Canalis

Rising main KSR


busbar trunking
for multi-storey buildings

Selection guide
Canalis rising main busbar trunking
cuts installation costs in multi-storey buildings
The Canalis KSR rising main busbar trunking system launched by
Telemecanique enables electrical distribution to be rapidly installed
in multi-storey buildings of all types, including office blocks, hotels,
hospitals and car parks. Canalis KSR improves safety, cuts
installation time and reduces the overall cost of installing
distribution systems.

Fire barriers at At around half the This simple connection


each floor weight of traditional method makes it
copper conductor easier to install the
Canalis KSR based busbar distribution system
incorporates a solid trunking, Canalis KSR safely, first time.
fire barrier at each can be fitted in many
floor, giving a installations by one Canalis KSR is one of
minimum of two hours person. Its lightness the safest rising main
fire protection. This means it needs fewer busbar trunking
minimises the risk of mechanical fixings, systems available.
fire spreading in making it even faster Interlocks on the
multi-storey to install. tap-off units prevent
buildings where live loads being
vertical ducting can Fast installation connected or
provide a path for allows contractors to disconnected. The
fumes, smoke and meet the extremely busbar sections are
fire. Canalis KSR short deadlines that finger-safe to IP2X,
meets the most are becoming even when no tap-off
stringent interpretation increasingly common units are fitted. All of
of the Building in todays building which means that
Regulations for fire market. tap-off units can be
safety. safely connected to a
Canalis KSR busbar live system if this is
Rated at 400-800A, sections are linked by unavoidable.
Canalis KSR is the joint kits bolted in
first rising main place, complete with
busbar trunking to use an expansion joint
aluminium conductors that ensures a secure,
as standard. The safe and easy-to-
system is lighter and make connection.
easier to handle on Silver-to-silver
site than conventional contacts provide
copper busbar excellent conductivity
trunking, allowing fast at all joints.
installation.

2
KSR is KSR rising main is a
suitable for specific version of
KSA busbar trunking
many
for energy distribution
applications to each floor of a
multi-storey building.
Canalis KSR is
designed for medium KSR retains all the
power distribution with construction principles
high tap-off density in of KSA trunking for
multi-storey office horizontal distribution,
blocks and in particular:
commercial and Aluminium
industrial buildings. conducting bars
The range is available are equipped with
in 3 ratings: 400A, bi-metal silver
630A and 800A. copper laminate
saddles fitted at
The standard IP54 the points of
degree of protection contact in the
makes KSR suitable joints and tap-off
for many locations. outlets
This is achieved by The jointing block
the addition of dust with spring-loaded
and damp proof contacts, locked
blanking plates on the by 1/4-turn
tap-off outlets and fastening (this
joints. Connection is block, which also
via tap-off units. absorbs the
expansion of the
These units, from 25
conductors,
to 400A, can be safely
eliminates any
removed while the mechanical stress
busbar trunking is at the fire barrier)
live because they
Tap-off outlets
feature mechanical
with automatic
and electrical
closing
interlocks as shutters
standard.
KSR riser can also be Degree of
protection is IP54
fitted with any other
products from the
established Canalis
KSA busbar trunking
range.

3
Canalis KSR (400A to 800A)
Description

Medium power busbar trunking

A
E

F B
B
4
Canalis KSR (400A to 800A)
Description

Medium power busbar trunking

Product description Product selection

Page
6-7 A Riser distribution lengths Page
19 A

Connection components,
Page
8 B feed units and end covers
Page
19 - 21 B

Page
9 C Fixings Page
20 C

Page
10 D Tap-off units Page
22 - 23 D

Page
11 E Accessories Page
20 E

Page
12 F Feeder lengths Page
20 F

Components for
Page
13 G changing direction
Page
21 G
5
Canalis KSR (400A to 800A)
Description

Medium power busbar trunking

Riser distribution lengths


A The KSR length is equal to the height between 2 floors (floor-to-floor), ranging from
2900 to 4840mm (standard length and made to measure fire barrier components).
They are equipped with:
3 or 4 tap-off outlets, always positioned at the same height with respect to the
centre line of the lower floor slab
1 fire barrier, placed at the level of passage through the floor slab, eliminating
any risk of fire propagation from one floor to another via the trunking. The fire
2 barrier, which has been tested by the laboratory of the University of Gand
(Belgium) conforms to the requirements of standard ISO834. According to
report 7296, the following results were obtained:
Thermal insulation : 120 minutes
Flame resistance : 120 minutes
Stability : 120 minutes

Straight distribution lengths


Straight lengths are designed to carry current and feed loads with low or medium
power. The straight lengths form the structure of the run.
They comprise:
1 A casing of galvanised sheet steel which is crimped closed
This casing, shaped and ribbed by rolling, provides excellent resistance to
3
bending and twisting. Two casing widths cover the whole range:
4
75mm wide sheet steel with RAL 7032 grey finish for 400A rating
113mm wide sheet steel with RAL 7032 grey finish for 630 and 800A
ratings
2 4 live conductors of the same cross-section:
5
Aluminium fitted with bi-metal silver-plated copper/aluminium laminate
riders electrically welded to junctions and tap-off positions for 400 to 800A
ratings. The lamination is a patented process by which the copper and
aluminium molecules are fused together under extreme pressure
6
3 Fibreglass reinforced polyester isolators at 250mm intervals.
These hold the conductors securely within the casing
4 A special protected earth (PE) conductor of the same type as the live
conductors with a cross-section 1/2 of the phase cross-section. It is
connected to the casing at each junction
5 Tap-off outlets on the front face of the trunking at 500mm intervals.
They are connected to the isolators to form a block, holding the bars.
They have a shuttered outlet which is opened and closed automatically
when connectors or tap-off units are plugged in, or removed
6 A mechanical and electrical jointing device Electrical connection is via a
block with spring and silver graphite contacts. This block absorbs the
differential conductor/casing expansion of each length equally.
It simultaneously connects all the live conductors, ensures continuity of the
protective earth conductor and its connection with the casing.
The electrical connection is made by a 1/4 screw turn for each conductor

6
Canalis KSR (400A to 800A)
Description

Medium power busbar trunking

Fire barrier lengths


To enable to pass from floor to floor of a multi-story building. Fire resistance of the
450 barriers is 2 hours (A120) conforming to ISO834
Riser support fire barrier length
The first floor is a combined base support length for the complete riser
including the fire barrier. This is a standard length 1150m.

57 700
55 103

215 13 290

Made to measure fire barrier length


Subsequent floor fire barriers are made to measure lengths to alter the length
of a run between floor to floor heights.
450 These components are manufactured from 900mm to 2300mm in multiples of
5mm. They do not have tap-off outlets.
L = 900 - 2300

450 - 1850

7
Canalis KSR (400A to 800A)
Description

Medium power busbar trunking

Connection components, feed units and end covers


B To feed a KSR riser run by cables, or directly from a distribution panel.

Supply cable
The feed can be from one end (end feed) or along a run (centre feed). They can be connected by aluminium or
copper cables fitted with suitable cable lugs. There is an undrilled aluminium gland plate which will accept cable
glands. This plate can be replaced by a plate fitted with 1-3 cable clamps depending on the rating (to be
ordered separately)

A End feed units - For bottom or top connection

B Centre feed unit - Through run type (1 cable feeds the right and left sections)
It is mounted along the run, between 2 straight lengths

Direct supply from switchboard


Using a connection unit with spreader bars mounted at the end of a horizontal run carried out using lengths
with or without additional tap-off outlets

C Flange feed unit - Fitted with splayed bars and a mounting plate. It is used for connection to a
distribution panel. It can be mounted at either end of a component

KV-KSR connector
The KV-KSR connector is fitted with a KV end length at one end and a KSA end length at the other. Due to its
flexible design, it ensures direct connection from a feed run to a distribution run and reduces any risk caused by
alignment faults

D End cover
The end cover protects and isolates the ends of the conductors. It is mounted on the last length.
Two products cover the entire KSR range: 400 and 800A.

A
C
8
Canalis KSR (400A to 800A)
Description

Medium power busbar trunking

Fixings
C Used to fix the riser run to the structure of the building, directly or via an adjustable universal guide.

Bottom support for riser


Equips the fire barrier first joint at the bottom of the rising main. Angle wall brackets are fixed to the wall by
standard fixings (supplied by others). This unit supports the complete rising main (for design guide see page 14)

Universal Guide
This bracket maintains the trunking in position at each floor. Two adjustable fixing straps are supplied to give a
30mm depth adjustment from the supporting wall.

9
Canalis KSR (400A to 800A)
Description

Medium power busbar trunking

Tap-off units BS88 fuse links


D Tap-offs are provided by KSR tap-off units, either :
Switch fuse and Fuse switch tap-offs 32A to 400A fuses
100 to 400A moulded case circuit breaker
Standard KSA units with isolators and fuse carriers for 25 to 160A fuses

These fused tap-off units are designed to protect the tap-off by means
of fuses (not supplied).
They can be fitted with carriers for the following fuses:
32 to 160A fused on-load tap-off unit, switch fuse on-load tap-off unit
250 to 400A fused off-load tap-off unit, fuse switch on-load tap-off unit

Tap-off units for Merlin Gerin circuit breaker


These units are designed to take Merlin Gerin Compact NS circuit breakers:
100 to 400A rating
Version N, H or L
With or without residual differential device
With rotary switch
For other types of circuit breaker, please consult your regional sales office.

Standard KSA units


These units can only be mounted on trunking which is installed horizontally on edge. To make installation easier,
it is performed in two stages:
The unit is hooked onto the trunking, then automatically located in front of the tap-off outlet by moving it
sideways
The fixing brackets are then locked and the mobile power block plugged in, using an internal device

Used for instant connection of loads or secondary runs (for example, for low power distribution).
The connectors and tap-off units conform to installation standards and regulations whatever type of neutral
point connection is used (TT, IT, TNS or TNC).
They can be removed and moved whilst live, with no load
The tap-off outlets are opened and closed automatically when units are plugged in or removed
With the cover open, no live part can be accessed. Degree of protection IP2X
Connectors and tap-off units are made in two versions
Protected version, degree of protection IP54, suitable for most industrial and commercial applications

Tap-off units with isolator for


modular equipment
All standard KSA tap-off units are available to
be fitted to the KSR busbar riser products.
A selection guide for the KSA range is available
upon request. Please contact Tel: 0870 608 8 608.

10
Canalis KSR (400A to 800 A)
Description

Medium power busbar trunking

Accessories
E To achieve the degree of protection, IP54, the following accessories are fitted to the riser.

Vertical and flat installation


1 Each tap-off outlet not being used, should be fitted with a sealed tap-off blanking plate
2 Each junction between components should be fitted with a jointing sleeve to maintain the IP54 projection
Various devices, for lead sealing in particular, can be used to complete the equipment of the
KSR rising main.

11
Canalis KSR (400 to 800A)
Description

Medium power busbar trunking

Feeder lengths (with or without tap-off outlets)


F These lengths, without tap-off outlets are used as feeders, running horizontally (generally in the basement or in
the utilities ducting) between the switchboard and the bottom of the distribution rising main.
Any complementary lengths required for this horizontal run (elbows, special lengths, fire barriers) can be
selected for the KSA components from the Canalis Busbar Trunking and Power Applications catalogue
available upon request. Please contact 0870 608 8 608.

12
Canalis KSR (400 to 800A)
Description

Medium power busbar trunking

Components for changing direction


G Edgewise elbow
One model for each size of casing for turning to left or right
Flat elbow
Two models for each size of casing (one ascending, one descending). Flat and edgewise elbows can be
manufactured upon request, with made to measure connection lengths, with multiple angles, with
built-in fire barrier, etc. for the KSA components from the Canalis Busbar Trunking and Power Applications
catalogue available upon request. Please contact 0870 608 8 608.

Edgewise tee and cross


For vertical branches on the main

13
Canalis KSR (400 to 800A)
Design guide

Medium power busbar trunking

Information required to design a KSR riser system


The types of load and their characteristics and floor locations
The power source and its characteristics and location
The structure of the premises (availability of fixing points for trunking)
Any influences external to the installation site. (ambient temperature, dust, water, etc)

Distribution run layout


The siting of rising main depends on the position of the loads, the location of the general power supply and the
availability of fixing points. A single supported KSR riser run can serve up to 12 floors (60 metres).

Selection of the trunking according to the rated operating current Ib


k1 = average demand coefficient Ib = total current x k1 Basement
Total current = sum of currents drawn by the loads on a run

Applications k1 Rated operating current Ib Selected trunking


Lighting, heating 1 0...100 A KS-10 4 tap-offs per floor
100...160 A KS-16
Distribution 160...250 A KS-25
2 or 3 loads 0.9 315...400 A KS-40
4 or 5 loads 0.8 400...500 A KS-50
6...9 loads 0.7 500...630 A KS-63
10...40 loads 0.6 630...800 A KS-80
40 or more 0.5

Permissible current Iz according to the ambient temperature


(at the installation site)
The nominal current Inc of the trunking is specified for an average daily ambient temperature of 35C
(and a maximum of 40C). Depending on the actual temperature, an uprating or derating coefficient (f1) may be
applied to the nominal current Inc : see the characteristics on page 17.

Checking the voltage drop


The voltage drop in Canalis KS is given in V/100m/A in the characteristics table on page 17.

Polarity selection
3-pole distribution + N 3-pole distribution +
+ PE (IT-TT-TNS) PEN (TNC)
3L + N + PE 3L + N + PE
(IT-TT-TNS) KSA-D4 (IT-TT-TNS) KSA-ED4
trunking trunking
3-pole + N + PE tap-offs 3-pole + PEN tap-offs
possible, type 3-pole + possible, type 3-pole +
3L + PE
PE or 3-pole + N + PE 3L + PE PEN (TNC) or 3-pole +
(IT-TT-TNS) (IT-TT-TNS) N + PE (TNS).

14
Canalis KSR (400 to 800A)
Design guide

Medium power busbar trunking

Protecting the trunking against overloads (1)

To enable it to be extended, prefabricated busbar trunking is generally protected to its nominal current Inc
(or to its permissible current Iz if the K1 coefficient is applied according to the ambient temperature).

Protection using fuses


Calculate the standard nominal current In of the fuse so that : In Inc
k1
Select the circuit breaker setting current Ir so that : Ib Ir Inc
Note: Protecting trunking using a circuit breaker makes it possible to use the trunking at full capacity.

Protection using a circuit breaker


Select the circuit breaker setting current Ir so that : Ib Ir Inc
Note: Protecting trunking using a circuit breaker makes it possible to use the trunking at full capacity.

Electrodynamic protection against short-circuit currents


The electrodynamic withstand of the trunking should be taken into account when selecting a protective device
(permissible rated peak current).
Determine the 3-phase short-circuit current, prospective lcc 3 (KA) at the start of the Canalis KSR
Check the current limitation curve of the selected protective device, that this limits the peak current (kA) to a
value below the permissible rated peak current of the KSR trunking. Limited current Canalis current

Protection using a Merlin Gerin Compact circuit breaker


The circuit breaker/Canalis co-ordination table below gives the maximum short-circuit current for which the
KSR trunking is protected, according to the type of circuit breaker.
Prospective Icc 3, max (Ka rms) voltage 380/415V.

Canalis KSR : rating (A) 100 160 250 400 500 630 800
Type of NS100 N 25
Merlin Gerin H 25
circuit breaker (1)
L 25
NS160 N 20 36
H 20 70
L 20 70
NS250 N 36 36
H 55 70
L 55 150
NS400 N 45 45
H 45 70
L 45 150
NS630 N 45 45 45
H 70 70 70
L 150 150 150
C801 N 40 50
H 40 50
L 55 50
C1001 N 50
H 50
L 80
(1) By calculation or using graphs, pre-calculated tables, etc.
Note: To obtain details of the Merlin Gerin circuit breaker range, please refer to the circuit breaker brochure
available by phone from 0870 608 8 608
15
Canalis KSR (400 to 800A)
Design guide

Medium power busbar trunking

Selection of IP degree of protection


External influences are taken into consideration when siting the installation.
The IP54 degree of protection of Canalis KSR means that it is suitable for
installation in most industrial and commercial locations.
Especially for locations or sites which may be subject to water splashes in any
direction, the degree of protection is achieved by installing sealed tap-off blanking
plates and sealed jointing sleeves. (See page 20).

Changing levels in horizontal distribution


The trunking is mounted vertically, the degree of protection at a junction is
IP54. This is achieved by fitting a standard sealed jointing sleeve at each junction.

Tap-off units
The complete range of tap-off units for KSR are IP54 dust and damp proof range,
for very dusty or damp environments.

KSE = IP54

Mounting position

230

21
120 - 150

Selecting the power supply B

A cable feed unit can be mounted at either end of a run, bottom or top
500 and 800A feed unit

Two types depending on position:


Bottom (right hand) mounting (fig. A)
Top (left hand) mounting (fig. B)
All types of neutral system. Connected by means of cable lugs.
A
Switchboard feed may be connected via cable or busbar interconnector.

16
Canalis KSR (400 to 800A)
Characteristics (1)

Medium power busbar trunking

General characteristics (1)

Type of trunking KSA-40 KSA-63 KSA-80

Number of conductors 4 4 4

Nominal rated current INC to 35 C 0


A 400 630 800

Rated insulated voltage Conforming to IEC 158-1 Ui V 660 660 660

Rated operating voltage Ue V 660 660 660

Rated frequency F Hz 50/60 50/60 50/60

Fault loop characteristics


Type of trunking KSA-40 KSA-63 KSA-80

Between live conductors


Average resistance of loop Rb1phph m/m 0.38 0.202 0.122
(thermal stabilisation temp. 01)
phN m/m 0.38 0.202 0.122

phPEN m/m 0.2613 0.1409 0.0929

Average resistance of loop (1)


Rb2phph m/m 0.45 0.239 0.144
(short-circuit conventional temp.)
phN m/m 0.45 0.239 0.144

phN m/m 0.3113 0.169 0.1101

Average reactance loop Xbphph m/m 0.252 0.154 0.1475

phN m/m 0.2915 0.197 0.1895

phPEN m/m 0.2115 0.1433 0.1395

Between live conductor and PE


Average resistance of loop Rb1phPE m/m 0.304 0.167 0.128
(thermal stabilisation temp. 01)

Average resistance of loop (1) Rb2phPE m/m 0.365 0.201 0.153


(short-circuit conventional temp.)

Average reactance loop XbphPE m/m 0.303 0.225 0.226

(1) Conforming to international standard IEC 439-2 and European standard EN 60439.2

17
Canalis KSR (100 to 800A)
Characteristics (1)

Medium power busbar trunking

Conductor characteristics
Type of trunking KSA-40 KSA-63 KSA-80

Live conductors (per conductor)


GE resistance, cold state Rboph(1) m/m 0.142 0.074 0.045
(ambient temperature 20C)

R1 average resistance at/nc Rb1ph(1) m/m 0.190 0.101 0.061


(ambient temperature 35C)

X1 average resistance at/nc Xbph(1) m/m 0.112 0.070 0.071


and at rated frequency (Hz)
Protective conductors
Average resistance, cold state m/m 0.105 0.061 0.061
(ambient temperature 35C)

Other characteristics
Type of trunking KSA-40 KSA-63 KSA-80

Short-circuit withstand capacity


Maximum thermal limit 12 t ph or N kA 354x106 1225x106 1758x106

PE kA 354x106 1225x106 1225x106

PEN kA 500x10 6
2000x10 6
2500x106

Permissible rated peak current Ipk kA 49.2x106 67.5x106 78.7x106

Degree of protection
IP54 With accessories.
Voltage drop Composite voltage drop, hot state, expressed in V/100 m/A
for 3 phase 50Hz current, with load
distributed along the run. Where the load is concentrated
at the end of a feed run, the voltage drops
are twice the values indicated in the table.
For a power factor Cos f=1.0 V/100 m/A 0.01645 0.00875 0.00528

For a power factor Cos f=0.9 V/100 m/A 0.01904 0.01051 0.00743

For a power factor Cos f=0.8 V/100 m/A 0.01898 0.01063 0.00792

For a power factor Cos f=0.7 V/100 m/A 0.01844 0.01045 0.00805

Destination of permissible current Derating or uprating factor to be applied to the rated


Iz for a busbar trunking system, current of the trunking where the average daily ambient
according to ambient temperature temperature is other than 35C

Average ambient temperature C 15 20 25 30 35 40 45 50 55

Factor f1 1.11 1.08 1.06 1.03 1.00 0.97 0.94 0.91 0.87

(1) Conforming to international standard IEC 439-2 and European standard EN 60439.2

18
Canalis KSR (400 to 800A)
References

Rising main busbar

Floor distribution lengths


Rating A Length no. of tap-off outlets Catalogue number 3Ph Weight kg
(front face) +N+PE or 3Ph+PEN

400 2000 3 KSA40VD420 16

2500 4 KSA40VD425 20

630 2000 3 KSA63VD420 24

2500 4 KSA63VD425 30

800 2000 3 KSA80VD420 28

2500 4 KSA80VD425 35

Additional fire barrier lengths


Rating A Length Length of Length of part on Catalogue number 3Ph Weight kg
(L) top part measurement Y= +N+PE or 3Ph+PEN Min. Max. 450

400 900-2300(1) 450 450...1850 KSA40EF4B 8 20 900 - 2300


Fire
630 900-2300 (1)
450 450...1850 KSA63EF4B 12 30 barrier

Y= 450 - 1850
800 900-2300 (1)
450 450...1850 KSA80EF4B 14 35

End feed unit cable connector and end cover


Description Rating A Connection Type/Max Catalogue number 3Ph Weight kg
cross section +N+PE or 3Ph+PEN

Bottom end feed 400 Lugs/ 2x300mm2 (M12 screws) KSA50AB452 22.000
unit by cables
Bottom end feed 800 (630) Lugs/ 3x300mm2 (M12 screws) KSA80AB452 36.200
unit by cables
End cover 400 KSB50FA2 0.440

800 (630) KSB80FA2 0.510

Riser base support length (bracket) including a fire barrier


Rating A Length Total supportable Catalogue number 3Ph Weight kg
height +N+PE or 3Ph+PEN

400 1150 60m (12 floors) KSA50VA412 (2)


20

630 and 800 1150 60m (12 floors) KSA80VA412 (2)


30 Fire
barrier

(1) When ordering, state the required length in mm (in multiples of 5 mm) after the reference.
Example : KSA-40EF4B L = 1250 mm.
(2) Order 1 KSA00ZA1 per riser base support length

19
Canalis KSR (400 to 800A)
References

Rising main busbar

Fixings vertical riser


Description Rating A Maximum height m Catalogue number 3Ph Weight kg
+N+PE or 3Ph+PEN

400 50 KSA00ZA1 8.200


Riser base support
wall bracket 630 50 KSA00ZA1 8.200
(used with Riser support length)
800 50 KSA00ZA1 8.200

Riser guiding bracket All KSA80ZM52


(1bracket per floor) with
depth adjustment bracket

IP54 - dust and damp proof accessories


Description Rating A Connection Type/Max Catalogue number 3Ph Weight kg
cross section +N+PE or 3Ph+PEN

Junction sleeve 400 KSE50YA2 2.250

630/800 KSE80YA2 2.600

End cover sleeve 400 KSE50YF2 2.280

630/800 KSE80YF2 2.600

Tap-off outlet shutter 400/630/800 KSE80YB2 0.080

Sealing device All KSA80YB3 0.080

Feeder straight lengths manufactured to required length


Without tap-off outlets for horizontal runs

Rating A Length mm Reference Weight kg (1) When ordering, state


the required length in
500 (400) 500 to 1995 KSA-50ES4A (1)
15.000 mm (in multiples of
5mm) after the
800 (630) 500 to 1995 KSA-80ES4A (1)
19.600 reference.
Example: KSA-80ES4A
L=1250mm.
Straight lengths for switchboard interconnection
Without tap-off outlets for horizontal runs

Rating A Length mm Reference Weight kg

400 2500 KSA-40EA450 40.300

2500 KSA-40EA430 24.200

500 2500 KSA-50EA450 48.800

2500 KSA-50EA430 29.300

630 2500 KSA-63EA450 62.500

2500 KSA-63EA430 37.500

800 2500 KSA-80EA450 80.000

2500 KSA-80EA430 48.000

Fixing device horizontal feeder lengths (order in multiples of 10)


Description Rating A Mounting Type/Max Reference Weight kg
cross section

Bracket 500 (400) KSA-50EZ3 0.330

800 (630) KSA-80EZ3 0.400

20
Canalis KSR (400 to 800A)
References

Rising main busbar

Connection components and feed units (2)

Description Rating A Connection Mounting Unit reference Weight kg


Type/Max
cross section

Switched end feed 500 Lugs 1 x 300mm2 Bottom KSA50AB452SW 30.00


unit by cables isolator
bottom
Switched end feed 800 Lugs 2 x 300mm2 Bottom KSA80AB452SW 65.00
KSA-50AB452
unit by cables isolator OR
bottom Lugs 3 x 240mm2
End feed unit 500 (400) Lugs/2 x 300mm2 Top KSA50AB462 22.00
by cables top M12 screws
End feed unit 800 (630) Lugs/3 x 300mm2 Top KSA80AB462 36.20
by cables top M12 screws
Centre feed unit 500 (400) Lugs/2 x 300 mm2 Along the run KSA-50BT402 39.000
(M12 screw)
800 (630) Lugs/3 x 300 mm2 Along the run KSA-80BT402 40.000
(M12 screw)
Flange feed unit 500 (400) Bars Bottom or top KSA-50ER4 4.100
(M12 screw)
800 (630) Bars Bottom or top KSA-80ER4 6.150
(4 x M10 screw)
N KV-KS connector 500 (400) Bottom or top KV0-50ER41001 23.800
KV0-50ER41001 800 (630) Bottom or top KV0-80ER41001 43.000

Components for changing direction (2)

Description Rating A Mounting Type/Max Unit reference Weight kg


cross section

Elbows 500 (400) Edgewise KSA-50LC40 9.860

Flat upwards (1)


KSA-50LP41 10.000

Flat downwards (1)


KSA-50LP42 10.000

800 (630) Edgewise KSA-80LC40 15.000


KSALP41
Flat upwards (1)
KSA-80LP41 13.700

Flat downwards (1) KSA-80LP42 13.700

Tee 500 (400) Edgewise KSA-50TC40 15.000

800 (630) Edgewise KSA-80TC40 18.240

Cross 500 (400) Edgewise KSA-50XC40 16.500

800 (630) Edgewise KSA-80XC40 20.000

(1) IP54 achieved with sealing accessories. See page 20


(2) Other run components IP54 as standard, common to versions of 3L+N+PE and 3L+PEN straight lengths.

21
Canalis KSR (400 to 800A)
References

Medium power busbar trunking

Tap-off units, switchfuse and fuseswitch


Rating A Fuse size Connection Continuous (1) Reference Reference Weight kg
AC 22/23 mm2 rating of device
A

32 BS88 (2)
10 32 KSE-03ST41 Twinbreak Switchfuse 9.0

63 BS88 (2)
35 63 KSE-06ST41 Twinbreak Switchfuse 10.5

100 BS88 (2)


70 90 KSE-10ST41 Twinbreak Switchfuse 10.5

125 BS88 (2)


150 100 KSE-12ST41 Twinbreak Switchfuse 11.0

160 BS88 (2)


240 120 KSE-16ST41 Twinbreak Switchfuse 11.0

250 BS88 (2)


240 200 KSE-25ST41 Fupact Fuseswitch 26.0

315 BS88 (2)


240 250 KSE-31ST41 Fupact Fuseswitch 26.5

400 BS88 (2)


240 250 KSE-40ST41 Fupact Fuseswitch 26.5

(1) In 350C ambient.


(2) BS 88 fuse links not provided.

22
Canalis KSR (400 to 800A)
References

Medium power busbar trunking

Tap-off units for Merlin Gerin Compact NS fixed circuit breaker complete
Fully assembled fitted with N frame MCCB and door interlocked rotary handle

Number of conductors 3L + N + PE

Scheme (1)
Trunking TT TNS
Tap-off TT TNS

Tap-off scheme

Rating A Type of circuit breaker Reference Weight kg


KSE-16DB411SP3 fitted

25 NS100N/TM25D KSE16DB411SP1 12.6

63 NS100N/TM63D KSE16DB411SP2 12.9

100 NS100N/TM100D KSE16DB411SP3 12.9

125 NS100N/TM125D KSE16DB411SP4 12.9

160 NS160N/TM160D KSE16DB411SP5 13.1

200 NS250N/TM200D KSE25DB411SP1 15.8

250 NS250N/TM250D KSE25DB411SP2 15.8

400 NS400N/STR23SE KSE40DB411SP3 19.5

Empty tap-off units for Merlin Gerin Compact NS fixed circuit breaker
Standard extendable rotary handle (not included)

Rating A Type of circuit breaker Reference Weight kg

100 NS100 (either) N,H,L (1)


KSE16DB411 (2)
11.0

160 NS160 (either) N,H,L (1)


KSE16DB411 (2)
11.0

250 NS250 (either) N,H,L (1)


KSE25DB411 (2)
13.5

400 NS400 (either) N,H,L (1)


KSE40DB411 (3)
13.5

(1) Selection of moulded case circuit breaker, please refer to the Merlin Gerin circuit breaker brochure
available from 0870 608 8 608
KSE-16DB411
(2) A standard extended rotary handle part No. 29338 needs to be fitted with the MCCB.
(3) A standard extended rotary handle Part No. 32598 needs to be fitted with the MCCB.

23
Canalis KSR (400 to 800A)
References

Medium power busbar trunking

Trunking riser lengths 400, 600 and 800A


KSA-40VD, KSA-63VD, KSA-80VD

a
250 250

146

Rating A a
500
500 400/500 75

630/800 113

2000
2500

500
500

500

24
Canalis KSR (400 to 800A)
References

Medium power busbar trunking

Trunking feeder lengths 400, 500, 630 and 800A


KSA-40ED, KSA-50ED, KSA-63ED, KSA-80ED

750 1000 1000 1000 1000 250

250 1000 1000 1000 1000 750

5000

146
Rating A a

400/500 75

a 630/800 113

Fire barrier lengths 400, 600, 800A

450
450

L = 900 - 2300

Y= 450 - 1850
57
700
55 103

215 13 290

120 - 150

Straight lengths manufactured to required length


KSA-ES4A
Rating A a

400/500 75

(1) a 630/800 113

(1) Minimum 500. Maximum 1995

25
Canalis KSR (400 to 800A)
Dimensions (mm)

Medium power busbar trunking

Feed units for 400 and 800A trunking - KSA-BT402, KSA-AB42


KSA-BT402 KSA-AB42
A1 D1
A D
Rating A A A1 B

400/500 290 235 510


B
B-20 630/800 390 316 556

Cable outlet
170 G

11
B A F

300 660 1000


11

177 C-20
C

Rating A A B C D D1 F G

400/500 600 770 406 230 175 300 150

630/800 680 850 556 310 236 300 190

Cable outlet

KSA-50AB402SW 127
89
KSA-80AB402SW 147
91

344 409

11 450 11
450
1058
928
900
400 400

770

259
388
331 650 299
433
695 429

Flange feeder unit


KSA-50ER4 250 220 170 7 KSA-80ER4 290 260 210 7

290 290
340 340

370 370

14
315 338 11
40
37

143 20
166 40
N 16
N 72
80 80 80
26 80 80 80
Canalis KSR (400 to 800A)
Dimensions (mm)

Medium power busbar trunking

End covers KV-KS connector


KSA-50ER4, KSA-80ER4 KV0-ER41001

146
20

a
2000

Rating A a

500 75

800 113

Elbows, tee and cross for 400 to 800A trunking


KSA-LC40 KSA-LP41 KSA-LP42

N N
146
290
290
N

290 290 290

a a
a
290

KSA-TC40 KSA-XC40
Rating A a
N N
146 146
400/500 75

630/800 113

290
290

580
a
290 290 290
580

a
290 290
580

27
Canalis KSR (400 to 800A)
Dimensions (mm)

Medium power busbar trunking

Fixing brackets
KSA-80ZM52 KSA-50EZ3 KSA-80EZ3

40 50 50 36
40 50 50 36

176
176
230
152 30 8x14
115 30 8x14

21
120-150

Sealing and joining kits Tap-off blanking plate


KSE-50YA2 KSE-80YA2 KSE-80YB2
190 200 155
a Rating A a
105 140
100/250 70

40/500 90

323 95 630 and 800 125


323

Dust and damp proof tap-off units with/without isolator for modular equipment
KSE-05DA KSE-10DA

270 395

50 7.5 modules (140 x 47)


7.5 modules (140 x 47)
195
113*

183
190 100

70 40

52

28
Canalis KSR (400 to 800A)
Dimensions (mm)

Medium power busbar trunking

Dust and damp proof tap-off units for Merlin Gerin circuit breakers
KSE-16DB11 KSE-25DB11 KSE-40DB11

147
197 207
257 275
325

163
163
368 163
15 368
15 368
18

465

590

780

Dust and damp proof tap-off units for fused switch disconnector
KSE-03ST41 KSE-06ST41 KSE-12ST41 KSE-25ST41
KSE-10ST41 KSE-16ST41 KSE-31ST41
KSE-40ST41
51 51 51 46

147 147 147 232

50 50 50
50

271 10 271 10 271 10 421 10

306
406 456

606

29
Canalis KSR (400 to 800A)
Riser system

Medium power busbar trunking

4 tap-off outlets floor to floor 3500mm to 4900mm

450

Fire barrier
Second floor

250

500

Floor to floor height


3500 - 4900

Feeder busbar 500 2500

Guide bracket 500

450

Riser suppor bracket


1150
Fire barrier First floor

250

500

3500
2000
Feeder busbar 500

Guide bracket

End feeder box 505

Ground floor

30
Canalis KSR (400 to 800A)
Riser system

Medium power busbar trunking

3 tap-off outlets floor to floor 2900mm to 3495mm

450

Fire barrier
Second floor

250

500

Floor to floor height


2900 - 3495

Feeder busbar 500 2000

Guide bracket

450

Riser suppor bracket


1150
Fire barrier First floor

250

500

3500
2000
Feeder busbar 500

Guide bracket

505
End feeder box

Ground floor

31
Nationwide support on one number -
call the Customer Information Centre on

0870 608 8 608


Fax 0870 608 8 606
Schneider Electrics local support
Schneider Electric is committed to supporting its customers at every stage of a project. Our 180 sales engineers, the largest
dedicated sales force in the UK electrical industry, operate from 4 customer support centres.
Our sales engineers are skilled at assessing individual requirements and combined with the expert support of our product
specialists, will develop the most effective and economical answer taking relevant regulations and standards fully into account.
To access the expertise of the Schneider Electric group, please call 0870 608 8 608. Each customer support centre includes
facilities for demonstrations and training, and presentation rooms fully equipped with audio visual and video, providing
excellent meeting facilities.

Merlin Gerin is a world leader in the manufacture and


supply of high, medium and low voltage products for the
distribution, protection, control and management of
electrical systems. Its quality products, solutions and
services are focused on the needs of both the commercial
and industrial sectors.

Modicon is a world leader in high technology


programmable controllers (PLCs) and motion control
systems used in industrial automation. Its international
catalogue includes PLCs, numerical controllers, terminals,
software, multiple fieldbus and ethernet communication
networks, and human machine interfaces (HMI).

Square D is a total quality organisation and its business


is to put electricity to work productively and effectively,
protecting people, buildings and equipment. Its low voltage
electrical distribution equipment, systems and services are
used extensively in residential and commercial applications.

Telemecanique is a UK market leader and world expert


in industrial control and automation. It provides complete
solutions, with its range of components, programmable
logic controllers, variable speed drives and communications
software. In addition, it offers power distribution through
prefabricated busbar trunking.

Local customer support centres


Scotland South West North West Greater London
Schneider Electric Ltd Schneider Electric Ltd Schneider Electric Ltd Schneider Electric Ltd
Unit 11000 190 Aztec West 8 Brindley Road 2nd Floor
Academy Business Park Park Avenue City Park Business Village 408 Strand
Gower Street Almondsbury Cornbrook London WC2R 0NE
Glasgow G51 1PR Bristol BS32 4TP Manchester M16 9HQ webmasterGB@schneider.co.uk
webmasterGB@schneider.co.uk webmasterGB@schneider.co.uk webmasterGB@schneider.co.uk

Regional product showrooms


Industrial systems and solutions product showroom
Schneider Electric Ltd, University of Warwick Science Park, Sir William Lyons Road, Coventry CV4 7EZ

Building systems and solutions product showroom


Schneider Electric Ltd, Fordhouse Road, Wolverhampton WV10 9ED

Energy and Infrastructure systems and solutions product showroom


Schneider Electric Ltd, 123 Jack Lane, Hunslet, Leeds LS10 1BS

http://www.schneider.co.uk
CAN 5226 JUN 2002

Vous aimerez peut-être aussi