Vous êtes sur la page 1sur 7

2054 IEEE Transactions on Power Delivery, Vol. 10, No.

4, October 1995

Control Sensitivity Indices for Stability Analysis of HVdc Systems


O.B. Nayak? A.M. Gole? D.G. Chapman* J.B. Davies*
(Member) (Member) (Senior Member) (Non- Member)
University of Manitoba?, Manitoba Hydro*
Winnipeg, Manitoba, Canada
Abstract - This paper presents a new concept called the Control Normally VSF is positive (voltage increases with reactive
Sensitivity Index or CSI, for the stability analysis of HVdc conver- power increase); a negative value indicates voltage instabili-
ters connected to weak ac systems. The CSI for a particular con- ty. Hammad et al. have successfully used this method to
trol mode can be definedas the ratio of incrementalchanges in the
develop optimal methods for voltage control at the conver-
two system variables that are most relevant to that control mode.
The index provides valuable information on the stability of the ter bus. FrankCn and Anderson [3] use a similar technique
system and, unlike other approaches, aids in the design of the con- to study the voltage stability under various converter control
troller. It also plays an important role in defining non-linear gains modes and tap changer control. They also show the equiva-
for the controller. This paper offers a generalized formulation of lence between the M A P index of Ainsworth [11and the VSF
CSI and demonstrates its application through an analysis of the [2], [5] of Hammad et al. Pilotto et al. [ 6 ]demonstrated the
CSI for three modes of HVdc control. The conclusionsdrawn from application of the VSF method in the analysis of a converter
the analysis are confirmed by a detailed electromagnetic tran-
sients simulation of the addc system. The paper concludes that
connected to a weak ac system and verified their results with
the CSI can be used to improve the controller design and, for an EMTP simulation.
inverter in a weak ac system, the conventional voltage control The Control Sensitivity Index approach presented here is
mode is more stable than the conventional y control mode. based on analyzing the sensitivity of the power system re-
sponse to a change in an output quantity of the controller
Keywords: HVdc, Weak Ac Systems,VoltageStability, Electromag- under consideration. The CSI approach focuses on the
netic Ikansients Simulation, Control Sensitivity Zndex.
characteristics of the system which are directly associated
I. INTRODUCTION with the controller. It is to be noted that nowhere in the
formulation of CSI is any controller parameter used.
In recent years several authors [1],[2],[3],[4] have pres- Instead, the system characteristic is analyzed from the point
ented methods for the stability analysis of HVdc converters of view of a controller output quantity. The CSI approach
terminating at ac system locations having low short circuit will be useful to HVdc control engineers as well as system
capacities. These methods have usually been based on planning and design engineers.
steady state models, assuming fundamental frequency op- In common with MAP and VSF methods mentioned
eration. They provide valuable insight into the basic mecha- above, the CSI calculation is also based on the steady state
nisms of phenomena such as voltage instability. They are network equations, assuming fundamental frequency ac
more realistic than earlier approaches which used concepts voltages and hence, considers only the steady state instabili-
such as the short circuit ratio (SCR) or the effective short ty associated with a control mode. The results from CSI
circuit ratio (ESCR). Ainsworth [l] has introduced the con- analysis are confirmed with digital simulation using an elec-
cept of Maximum Available Power ( M A P ) for the case of tromagnetic transients simulation program (EMTDCTM).
a transmission system with the rectifier in constant power The system studied uses design parameters from the
control and the inverter in constant extinction angle (y) con- CIGRE benchmark system [7].
trol. Hammad et al. [2] have introduced the concept of
Voltage Stability Factor (VSF) which is the incremental
11. THE FORMULATION
change in the ac busbar voltage at the converter bus due to
a change in reactive power supply at that bus, i.e., dV/dQ.
The HVdc power flow is discussed in Section II-A. The
CSI formulation is discussed in Section II-B.
95 WM 277-4 PWRD A paper recommended and approved
by t h e IEEE Transmission and D i s t r i b u t i o n Committee A . Power Flow Formulation
of the IEEE Power Engineering Society f o r p r e s e n t a t -
i o n a t t h e 1995 IEEE/PES Winter Meeting, January 29, The method used in these investigations is explained with
t o February 2 , 1995, New York, NY. Manuscript sub- the aid of a HVdc inverter connected to an ac system equiva-
mitted J u l y 25, 1994; made a v a i l a b l e f o r p r i n t i n g lent of impedance Z, as shown in Figure 1. The ac filters and
December 28, 1994. fixed capacitors are shown as an impedance Zf.
I . Power Flow Equations: The steady state operation of
the HVdc system, shown in Figure 1, is fully described by
the six power flow equations given below [SI.

0885-8977/95/$04.00 0 1995 IEEE


2055

h Here, & is the vectorxwith steady state solutionvalues. The


+ cosy ) = o
xc I d
- T ( cosa relation between a nearby estimated solution X and the
steady state solution X i is given by Equation (8).
cos@ - rosaicos
) = 0 F(X0) = F(X) + mX) (8)
and hence F(X) = - A F ( X )

and AF(X) =
""x"] AX
[7-
(VI- + R, V I G, + where IaF(X)1 is the Jacobian J of matrix F a t X
L
axJ

and AX = Xo - X (9)

(-?+!A + X, V I G, - Thus, F(X) = - J d X (10)


Only the elements corresponding to the design variables
R, V d Id tan @ vectorx, are non-zero in Equation (9) (other elements ofX,
VI
+ R, V I Bf - E , sin 6
say3 are fixed, and the corresponding Axj terms are zero).
Hence, Equation (10) can be written with a reduced Jaco-
Pd - v d Id =0
bian J, which contains only those columns of J that corre-
Where the variables are: spond to elements in X, .
V I : Line to line voltage at the ac busbar Thus, F ( X ) = - J , AX, (104
X, : Commutation impedance
Id : Dc current and AX, = - J;' F(X) (11)
T : Transformer turns ratio From Equation (9) and (ll),the new values of X, can be
a : Inverter jiring angle estimated as follows:
y : Inverter extinction angle x, = x, + A X , (14
@ : Power factor angle of inverter ac current The steady state solution is obtained by iteratively solving
Vd : Inverter dc voltage Equation (11) and (12) till F(X) given by Equation (loa)
P d : Inverter dc power equalszero. The system JacobianJ is given in the Appendix.
2,: Ac filter impedance, ( G, + j B, )-' B. CSI Formulation
E, : Ac system source voltage magnitude
The CSI concept is explained in the next Section 11-B2.
6 : Phase angle between E, and VI The mathematical formulation of CSI is presented in Sec-
+

p&k,TG
yT=i$-jj[
Z, : Ac system impedance, ( R, j X, ) tion 11-B3.
1. Controlled and Controlling Parameters: The operating
variables are those quantities which willvary during dynamic
fl operation. There are seven operating variables in this setup,
out of which one variable should be controlled. HVdc sys-
a xc tems are operated in various control modes such as constant
-- extinction angle control (CEA) and constant power control
Figure I :Inverter Connected to Ac System mode. Any given controller is designed to directly control
one of the operating variables by directly varying one other
2. Design Variables: Out of the many design variables operating variable ( the remaining variables are affected
present in the above power flow equations, and as given by indirectly according to Equations 1-6 ). In this paper, these
vector X below, only a reduced set of 6 variables ( design parameters are referred to as the controlled parameter and
variables, X, ) is determined by the power flow solution (see the controllingparameter, respectively. In CEA mode, for
next section). The remaining quantities are specified. example, the controller attempts to maintain extinction
T-
-[ VI I d a y @ T v d E, 6 P , B
I angle y (controlled parameter) at a specifiedvalue by direct-
ly varying inverter firing angle a (controlling parameter). A
x,' = [LI @ vd
pd]
conventional CEAcontroller design is based on the fact that
an increase in a order causes the system to respond with a
3. Load Flow Solution: Equations (1) - (6) can be repre-
decrease in y . A shift in the system characteristics will
sented in matrix form as follows:
change the controller performance and can even lead to
W O ) = 101 (7) unstable operation.
2056

2. Control Sensitivity Index: From the above discussion, it


is imperative that the system characteristics with respect to
the controlled and controlling parameters should match the
controller characteristics for fast control and stable opera- a
tion of the system. The system characteristics necessary for
the proper design of a controller is called the Control Sensi-
tivity Index (CSZ) for that controller and is defined as "the
rate of change of controlledparameter with respect to the con-
trollingparameter ". Figure 2 :Inverter Connected to Ac System
3. CSZ Calculation: Once the power flow solution is ob-
index (CSI,) for the constant extinction angle mode of con-
tained ( see Section 11-A3 ), the CSI can be computed as
trol since y is controlled by a. The gains & and K, of the
follows:
controller are normally positive, which means that if the
The RHS of Equation (10) can be written as:
measured extinction angle yis larger than the order yrYref, the
J AX = AX, + J , dy (13) error causes the firing angle order a to increase. This strate-
Here& is a square matrix consisting of columns of theJ that gy assumes that the increase in a will cause yto decrease, i.e.,
are related to X, variables ( which are all the operating vari- that the quantity dylda is negative. A positive value of CSI,
ables except for the controlling parameter ), and Jy is one would indicate instability. Also the magnitude of CSI, is a
column of J that corresponds to the controlling-parameter measure of the sensitivity of the system response to a change
y. In steady state, Equation (10) is zero and hence, Equation in a order, and thus the knowledge of CSI, aids in the selec-
(13) can be re-arranged as: tion of controller gains. A high magnitude of CS1,indicates
1 AX, that a very small change in a would result in a large change
- = 4;'J , (14) in y.
dY
The CSI, for the desired controller is the entry &/dy of Figure 3 shows dy/da as a function of the Effective Short
Equation (14), where x is the controlled parameter. For Circuit Ratio (ESCR) of the ac system where the inverter is
Constant Extinction Angle (CEA) control, for example, the fully compensated. It is assumed that the rectifier is operat-
CSI, would be dylda . The same formulation can also be ing in constant current control mode and hence the dc cur-
used to obtain VSF by selecting the appropriate X , and y rent Id is assumed fixed (at a value of 1.0 pu for the plots in
variables. Description of the operating Jacobian& the con- Figure 3 ). Figure 3 shows CSI plots for three different SCR
trolling Jacobian .$, and the operating vector X, for CEA angles (damping angles of the system equivalent impedance
mode of control are given in the Appendix. &).For an angle of 75", the critical ESCR is about 0.4 (SCR
= 0.9). For a smaller damping angle of 65", the critical ESCR
is larger (about 0.6) whereas if the equivalent is purely in-
111. ANALYSIS OF CSI
ductive 90",the system is stable even at very low ESCR
values. This appears counter intuitive because it indicates
To demonstrate the applicability of CSI for analyzing the that a system with very low damping can be stable at ex-
stability of HVdc systems, the indices for the case of Con- tremely low ESCR values. However, evaluating the critical
stant Extinction Angle, Constant Power and Constant Volt- ESCR from simulations using a full scale electromagnetic
age Control modes are presented here. The flow chart in the transient program confirms CSI, results as shown by the
Appendix shows the approach taken to obtain the CSI of a dark squares in Figure 3 .
particular control mode with varying SCRs ( SCR =
h/& pu I ). The CSI plots (Figures 3,7 and 8) are developed 4
by starting at a large SCR magnitude and gradually reducing I I
it to a point a little past the point of instability. Note that the
inverter is fully compensated in all these cases and the experimental poini
ESCR is computed on this basis. In the formulation of the
CSI, the converter dynamics are neglected, i.e., the HVDC
control is assumed to be instantaneous. Likewise, the ac
voltage control for the system equivalent is neglected, i.e., it
is assumed that E, in Figure 1 is constant for a given SCR.
The system data are given in the Appendix. -3 -
Note: ESCR is based on fully compensated inverter
-4 I I I I I I I I I
1 .I Constant Extinction Angle Control 0 0.25 0.50 0.75 1.00 1.25 1.50 1.75 2.00 2.25 2.50

Figure 2 shows a block diagram of a typical extinction IESCRI


angle controller. The index dylda is the control sensitivity Figure 3 :Calculated and Simulated CSI dyrda,Id = I pu
2057

In the simulation, the inverter was first operated with a


constant firing angle corresponding to the steady state solu-
tion. A step change A a was made and the corresponding
extinction angle change Ay was measured from which the
index was calculated.
Figure 4 shows how the CSI, varies with the level of dc
current, for a fixed ESCR (system impedance angle as-
sumed fixed at 75" for all cases). For an ESCR of 0.3 (SCR
0.8) , the dc current cannot exceed 1.0 p.u. without loss of
stability. For stronger systems, this current can be larger
than rated, indicating a stable overload capacity ( provided
other conditions are acceptable).

+1 - y Controller Sign
C
.Do 0 -

4
1
-l.O: -1
p -1.4- 30
Extinction Angle
-0
-1.8-
-1.8 ---__
2 15

0
2.5( 1.96)
-2.2
-2.2, 8 I
I II I II II I
I I II II tt ._._I-

0 0.2 0.4 0.6 0.8 1 .o 1.2 Inv. Firing Angle


2
U
142
Id, Pu I30

Figure 4 :CSI dylda v/s Id for Various Fixed ESCR


Another application of the information shown in
Figure 4 would be to design an adaptive non-linear gain I I I I I I I 1 I I
0 0.2 0.4 0.6 0.8 I .a
block for the extinction angle controller. For a given short Time (s)
circuit ratio, the gain could be adjusted according to the Figure 6 :Simulated Converter Responses with Conventional
reciprocal of the dylda index, as the current varies. Gamma Controller and with its Sign Reversed
Figure 5 shows the block diagram for such a controller. This
ensures uniform sensitivity of they response over the entire It is to be noted that the authors do not claim at this point,
operating range. It should be noted that the use of a differ- that the above control strategy is a practical one. However,
they strongly feel that it is an area that is worth investigating
ent characteristic for each SCR may be impractical due to
further.
the difficulty of determining the SCR at an HVdc converter
station. However, Figure 4 shows that for SCRgreater than Although the critical ESCR can be calculated using the
VSF approach, a straightforward calculation of VSF would
2.0 (ESCR > 1.47) , the characteristics are closer together
indicate that y control is never possible below the critical
and one can use an average characteristic in the controller.
ESCR. For example, the VSF calculation for constant y
controlin [2] uses the constraint Ay= 0, thus, eliminatingany
reference to y. By focusing directly on the controllable
quantity (such as y in CEA control) as in the case of CSI
calculation, the reason for stable operation of the modified
controller, with system ESCR below the critical value, be-
comes directly apparent.
B. Constant Power Control
J L
When the rectifier is in constant power control operation,
Figure 5 :Adaptive Extinction Angle Controller the power controller normally adjusts the current order so
that the ordered power is maintained. Thus the index dpd!
The results of Figure 3 indicate yet another interesting dId could be used as the Control Sensitivity Index (CSI,).
possibility. If the sign of the controller gains were reversed, This criterion is the same as the M A P criterion by Ains-
2058

worth[ 11and has been shown to be exactly equivalent to the of 0.1 pu/deg, which agrees with the theoretical calculation
VSF at the critical point by FrankCn et al. [3]. The inverter in Figure 8 . The critical ESCR is also confirmed through
is assumed to be in constant extinction angle (CEA) control. simulation. The CSI, value from Figure 8 indicates that a
Figure 7 shows the CSI, (dPd/dId) for the test system with a voltage controller should have smaller gains if the system
very strong rectifier ac system and an inverter ac system of ESCR is in the vicinity of critical value as the system is ex-
varying short circuit ratio. As can be seen, the critical ESCR tremely sensitive to firing angle changes.
value is in the neighborhood of 1.47 (SCR 2.0).
Figure 7 also shows the variation of the CSI with different 1.054 I
equivalent system damping angles. The damping angle does Dc Voltage
not appear to play as important a role in this case as in the
case of the extinction angle controller since the critical
ESCR is virtually independent of the damping angle.

21 -
D O -
4 20
L

Extinction Angle
19 I k r , I I

e; I
-2{ -",' //scR

D. Comparison of Three Modes of Control


I I I I I I I I I Figure 10 shows CSI graphs and Table 1 . 1 summarizes
0 0.25 0.50 0.75 1.00 1.25 1.50 1.75 2.00 2.25 2.50 the critical SCR and critical ESCR (CSCR, CESCR) values,
IESCRI for the three control modes discussed above. It is clear that
Figure 7 :CSlpfor Constant Power Control the critical ESCR is smallest (0.25) for the inverter in volt-
age control with the rectifier at constant Id, indicating this to
C. Constant Voltage Control be a superior control mode (amongst the three control
modes) for inverters connected to very weak ac systems. For
In the calculation of CSI, for voltage control at the invert-
er the rectifier is assumed to be operating at a constant the inverter in constant extinction angle control with the
rectifier in constant current operation, the critical ESCR
current (AId=O). The inverter dcvoltage is maintained con-
(0.4) is slightly larger than that in the constant voltage con-
stant by controlling the inverter firing angle. The relevant
trol mode. The critical ESCR (1.47) is highest when the
CSI, is thus dVd/da. Figure 8 shows CSI, as a function of
rectifier is in the power control mode. Also, with constant
ESCR and the critical ESCR appears to be 0.25 (SCR 0.74).
gamma control (CSIy), the critical ESCR is reduced when
Figure 9 shows digital simulation results for a 5% in-
the damping angle of SCR is close to 90". On the other hand
crease in dc voltage order for an inverter connected to a
system of ESCR 0.3 (SCR 0.8). As can be seen, the change with constant power control (CSI,), the critical ESCR is
in the firing angle is 0.5 degrees which gives a value for CSI, virtually unaffected by the damping angle in the practical
2
-Constant Power, CSI,
3] as calculated from Figure 9 I Constant Voltage, CSI,
a-
m ------________
-3a
3a>
-3

0 0.5 1 .o 1.5 2.0


0
IESCRI

Figure 8 :CSI,,for Constant Voltage Control Figure 10 :CSI for Three Control Modes
2059

range of 65 to 90. The latter conclusion has also been IEEE Transactions on Power Systems, Vol. 1, No. 1, Febru-
reported in Section 2.5 (Calculation of critical short circuit ary 1986,pp 209-2 16.
ratios) of the joint IEEE/CIGRE Guide [4]. [6] L.A.S. Pilotto, et al., Transient Ac Voltage Related Phe-
nomena for HVdc Schemes Connected to Weak Ac Sys-
tems, IEEE Transactionson Power Delivery,Vol. 7, No. 3,
July 1992, pp 1396-1404.
[7] M. Szechtman, et al., First Benchmark Model for HVdc
Control Studies,Electra, Vol. 135, April 1991, pp 55-73.
Table 1 .I :Summary of Critical SCR and ESCR values [8] E.W. Kimbark, Direct Current Transmission - Volume I ,
Chapter 3 , John Wiley & Sons, Inc. 1971.
IV. CONCLUSIONS
VII. BIOGRAPHIES
The Control Sensitivity Index is a new approach for analy-
Om Navak received his B.E. (hons.)
sis of dc converters in weak systems. This method has clear from Mysore University, India in 1984 af-
advantages over other methods as it establishes a direct ter which he worked with Bosch for one
association between the system instability and the control year and with Siemens as a Project Engi-
mode. The paper also successfully demonstrates how the neer for two years. He received his M.Sc.
and Ph.D. degrees from the University of
knowledge of this association can be used in the design of a Manitoba in 1990 and 1993, respectively.
stable controller. The critical ESCRs given by the CSI are At present Dr.Nay& is a Research Engi-
consistent with those obtained by other approaches where neer at the Manitoba HVDC Research
Centre. His research interests include
available. Also, the theoretical calculations of CSI conform HVdc controls and various aspects of digi-
very well with the digital simulation results. tal simulation of electromagnetic tran-
The paper presents CSI calculations for three control sients in power systems.
modes for the same HVdc system. For a weak inverter sys- Ani Cole obtained the B. Tech. (EE) de-
tem, the most stable control option is to have the inverter in gree from IIT Bombay in 1978 and the
voltage control and the rectifier in constant current control. Ph.D. degree from the University of Man-
itoba in 1982. He is currently an associate
professor in the department of Electrical
V. ACKNOWLEDGEMENT and ComputerEngineeringat the Universi-
ty of Manitoba. He is a registered Profes-
This project was carried out under a research grant from sional Engineer in the Province of Manito-
Manitoba Hydro. This sponsorship is gratefully acknowl- ba and a member of the IEEE PES society.
Dr.Gole is Vice-chairman of IEEE PES
edged. 5 WG 15.05.02 DvnamicPerformance and
Modeling ofDC andPower Electronicsfor
VI. REFERENCES Transmission Systems.
received his B.Sc. (EE)
[l] J.D. Ainsworth, et al., Static and Synchronous Compensa- from the University of Manitoba in 1968
and the Ph.D. degree from the University
tors for HVdc Transmission ConvertersConnected to Weak of London (Imperial College) in 1973. He
Ac Systems, CIGRE Conference, Paris, 1980, Paper No. is currently responsible for the planning of
31-01. HVDC systems and system control at
Manitoba Hydro. Dr.Chapman is a regis-
A.E. Hammad, et al., A New Approach for the Stability tered Professional Engineer in the Prov-
Analysis and Solution of Ac Voltage Stability Problems at ince of Manitoba and an Adjunct Professor
HVdc Terminals, International Conference on DC Power with the University of Manitoba.
Transmission,Montreal, June 1984, pp 164-1 70.
B. FrankCn and G . Anderson, Analysis of HVdc Conver- Brett Dav ies obtained the B.S.E.E. and
ters Connected to Weak Ac Systems, IEEE Transactionson M.Eng. degrees from the University of
Power Systems, Vol. 5 , No. 1, February 1990, pp 235-242. Manitoba in 1973 and 1977 respectively.
Since 1975he has been with Manitoba Hy-
[4]IEEEKIGRE, Guideforplanning DCLinks Terminating dro where he works on control problems
at Ac Locations having Low Short Circuit Capacities - related to ac and dc transmission. He is a
registered Professional Engineer in the
Part I: AC/DC System Interaction Phenomena, IEEE Province of Manitoba.
Standards Department, 1993.
[5]A.E. Hammad, W. Kuhn, A Computation Algorithm for
Assessing Voltage Stability at AC/DC Interconnections,
2060

VIII. APPENDIX

(y)
Initial Conditions & 12 Pulse
INVERTER

5.0 2kA 990MW I 7.505 83.43 0.22 0.0843

I I 0

0
0
Load Flow Solution
CSI Calculation
Change SCR, ESCR 194.4
It
Damped
IOW
frequency

ymin=l5
I
I+
a=l5
(Z) -11

13.055
Fixed
Capacitor

Flow Chart for CSI Calculation Total +0.028+1/(,b28.13e-6)


All Resistances in Inductances in H, Capacitances in p F
Complete System Data

I -J5xc I
-fiXcIdsina I -J5~,1,siny
T(cosa + cosy) T(cosa + ~ o s y ) ~ 1 T ( c o s+a cosy):
0

L L
-sin+ 1 0 0

-3 2 3 0 0
4 T c o s y j+

1 + U + R s G f -
v: (7. 0 0
v,cos2+
.v,x
J= I XV
y t aI n + + X,Bf) I ?tan+) 1

5x1 1

Vous aimerez peut-être aussi