P OWER Q U ALIT Y STUDIE S

Modelling an A PPLICA TI O N NO TES

Industrial Power Network

The network shown illustrates a model of an industrial power


network used to analyse certain power quality issues. Some of
the issues addressed are:
Voltage amplication problems due to capacitor bank switching
Performance of an industrial drive
Modelling of motor start up
Modelling of motor loads and normal industrial loads
Transformer saturation issues
Harmonics and icker
Methods to reduce transients.

The single line view of the PSCAD model of this network is shown in
Figure 1. The main distribution network is modelled as an impedance
behind a voltage source. For the study concerned, a simple represen-
Figure 1 Single line view of the tation as shown in Figure 3 was identied as sufcient. If the study
PSCAD model of an industrial required a more accurate representation of the network frequency
power network.
response, more buses behind the 11 kV system bus must be added to
the model.
Figure 2 Voltage Source Parameters. The source impedance can be determined from the short circuit level
at this bus.
The user may select a more detailed representation for the system
equivalent where a combination of L-R-C elements can be used to
represent the impedance. The zero sequence can be dened to be
different from the positive sequence impedance. The data can be
entered as R, L and C values or in the more common impedance/
phase angle format.
Figure 3 11 kV System Bus.

PSCAD simulations can be used to design


the optimum value of the insertion resistor.
Figure 4 shows the arrangement of the utility side capacitors. If
there is more than a single bank, more parallel units are
to be added to the model. The short line connecting the capacitors
to the system bus at the substation is represented using series R-L
elements. The user may decide to represent this as a coupled PI
section where the mutual effects between the phases are included.
The utility side capacitors used for voltage support of the bus
also include a 400 Ohm damping resistor. PSCAD simulations can
Figure 4 Utility Capacitor Bank.
be used to design the optimum value of the resistor. The capacitor
breaker is controlled by Timed Breaker Logic unit but the user may
design the breaker on/off signals using many different arrangements.

Figure 5 Single and double circuit pi


section models.
The transformer at the customer location is modelled as a
Delta-wye unit made up of single phase banks. PSCAD includes
models for three-limbed cores as well as ve-limbed cores.
The appropriate model should be selected depending on the actual
Figure 6 Industrial Loads
arrangement of the unit under study. The following standard data are
required to model the transformer:
MVA rating and the winding voltage ratings
Impedance
Percentage no load current
Losses.

The transformer model takes into account the non-linear


behaviour of the core. Additional data pertaining to the
non-linear no-load characteristics needs to be entered if
saturation is to be included in the solution. Some studies
that would require the inclusion of saturation effects include:
Harmonic distortion issues at the bus
Inrush current and protection issues
Ferro-resonance investigation.

High frequency transients, a serious power


quality issue, can lead to production line
shutdown and unplanned down time.
Figure 6 shows the model of the industrial load. The power factor
correcting capacitors and the motor drive units are modelled along
with the rest of the loads. The loads can be represented as R-L-C
combinations, constant P-Q load, constant current load or any other
method. The power factor correcting capacitor breaker is manually
controlled to easily simulate the switching of the utility capacitors
when this power factor correcting unit is in service and out of service.
The main capacitor bank was turned on at 0.5 s in the
simulation results shown in Figure 7. When the PF correcting unit is
on, there is energy exchange between the two capacitors and the
result is an amplied voltage at the customer low
voltage bus. Inclusion of properly sized damping resistors
in parallel with the main capacitors will help reduce the
transient peaks.
The high frequency voltage transients can charge the DC link
Figure 7 PF unit off, PF unit on and capacitor of the machine drive converter. The power electronic
PF unit on and with no
devices are quite susceptible to excessive voltage and the protection is
damping resistor on main caps.
designed so that the drive will be disconnected in the event of exces-
sive DC link voltage. This is a serious power quality issue as production
lines associated with the drive will undergo unplanned down time.

Figure 8 Synchronized Switch- The capacitor energizing transient can be suppressed using different
ing Control. strategies.

Synchronized Switching of Breaker Poles


The individual poles of the breaker are closed at corresponding voltage
zero points. A separate control unit is required to issue the synchro-
nized breaker signals (Figure 8).
Figure 14 Load torque as a function of speed.

The Multiple Run component of PSCAD


can be used to run a number of simulations,
with selected parameters changed
in a controlled manner for each run.
Figure 9 Machine drive arrangment.
Pre-Insertion Resistance
The breaker model in PSCAD allows the user to select
the pre-insertion option and the option to close individual poles
separately.
The detailed model of the Induction motor drive
(arranged in a PSCAD page module) is shown in Figure 9.
The overvoltage at the DC link capacitor bank can be limited
by the proper design of the capacitor size and the use of
a series inductor in the DC link to limit the rate of charging
of the capacitor.
The Multiple Run component of PSCAD can be used to Figure 10 Multiple Run component.
run a number of simulations, with selected parameters changed in a
controlled manner for each run. The application note on the use of
multiple run component lays out the steps involved in detail.
In the drive example shown in Figure 9, the system side converter
is modelled as an uncontrolled diode bridge. The machine side is a
controlled bridge using IGBT units. The ring pulses are generated
using the control model shown in Figure 11. The control system
blocks required to drive the ring pulses are found in the CSMF
part of the master library. Some useful blocks in designing a more
complex ring control system are shown in Figure 12. These include
the PLL, VCO, Interpolated ring pusle module, comparators and
signal generators.
The control blocks can be used to model the load torque prole. Figure 11 Firing pulses generated using the control model.
This is an input to the machine model (Figure 14).
The drive converters produce harmonics. It is necessary to analyse
harmonics produced by the non-linear loads and determine if lter-
ing is required. Figure 13 shows the FFT module that can be used.
Polymeters can be used to display the harmonic prole. This model
can be extended to study the following without much modication
and effort:
Motor starting transients Figure 12 Blocks in the CSMF library.
MOV duty during switching events
Breaker Transient Recovery Voltage issues.

Prepared by Dr. Dharshana Muthumuni. Please email


info@pscad.com if you have an article you would like
to submit on the use of PSCAD.

Figure 13 FFT module.


Manitoba HVDC Research Centre Inc.
244 Cree Crescent
Winnipeg, Manitoba, Canada R3J 3W1
T +1 204 989 1240 F +1 204 453 5074
info@pscad.com

www.pscad.com

Innovation...
in applied research
and development.
The Manitoba HVDC Research Centre performs
innovative research and development into advanced power
system technologies, power electronics and power system
simulation. We offer specialized
engineering services and develop leading-edge
technology products for the power systems
community. Founded in 1981, we are part of the
Manitoba Hydro family, Canadas fourth largest
electrical power and gas utility.

PSCAD Setting the Standard Through the


introduction of the PSCAD simulation software,
now used in over 60 countries, the Centre has helped revolu-

0905
tionize power system simulation.

Printed in Canada
RTDS Worlds First RTDS, the worlds rst
real time digital simulator of power systems was
developed at the Centre.

2005 Manitoba HVDC Research Centre Inc.


RTP Making Waves Our RTP (Real Time Playback)
power system wave-form generator offers portable,
low cost, high delity transient testing capability.

Successful Partnerships Longstanding strategic


technology alliances with organisations such as
ABB and Siemens, and a technology advisory board

Articles and submissions addressing the use of PSCAD in the real world are always welcome.
with representation from research organizations,
universities and electrical equipment manufacturers have
fostered our success we continue to seek new technology
initiatives and research partnerships.

Power of Positive Thinkers It is thanks to the


extraordinary efforts of our researchers that the
Centre has become a world leader in power systems
simulation technologies, power systems analysis and related
technologies.

With our large worldwide base of technology users


and research partners, we have our nger on the pulse of the
electric energy industry around the globe.

Vous aimerez peut-être aussi