EVAC 3
Evacuation units for elevators
EVAC 3
Ev a c u a t i o n u n i t s f o r elevators

The simplest evacuation during a power failure


The EVAC 3 series units are evacuation modules specifically
designed for elevator technology. The compact construction
and sophisticated design make the modules perfect for both
control cabinet installation (EVAC 3B) and wall installation
(EVAC 3C).

Functional description
The EVAC 3 evacuation unit monitors the power supply of the
ZETADYN 3 frequency inverter. With the drop out of one or
more phases the ZETADYN 3 will be disconnected from the
mains power supply. At the same time, the elevator control is
informed about the mains failure. The battery supply voltage
is switched in, time delayed.

The EVAC 3 evacuation unit switches the ZETADYN 3 into


emergency operation mode and the elevator can be run at
reduced speed, direction-independent.

An expensive and delayed rescue of trapped passengers by


external personnel is no longer necessary.

General features
C an be used for both synchronous and induction motors
C an be used for ZETADYN 3 frequency inverters
11 A to 74 A
C ontrol cabinet installation (EVAC 3B) or wall installation
(EVAC 3C)
6 0 min availability (with limited number of trips)
I ntegrated mains power supply monitoring
I ntegrated charger for controlled charging of lead-acid
rechargeable batteries
O peration and configuration by the ZETAPAD operating
panel
M onitoring of the battery temperature
P erformance test by digital input

2 www.ziehl-abegg.com
EVAC 3B
The solution for control cabinet installation

The compact design of the EVAC 3B facilitates easy


installation in a control cabinet.
In combination with the ZETADYN 3BF, the perfect solu-
tion.

Individual features
LED display for operation / malfunction
4 x relay outputs
2 x digital inputs (24 VDC)
Battery voltage 96 VDC ... 216 VDC

Additionally required components


Battery set matching the required power
Uninterruptible power supply (UPS) 230 VAC to supply:
Elevator control
Cabin light
EVAC 3B
Door drive
Motor brake
Power contactors to switch from normal to battery
operation
Main switch 4-pole

Block diagram EVAC 3B

www.ziehl-abegg.com 3
EVAC 3C
Th e c o m p a c t s o l u t i o n

The special design and integrated components facilitates


simple and quick installation of the EVAC 3C on the wall
in the machine room or in the elevator shaft.

The external main switch provides problem-free use with


machine room less elevators.
In combination with the ZETADYN 3C, the perfect solu-
tion.

Individual features
L ED display for operation / malfunction
4 x relay outputs
4 x digital inputs (24 VDC)
B attery voltage 96 VDC ... 216 VDC
E xternal main switch; that enables installation in the ele-
vator shaft
P refabricated cables for quick installation
I ntegrated power contactors for switching from
normal to battery operation
I ntegrated inverter 230 VAC / 500 W for supplying:
Elevator control
Cabin light
Door drive
Motor brake
S D card slot for data backup

Additionally required components


B attery set matching the required power
M ain switch 3-pole (with auxiliary contact)

Block diagram EVAC 3C

4 www.ziehl-abegg.com
EVAC 3
Te c h n i c a l D a t a

Technical data EVAC 3

Type designation EVAC 3B EVAC 3C032 EVAC 3C046 EVAC 3C074


3~ 360 440, 3~ 360 440, 3~ 360 440, 3~ 360 440,
Mains connection voltage [VAC]
50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz
Nominal current [A] 32 74 32 46 74

Power loss [W] < 20 < 20 < 20 < 20

Power consumption, charging [W] 300 300 300 300

Inverter 230 VAC [W] - 500 500 500

Battery voltage [VDC] 96 216 96 180 96 180 96 180


Lead-acid Lead-acid Lead-acid Lead-acid
Battery type
rechargeable battery rechargeable battery rechargeable battery rechargeable battery
Time limit, evacuation mode [min] 60 60 60 60

Weight [kg] 2 30 46 74

Dimensions

EVAC 3C EVAC 3B

www.ziehl-abegg.com 5
EVAC 3
Sy s t e m c o m p o n e n t s

Battery set

Both evacuation units require a battery set for the power sup-
ply of the frequency inverter and additional components.

The required voltage and capacity of the battery set is deter-


mined by the technical data of the motor and the duration or
number of evacuation trips.

Technical data battery set

Type designation EVAC BATT 032-120-24 EVAC BATT 050-120-24 EVAC BATT 074-120-24

Nominal voltage [VDC] 120 (2 x 60) 120 (2 x 60) 120 (2 x 60)

Nominal capacity [Ah] 24 24 24

Nominal current [A] 32 50 74

Dimensions WxHxD [mm] 1180 x 194 x 130 1180 x 194 x 130 1180 x 194 x 130

Weight [kg] 2 x 50 2 x 50 2 x 50

Technical data battery set

Type designation EVAC BATT 032-180-7.2 EVAC BATT 032-180-24 EVAC BATT 050-180-24 EVAC BATT 074-180-24

Nominal voltage [VDC] 180 (84 + 96) 180 (3 x 60) 180 (3 x 60) 180 (3 x 60)

Nominal capacity [Ah] 7.2 24 24 24

Nominal current [A] 32 32 50 74

Dimensions WxHxD [mm] 908 x 167 x 116 1180 x 194 x 130 1180 x 194 x 130 1180 x 194 x 130

Weight [kg] 24 + 26 3 x 50 3 x 50 3 x 50

Battery set (only EVAC 3C)

Prefabricated cables are available for fast and simple con-


nection of the EVAC 3C:

(1) EVAC 3C ZETADYN 3C (Power supply)


(2) EVAC 3C ZETADYN 3C (Signals)
(3) EVAC 3C Battery set
(4) EVAC 3C Elevator control (230VAC)
(5) EVAC 3C Elevator control (Signals)
(6) EVAC 3C Main switch (Monitor)

6 www.ziehl-abegg.com
EVAC 3
Se r v i c e

More competence. Mehr experience.


More commitment.

Along with the excellent, easy to operate products, perso-


nal customer support and rapid, punctual delivery, customer
focused service is one of our great strengths. Competent
support by expert and experienced service technicians are
the prerequisite for saving money and time onsite. With just
such a comprehensive service package, we make a signi-
ficant contribution to quickly commissioning your elevator
installation.

TV-safe drive-system engineering designs

Application-engineering advice to help select the in-


verters, machines, evacuation modules and brake
resistors

All parameters in the ZETADYN 3 are factory preset


before delivery when you order drive packages (machine
with control unit) from Ziehl-Abegg

Service hotline for commissioning or technical questions

Technical service and training on-site

Service - Hotline

Tel.: +49 (0)7940 16-308


Fax: +49 (0)7940 16-249
E-Mail: hotline.ra@ziehl-abegg.de

www.ziehl-abegg.com 7
T he Ro y a l L e a g u e

Ziehl-Abegg - 00000000-GB - 04/2011 - mag - 1 - K&E - Subject to technical modifications

Ziehl - A begg AG Heinz-Ziehl - Strae D -74653 Knzelsau +49 79 40 16 - 0 info@ ziehl - abegg.c om w w w.ziehl - abegg.c om

Vous aimerez peut-être aussi