Vous êtes sur la page 1sur 7

CIGR 1996 : 11-103 O

STATIC STARTING OF GAS TURBINE DRIVEN GENERATORS


MECHANICAL AND ELECTRICAL DESIGN CONSIDERATIONS
Authors : R. Fenton*, G. Ghanime, E. Kazmierczak, R. Nold

General Electric

United States

Summary introduced to keep contact pressures high


Starting of gas turbine-generators through between certain components there is
the use of variable frequency load potential for heating damage as currents
commutated inverters has been increasing in pass between lightly loaded contacts during
popularity with power generation suppli ers static start operation.
as they realize the benefits of improved The testing and analysis shows that the
reliability and reduced power plant costs. combined gas turbine-generator rotor train
This starting means is referred to as static has a very light damping to torsional
start. modes. The importance of avoiding
Static start is being applied to increasingly resonant speeds and, in turn, the associated
larger generator sizes due to the output of responses, is clear as presented in the
gas turbines becoming larger and the power station response runs. The starting of
application of static start to single-shaft gas turbine-generators has historically been
combined-cycle machines. done through the use of mechanical starting
Application of static start technology to devices. These include diesel engines and
large generator sizes increases the risk of electric motors which are temporarily
duty to the turbine-generator from coupled to the main rotor train through a
electromagnetic heating, transfer of induced hydraulic speed increasing gear .
current between components and harmonic
torque pulsations. Keywords: GeneratorGas Turbine -
This paper will describe the operation of the Electromagnetic - Induced - Torsional
generator in the static start mode. The
mechanisms involved that could potentially These systems are inherently mechanical in
damage the generator are discussed. Key design and can play an important factor in
elements of the systematic development the overall availability of the turbine-
process are described. They include an generator system. Mechanical starting
analytically-based analysis phase, systems also are required to be installed
component bench testing, generator/LCI directly in line with the main turbine-
factory testing and a confirmation test at a generator rotor train. As a result, the
power plant. power plant deck, foundation and buildings
The paper shows the importance of must be sized to handle this equipment.
evaluation of the electromagnetic and In the last few years an alternative starting
thermal performance of the generator system has been gaining popularity with
windings and rotor components during all power plant operators. This is an electrical
phases of static start operation. This is starting system which utilizes the inherent
particularly important for operation at low torque producing ability of the main
speeds due to reduced ventilation and low generator to bring the rotor train to
rotor component contact pressures. If synchronous speed. This system is
provisions in the rotor design are not commonly referred to as static start.
*Robert E. Fenton, General Electric Company , 1 River Road, Building 273-460, Schenectady,
NY 12345
A typical static start system uses a remotely systems that required modest ener gy levels
located load commutated inverter (LCI) to to reach synchronous speed.
supply variable frequency power to the As equipment owners began to recognize
generator terminals. The remote location of the benefits associated with shorter
the LCI ensures that foundations and foundations, reduction in mechanical parts
buildings are kept to an absolute minimum count and improved availability , they have
length, saving substantial cost. asked for static starters on lar ger and lar ger
Simultaneously, a DC field current is rotor trains. Figure 1 shows the increasing
injected into the generator field winding. rotor train polar moment of inertia in (Kg-
The interaction of these two fields produces m-m) based on the year of introduction, for
a torque on the rotor train. This torque can one turbine-generator supplier.
be sized to overcome the various system The higher energy levels associated with
losses and accelerate the rotor train to these lar ger systems has focused increased
synchronous speed. concern on the ef fects this starting system
The LCI is a computer controlled power has on the generator hardware. This
electronics device which converts 50/60 Hz concern is driven by two facets of the LCI
auxiliary bus power into controlled variable operation. First is the harmonic content of
frequency power. The frequency range is the armature current. Second is the reduced
typically from 0.002 Hz to 50/60 Hz. The heat transfer associated with low speed
variable frequency power is controlled operation.
through voltage commutation. Operation of the generator at low speeds
Computer control of the frequency allows results in poorer ventilation. Careful
for smooth acceleration, in addition to stable consideration must be given to the
control at required turbine/generator evaluation and control of the thermal duty
maintenance points or speed hold points. on the machine windings and other
Gas turbine systems require steady state, components. For most static start
low speed operation for turbine cooling, applications, generator stator winding
cleaning, warm-up and pur ging, The current levels are low enough that stator
static start system is ideal for meeting these winding heating is not usually limiting.
unique needs. Field winding heating and rotor surface
Static starters have been applied to power heating, however, are important
generation equipment for a number of considerations for low speed operation.
years. These applications started with Collector and brush heating also need to be
relatively low polar moment of inertia considered for low speed operation.

Figure 1
Rotor Train Polar Moment of Inertia
Rotor surface, stator winding and field amortisseur and rotor wedges, rotor wedges
winding current magnitudes are influenced and rotor iron, rotor iron and retaining ring,
by the output torque required at any given end amortisseur and coil slot amortisseur
speed and by the LCI system voltage and end amortisseur and retaining ring.
selection and operating strategy , i.e. how Other areas of localized heating occur on the
voltage and current inputs are controlled as rotor surface due to physical constriction of
a function of speed. Typically there are the current such as at the iron ligaments in
conflicting requirements in that, for a given the rotor poles formed between the ends of
torque and speed, operation at a lower field the transverse pole fac
winding current magnitude results in lar ger e cross slots and first axial rotor coil slots.
stator winding and rotor surface current It is these areas of localized heating that are
magnitudes. Therefore, specification and of the most interest for static start
control strategy of the LCI system are based application.
on a reasonable solution to meet competing Most turbine-generator designs rely on the
requirements. lar ge centrifugal force present at rated
Harmonic distortion resulting from power speed to provide high pressures on the
electronics is well known. LCIs produce overlapping rotor component joints and
harmonic distortion as a result of their correspondingly low contact resistances.
normal operation. This harmonic content However , static start requires operation at
negatively af fects the generator in three low speeds where centrifugal force is
ways: Rotor surface currents, rotor surface smaller which may result in inadequate
heating and pulsating shaft torques. contact pressures. Localized heating
damage can occur if current density is too
Rotor Surface Currents & Heating high. At very low speeds, contact may
The interaction of the LCI and the actually be intermittent, opening and closing
synchronous machine is such that the stator depending on the rotor position.
current profile is approximately sinusoidal. To address overlapping contact issues, two-
Depending on the actual operating dimensional finite element tools were used
frequency the current waveform may look to analyze a transverse bindcross-section of
like a square wave at best, or a notched a generator rotor. More detailed work has
square wave at worst. A Fourier Series of been done to include the ef fects of the axi-
the current waveform shows that it is periodic nature of the end region fields.
comprised of a fundamental with significant The finite element analysis was used to
harmonics of the order 6n+/-1 where n= 1, establish the magnitudes and distribution of
2, 3. Harmonics for n greater than 3 do currents and losses on the rotor surface for
exist but are quite small in magnitude and subsequent use in laboratory tests. The ef
do not have a major ef fect on the operation fects of variables such as rotor induction
of the generator. frequency , material properties and stator
The presence of stator current harmonics current loading are easily explored with
from LCI operation results in the induction finite element tools.
of currents of various magnitudes,
wavelengths and frequencies on the surface Pulsating Shaft Torques
of the rotor . These currents flow in series- The harmonic content of the stator current
parallel paths comprised of rotor iron, rotor not only causes rotor heating but it also
wedges, amortisseur and retaining rings and impacts the rotor by driving a series of
distribute according to the impedance of the torsional torque pulsations. The flux fields
paths. Ohmic losses and subsequent resulting from the current harmonics interact
heating are generated in the various with the DC flux field due to rotor current to
components of the rotor due to the induced cause air gap torques. These torques have
rotor surface currents. the frequencies of 6n where n = 1, 2, 3.
Many of the current paths involve a Since the torque pulsations are proportional
transition of currents from one or more to the magnitude of the stator current
components to another by means of harmonics, torques with frequencies above
overlapping contacts. Contact resistance n = 4 are insignificant.
results from roughness, and oxidation of Turbine-generator rotors have a number of
the faying surfaces resulting in areas of torsional natural frequencies below the rated
localized heating. Examples of overlapping synchronous speed.
contacts are between the coil slot
Due to the geometry of the rotor and An important part of a development plan is
associated bearings these natural to test or verify the analytical methods.
frequencies are lightly damped, and will This development program used a four
resonate if ener gized. As a result, the phase test program to verify design
torsional response becomes an important integrity of the components and analysis
consideration in defining the operational systems discussed already.
reliability of machine. Phase 1 included laboratory bench testing to
Accurate response prediction requires determine the nature of contact resistances.
analysis techniques which include This information was used to ensure that
consideration of all forcing functions in local heating would not damage
addition to the mass-elastic properties of the components.
shaft system. The severity of the torsional Detailed models were constructed for
oscillations and stresses depends upon the extensive laboratory contact testing.
relationship between the frequency of Overlapping contacts were tested with
harmonic torques and the torsional natural variable pressure, current loading and
frequencies of the shaft system. materials. Tests were also made on
To analytically determine the effect of static- components with dif ferent surface
start torque on the torsional shaft response, roughness, silver plating and surface films
the full train mass-elastic model was made. resulting from oxidation or application of
A torsional frequency analysis was lubricants. Contact voltages and temperature
performed on the turbine-generator train were recorded as a function of time for each
model to determine the natural frequencies, test condition. The contact parts were
corresponding mode shapes and the disassembled and inspected for damage
Campbell diagram. The forcing function after each test.
used for the calculation was a Fourier Series A conservative design approach based upon
of the air gap torque and its associated the laboratory test results was employed for
harmonic coef ficients. The construction of static start applications. A patented arch
the Campbell diagram was an absolute spring arrangement was developed to
requirement since it showed the speed hold maintain suf ficient pressure on the
points with respect to the resonant shaft overlapping component joints at very low
frequencies. speeds. This arrangement is shown in
The forcing function and the full train model Figure 2.
were then used to calculate the transient
torsional response. This calculation was
repeated for each resonant frequency so a
complete picture of the shaft response could
be generated. This provided part of the
technical design criteria for the shaft
system.
A second necessary analysis included the
steady state shaft response at each of the
resonant frequencies. This analysis was
done to determine the severity of the
response at the speed hold points. Since
torsional damping is known to be very low, Figure 2
an accurate analytical model was necessary Rotor Slot Arch Spring Construction
to prevent damaging rotor oscillations from
occurring. Phase 2 of the testing included verification
of new components. For static start
Reliable Design Through Analysis, applications the only new generator
Verification component is the metallic arch spring. The
Significant system and component design arch spring loads the coil slot amortisseur
went into the development of generators for against the wedge and the wedge against the
use with LCIs. Proper analysis was rotor iron. In the end region the spring
required to ensure that improvements made loads the coil amortisseur against the end
to handle the short term starting issues did amortisseur and the end amortisseur against
not adversely af fect the long term generator the retaining ring. It is of interest to note
availability and reliability . that full length coil slot amortisseur bars are
used on generators with segmented rotor which showed the maximum strain
coil slot wedges to provide an additional occurring in the load coupling. The signal
low impedance current path at the axial was transmitted through a telemetry collar to
wedge gaps. a monitoring device and a tape recorder .
Prior to the first commercial application, the The train was brought up to the gas turbine
arch spring design was subjected to pur ge speed and then to firing speed. The
numerous mechanical acceptability tests. 3-D waterfall spectrum, Figure 3, clearly
These tests included wedge assembly tests, shows the 6/rev and the 12/rev resonance of
spring low cycle fatigue and static deflection the first natural frequency of the shaft
tests, thermal and load cycling tests, and system along with the shaft strain
hydrogen atmosphere tests. amplitude.
Local heating at the rotor pole face cross The field test confirmed the results of the
slot ligaments was reduced by increasing analyses in showing that continuous
the size of the ligament. Cross slots are operation or dwelling at or very near a
used to minimize rotor bending stif fness resonant speed will result in high oscillatory
dissymmetry at running speeds to control torque and will therefore yield to component
fatigue failure. The analysis indeed showed
that the steady state torque response could
be 28 times as great as the transient torque
response. Due to the fact that the torsional
response peaks are narrow-banded with a
very small logarithmic decrement, the speed
control should be tuned to avoid prolonged
operation at resonant points as the build-up
of response is limited only by damping and
the vibratory stress would quickly exceed
the endurance limit of the shaft material.
Phase 4 of the test program involves a full
scale synchronous machine test, operating
under static start conditions. The purpose
of this test was to measure temperature rises
and qualify the design concepts. This test
was run within the factory under controlled
Figure 3 conditions using a 229 MV A hydrogen-
The 3-D Waterfall Spectrum cooled generator. An actual LCI system
was used during the testing. The
two per rev . vibrations. This was synchronous machine was directly coupled
accomplished by decreasing the depth of the to a motor and cycloconverter and
cross slot while increasing the number of electrically coupled to the LCI. Both the
cross slots and putting them on a shorter LCI and cycloconverter were tied to a 13.8
axial pitch to maintain their functionality . kV bus. The resulting pumpback system
Where possible, it is desirable to not allow allowed for the LCI and synchronous motor
wedge joints to be axially aligned with cross to develop significant torque at varying
slots to further reduce local heating. speeds. This closely matches many of the
Phase 3 of the testing involved verification low speed operating conditions that users
of analytical methods with regard to rotor will experience in their power stations. The
train torsional responses. To verify the rotor was also extensively instrumented in
issues involving torsional response torques order to gain information on component
a field test was performed on a simple cycle heating while running at various speeds
gas turbine-generator train with the purpose and current loading. Figure 4 shows the
of identifying the magnitude of the response levels of output torque achieved during the
torque and the damping as well as the test as compared to the designed output
location of the harmonic resonances. The starting torque for this size machine. The
coupling that connects the generator flange machine was tested well above the design
to the gas turbine flange was instrumented points, in the low speed regime, to ensure
with strain gauges. The gauge location was that all issues of contact resistances, rotor
based on the torsional vibration analyses surface heating and field winding ventilation
were verified.
Upon completion of the factory test, the
generator rotor was disassembled to inspect
the components for any indications of
excessive duty . The factory testing lasted
for 1 10 hours. This equates to 220 start
cycles based on an average customer start
cycle of 30 minutes.
The rotor surface was free of discoloration
associated with the overheating of materials
due to surface currents. Further
disassembly of the rotor wedges showed
Figure 4 that there was no discoloration or pitting
Design Torque vs. Tested Torque damage on the mating surfaces of the rotor
components. The springs worked well to
Heat runs were done at low speed to hold all the components tightly .
evaluate generator field winding transient
thermal performance. Figure 5 shows the Conclusion
field hot spot temperature rise as a function Static starting of medium sized turbine-
of time once field current is applied. This generators driven by gas turbines is quite
data provides valuable information common. This paper described the use of
regarding resistive heat generation and the generators as a synchronous starting motor
removal of that heat at low operating using a variable frequency load commutated
speeds. It confirms that if the rotor is inverter . Static start is now being applied
transitioning through the low speed region to increasingly lar ge generator sizes due to
quickly enough, the thermal time constant the output of gas turbines becoming lar ger
provides suf ficient mar gin to operate at and applications of static start to single-shaft
near rated flux. combined-cycle machines.
Application of static start technology to lar
ge generator sizes increases the risk of duty
to the turbine-generator from
electromagnetic heating, transfer of induced
current between components and harmonic
torque pulsations.
This paper has described the operation of
the generator in the static start mode. It has
described the mechanisms involved that
could potentially damage the generator.
Key elements of the systematic development
Figure 5 process have been described. They include
Field Winding Transient Performance at an analytically based analysis phase,
Rated Flux component bench testing, generator/LCI
factory testing and a confirmation test at a
In addition to the transient field heating power plant. The paper has shown the
discussed above, Figure 5 provides importance of evaluation of the
important insights to the selection of field electromagnetic and thermal performance of
current for low speed hold points. It the generator windings and rotor
confirms that the steady state temperature components during all phases of static start
rise is predominately driven by the square operation. This is particularly important
root of the speed in this low range for operation at low speeds due to reduced
spectrum. The data shown in Figure 5 is ventilation and low rotor component contact
taken from a field current setting equivalent pressures. If provisions in the rotor design
to full magnetic flux. At speed 1, this level are not introduced to keep contact pressures
of flux would result in long term insulation high between certain components there is
damage due to the temperature rises. If potential for heating damage as currents
operation at speed 1 is required, defluxing pass between lightly loaded contacts during
of the machine would be necessary to static start operation.
prevent excessive temperatures. The testing and analysis have shown that
the combined gas turbine-generator rotor
train has very light damping of its torsional place of variable frequency LCI starting
modes. The importance of avoiding systems is an example of this.
resonant speeds and in turn the associated The generator has been asked to perform the
responses is clear as presented in the power additional duty of producing starting torque
station response runs. without adversely af fecting its inherent ef
There are many cases where technology ficiency and reliability as the supplier of
advances in equipment design and analysis electric power.
methods can be used to increase the Through a well structured development
capability and flexibility of utility owned program which includes analysis, bench
equipment without ef fecting overall system testing, full scale factory testing and field
reliability . The desire of many utilities to testing, we have been able to eliminate the
eliminate mechanical starting systems in risk associated with the additional starting
duty .

Vous aimerez peut-être aussi