The 3300/20 Dual Thrust Position Monitor provides early warning of thrust
3300/20
bearing failure. It continuously measures and monitors two independent
channels of shaft axial position relative to the axial clearances within the
DUAL THRUST machine. Ideally, the axial probes are installed to observe the thrust collar
MONITOR
directly, so the measurement represents the position of the collar relative to the
25 24
vdc 25
thrust bearing clearance.
20 N N 20
O O
R 20 R
15 M M 15
M 10 10 M
Caution
I 16 I
L L
S 5 5 S
/
D
I
S
0 12 0 I
/
D
S
Because thrust measurements are made by observing the gap voltage of the
P P
L
A
C
5
C8 C
5 L
A
C
proximity probe used as an input, a transducer failure (gap out of range) can be
E 10 O O 10 E
M
E
N
U
N
T
15 E
U
N
T
E
M
E
15 N
interpreted by the monitor as thrust position movement and result in a false
T R4 R T
20 20 thrust alarm. For this reason, Bently Nevada LLC. does not recommend the use
25 0 25
of a single probe for thrust position applications. Instead, these applications
OK should use two proximity probes observing the same collar or shaft and
A
DANG ER
B
configure the monitor as AND voting whereby both transducers must
ALERT
simultaneously reach or exceed their alarm setpoints for the monitors alarm
BYPASS
relays to actuate. This 2-out-of-2 voting scheme (also known as AND voting)
provides optimum protection against both false trips and missed trips. While the
DANG ER ALERT 3300/20 monitor can be programmed for either single voting (OR) or dual voting
(AND), dual voting is strongly recommended for all thrust position applications.
GA P
Caution
A B
BUFFER ED TR ANSD UCER S
Probe adjustment and range is critical in this monitor for machinery protection.
Improper adjustment of the transducer may prevent the monitor from alarming
(no machinery protection). For proper adjustment, follow instructions in the
manual.
Page 1 of 6
0 to -10 Vdc: 1.1% of
Specifications signal, 15 mV offset.
Inputs Output
Signal: Impedance
(voltage
Accepts one or two proximity outputs):
probe signal inputs.
100 . Minimum load resistance
Input is 10 k .
Impedance:
Voltage
10 k . Compliance
Sensitivity: (current
outputs):
User-programmable for 200
mV/mil (8 V/mm) or 100 mV/mil (4 0 to +12 Vdc range across load.
V/mm). Load resistance is 0 to 600
when using +4 to +20 mA option.
Power:
Buffered
Nominal consumption of 1.5 Transducer
watts. Outputs:
Signal Conditioning There is one coaxial connector
Accuracy: per channel on the front panel
and one terminal connection per
Within 0.33% of full-scale channel on the rear panel. All are
typical, 1% maximum. All short-circuit protected.
specified at temperature of +25C
(+77F). Output
Impedance:
Outputs
100 .
Recorder:
Transducer
User-programmable for +4 to +20
Supply Voltage:
mA, 0 to -10 Vdc, or +1 to +5 Vdc.
Voltage or current outputs are User-programmable in power
proportional to programmed supply for -24 Vdc or -18 Vdc.
monitor full-scale. Independent Current limited on individual
recorder outputs are provided for monitor circuit board.
each channel. Monitor operation
Note: Contact your nearest sales professional if 3000 series
is unaffected by short-circuits on
transducers are to be used in the monitoring system which also
recorder outputs.
uses 3300 and/or 7200 series transducers.
Recorder
Accuracy (in Alarms
addition to Alarm
signal Setpoints:
conditioning
Both alarms (Alert and Danger)
accuracy) at
are bi-directional (normal and
+25C (+77F):
counter), digitally adjustable from
+4 to +20 mA: 0.7% of 0 to 100% of full-scale and can be
signal, 0.09 mA offset. set within LCD resolution (1.6%)
to desired level. Once set, alarms
+1 to +5 Vdc: 1.1% of
are repeatable within 0.39% of
signal, 10 mV offset.
full-scale.
Page 2 of 6
Displays Relative
Meter: Humidity:
Page 3 of 6
1. AND voting logic is not available with Quad Relays.
Ordering Information
For spares, order the complete catalog number as 2. At least one relay module must be ordered with each
described below. This includes a front panel 3300 System. If one common relay module per system
assembly, monitor PWAs with sheet metal, and has been ordered, all monitors of this type must be
appropriate relay module. This unit is optioned, jumper programmed at the factory to activate a relay
tested and ready to install in your system. Spare bus. Order SCK (Special Configuration Kit) 157520-119
relay modules can be ordered separately. & -120 for bus one or 157520-121 & -122 for bus two.
Option Descriptions 4. Quad Relays are not available with the Internal Safety
A: Full-scale Range Option Barriers option.
01 25-0-25 mils D: Agency Approval Option
02 30-0-30 mils 00 Not required
03 40-0-40 mils 01 CSA/NRTL/C
05 50-0-50 mils 02 ATEX self certification
06 75-0-75 mils
Note: ATEX approval requires the monitor rack be installed in a
11 0.5-0-0.5 mm
weatherproof housing.
12 1.0-0-1.0 mm
13 2.0-0-2.0 mm E: Safety Barrier Option
B: Transducer Input Option 00 None
01 3300 or 7200 Proximitor 01 External
systems, 200 mV/mil (Ranges 02 Internal
01, 02, 03, 11, and 12 only.)
02 7200 11 mm (not 3300XL) Spare Relay Module Assemblies
Proximitor system, 100 mV/mil
03 7200 14 mm or 3300 HTPS (Order the option in parenthesis for ATEX approved
Proximitor systems, 100 spares)
mV/mil 81544-01(02)
04 3000 Proximitor 200 mV/mil
(Transducer Output Voltage in No Relays
power supply must be set for 81545-01(02)
18 Vdc or use power conver-
ter. Ranges 01 and 11 only.) Dual Epoxy Relays
05 3300XL NSv and 3300 RAM
81546-01(02)
Proximitor Sensor, 200 mV/mil
(Ranges 01 and 11 only). Dual Hermetic Relays
Note:
84152-01(02)
1. For 3300 XL 11mm transducers, use mod 146300-01.
Quad Relays
2. Contact your nearest sales professional if 3000 series 88984-01(04)
transducers are to be used in a monitoring system
which also uses 3300 and/or 7200 Series transducers. Dual Hermetic, Internal Barriers
88984-02(05)
C: Alarm Relay Option
00 No Relays Dual Epoxy, Internal Barriers
01 Epoxy-sealed
02 Hermetically-sealed 88984-03(06)
03 Quad Relay (Epoxy-sealed No Relay, Internal Barriers
only)
04 Spare Monitor-No SIM/SIRM Notes:
Notes:
1. External Safety Barriers must be ordered separately.
Specifications and Ordering Information
Part Number 141500-01
Rev. J (06/07)
Page 4 of 6
2. Quad Relays are not available with Internal Safety Danger Relay
Barriers option. Mode Option
Normally de-energized
Field-programmable Options
Normally energized
These options are field-programmable via plug-in
jumpers. Recorder
Outputs Option
Bold text indicates options as shipped from the
factory. +4 to +20 mA
+1 to + 5 Vdc
First Out Option
0 to -10 Vdc
Enabled
Danger Relay
Disabled
Voting Option
AND voting for relay drive
OR voting for relay drive
OK Mode Option
Note: For Quad Relays, AND voting logic must be done externally
Nonlatching by wiring the contacts in series.
Page 5 of 6
Field wiring diagram
3300/20 Dual Thrust Position Monitor
Thrust Collar
Channel A
Probe
R
Proximitor
3300/20
Channel B
DUAL THRUST
Probe Shaft
MONITOR
25 24
vdc
25
3 Conductor
20 N
O
R
M
20
N
O
R
M
20
Shielded Cable
15 15
10 10
M 16
M
I
L 5 5
L
S S
/ /
D 0 12 0
D
I
S S
P 5 5
P
L L
A C 8 C
A
C 10 O O 10
C
E U U E
M N N M
E 15
T
E
T
E 15
E
N R 4 R N
T
20 20
T
CH A CH B
-VT
Channel B
25 0 25
Channel A COM
OK PWR
OUTPUT
DANGER COM
A B
ALERT IN
Shield (Green)
BYPASS BUF
(To single earth
COM
point ground) 4 pl.
REC
DANGER ALERT
To Channel A To Channel B
Recorder Recorder Output
GAP
Output ALERT DANGER
A B
NC
BUFFERED TRANSDUCERS
ARM
Alert NO Danger
Relay NC
Relay
Contacts ARM
Contacts
NO
Page 6 of 6