disconnecting means at the point of
1 Purpose and scope connection of electrical power to the machine.
1.1 This Standard provides detailed information for the application of 2.2.9 metal-to-metal: Attachment of metal parts to the machine with
electrical apparatus to electrically driven or controlled irrigation machines. bolts and screws to provide an adequate contact for bonding purposes
The purpose of this Standard is to improve the degree of personal safety where all paint and dirt have been removed from under the bearing
in operation and application of products and materials under a surface area of bolt or screw heads.
reasonable range of conditions. 2.2.10 readily accessible: Capable of being opened quickly for
1.2 This Standard covers all electrical equipment, apparatus, maintenance, repair, or inspection. May be fastened by latches or held by
components, and wiring necessary for electrically driven or controlled mechanical interlocks or similar apparatus. A cover firmly attached by two
irrigation machines, from the point of connection of electric power to the or more screws is not considered readily accessible.
machine. 2.2.11 weatherproof: Constructed or protected so that exposure to the
1.3 Provisions of this Standard apply to electrical equipment for use on environment will not interfere with successful operation.
circuits operating at voltages between 30 and 600 V.
3 General requirements
2 Definitions and glossary of terms 3.1 Disconnecting means
2.1 For purposes of this Standard the following definitions shall apply: 3.1.1 A machine disconnect with overcurrent protection capable of being
locked in the OFF position shall be provided at the point of connection of
2.1.1 irrigation machine: (Hereinafter called machine.) An electrically electric power to the machine.
driven or controlled machine, not portable by hand, used primarily to
transport and distribute water for agricultural purposes. 3.2 Enclosures
2.1.2 power conductors: Those conductors that carry current to 3.2.1 All enclosures shall be constructed to meet at least the minimum
provide electric power from the machine disconnect to the drive motors. standards for a National Electrical Manufacturers Association Type 3R
enclosure as specified in NEMA Standard IS1.1, Controls and Systems.
2.1.3 control conductors: Those conductors that carry current to
control devices necessary for movement of the machine. 3.2.2 Entrances into, exits from, and penetrations of the enclosure shall
be made in such a manner as to reduce the possibility of the collection
2.1.4 auxiliary conductors: Those conductors used to carry current to of water or contaminants at the point of connection and to preserve the
devices that are not required for the movement of the machine. minimum NEMA rating of the enclosure as specified in paragraph 3.2.1.
2.1.5 main control panel: An enclosure containing the main controller 3.2.3 Dimensions of enclosures shall not be less than the maximum
and other control devices necessary for starting and stopping the dimensions of the enclosed equipment plus the required electrical
machine. clearances as specified in National Fire Protection Association Standard
2.1.6 auxiliary panels: Enclosed assemblies of auxiliary control devices No. 70, National Electrical Code (American National Standard, C1).
for the machine, such as motor controllers, relays, switches, and 3.2.4 Where used, gaskets shall be securely attached to one of the
transformers, but not including the main controller or main start and stop mating parts.
function switches. A junction box is not an auxiliary panel.
3.2.5 Enclosures should be mounted in such a manner as to minimize
2.2 The following glossary of terms applies to this Standard: the possibility of subsequent physical damage to the enclosure.
2.2.1 bonded: A reliable connection to assure the required electrical 3.3 Interlocking
conductivity between metal parts required to be electrically connected.
3.3.1 Where personal hazard or property damage may be caused by the
2.2.2 collector ring: An assembly of slip rings for transferring electrical failure of any one device to function properly, protective interlocks shall
energy from a stationary to a rotating member. be provided. Where practicable, these interlocks shall interrupt all
2.2.3 front-mounted: Mounting of replaceable devices so that they may operations, providing such interruption will not create a hazardous
be individually replaced from the front of an enclosure without removing condition.

ASABE STANDARDS 2010 ANSIASAE S362.2 JAN1983 R2009 1


3.4 Automatic or remote starting 4.1.4 Metallic sheath of any cable or conduit shall not be used as the
3.4.1 Automatic restarting shall be connected in such a manner that primary grounding conductor.
restarting will occur only on resumption of full single-phase or three- 4.2 Metal-to-metal contact with a part which is bonded to the grounding
phase voltage, as needed, following a power outage. conductor and the noncurrent-carrying parts of the machine shall be
3.4.1.1 Automatic restarting shall not be construed to encompass the considered as an adequate grounding path.
functions of a device or circuit designed for reversing the direction of 4.3 Metallic sheath of cable or conduit, where used, shall be grounded.
travel of the machine at a preset point or points. 4.4 External metal parts which could become inadvertently energized
3.4.2 Machines equipped with automatic restarting or remote starting shall be grounded.
shall have affixed to the machine a safety sign indicating that the 4.5 Motor frames shall be bonded to the grounding conductor.
machine can start automatically.
4.6 Metal frames of devices such as switches, solenoids, and junction
3.4.2.1 This safety sign shall be affixed to the machine disconnect. It boxes shall be bonded to the grounding conductor or to the noncurrent
shall also be affixed to the main control panel if the machine disconnect carrying metal parts of the machine.
is not part of or adjacent to the main control panel.
4.7 The grounding conductor shall not have less ampacity than its
3.4.2.2 Wording and size of this sign are specified in Section 10Safety associated power conductors.
Signs.
4.7.1 When there is a reduction of conductor size because of the use of
3.5 All conductors within an enclosure shall be clearly marked or color an interposing relay, controller, or similar device, the grounding conductor
coded for identification as specified in paragraph 8.6. may also be reduced to the same size as the power, control, or auxiliary
3.6 Transformers shall be of the isolated type with proper overcurrent conductors originating at the interposing device.
protection for the transformer, conductors, or control devices it serves. 4.8 Where a machine has a stationary point, such machine shall include
3.7 Terminal blocks or strips shall be sized to accommodate the number provision for the connection of the machine-grounding conductor to
and size of the conductors terminated or connected thereto and shall be the grounding-electrode conductor. Proper installation of the grounding-
rated for the voltage and current transmitted on the connected or electrode conductor shall complete an electrical path from the machine-
terminated conductors. grounding conductor to the grounding electrode.
3.8 Control devices such as relays, limit switches, and similar equipment 4.8.1 A prominently displayed, durable sign shall be permanently affixed
shall be suitable for the application and shall be capable of handling the to the main control panel which indicates the need for proper grounding.
voltage and current imposed on or through the devices. 4.8.2 The installation and operating instructions for the machine shall
3.9 Panel-mounted devices shall be front-mounted and front-wired for include specific recommendations for connecting or installing the
convenient servicing. grounding electrode in accordance with the applicable sections of the
3.10 Current ratings NFPA Standard No. 70, National Electrical Code.
3.10.1 Machines. Where a machine is multimotored and individual 4.9 A common connection point for all grounding conductors shall be
motors are controlled by alignment switches or similar devices, and provided.
where intermittent duty is inherent, the equivalent continuous-current
rating and the peak-current rating shall be determined as follows:
5 Main control panel
3.10.1.1 The equivalent continuous-current rating shall be calculated as
125% of the full-load current rating of the largest motor plus a quantity 5.1 The enclosure for the main panel shall conform to paragraph 3.2.
equal to the sum of the full-load current ratings of all remaining motors 5.2 Disconnecting means
multiplied by the maximum percent duty cycle at which the remaining 5.2.1 If the machine disconnect is not in or adjacent to the main control
motors can continuously operate. panel, a disconnecting means capable of being locked in OFF position
3.10.1.2 The peak-current demand shall be equal to the sum of the shall also be provided in or adjacent to the main control panel.
locked-rotor current of the two largest motors plus 100% of the full-load 5.2.2 If the main control panel is remote from the machine, a
current ratings of all other motors on the circuit. disconnecting means capable of being locked in the OFF position shall
3.10.2 Center pivot machines. Where a machine is multimotored and be provided at the machine for removing power from all circuits of 30 V
individual motors are controlled by alignment switches or similar devices, or more.
where the machine operates in a circle, and where intermittent duty is 5.2.3 If the main control panel contains a disconnecting means, it shall
inherent, the continuous-current rating and the peak-current rating shall be interlocked with the enclosure opening.
be determined as follows:
NOTE: Means may be provided for qualified persons to gain access
3.10.2.1 The equivalent continuous-current rating shall be calculated as to enclosures without removing power if the interlocking is reactivated
125% of the full-load current rating of the largest motor plus 60% of the automatically when the enclosure is closed.
sum of the full-load current ratings of the remaining motors.
5.2.4 If a disconnecting means is adjacent to the main control panel and
3.10.2.2 The peak-current rating shall be calculated as two times the live parts of components are not readily accessible, the enclosure
locked-rotor current of the largest motor plus 80% of the sum of the opening is not required to contain an interlock. It is recommended,
full-load current ratings of the remaining motors. however, that interlocking be provided.
5.2.5 Equipment within an enclosure receiving electrical energy from
4 Grounding more than one source shall not be required to have a disconnecting
means for the additional source provided its voltage is 30 V or less or
4.1 A grounding conductor used for no other purposes than machine meets the requirements of Section 725-31 of the NFPA Standard No. 70,
grounding shall be provided. National Electrical Code.
4.1.1 The grounding conductor shall be bonded to the machine within 5.3 Hinged doors for enclosure openings shall have a mechanical stop
the main control panel enclosure and each auxiliary panel enclosure. to prevent strain on conductors and termination points contained in or on
4.1.2 The ground conductor shall be within the same sheath, jacket, or the door.
conduit as the power, control, or auxiliary conductors. 5.3.1 Conductors to components or terminations contained in or on the
4.1.3 The grounding conductor may be bare or insulated as specified in hinged door shall be fastened so that any conductor flexing occurs at the
paragraph 8.6.2.1. fastener and not at conductor terminals.

2 ANSIASAE S362.2 JAN1983 R2009 ASABE STANDARDS 2010


5.4 The main control panel shall not be used as a raceway. operating environment will not interfere with successful operation. It is
5.5 Attachment plugs and receptacles shall be of a locking type of NEMA recommended that the motors be labeled by the motor manufacturer to
configuration to prevent accidental disconnections and shall be of indicate that they are specifically designed for use on an irrigation
proper design for the voltage, current, and environment for which they machine in addition to the nameplate marking specified in NFPA
are used. Standard No. 70, National Electrical Code.
5.5.1 Where two or more mating receptacles are installed on a machine, 7.1.2 Motors shall be rodent proof.
they shall not be interchangeable unless both receptacles serve the 7.1.3 If a junction box is supplied, the usable volume of the housing
same purpose, and have the same voltage and current rating, and should be a minimum of 200 cm3 (12 in.3) with 50 mm (2 in.) minimum
interchangeability will not affect the operation or safety of the machine. dimension of the opening. The junction box shall be equipped with an
Mating receptacles shall be wired so that no energized terminals are easily accessible, internal frame grounding terminal.
exposed when the receptacles are disconnected. 7.2 Motor controllers
5.6 Operator control devices 7.2.1 Controllers shall be marked with the manufacturers name or
5.6.1 All operator-controlled devices such as selector switches and start identification, voltage, horsepower rating, and such other data as may be
and stop controls shall be clearly marked as to their function. needed to properly indicate the motors for which they are suitable.
5.6.2 All push buttons and selector switches, indicating lights, etc., which 7.2.2 Running overcurrent protection
are exterior-mounted, shall be of the weatherproof type and shall be 7.2.2.1 Motor running overcurrent protection shall be provided to protect
installed to conform to paragraph 3.2.2. each motor, motor controller, and motor feeder conductor against
5.6.3 Stop push buttons shall be red in color. Red color shall not be excessive heating due to motor overload or failure to start.
used for push buttons having functions other than stop. 7.2.2.2 To provide the maximum possible protection, motor running
5.6.4 All controls shall be protected from possibility of accidental overcurrent devices should be sized smaller than the maximum allowable
operation by normal servicing or by normal movement of the machine. wherever possible.
5.7 Overcurrent protective devices shall be provided and sized in 7.2.2.3 The minimum number and location of running overcurrent
accordance with the requirements of the device or devices served, but protection devices shall be determined from Table 1.
shall not exceed the current allowed by NFPA Standard No. 70, National 7.2.2.4 Thermal devices or systems mounted in the motor and sensitive
Electrical Code, for the conductors employed. to the temperature of the motor, or to both motor temperature and
5.7.1 The preferred main or master overcurrent device should consist of current, may be used in lieu of externally mounted overload units. The
properly sized fuses (single or dual element) complete with the required thermal devices or systems shall be capable of protecting the motor
holders or fuse blocks. against stalled conditions and repeated starting under locked-rotor
5.8 If the machine operates where intermittent duty is inherent, a conditions.
controller in the main control panel, which is used to manually or 7.2.2.5 Automatic resetting of an overload protective device shall not
automatically start and stop the complete machine, shall have an restart the motor where restarting could damage the machine or result in
interrupting capability not less than the peak current as determined in unsafe operation.
paragraphs 3.10.1.2 or 3.10.2.2 and a continuous current rating not less
than determined in paragraphs 3.10.1.1 or 3.10.2.1.
5.9 A basic wiring diagram of the machine shall be affixed inside the 8 Conductors
main control panel with components properly identified. 8.1 General
5.10 The main control panel shall contain a nameplate stating the 8.1.1 All conductors shall be within either an enclosure, a raceway, or a
manufacturers name, the design voltage, phase and frequency of the jacketed cable.
incoming power supply, and the current rating of the recommended
overcurrent protection for the main power circuit. 8.1.2 Conductors within 2.6 m (8 ft) of the ground shall be protected from
physical damage by enclosure in rigid metal conduit, liquid-tight flexible
metal conduit, jacketed metallic-sheathed cable, or other suitable means.
6 Auxiliary panels 8.1.3 Mechanical protection for conductors may be provided by
6.1 Enclosures for auxiliary panels shall conform to paragraph 3.2. utilization of the machine structure.
6.2 A disconnecting means (one or more) shall be provided where an NOTE: It is the intent of paragraphs 8.1.2 and 8.1.3 to protect
enclosure contains relays, controllers, switches or other similar devices conductors from physical damage by livestock or hazards
that may need maintenance or repair and where such enclosures are encountered in normal usage of the machine.
farther than 9 m (30 ft) from the machine disconnect. 8.2 Size
6.3 Enclosure-covers shall be secured in a manner that will prevent 8.2.1 The size of power conductors shall be based on the assumption
accidental opening or removal during or resulting from normal operation that the maximum voltage at any motor will be the design motor voltage
of the machine.
6.4 Each auxiliary panel shall have affixed to the panel a safety sign
indicating the possible presence of a hazardous voltage.
6.4.1 Although paragraph 6.2 provides for disconnection of power in an Table 1 Running overcurrent devices
auxiliary panel, the safety sign is specified to dissuade casual opening of
the auxiliary panel and to indicate possible danger should the panel be Number and location of
opened for servicing. overcurrent units (such
Kind of motor Supply system as trip coils, relays, etc.)
6.4.2 Wording and size of this safety sign are specified in Section 10
Safety Signs. 1-phase ac or dc 2-wire, 1-phase ac or dc, 1 in ungrounded
one conductor grounded conductor
7 Motors and motor controllers 1-phase ac or dc 3-wire, 1 phase ac or dc, 1 in either ungrounded
grounded neutral conductor
7.1 Motors
3-phase ac any 3-phase 3, one in each phase
7.1.1 Motors shall be constructed or protected so that exposure to the

ASABE STANDARDS 2010 ANSIASAE S362.2 JAN1983 R2009 3


plus 5% with allowance for a 10% voltage drop using this assumed frame and operated under a sprinkler system need not be flameresistant.
maximum and the average continuous current calculated from However, it should be resistant to sunlight, moisture, and corrosion. The
paragraphs 3.10.1.1 or 3.10.2.1. jacketing should also provide some mechanical protection, flexibility, and
8.2.1.1 In addition to voltage drop considerations, the ampacity of power be suitable for operation within temperatures of 10 to 60 C, and
conductors shall equal or exceed that permitted by NFPA Standard No. should not be attractive to livestock. Nonwicking filler material should be
70, National Electrical Code. used. The jacketing construction should allow proper termination to
provide a mechanically strong, weatherproof connection that can be
8.2.2 Control and auxiliary conductor size shall provide sufficient
field-installed with standard electrical tools.
ampacity to carry the total current drawn by the devices served and shall
not be smaller than shown in Table 2. 8.6 Identification
NOTE: Conductors smaller than No. 18gage are included to 8.6.1 All conductors within an enclosure shall be identified in some
anticipate use of solid-state control devices which may operate at manner at each termination, and this identifying means shall be
currents of 1 rna or smaller. Conductors smaller than No. 18gage consistent throughout the machine.
shall not be used for other than circuits serving solid-state control 8.6.2 Color coding for identification
devices. 8.6.2.1 Grounding conductors shall be either bare, green, or green with
8.2.3 Conductors supplying a motor shall have an ampacity not less than a yellow stripe.
125% of the motor full-load current. 8.6.2.2 Grounded conductors shall be white or natural gray.
8.3 Standing 8.6.2.2.1 Where grounded conductors of different systems are in the
8.3.1 Conductors used to connect or interconnect control devices that same cable, conduit, or tubing, additional grounded conductors may be
are physically displaced in normal operation of the machine shall be of identified by white with a colored stripe other than green.
stranded construction. 8.6.2.3 Where color coding is used for power conductors, the colors of
8.3.2 All power, control, and auxiliary conductors should be annealed black, red, and blue should be used for ungrounded conductors.
stranded copper with minimum stranding as shown in Table 2. 8.6.2.4 All ungrounded conductors of the same identification shall be
8.3.3 Crimp-type connectors shall not be used if solid conductor wires connected to the same circuit.
are employed. 8.6.2.5 All conductors for systems of different voltages shall be of
8.4 Insulation different colors.
8.4.1 Conductor insulation should be flame, moisture, and corrosion
resistant and should be suitable for operation within temperatures of
10 to 60 C. Conductor insulation shall be rated at not less than 75 C
9 Collector rings
wet location. 9.1 Enclosure
8.4.2 Conductors used to connect or interconnect components within an 9.1.1 Enclosures for a collector ring shall conform to paragraph 3.2.
enclosure shall be rated at not less than 600 V when any circuits utilize 9.1.2 Enclosures for collector rings are not required to have an interlock.
voltage over 300 Vac and less than 600 Vac. 9.2 Ampacity
8.4.3 All conductors within an enclosure shall be insulated with the 9.2.1 Slip rings transmitting current for power functions shall have a
exception of the grounding conductor which may be bare. continuous-duty rating not less than that determined in paragraph 3.10.
8.4.4 Conductor insulation in a cable, conduit, or tubing, where different 9.2.2 The remaining slip rings for control and auxiliary purposes shall
voltages are present, shall be rated at or above the highest voltage have a continuous-duty rating not less than 125% of the full-load current
carried in the cable, conduit, or tubing. of the largest device served plus the sum of the full-load currents of all
EXCEPTION: Control or auxiliary conductors may have a lesser other devices served.
voltage insulation providing that the control or auxiliary computors are 9.2.3 The current-carrying capacity of the slip ring used for machine
within an inner cable with an outer protective covering rated at or grounding shall be of the same ampacity as the slip ring with the greatest
above the highest voltage of the power conductors in the cable, ampacity in the assembly.
conduit, or tubing, and also providing that the conductor insulation
within this protective covering is rated at or above the highest voltage 9.2.4 When slip rings or slip-ring terminals are of different ampacity,
utilized within the inner multiconductor cable. each ring or terminal shall be identified with a durable marking which
indicates the ampacity.
8.5 Jacketing. Cable jacketing where the cable is attached to a metal

10 Safety signs
10.1 Automatic starting signs
Table 2 Copper conductor ampacity single conductor construction
(control or auxiliary circuits) 10.1.1 The safety sign for automatic starting specified in paragraph 3.4.2
shall have the following wording:
Ampacity in
Conductor Minimum
size AWG cable or raceway control enclosure standing

24 2 2 7
22 3 3 7
20 5 5 7
18 7 7 7
16 10 10 7
14 15 20 7
12 20 25 7
10 30 40 7
8 40 55 7

4 ANSIASAE S362.2 JAN1983 R2009 ASABE STANDARDS 2010


10.1.2 The upper portion of this sign shall have the word CAUTION in 10.3 Design and letter size
all capital letters in black on a yellow background. The lower portion for 10.3.1 The ratio of width to height of the upper portion of the sign shall
the remaining wording may have uppercase or lowercase letters in yellow fall within the range of 2:1 and 5:1.
on a black background.
10.3.2 The lower portion of the sign shall be the same width as the
10.2 Auxiliary panel signs upper portion.
10.2.1 The auxiliary panel safety sign specified in paragraph 6.5 shall 10.3.3 The height of the lower portion of the sign shall not be less than
have the following wording: the height of the upper portion.
10.3.4 Minimum height of letters shall be 13 mm (0.5 in.) in the upper
portion and 6.4 mm (0.25 in.) in the lower portion.
10.4 Additional safety signs should comply with American National
Standard ANSI/ASAE S318, Safety for Agricultural Equipment, or
American National Standard Z35.1, Specifications for Accident
Prevention Signs.
10.5 The safety-alert symbol specified in SAE J284 JAN91, Safety Alert
Symbol for Agricultural, Construction and Industrial Equipment, should be
used with each safety sign to indicate that safety is involved.
Cited Standards:
ANSI/ASAE S318, Safety for Agricultural Equipment
10.2.2 The upper portion of the auxiliary panel safety sign shall have the ANSI Z35.1, Specifications for Accident Prevention Signs
word DANGER in all capital letters in white on a red background. Lower NEMA IS1.1, Controls and Systems
portion for the remaining sign wording shall have uppercase letters for NFPA No. 70, National Electrical Code
the words VOLTS. The other words may be in uppercase or
SAE J284 JAN91, Saftey Alert Symbol for Agricultural, Construction and
lowercase letters. Words in the lower portion shall have letters in red on
a white background. Industrial Equipment
10.2.3 The underscore in paragraph 10.2.2 shall be replaced by the
design voltage of the machine as specified on the nameplate described
in paragraph 5.10.

ASABE STANDARDS 2010 ANSIASAE S362.2 JAN1983 R2009 5

Vous aimerez peut-être aussi