Regulators
Meters
Valves
Flanges
Filter/separators
Heaters
Instrumentation components

OGA Seminar 2012 3


Regulators
Body & Diaphragm pressure rating
Each manufacturer establishes the ratings for each
regulator
Based on regulator
Upstream / Downstream

OGA Seminar 2012 4


Table 6. Type 627R Capacities for 1 and 2-Inch body sizes (1)

1 Fisher
Type 627R

1. Capacity is based on 20 percent droop unless otherwise noted below.


- Blank areas indicate where maximum operating pressure for a give orifice is exceeded.
OGA Seminar 2012 5
Typical Commercial Type
Regulator Capacity Tables
2 Models 243-12-1 and 243-12-2 in SCFH of Natural Gas
(0.6 Specific Gravity - 14.65 psia - 60F)

Last capacity figure in each group indicates maximum allowable inlet pressure (except
for emergency conditions).
Heavy stepped line indicates the recommended maximum capacity and inlet pressure
for each orifice for operation within the optimum performance range.

OGA Seminar 2012 6


Typical Large Capacity
Regulator Tables
2, 3, 4 & 6 441-57S Capacity Table

OGA Seminar 2012 7


Typical Large Capacity
Regulator Limitations

OGA Seminar 2012 8


OGA Seminar 2012 9
OGA Seminar 2012 10
Diaphragm Meters Rotary Meters
Domestic Aluminum, Iron & Steel
Aluminum Based on meter body materials
5- 10 & 25 Psig WP 125, 175, 200, 285, 300, 720,
Commercial & Industrial 1480 psig WP
Large diaphragm
Aluminum Turbine
10-100 Psig WP Aluminum and Steel
Based on meter body materials
175, 275, 720, 1440 psig WP

OGA Seminar 2012 11


Valves CWP Valves CWP
Iron Steel
Class 125 Class 150
175 Psig WP 275 /285 Psig WP
Ductile Class 300
Class 250 720 / 740 Psig WP
500 Psig WP Class 600
1440 / 1480 Psig WP

OGA Seminar 2012 12


Cold Working Pressure (CWP) Rating
Rating of valve at ambient conditions,
usually from 20 to 100F
Pressure Rating
The maximum operating pressure established by the
Manufacturer
Temperature Ratings
The maximum and minimum temperatures at which
the valve can be used.

OGA Seminar 2012 13


Fittings
Cast Iron
Malleable Iron
Steel
Pipe Flanges
Cast Iron Flanges
Steel Flanges

OGA Seminar 2012 14


CLASS 125
Allowable working pressures
for these fittings are:
125 psi Working Steam pressure (W.S.P.)
175 psi Water, Cold Oil or Gas (W.O.G.)

CLASS 250
Allowable working pressures
for these fittings are:
250 psi Working Steam pressure (W.S.P.)
400 psi Water, Cold Oil or Gas (W.O.G.)
OGA Seminar 2012 15
Malleable Iron Threaded Fittings
Classes 150 and 300
CLASS 150
Allowable working pressures
for these fittings are:
150 psi Working Steam pressure (W.S.P.)
300 psi Water, Cold Oil or Gas (W.O.G.)
CLASS 300
Allowable working pressures
for these fittings are:
PRESSUE TEMPERATURE TABLE
FOR CLASS 300

Non-shock
PIPE SIZE W .S.P, Or hot oil
cold W .O.G.
in inches up to 550 O F
To 150 O F
1/8 to 1 300 psi 2000 psi
1 1/4 to 2 300 psi 1500 psi
2 1/2 to 4 300 psi 1000 psi
5 to 8 300 psi 800 psi
OGA Seminar 2012 16
Forged Fittings
Classes 2000, 3000, 6000 AND 9000
90o ELBOW 45o ELBOW TEE CROSS STREET ELBOW LATERAL

HEXAGON FLUSH ROUND HEAD HEXAGON SQUARE


BUSHING BUSHING PLUG HEAD PLUG HEAD PLUG

COUPLING REDUCER HALF COUPLING CAP

www.onlinepipe.com
OGA Seminar 2012 17
ASME B16.1

OGA Seminar 2012 18


Steel Flanges

OGA Seminar 2012 19


Steel Flanges ASME B16.5

ANSI CLASS

OGA Seminar 2012 20


Stamped vessel pressure ratings VS flange ratings
Stamped vessels are design to any working pressure
Flange pressure rating must match or exceed the maximum
working pressure of the unit
Stamped vessel pressure ratings
Maximum working pressures are from 20 to 100F and
subject to derating at elevated temperatures per ASME Code
Test pressures
Covered by ASME Code and are only tested to 1.3 x Design
Working Pressure
Buyer must specify a higher test pressure if desired
OGA Seminar 2012 21
Instrument supply The manufacturer can provide the operating
regulators & maximum pressures for their equipment

Sight gauges
Dump valves

Kimray Dump Valve


Liquid Level Gauge High-Pressure Instrument
Supply System with
Overpressure Protection
OGA Seminar 2012 22