Vous êtes sur la page 1sur 20

Cutler-Hammer Application Data

Westinghouse & 29-167R


Cutler-Hammer Products
Five Parkway Center Page 1
Pittsburgh, Pennsylvania, U.S.A. 15220

October 1997 Time/Current Characteristic Curves for


Mailed to: E/29-100A Westinghouse Series C R-Frame Westinghouse
Circuit Breakers
Series C
Molded Case
Circuit Breakers
R-Frame
Breaker Description Curve No. Page

Series C Types RD, CRD, RDC, CRDC Circuit Breakers Equipped With
Digitrip RMS 310 Trip Units
Typical Instantaneous Time-Phase Current Characteristic Curve
Based on In ....................................................................................... SC-5629-93 2
Typical Long Delay/Short Delay Time-Phase Current
Characteristic Curve Based on In ................................................... SC-5630-93 3
Typical Ground Fault/Protection Time/Current Characteristic
Curve Based on In ............................................................................ SC-5631-93 4

Series C Types RD, CRD, RDC, CRDC Circuit Breakers Equipped With
Digitrip RMS 510/610/810 Trip Units
Typical Instantaneous Time-Phase Current Characteristic Curve
Based on In ....................................................................................... SC-5626-93 5
Typical Long Delay/Short Delay Time-Phase Current
Characteristic Curve Based on Ir ................................................... SC-5627-93 6
Typical Ground Fault/Protection Time/Current Characteristic
Curve Based on In ............................................................................ SC-5628-93 7

Series C R-Frame Circuit Breakers Equipped With 1600/2000A Digitrip OPTIM Trip Units
Long Delay I2t, Short Delay I2t ........................................................... SC-6336-96 9
Long Delay I2t, Short Delay Flat ........................................................ SC-6337-96 10
Long Delay I4t, Short Delay Flat ........................................................ SC-6338-96 11
Instantaneous and Override, 1600 Amperes ................................... SC-6342-96 15
Instantaneous and Override, 2000 Amperes ................................... SC-6343-96 16
Ground Fault or Ground Fault Alarm Only, 1600 Amperes ........... SC-6345-96 18
Ground Fault or Ground Fault Alarm Only, 2000 Amperes ........... SC-6346-96 19

Series C R-Frame Circuit Breakers Equipped With 2500A Digitrip OPTIM Trip Units
Long Delay I2t, Short Delay I2t ........................................................... SC-6339-96 12
Long Delay I2t, Short Delay Flat ........................................................ SC-6340-96 13
Long Delay I4t, Short Delay Flat ........................................................ SC-6341-96 14
Instantaneous and Override .............................................................. SC-6344-96 17
Ground Fault or Ground Fault Alarm Only ...................................... SC-6347-96 20

Definitions
In is the maximum value of continuous current for which the trip unit can be set.
In is the basis (or reference) for both the Instantaneous and the Ground protection current
settings.
The value of the rating plug is printed on the Rating Plug.

Ir is the basis for both the Long Delay and the Short Delay (if provided) protection current
settings.
The value of Ir is the Long Delay Current Setting x In.

Individual oversize copies of curves listed above printed on onion-skin paper are available
in limited quantity from:
Cutler-Hammer
Westinghouse &
Cutler-Hammer Products
Five Parkway Center
Pittsburgh, PA 15220

When ordering onion-skin curves, use number at bottom of page where curve appears,
i.e., SC-5629-93. Requests for full sets of curves will not be honored.
Application Data
29-167R
Page 2

AB DE-ION Circuit Breakers


Types RD, CRD, RDC, CRDC Equipped With Digitrip RMS 310 Trip Units. Typical Instanta-
neous Time-Phase Current Characteristic Curve Based on I n

CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In)


.5 .6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10 20
10,000
Circuit Breaker Time/Current Curves (Phase Current)
2 HOURS

Series C R-Frame Circuit Breakers


5,000 Equipped With Type Digitrip RMS 310 Trip Units
Typical Trip Unit Nameplate
1 HOUR


Westinghouse
Digital
Protection
3,000
For use with Trip Unit Catalog Numbers
Cell No.
1600A Max. 2000A Max. 2500A Max. Digitrip RMS 310
2,000
RES1600LS RES2000LS RES2500LS
Standard Fixed RES1600LSG RES2000LSG RES2500LSG NP6635C68H07 Made in U.S.A.

Digitrip RMS 310 Rating Plug

Rating Plug RES1600LS RES2000LS RES2500LS For Use in R Circuit Breaker Only
Engaged Cat._ _
In

Remove

Short Delay
1,000 Pickup
In

500
NP6645C79H01

Frame Available Rating Plugs


Rating Ampere Type Catalog Short Delay
Amperes Rating (In) Number Pickup Range
300
(Max.) Amperes
1600 1600 Fixed 16RES16T 3200-12800
200 1400 Fixed 16RES14T 2800-11200
Maximum Total 1250 Fixed 16RES125T 2500-10000
Clearing Time 1200 Fixed 16RES12T 2400-9600
1000 Fixed 16RES10T 2000-8000
800 Fixed 16RES08T 1600-6400
Minimum Total 800, 1000, 1200, 1600 Adj. A16RES16T1 1600-12800
100
Clearing Time 800, 1000, 1250, 1600 Adj. A16RES16T2 1600-12800

2000 2000 Fixed 20RES20T 4000-16000


1 MINUTE

1600 Fixed 20RES16T 3200-12800


1400 Fixed 20RES14T 2800-11200
50 1250 Fixed 20RES125T 2500-10000
1200 Fixed 20RES12T 2400-9600
1000 Fixed 20RES10T 2000-8000
1000, 1200, 1600, 2000 Adj. A20RES20T1 2000-16000
30 1000, 1250, 1600, 2000 Adj. A20RES20T2 2000-16000
2X

2500 2500 Fixed 25RES25T 5000-15000


20 2000 Fixed 25RES20T 4000-12000
1600 Fixed 25RES16T 3200-9600
3X

1250 Fixed 25RES125T 2500-7500


1200 Fixed 25RES12T 2400-7200
1200, 1600, 2000, 2500 Adj. A25RES25T1 24000-15000
10 1250, 1600, 2000, 2500 Adj. A25RES25T2 2500-15000

Interrupting Ratings 50/60 Hz


RMS Sym. Amperes (kA)
Short Delay Breaker UL/CSA IEC 947-2 (Icu)
4X

5 Type
Pick Up 240V 480V 600V 220-240V 380-415V 500V
Settings RD, CRD 125 065 50 125 065 42
(Tolerance 10%) RDC, CRDC 200 100 65 200 100 65
3 Utilization Category A
8X

Ics = 0.25 Icu


Uimp = 8 kV
5X

2
Notes
TIME IN SECONDS

Curve accuracy applies from 20C to +55C ambient. For possible ampere derating for
ambient above 40C, refer to Cutler-Hammer.

1 Digitrip RMS 310 trip units are suitable for functional field testing with test kit Cat. No.
6X

STK2. For field testing using primary injection methods, follow NEMA publication AB-
4-1991.

For 2500A styles, maximum short delay pickup setting = 6X.


.5
For high fault current levels a fixed instantaneous override is provided at 17,500A
(Tolerance 15%).

.3 The end of the curve is determined by the interrupting rating of the circuit breaker.
7X

See above tabulation.

.2 For ground fault time-current curves see SC-5631-93.

Not UL/CSA Listed.

.1 .1

.05 .05
Fixed Instantaneous
.04
Override
.03 .03

.02
Interrupting
.02
Rating
Determines
End of
Curve
SECONDS

.01 .01

.005

.003

.002

.001 .001
.5 .6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10 20
10,000

20,000

30,000

40,000

50,000

100,000

CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In)

CURRENT IN AMPS Curve No. SC-5629-93

October 1997
Application Data
29-167R
Page 3

AB DE-ION Circuit Breakers


Types RD, CRD, RDC, CRDC Equipped With Digitrip RMS 310 Trip Units. Typical Long
Delay/Short Delay Time-Phase Current Characteristic Curve Based on In

CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In)


.5 .6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10 20
10,000
Circuit Breaker Time/Current Curves (Phase Current)
2 HOURS

Series C R-Frame Circuit Breakers


5,000
Equipped With Type Digitrip RMS 310 Trip Units
Typical Trip Unit Nameplate
1 HOUR


Westinghouse
Digital
Protection

3,000
For use with Trip Unit Catalog Numbers
Cell No.
1600A Max. 2000A Max. 2500A Max. Digitrip RMS 310

2,000 RES1600LSI RES2000LSI RES2500LSI


Standard Fixed RES1600LSIG RES2000LSIG RES2500LSIG
NP6635C68H07 Made in U.S.A.

Digitrip RMS 310 Rating Plug

Rating Plug RES1600LSI RES2000LSI RES2500LSI For Use in R Circuit Breaker Only
Engaged Cat.
_
In
_

Remove

Short Delay
Pickup
1,000 In

Short Delay
Time
Sec

500 NP6645C79H02

Frame Available Rating Plugs


Rating Ampere Type Catalog Short Delay
Amperes Rating (In) Number Pickup Range
300
(Max.) Amperes
Maximum Total
1600 1600 Fixed 16RS16T 3200-12800
Clearing Time 1400 Fixed 16RS14T 2800-11200
200
1250 Fixed 16RS125T 2500-10000
1200 Fixed 16RS12T 2400-9600
1000 Fixed 16RS10T 2000-8000
800 Fixed 16RS08T 1600-6400
800, 1000, 1200, 1600 Adj. A16RS16T1 1600-12800
100 Minimum Total 800, 1000, 1250, 1600 Adj. A16RS16T2 1600-12800
Clearing Time
2000 2000 Fixed 20RS20T 4000-16000
1 MINUTE

1600 Fixed 20RS16T 3200-12800


1400 Fixed 20RS14T 2800-11200
50 1250 Fixed 20RS125T 2500-10000
1200 Fixed 20RS12T 2400-9600
1000 Fixed 20RS10T 2000-8000
1000, 1200, 1600, 2000 Adj. A20RS20T1 2000-16000
30 1000, 1250, 1600, 2000 Adj. A20RS20T2 2000-16000

2500 2500 Fixed 25RES25T 5000-15000


20 2000 Fixed 25RES20T 4000-12000
1600 Fixed 25RES16T 3200-9600
1250 Fixed 25RES125T 2500-7500
2X

1200 Fixed 25RES12T 2400-7200


1200, 1600, 2000, 2500 Adj. A25RES25T1 24000-15000
10
1250, 1600, 2000, 2500 Adj. A25RES25T2 2500-15000
Interrupting Ratings 50/60 Hz
RMS Sym. Amperes (kA)
Breaker UL/CSA IEC 947-2 (Icu)
4X

Short Delay Type 240V 480V 600V 220-240V 380-415V 500V


5
Pick Up RD, CRD 125 065 50 125 065 42
Settings RDC, CRDC 200 100 65 200 100 65
(Tolerance Utilization Category A
6X

3 10%) Ics = 0.25 Icu


Uimp = 8 kV
Notes
2 Curve accuracy applies from 20C to +55C ambient. For possible ampere derating for
8X

ambient above 40C, refer to Cutler-Hammer.


TIME IN SECONDS

Digitrip RMS 310 trip units are suitable for functional field testing with test kit Cat. No.
STK2. For field testing using primary injection methods, follow NEMA publication AB-
7X

1 4-1991.

For 2500A styles, maximum short delay pickup setting = 6X.


For high fault current levels a fixed instantaneous override is provided at 17,500A
(Tolerance 15%).
The end of the curve is determined by the interrupting rating of the circuit breaker.
.5 See above tabulation.
3X

5X

For ground fault time-current curves see SC-5631-93.


300 ms Not UL/CSA Listed.
.3

200 ms
.2

100 ms
.1 .1

.05 .05
Fixed Instantaneous
I .04 Override
.03 .03
Interrupting
.02 .02
Rating
Determines
End of
Curve
SECONDS

.01 .01

.005

.003

.002

.001 .001
.5 .6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10 20
10,000

20,000

30,000

40,000

50,000

200,000
100,000

CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In)

CURRENT IN AMPS Curve No. SC-5630-93

October 1997
Application Data
29-167R
Page 4

AB DE-ION Circuit Breakers


Types RD, CRD, RDC, CRDC Equipped With Digitrip RMS 310 Trip Units. Typical Ground
Fault/Protection Time/Current Characteristic Curve Based on I n
CURRENT IN AMPERES
1000

2000

3000

4000
100

200

300

400
500
600
700
800
900

50 60 70 80 90
10,000 10,000

2 HOURS
2 HOURS

Circuit Breaker Time/Current Curves (Phase Current)

Series C R-Frame Circuit Breakers


5,000 Equipped with Type Digitrip RMS 310 Trip Units 5,000

1 HOUR
1 HOUR

for Ground Fault Protection


For use with Trip Unit Catalog Numbers
3,000 1600A Max. 2000A Max. 2500A Max. 3,000
RES1600LSG RES2000LSG RES2500LSG
RES1600LSIG RES2000LSIG RES2500LSIG 2,000
2,000


Westinghouse Westinghouse
Digital Digital
Protection Protection
1,000 1,000

Cell No. Cell No.

Digitrip RMS 310 Digitrip RMS 310


500 500
NP6635C68H07 Made in U.S.A. NP6635C68H07 Made in U.S.A.

Digitrip RMS 310 Rating Plug Digitrip RMS 310 Rating Plug
For Use in R Circuit Breaker Only For Use in R Circuit Breaker Only
300 Cat._ _ Cat._ _
300
Engaged Engaged
In In

200 Remove Remove


200
Short Delay Short Delay
Pickup Pickup
Gnd. Fault *Gnd. Fault Pickup Gnd. Fault *Gnd. Fault Pickup
In SETTING CURRENT In SETTING CURRENT
Pickup Pickup
A 200A A 200A
* * Short Delay
100 400A Time 400A 100
600A 600A
800A Sec 800A
1000A 1000A
B 1200A B 1200A

1 MINUTE
1 MINUTE

Gnd. Fault C 1200A Gnd. Fault C 1200A


Time D 1200A Time D 1200A
E E
Sec F Sec F
H H
50 K K 50
Gnd. Gnd.
NP6645C79H05 NP6645C79H06

30 Notes 30
Curve accuracy applies from 20C to +55C ambient.

20 Digitrip RMS 310 trip units are suitable for functional field testing with test kit Cat. No. STK2. 20
For field testing using primary injection methods, follow NEMA publication AB-4-1991.

For phase time-current curves see SC-5629-93 and SC-5630-93.

10 10
1000 A.
600 A.

5 5
200 A.

Ground Fault Pickup


3 Settings 3
(Tolerance 10% Except,
20% on 200 A. Setting)
2 2
1200 A.
400 A.

800 A.
TIME IN SECONDS

TIME IN SECONDS

1 1

.5 SEC
.5 .5

.3 SEC
.3 .3

.2 .15 SEC .2

.1 .1

.05 .05

.03 .03

.02 .02

.01 .01

.005 .005

.003 .003

.002 .002

.001 .001
500

700
200

300

400

600

800
900
1000

2000

3000

4000
100

50 60 70 80 90

CURRENT IN AMPERES Curve No. SC-5631-93

October 1997
Application Data
29-167R
Page 5

AB DE-ION Circuit Breakers


Types RD, CRD, RDC, CRDC Equipped With Digitrip RMS 510/610/810 Trip Units. Typical
Instantaneous Time-Phase Current Characteristic Curve Based on In

I M P O R T A N T
TRIP UNITS ARE NOT AVAILABLE WITH ONLY
INSTANTANEOUS PROTECTION. THIS CURVE MUST BE
USED in conjunction WITH Curve No. SC-5627-93 for LONG
DELAY (and if applicable SHORT DELAY) PROTECTION to
obtain the complete time-current characteristic.


Series C R-Frame Circuit Breakers with
DIGITRIP RMS 510/610/810 Trip Units
Typical Instantaneous Time-Phase Current Characteristic Curve (I)
CURRENT IN MULTIPLES OF PLUG RATING In
.05 .07 .1 .2 .3 .4 .5 .7 1 2 3 4 5 7 10 20 30 40 50 70
1000 1000
900 Available Rating Plugs Marked 50/60 Hz 900
800 800
700 Rating Plug Frequency Catalog 700
Amperes Rating (In) Hz Number
600 (Max.) Amperes 600
500 500
1600 1600 50/60 RP6R16A160
1250 50 RP6R16A125
400 400
1200 50/60 RP6R16A120
1000 50/60 RP6R16A100
300 800 50/60 RP6R16A080 300
2000 2000 50/60 RP6R20A200
1600 50/60 RP6R20A160
200 1250 50 RP6R20A125 200
1200 50/60 RP6R20A120
1000 50/60 RP6R20A100

2500 2500 50/60 RP6R25A250


2000 50/60 RP6R25A200
100 1600 50/60 RP6R25A160 100
90 90
80 Interrupting Ratings @ 50/60 Hz 80
70 RMS Sym. Amperes (kA) 70
60 Breaker UL/CSA IEC 947-2 (Icu) 60
50 Type 240V 480V 600V 220-240V 380-415V 500V 50
RD, CRD 125 65 50 125 65 42
40 RDC, CRDC 200 100 65 200 100 65 40
Utilization Category A
30 Ics = 0.5 Icu 30
Uimp = 8 kV

20 20
Tolerances
9
1 INST Range = 90% to 110% of setting
M2
10 Notes 10
9 For 2000A Rating Plug. 9
8 For 2500A Rating Plug. 8
7 7
TIME IN SECONDS

TIME IN SECONDS

For 800-1600A Rating Plugs.


6 The end of the curve is determined by the interrupting rating of the circuit 6
breaker. See above tabulation.
5 The Rating Plug is for 50 and 60 Hz applications. 5
7 Not UL/CSA listed.
4 For Types RD and RDC only. 4
M1 2 Curves apply from 20C to +55C ambient. Temperatures above 95C
3 cause automatic trip. For possible ampere derating for ambient above 3
M2
40C, refer to Cutler-Hammer.

2 2

1 3 5 1
.9 2 .9
.8 Available 3
.8
.7 Instantaneous 1 .7
.6 Settings 2.5 4 6 .6
.5 2, 2.5, 3, 4, 5, 6, M1 or M2 x In 8 .5
Values for M1 and M2 as marked on Rating Plug
M1
.4 .4
Plug Rating (In) M1 M2
.3 .3
800-1600 A 8 x In 10 x In
2000 A 8 x In 9 x In
.2 7 x In 7 x In .2
2500 A
10
3
M2
.1 .1
.09 .09
.08 .08
.07 .07
.06 .06
.05 .05
.04 .04

.03 .03
Application
.02
Determines 4
.02
End of Curve

.01 .01
.05 .07 .1 .2 .3 .4 .5 .7 1 2 3 4 5 7 10 20 30 40 50 70

CURRENT IN MULTIPLES OF PLUG RATING In Curve No. SC-5626-93

October 1997
Application Data
29-167R
Page 6

AB DE-ION Circuit Breakers


Types RD, CRD, RDC, CRDC Equipped With Digitrip RMS 510/610/810 Trip Units. Typical
Long Delay/Short Delay Time-Phase Current Characteristic Curve Based on Ir


Series C R-Frame Circuit Breakers with
DIGITRIP RMS 510/610/810 Trip Units
Typical Long Delay and Short Delay
Time-Phase Current Characteristic Curve (LS)

CURRENT IN MULTIPLES OF LONG DELAY SETTINGS Ir


.05 .07 .1 .2 .3 .4 .5 .7 1 2 3 4 5 6 8 10 20 30
1000 1000
900 Available Rating Plugs 50/60 Hz 900
800 Available Rating Plug Frequency Catalog 800
700 Long Delay (Ir) Amperes Rating (In) Hz Number 700
600 Settings (Max.) Amperes 600
500 .5, .6, .7, .8, .85, .9, .95 or 1 x In = Ir 1600 1600 50/60 RP6R16A160 500
1250 50 RP6R16A125
400 1200 50/60 RP6R16A120 400
1000 50/60 RP6R16A100
300 800 50/60 RP6R16A080
300
Maximum 2000 2000 50/60 RP6R20A200
Total 1600 50/60 RP6R20A160
200 Clearing 1250 50 RP6R20A125 200
Time 1200 50/60 RP6R20A120
1000 50/60 RP6R20A100

2500 2500 50/60 RP6R25A250


2000 50/60 RP6R25A200
100 1600 50/60 RP6R25A160 100
90 90
80 Interrupting Ratings @ 50/60 Hz 80
70 RMS Sym. Amperes (kA) 70
60 Breaker UL/CSA IEC 947-2 (Icu)
60
Type 240V 480V 600V 220-240V 380-415V 500V
50 50
RD, CRD 125 65 50 125 65 42
40 RDC, CRDC 200 100 65 200 100 65 40
Utilization Category A
30 Ics = 0.5 Icu 30
Uimp = 8 kV

20 20
Minimum 24 Tolerances
Total LDS Range = 150% to 130% of Setting.
Clearing LDT Range = 67% to 100% of Setting, at 6 x Ir .
SDS Range = 90% to 110% of Setting.
Time Available
10 Long Delay Notes 10
9 7 9
8
8 Time Long Time Memory function automatically shortens long time delay as 8
7 S2
Settings 1 overload conditions recur.
7
TIME IN SECONDS

TIME IN SECONDS

Shown With zone interlocking on short delay utilized and no restraining signal, the
6 minimum time band SDM applies regardless of setting. 6
@ 6 x Ir The end of the curve is determined by the interrupting rating of the circuit
5 4 2, 4, 7, 10, 12, 5
breaker. See above tabulation.
4 6 15, 20, 24 For high fault current levels a fixed instantaneous override is provided at
4
17,500A (Tolerance 15%).
The Rating Plug is for 50 and 60 Hz applications.
3 2.5 4 Not UL/CSA listed. 3
2 For Types RD and RDC only.
Curves apply from 20C to +55C ambient. Temperatures above 95C cause
2 automatic trip. For possible ampere derating for ambient above 40C, refer 2
to Cutler-Hammer.
2
2
3 5
1 Available 1 1
.9 Short Delay .9
.8 .8
2.5 4 6 Settings
.7 .7
2, 2.5, 3, 4, 5, 6,
.6 S1(7) or S2(8) x Ir .6
.5 .5 .5
.5* 2 .5 2
.5
7
.4 .4
S1 Available Flat .4
.4 2 Response
.3 .4
.3 Short Delay .3
.3* 2 .3 2 .3
Time Settings
.2 .2 .1, .2, .3, .4, or .5.2
.2 2
.2

SDM SDM Application


.1 Available .1 .1 .1
.09 Determines 3
.09
I2t Shape .1* 2 .1 2
End of Curve
.08 .08
Short Delay Time
.07 .07
Settings Fixed
.06 Indicated by * .06
.05
Instantaneous.054
Override
.04 .04

.03 .03

.02 .02

.01 .01 .01


.05 .07 .1 2 3 .2 4 .35 .4 7 .5 10 .7 1 20 2 3 4 5 6 8 10 20 30 40 10 20 30 40 50 70
IMPORTANT CURRENT IN kA
CURRENT IN MULTIPLES OF LONG DELAY SETTINGS Ir Curve No. SC-5627-93

October 1997
Application Data
29-167R
Page 7

AB DE-ION Circuit Breakers


Types RD, CRD, RDC, CRDC Equipped With Digitrip RMS 510/610/810 Trip Units. Typical
Ground Fault/Protection Time/Current Characteristic Curve Based on In


Series C R-Frame Circuit Breakers with
DIGITRIP RMS 510/610/810 Trip Units
Typical Time-Ground Current Characteristic Curve (G)

CURRENT IN MULTIPLES OF PLUG RATING In


.05 .07 .1 .2 .3 .4 .5 .7 1 2 3 4 5 7 1 .2 .3 .4 .5 .7 1 2 3 4 5 7 10
1000 1000
900 Ground Fault Settings (Amperes) 900
800 800
Code A B C D E F H K
700 700
600 Available 800 200 240 280 320 400 480 600 800 600
500
A K Ground Fault
500
In plug ratings available

Settings (Typical) 1000 250 300 350 400 500 600 750 1000
400 for Exact Values 600 720 900 1200 400
1200 300 360 420 480
and Tolerances of
300 Letter Codes, 1250 312 375 438 500 625 750 938 1200 300
See Chart
1600 400 480 560 640 800 960 1200 1200
200 200
2000 500 600 700 800 1000 1200 1200 1200

2500 625 750 875 1000 1200 1200 1200 1200

Notes
100 With zone interlocking on ground fault utilized and no restraining signal, the minimum time 100
90 band GDM applies regardless of setting. 90
80 Except as noted tolerances on current levels are 10% of values shown in chart. 80
70 The rating plug is for 50 Hz and 60 Hz, applications. 70
All tabulated values are based on the use of a residual sensing scheme with the same
60 rated current sensor in all phase and neutral conductors. 60
50 For Testing Purposes Only: When using an external single phase current source to check 50
low level ground fault current settings, it is advisable to use the Auxiliary Power Module
40 (APM). See TEST PROCEDURES in Instruction Leaflet. 40

30 30

20 20

10 10
9 9
8 8
7 7
TIME IN SECONDS

TIME IN SECONDS

6 6
5 5
4 4

3 3
D
2 2
B
2
I t Shape for Ground
Time Delay Settings Indicated by *
1 1
.9 .9
.8 A .8
.7 .7
.6 .6
.5 .5
.5 1 .5* 1
.4 .4
Available Available
.4 1
Ground Fault
.3 Ground Fault .3
.3 1 Time Delay .3* 1 Time Delay
Settings Settings
.2 Flat Response I2t Response .2
.2 1

GDM GDM
.1 .1
.09 .09
.08 .1 1 .1* 1
.08
.07 .07
.06 .06
.05 .05
.04 .04

.03 .03

.02 .02

.01 .01
.05 .07 .1 .2 .3 .4 .5 .7 1 2 3 4 5 7 1 .2 .3 .4 .5 .7 1 2 3 4 5 7 10

CURRENT IN MULTIPLES OF PLUG RATING In Curve No. SC-5628-93

October 1997
Application Data
29-167R
Page 8

AB DE-ION Circuit Breakers

Cutler-Hammer
Westinghouse &
Cutler-Hammer Products
Five Parkway Center
Pittsburgh, Pennsylvania, U.S.A. 15220

Printed in U.S.A.

October 1997
Application Data
29-167R
Page 9

AB DE-ION Circuit Breakers


R-Frame Circuit Breakers Equipped with 1600/2000A Digitrip OPTIM Trip Units; Long Delay I2t, Short Delay I2t
CURRENT IN MULTIPLES OF LONG DELAY SETTING Ir

100
0.5
0.6
0.7
0.8
0.9

10

20

40
50
30

60
70
80
90
2 HOURS

7
8
9
1

6
10,000
Circuit Breaker Time/Current Curves (Phase Current)
Available Long Delay Series CT R - Frame Circuit Breakers
Pickup Settings (I r) Equipped With 1600/2000A Digitrip Optim Trip Units
5,000 0.5 to 1 x In = Ir Response: LONG DELAY I2t, SHORT DELAY I2t
1 HOUR

in 0.01 increments
Available Rating Plugs

Maximum Ampere Rating Plug Long Delay Short Delay


3,000 Ampere Rating Catalog Pickup Range Pickup Range
Rating (In) Number 0.4 to 1 x In 1.5 to 8x Ir
Amperes Amperes
2,000
1600 1600 ORPL16A160 640 -1600 960 - 12800
1250 ORPL16A125 500 -1250 750 - 10000
1200 ORPL16A120 480 -1200 720 - 9600
1000 ORPL16A100 400 -1000 600 - 8000
800 ORPL16A080 320 - 800 480 - 6400

1,000 2000 2000 ORPL20A200 800 -2000 1200 - 16000


1600 ORPL20A160 640 -1600 960 - 12800
1250 ORPL20A125 500 -1250 750 - 10000
1200 ORPL20A120 480 -1200 720 - 9600
1000 ORPL20A100 400 -1000 600 - 8000
Maximum
Total
500 Clearing
Time

300

200

100 Interrupting Rating @ 50/60 Hz RMS Sym. Amperes (kA)


1 MINUTE

Breaker UL / CSA

Type Volts 240 480 600


RD, CRD 125 65 50
50 kA
RDC,CRDC 200 100 65

IEC 947-2
Minimum Volts 240 415 690
30 Total
24
Clearing Rating I CU I CS I CU I CS I CU I CS
Time RD,CRD 135 100 70 50 25 13
20 RDC, CRDC
kA
200 100 100 50 35 18

U IMP = 8kV Utilization Category A

Notes
1) For field testing primary injection methods, follow NEMA AB4-1991 publications.
Available 2) Calibration response in short delay pickup range is the same for 1, 2, or 3 poles in series.
10 Long Delay 3) There is a memory effect that can act to shorten the long delay. The memory effect
comes into play if a current above the long delay pickup value exists for a time and then
Time Settings
TIME IN SECONDS

7 is cleared by the tripping of a downstream device or the circuit breaker itself. A


Shown @ 6 x Ir subsequent overload will cause the circuit breaker to trip in shorter time than normal.
The amount of time reduction is inverse to the amount of time that has elapsed since the
2-24 seconds +0 -30% previous overload. Approximately five minutes is required between overloads to
in 0.1 second completely reset the memory.
increments 4) The end of the curve is determined by the interrupting rating of the circuit breaker.
5 4 See above tabulation.
5) For ground fault time / current curves see SC-6345-96 (1600A), SC-6346-96 (2000A), and
SC-6347-96 (2500A)
6) This curve is shown as a multiple of the Long Delay Pickup Setting, (I r). This Ir setting is
programmed in primary value amperes via a Breaker Interface Module, or OPTIMizer,
3 or a Remote PC (IMPACC System).
7) The Long Delay Pickup Point (indicated by a flashing LED on the product) nominally occurs
2 at 116% of the Ir current, with a +/- 5% tolerance. The short delay settings have conventional
100%, +/- 5% as the pickup points.
2 8) For additional curve tolerances contact Cutler-Hammer.
9) Total clearing times shown include the response times of the trip unit, the breaker opening,
and the extinction of the arcing current.

Available
Short Delay 1
1 Pickup Settings
1.5 to 8 x Ir
5% in 0.1
increments

.5 .5
.5

.3 .3
.3
TIME IN SECONDS

.2 .2

.1 Application
.1 Determines .1
End of Curve

Available I2t Slope


.05 Short Delay Time Settings .05
0.1 to 0.5 seconds in
0.01 second increments

.03 .03

.02 .02

.01 .01
3000

4000
2000

5000

10,000
1000

6000
7000

9000
8000
800
300

500
100

400

600
700

900
0.5

0.8
0.9

10

50

90
0.6
0.7

200
20

70
80
1

40
30
4

60
3

7
8
2

5
6

CURRENT IN MULTIPLES OF LONG DELAY SETTING I r Curve No. SC-6336-96

October 1997
Application Data
29-167R
Page 10

AB DE-ION Circuit Breakers


R-Frame Circuit Breakers Equipped with 1600/2000A Digitrip OPTIM Trip Units; Long Delay I2t, Short Delay Flat
CURRENT IN MULTIPLES OF LONG DELAY SETTING Ir

100
0.5
0.6
0.7
0.8
0.9

10

20

40
50
30

60
70
80
90
2 HOURS

7
8
9
1

10,000
Circuit Breaker Time/Current Curves (Phase Current)
Available
Long Delay (Ir) Series CT R - Frame Circuit Breakers
Settings Equipped With 1600/2000A Digitrip Optim Trip Units
5,000 0.5 to 1 x In = Ir Response: LONG DELAY I2t, SHORT DELAY FLAT
1 HOUR

in 0.01 increments
Available Rating Plugs

Maximum Ampere Rating Plug Long Delay Short Delay


3,000 Ampere Rating Catalog Pickup Range Pickup Range
Rating (In) Number 0.4 to 1 x In 1.5 to 8x Ir
Amperes Amperes
2,000
1600 1600 ORPL16A160 640 -1600 960 - 12800
1250 ORPL16A125 500 -1250 750 - 10000
1200 ORPL16A120 480 -1200 720 - 9600
1000 ORPL16A100 400 -1000 600 - 8000
800 ORPL16A080 320 - 800 480 - 6400

1,000 2000 2000 ORPL20A200 800 -2000 1200 - 16000


1600 ORPL20A160 640 -1600 960 - 12800
1250 ORPL20A125 500 -1250 750 - 10000
1200 ORPL20A120 480 -1200 720 - 9600
1000 ORPL20A100 400 -1000 600 - 8000
Maximum
Total
500 Clearing
Time

300

200

100 Interrupting Rating @ 50/60 Hz RMS Sym. Amperes (kA)


1 MINUTE

Breaker UL / CSA

Type Volts 240 480 600


RD, CRD 125 65 50
50 kA
RDC,CRDC 200 100 65

IEC 947-2

Minimum Volts 240 415 690


30 24
Total Rating I CU I CS I CU I CS I CU I CS
Clearing
Time RD,CRD 135 100 70 50 25 13
20 RDC, CRDC
kA
200 100 100 50 35 18

U IMP = 8kV Utilization Category A

Notes
1) For field testing primary injection methods, follow NEMA AB4-1991 publications.
Available 2) Calibration response in short delay pickup range is the same for 1, 2, or 3 poles in series.
10 Long Delay
3) There is a memory effect that can act to shorten the long delay. The memory effect
comes into play if a current above the long delay pickup value exists for a time and then
Time Settings
TIME IN SECONDS

7 is cleared by the tripping of a downstream device or the circuit breaker itself. A


Shown @ 6 x Ir subsequent overload will cause the circuit breaker to trip in shorter time than normal.
The amount of time reduction is inverse to the amount of time that has elapsed since the
2-24 seconds +0 -30% previous overload. Approximately five minutes is required between overloads to
in 0.1 second completely reset the memory.
4) The end of the curve is determined by the interrupting rating of the circuit breaker.
5 increments See above tabulation.
4
5) For ground fault time / current curves see SC-6345-96 (1600A), SC-6346-96 (2000A), and
SC-6347-96 (2500A)
6) This curve is shown as a multiple of the Long Delay Pickup Setting, (I r). This Ir setting is
programmed in primary value amperes via a Breaker Interface Module, or OPTIMizer,
3 or a Remote PC (IMPACC System).
7) The Long Delay Pickup Point (indicated by a flashing LED on the product) nominally occurs
at 116% of the Ir current, with a +/- 5% tolerance. The short delay settings have conventional
2 100%, +/- 5% as the pickup points.
2 8) For additional curve tolerances contact Cutler-Hammer.
9) Total clearing times shown include the response times of the trip unit, the breaker opening,
and the extinction of the arcing current.

Available
Short Delay 1
1 Pickup Settings
1.5 to 8 x Ir
5% in 0.1
increments

.5 .5
.5

.3 .3
.3
TIME IN SECONDS

.2 .2

.1 Application
.1 Determines .1
End of Curve

.05 .05
Available Flat
Short Delay Time Settings
0.1 to 0.5 seconds
.03 in 0.01 second increments .03

.02 .02

.01 .01
3000

4000
2000

5000
1000

6000
7000

9000
10,000
8000
800
300

500
100

400

600
700

900
0.5

0.8
0.9

10

50

90
0.6
0.7

200
20

70
80
1

40
30
4

60
3

7
8
2

5
6

CURRENT IN MULTIPLES OF LONG DELAY SETTING Ir Curve No. SC-6337-96

October 1997
Application Data
29-167R
Page 11

AB DE-ION Circuit Breakers


R-Frame Circuit Breakers Equipped with 1600/2000A Digitrip OPTIM Trip Units; Long Delay I4t, Short Delay Flat
CURRENT IN MULTIPLES OF LONG DELAY SETTING Ir

100
0.5
0.6
0.7
0.8
0.9

10

20

40
50
30

60
70
80
90
2 HOURS

7
8
9
1

6
10,000
Circuit Breaker Time/Current Curves (Phase Current)
Available Long Delay Series CT R - Frame Circuit Breakers
Pickup Settings (I r) Equipped With 1600/2000A Digitrip Optim Trip Units
5,000 0.5 to 1 x In = Ir Response: LONG DELAY I4t, SHORT DELAY FLAT
1 HOUR

in 0.01 increments
Available Rating Plugs

Maximum Ampere Rating Plug Long Delay Short Delay


3,000 Ampere Rating Catalog Pickup Range Pickup Range
Rating (In) Number 0.4 to 1 x In 1.5 to 8x Ir
Amperes Amperes
2,000 Maximum
1600 1600 ORPL16A160 640 -1600 960 - 12800
Total 1250 ORPL16A125 500 -1250 750 - 10000
Clearing 1200 ORPL16A120 480 -1200 720 - 9600
Time 1000 ORPL16A100 400 -1000 600 - 8000
800 ORPL16A080 320 - 800 480 - 6400

1,000 2000 2000 ORPL20A200 800 -2000 1200 - 16000


1600 ORPL20A160 640 -1600 960 - 12800
1250 ORPL20A125 500 -1250 750 - 10000
1200 ORPL20A120 480 -1200 720 - 9600
1000 ORPL20A100 400 -1000 600 - 8000

500

Minimum
300 Total
Clearing
Time
200

100 Interrupting Rating @ 50/60 Hz RMS Sym. Amperes (kA)


1 MINUTE

Breaker UL / CSA

Type Volts 240 480 600


RD, CRD 125 65 50
50 kA
RDC,CRDC 200 100 65

IEC 947-2

Volts 240 415 690


30
Rating I CU I CS I CU I CS I CU I CS
RD,CRD 135 100 70 50 25 13
20 RDC, CRDC
kA
200 100 100 50 35 18

U IMP = 8kV Utilization Category A

Notes
1) For field testing primary injection methods, follow NEMA AB4-1991 publications.
2) Calibration response in short delay pickup range is the same for 1, 2, or 3 poles in series.
10 3) There is a memory effect that can act to shorten the long delay. The memory effect
comes into play if a current above the long delay pickup value exists for a time and then
TIME IN SECONDS

is cleared by the tripping of a downstream device or the circuit breaker itself. A


5 subsequent overload will cause the circuit breaker to trip in shorter time than normal.
The amount of time reduction is inverse to the amount of time that has elapsed since the
previous overload. Approximately five minutes is required between overloads to
completely reset the memory.
4) The end of the curve is determined by the interrupting rating of the circuit breaker.
5 See above tabulation.
5) For ground fault time / current curves see SC-6345-96 (1600A), SC-6346-96 (2000A), and
SC-6347-96 (2500A)
6) This curve is shown as a multiple of the Long Delay Pickup Setting, (I r). This Ir setting is
Available -programmed in primary value amperes via a Breaker Interface Module, or OPTIMizer,
3 Long Delay or a Remote PC (IMPACC System).
7) The Long Delay Pickup Point (indicated by a flashing LED on the product) nominally occurs
Time Settings at 116% of the Ir current, with a +/- 5% tolerance. The short delay settings have conventional
Shown @ 6 x Ir 100%, +/- 5% as the pickup points.
2 1-5 seconds +10 -40% 8) For additional curve tolerances contact Cutler-Hammer.
9) Total clearing times shown include the response times of the trip unit, the breaker opening,
in 0.1 second and the extinction of the arcing current.
1 increments

1 Available 1
Short Delay
Pickup Settings
1.5 to 8 x Ir
5% in 0.1
increments
.5 .5
.5

.3 .3
TIME IN SECONDS

.2 .2

.1 Application
.1 Determines .1
End of Curve

.05 .05
Available Flat
Short Delay Time Settings
0.1 to 0.5 seconds
.03 in 0.01 second increments .03

.02 .02

.01 .01
3000

4000
2000

5000
1000

6000
7000

9000
8000
800

10,000
300

500
100

400

600
700

900
0.5

0.8
0.9

10

50

90
0.6
0.7

200
20

70
80
1

40
30
4

60
3

7
8
2

5
6

CURRENT IN MULTIPLES OF LONG DELAY SETTING I r Curve No. SC-6338-96

October 1997
Application Data
29-167R
Page 12

AB DE-ION Circuit Breakers


R-Frame Circuit Breakers Equipped with 2500A Digitrip OPTIM Trip Units; Long Delay I2t, Short Delay I2t
CURRENT IN MULTIPLES OF LONG DELAY SETTING Ir

100
0.5
0.6
0.7
0.8
0.9

10

20

40
50
30

60
70
80
90
2 HOURS

7
8
9
1

10,000
Circuit Breaker Time/Current Curves (Phase Current)
Available Long Delay Series CT R - Frame Circuit Breakers
Pickup Settings (I r) Equipped With 2500A Digitrip Optim Trip Units
5,000 0.5 to 1 x In = Ir Response: LONG DELAY I2t, SHORT DELAY I2t
1 HOUR

in 0.01 increments
Available Rating Plugs

Maximum Ampere Rating Plug Long Delay Short Delay


3,000 Ampere Rating Catalog Pickup Range Pickup Range
Rating (In) Number 0.4 to 1 x In 1.5 to 6.4 x Ir
Amperes Amperes
2,000
2500 2500 ORPL25A250 1000 -2500 1500 - 16000
2000 ORPL25A200 800 -2000 1200 - 12800
1600 ORPL25A160 640 -1600 960 - 10240

1,000

Maximum
Total
500 Clearing
Time

300

200

100 Interrupting Rating @ 50/60 Hz RMS Sym. Amperes (kA)


1 MINUTE

Breaker UL / CSA

Type Volts 240 480 600


RD 125 65 50
50 kA
RDC 200 100 65

IEC 947-2
Minimum Volts 240 415 690
30 Total 24
Clearing Rating I CU I CS I CU I CS I CU I CS
Time RD 135 100 70 50 25 13
20 RDC
kA
200 100 100 50 35 18

U IMP = 8kV Utilization Category A

Notes
1) For field testing primary injection methods, follow NEMA AB4-1991 publications.
Available 2) Calibration response in short delay pickup range is the same for 1, 2, or 3 poles in series.
10 Long Delay 3) There is a memory effect that can act to shorten the long delay. The memory effect
comes into play if a current above the long delay pickup value exists for a time and then
7 Time Settings
TIME IN SECONDS

is cleared by the tripping of a downstream device or the circuit breaker itself. A


Shown @ 6 x Ir subsequent overload will cause the circuit breaker to trip in shorter time than normal.
The amount of time reduction is inverse to the amount of time that has elapsed since the
2-24 seconds +0 -30% previous overload. Approximately five minutes is required between overloads to
in 0.1 second completely reset the memory.
increments 4) The end of the curve is determined by the interrupting rating of the circuit breaker.
5 4 See above tabulation.
5) For ground fault time / current curves see SC-6345-96 (1600A), SC-6346-96 (2000A), and
SC-6347-96 (2500A)
6) This curve is shown as a multiple of the Long Delay Pick-up Setting, (Ir). This Ir setting is
programmed in primary value amperes via a Breaker Interface Module, or OPTIMizer,
3 or a Remote PC (IMPACC System).
7) The Long Delay Pick-up Point (indicated by a flashing LED on the product) nominally occurs
2 at 116% of the Ir current, with a +/- 5% tolerance. The short delay settings have conventional
100%, +/- 5% as the pickup points.
2 8) For additional curve tolerances contact Cutler-Hammer.
9) Total clearing times shown include the response times of the trip unit, the breaker opening,
and the extinction of the arcing current.

Available
Short Delay 1
1 Pickup Settings
1.5 to 6.4 x Ir
5% in 0.1
increments

.5 .5
.5

.3 .3
.3
TIME IN SECONDS

.2 .2

.1 Application
.1 Determines .1
End of Curve

Available I2t Slope


.05 Short Delay Time Settings
.05
0.1 to 0.5 seconds in
0.01 second increments

.03 .03

.02 .02

.01 .01
3000

4000
2000

5000
1000

6000
7000

9000
8000
800

10,000
300

500
100

400

600
700

900
0.5

0.8
0.9

10

50

90
0.6
0.7

200
20

70
80
1

40
30
4

60
3

7
8
2

5
6

CURRENT IN MULTIPLES OF LONG DELAY SETTING Ir Curve No. SC-6339-96

October 1997
Application Data
29-167R
Page 13

AB DE-ION Circuit Breakers


R-Frame Circuit Breakers Equipped with 2500A Digitrip OPTIM Trip Units; Long Delay I2t, Short Delay Flat
CURRENT IN MULTIPLES OF LONG DELAY SETTING Ir

100
0.5
0.6
0.7
0.8
0.9

10

20

40
50
30

60
70
80
90
2 HOURS

7
8
9
1

6
10,000
Circuit Breaker Time/Current Curves (Phase Current)
Available Long Delay Series CT R - Frame Circuit Breakers
Pickup Settings (I r) Equipped With 2500A Digitrip Optim Trip Units
5,000 0.5 to 1 x In = Ir Response: LONG DELAY I2t, SHORT DELAY FLAT
1 HOUR

in 0.01 increments
Available Rating Plugs

Maximum Ampere Rating Plug Long Delay Short Delay


3,000 Ampere Rating Catalog Pickup Range Pickup Range
Rating (In) Number 0.4 to 1 x In 1.5 to 6.4 x Ir
Amperes Amperes
2,000
2500 2500 ORPL25A250 1000 -2500 1500 - 16000
2000 ORPL25A200 800 -2000 1200 - 12800
1600 ORPL25A160 640 -1600 960 - 10240

1,000

Maximum
Total
500 Clearing
Time

300

200

100 Interrupting Rating @ 50/60 Hz RMS Sym. Amperes (kA)


1 MINUTE

Breaker UL / CSA

Type Volts 240 480 600


RD 125 65 50
50 kA
RDC 200 100 65

IEC 947-2

Minimum Volts 240 415 690


30
Total 24
Rating I CU I CS I CU I CS I CU I CS
Clearing
Time RD 135 100 70 50 25 13
20 RDC
kA
200 100 100 50 35 18

U IMP = 8kV Utilization Category A

Notes
1) For field testing primary injection methods, follow NEMA AB4-1991 publications.
Available 2) Calibration response in short delay pickup range is the same for 1, 2, or 3 poles in series.
10 Long Delay
3) There is a memory effect that can act to shorten the long delay. The memory effect
comes into play if a current above the long delay pickup value exists for a time and then
7 Time Settings
TIME IN SECONDS

is cleared by the tripping of a downstream device or the circuit breaker itself. A


Shown @ 6 x Ir subsequent overload will cause the circuit breaker to trip in shorter time than normal.
The amount of time reduction is inverse to the amount of time that has elapsed since the
2-24 seconds +0 -30% previous overload. Approximately five minutes is required between overloads to
in 0.1 second completely reset the memory.
4) The end of the curve is determined by the interrupting rating of the circuit breaker.
5 4 increments See above tabulation.
5) For ground fault time / current curves see SC-6345-96 (1600A), SC-6346-96 (2000A), and
SC-6347-96 (2500A)
6) This curve is shown as a multiple of the Long Delay Pick-up Setting, (Ir). This Ir setting is
programmed in primary value amperes via a Breaker Interface Module, or OPTIMizer,
3 or a Remote PC (IMPACC System).
7) The Long Delay Pick-up Point (indicated by a flashing LED on the product) nominally occurs
2 at 116% of the Ir current, with a +/- 5% tolerance. The short delay settings have conventional
100%, +/- 5% as the pickup points.
2 8) For additional curve tolerances contact Cutler-Hammer.
9) Total clearing times shown include the response times of the trip unit, the breaker opening,
and the extinction of the arcing current.

Available
Short Delay 1
1 Pickup Settings
1.5 to 6.4 x Ir
5% in 0.1
increments

.5 .5
.5

.3 .3
.3
TIME IN SECONDS

.2 .2

Application
.1 Determines
.1 End of Curve .1

.05 .05
Available Flat
Short Delay Time Settings
0.1 to 0.5 seconds
.03 in 0.01 second increments .03

.02 .02

.01 .01
3000

4000
2000

5000

10,000
1000

6000
7000

9000
8000
800
300

500
100

400

600
700

900
0.5

0.8
0.9

10

50

90
0.6
0.7

200
20

70
80
1

40
30
4

60
3

7
8
2

5
6

CURRENT IN MULTIPLES OF LONG DELAY SETTING I r Curve No. SC-6340-96

October 1997
Application Data
29-167R
Page 14

AB DE-ION Circuit Breakers


R-Frame Circuit Breakers Equipped with 2500A Digitrip OPTIM Trip Units; Long Delay I4t, Short Delay Flat
CURRENT IN MULTIPLES OF LONG DELAY SETTING Ir

100
0.5
0.6
0.7
0.8
0.9

10

20

40
50
30

60
70
80
90
2 HOURS

7
8
9
1

10,000
Circuit Breaker Time/Current Curves (Phase Current)
Available Long Delay Series CT R - Frame Circuit Breakers
Pickup Settings (I r) Equipped With 2500A Digitrip Optim Trip Units
5,000 0.5 to 1 x In = Ir Response: LONG DELAY I4t, SHORT DELAY FLAT
1 HOUR

in 0.01 increments
Available Rating Plugs

Maximum Ampere Rating Plug Long Delay Short Delay


3,000 Ampere Rating Catalog Pickup Range Pickup Range
Rating (In) Number 0.4 to 1 x In 1.5 to 6.4 x Ir
Amperes Amperes
2,000 Maximum 2500 2500 ORPL25A250 1000 -2500 1500 - 16000
Total 2000 ORPL25A200 800 -2000 1200 - 12800
Clearing 1600 ORPL25A160 640 -1600 960 - 10240
Time

1,000

500

Minimum
300 Total
Clearing
Time
200

100 Interrupting Rating @ 50/60 Hz RMS Sym. Amperes (kA)


1 MINUTE

Breaker UL / CSA

Type Volts 240 480 600


RD 125 65 50
50 kA
RDC 200 100 65

IEC 947-2

Volts 240 415 690


30
Rating I CU I CS I CU I CS I CU I CS
RD 135 100 70 50 25 13
20 RDC
kA
200 100 100 50 35 18

U IMP = 8kV Utilization Category A

Notes
1) For field testing primary injection methods, follow NEMA AB4-1991 publications.
2) Calibration response in short delay pickup range is the same for 1, 2, or 3 poles in series.
10 3) There is a memory effect that can act to shorten the long delay. The memory effect
comes into play if a current above the long delay pickup value exists for a time and then
TIME IN SECONDS

is cleared by the tripping of a downstream device or the circuit breaker itself. A


subsequent overload will cause the circuit breaker to trip in shorter time than normal.
The amount of time reduction is inverse to the amount of time that has elapsed since the
previous overload. Approximately five minutes is required between overloads to
completely reset the memory.
4) The end of the curve is determined by the interrupting rating of the circuit breaker.
5 See above tabulation.
5) For ground fault time / current curves see SC-6345-96 (1600A), SC-6346-96 (2000A), and
SC-6347-96 (2500A)
6) This curve is shown as a multiple of the Long Delay Pick-up Setting, (Ir). This Ir setting is
Available programmed in primary value amperes via a Breaker Interface Module, or OPTIMizer,
3 Long Delay or a Remote PC (IMPACC System).
7) The Long Delay Pick-up Point (indicated by a flashing LED on the product) nominally occurs
Time Settings at 116% of the Ir current, with a +/- 5% tolerance. The short delay settings have conventional
Shown @ 6 x Ir 100%, +/- 5% as the pickup points.
2 1-5 seconds +10 -40% 8) For additional curve tolerances contact Cutler-Hammer.
9) Total clearing times shown include the response times of the trip unit, the breaker opening,
in 0.1 second and the extinction of the arcing current.
increments

Available 1
1
Short Delay
Pickup Settings
1.5 to 6.4 x Ir
5% in 0.1
increments
.5 .5
.5

.3 .3
TIME IN SECONDS

.2 .2

Application
.1 Determines
.1 .1
End of Curve

.05 .05
Available Flat
Short Delay Time Settings
0.1 to 0.5 seconds
.03 in 0.01 second increments .03

.02 .02

.01 .01
3000

4000
2000

5000
1000

6000
7000

9000
8000
800

10,000
300

500
100

400

600
700

900
0.5

0.8
0.9

10

50

90
0.6
0.7

200
20

70
80
1

40
30
4

60
3

7
8
2

5
6

CURRENT IN MULTIPLES OF LONG DELAY SETTING I r Curve No. SC-6341-96

October 1997
Application Data
29-167R
Page 15

AB DE-ION Circuit Breakers


R-Frame Circuit Breakers Equipped with 1600A Digitrip OPTIM Trip Units; Instantaneous and Override
CURRENT IN MULTIPLES OF PLUG RATING In

100
10

20

40
50
30

60
70
80
90
4
5

7
8
9
1

6
2 HOURS

10,000
Circuit Breaker Time/Current Curves (Phase Current)
Series CT R - Frame Circuit Breakers
Equipped With 1600A Digitrip Optim Trip Units
5,000 Response: INSTANTANEOUS AND OVERRIDE
1 HOUR

Available Rating Plugs

Maximum Ampere Rating Plug Override


3,000 Ampere Rating Catalog
Instantaneous
Pickup Range Amperes
Rating (In) Number 2 to 10 x In
Amperes
2,000
1600 1600 ORPL16A160 3200 -16000 14875 -20125
1250 ORPL16A125 2500 -12500 14875 -20125
1200 ORPL16A120 2400 -12000 14875 -20125
1000 ORPL16A100 2000 -10000 14875 -20125
800 ORPL16A080 1600 - 8000 14875 -20125

1,000

500

300

200

100 Interrupting Rating @ 50/60 Hz RMS Sym. Amperes (kA)


1 MINUTE

Breaker UL / CSA

Type Volts 240 480 600


RD, CRD 125 65 50
50 kA
RDC, CRDC 200 100 65

IEC 947-2

Volts 240 415 690


30
Rating I CU I CS I CU I CS I CU I CS
RD, CRD 135 100 70 50 25 13
20 RDC, CRDC
kA
200 100 100 50 35 18

U IMP = 8kV Utilization Category A

Notes
1) For field testing primary injection methods, follow NEMA AB4-1991 publications.
2) Calibration response in short delay pickup range is the same for 1, 2, or 3 poles in series.
10 3) There is a memory effect that can act to shorten the long delay. The memory effect
comes into play if a current above the long delay pickup value exists for a time and then
is cleared by the tripping of a downstream device or the circuit breaker itself. A
TIME IN SECONDS

subsequent overload will cause the circuit breaker to trip in shorter time than normal.
The amount of time reduction is inverse to the amount of time that has elapsed since the
previous overload. Approximately five minutes is required between overloads to
completely reset the memory.
4) The end of the curve is determined by the interrupting rating of the circuit breaker.
5 See above tabulation.
5) For ground fault time / current curves see SC-6345-96 (1600A), SC-6346-96 (2000A), and
SC-6347-96 (2500A)
6) The instantaneous settings have conventional 100%, +/- 10% as the pickup points.
7) For additional curve tolerances contact Cutler-Hammer.
3 8) Total clearing times shown include the response times of the trip unit, the breaker opening,
and the extinction of the arcing current.

1 1
Available Instantaneous
Pickup Settings
2 10 2 to 10 x In 10%
In 0.1 Increments
.5 .5
.5 Fixed
Instantaneous
Override
.3 .3
.3
Available Flat Response
Short Delay Time Settings
.2 0.1 to 0.5 seconds in .2
0.01 second increments

.1
.1 .1

Application
.05 Determines .05
End of Curve

.03 .03

.02 .02

.01 .01
10,000

20,000

30,000

40,000

50,000
60,000
70,000
80,000
100
50

90
20

40

70
80

3000

4000

5000
6000
7000
8000
9000
30

60

1000

2000
3

7
8

10
2

4
1

5
6

CURRENT IN MULTIPLES OF PLUG RATING I n AMPERES Curve No. SC-6342-96

October 1997
Application Data
29-167R
Page 16

AB DE-ION Circuit Breakers


R-Frame Circuit Breakers Equipped with 2000A Digitrip OPTIM Trip Units; Instantaneous and Override
CURRENT IN MULTIPLES OF PLUG RATING I n

100
10

20

40
50
30

60
70
80
90
4
5

7
8
9
1

6
2 HOURS

10,000
Circuit Breaker Time/Current Curves (Phase Current)
Series CT R - Frame Circuit Breakers
Equipped With 2000A Digitrip Optim Trip Units
5,000 Response: INSTANTANEOUS AND OVERRIDE
1 HOUR

Available Rating Plugs

Maximum Ampere Rating Plug Instantaneous Override


3,000 Ampere Rating Catalog Pickup Range Amperes
Rating (In) Number 2 to 8 x In
Amperes

2,000
2000 2000 ORPL20A200 4000 -16000 14875 -20125
1600 ORPL20A160 3200 -12800 14875 -20125
1250 ORPL20A125 2500 -10000 14875 -20125
1200 ORPL20A120 2400 - 9600 14875 -20125
1000 ORPL20A100 2000 - 8000 14875 -20125
1,000

500

300

200

100 Interrupting Rating @ 50/60 Hz RMS Sym. Amperes (kA)


1 MINUTE

Breaker UL / CSA

Type Volts 240 480 600


RD, CRD 125 65 50
50 kA
RDC, CRDC 200 100 65

IEC 947-2

Volts 240 415 690


30
Rating I CU I CS I CU I CS I CU I CS
RD, CRD 135 100 70 50 25 13
20 RDC, CRDC
kA
200 100 100 50 35 18

U IMP = 8kV Utilization Category A

Notes
1) For field testing primary injection methods, follow NEMA AB4-1991 publications.
2) Calibration response in short delay pickup range is the same for 1, 2, or 3 poles in series.
10 3) There is a memory effect that can act to shorten the long delay. The memory effect
comes into play if a current above the long delay pickup value exists for a time and then
is cleared by the tripping of a downstream device or the circuit breaker itself. A
TIME IN SECONDS

subsequent overload will cause the circuit breaker to trip in shorter time than normal.
The amount of time reduction is inverse to the amount of time that has elapsed since the
previous overload. Approximately five minutes is required between overloads to
completely reset the memory.
4) The end of the curve is determined by the interrupting rating of the circuit breaker.
5 See above tabulation.
5) For ground fault time / current curves see SC-6345-96 (1600A), SC-6346-96 (2000A), and
SC-6347-96 (2500A)
6) The instantaneous settings have conventional 100%, +/- 10% as the pickup points.
7) For additional curve tolerances contact Cutler-Hammer.
3 8) Total clearing times shown include the response times of the trip unit, the breaker opening,
and the extinction of the arcing current.

1 1
Available Instantaneous
Pickup Settings
2 8 2 to 8 x In 10%
In 0.1 Increments
.5 .5
.5 Fixed
Instantaneous
Override
.3 .3
.3
Available Flat Response
Short Delay Time Settings
.2 0.1 to 0.5 seconds .2
in 0.01 second increments

.1
.1 .1

Application
.05 Determines .05
End of Curve

.03 .03

.02 .02

.01 .01
10,000

20,000

30,000

40,000

50,000
60,000
70,000
80,000
100
50

90
20

40

70
80

3000

4000

5000
6000
7000
8000
9000
30

60

1000

2000
3

7
8

10
2

4
1

5
6

CURRENT IN MULTIPLES OF PLUG RATING In AMPERES Curve No. SC-6343-96

October 1997
Application Data
29-167R
Page 17

AB DE-ION Circuit Breakers


R-Frame Circuit Breakers Equipped with 2500A Digitrip OPTIM Trip Units; Instantaneous and Override
CURRENT IN MULTIPLES OF PLUG RATING In

100
10

20

40
50
30

60
70
80
90
4
5

7
8
9
1

6
2 HOURS

10,000
Circuit Breaker Time/Current Curves (Phase Current)
Series CT R - Frame Circuit Breakers
Equipped With 2500A Digitrip Optim Trip Units
5,000 Response: INSTANTANEOUS AND OVERRIDE
1 HOUR

Available Rating Plug

Maximum Ampere Rating Plug Instantaneous Override


3,000 Ampere Rating Catalog Pickup Range Amperes
Rating (In) Number 2 to 6.4 x In
Amperes

2,000
2500 2500 ORPL25A250 5000 -16000 14875 -20125
2000 ORPL25A200 4000 -12800 14875 -20125
1600 ORPL25A160 3200 -10240 14875 -20125

1,000

500

300

200

100 Interrupting Rating @ 50/60 Hz RMS Sym. Amperes (kA)


1 MINUTE

Breaker UL / CSA

Type Volts 240 480 600


RD 125 65 50
50 kA
RDC 200 100 65

IEC 947-2

Volts 240 415 690


30
Rating I CU I CS I CU I CS I CU I CS
RD 135 100 70 50 25 13
20 RDC
kA
200 100 100 50 35 18

U IMP = 8kV Utilization Category A

Notes
1) For field testing primary injection methods, follow NEMA AB4-1991 publications.
2) Calibration response in short delay pickup range is the same for 1, 2, or 3 poles in series.
10 3) There is a memory effect that can act to shorten the long delay. The memory effect
comes into play if a current above the long delay pickup value exists for a time and then
is cleared by the tripping of a downstream device or the circuit breaker itself. A
TIME IN SECONDS

subsequent overload will cause the circuit breaker to trip in shorter time than normal.
The amount of time reduction is inverse to the amount of time that has elapsed since the
previous overload. Approximately five minutes is required between overloads to
completely reset the memory.
4) The end of the curve is determined by the interrupting rating of the circuit breaker.
5 See above tabulation.
5) For ground fault time / current curves see SC-6345-96 (1600A), SC-6346-96 (2000A), and
SC-6347-96 (2500A)
6) The instantaneous settings have conventional 100%, +/- 10% as the pickup points.
7) For additional curve tolerances contact Cutler-Hammer.
3 8) Total clearing times shown include the response times of the trip unit, the breaker opening,
and the extinction of the arcing current.

1 1
Available Instantaneous
Pickup Settings
2 6.4 2 to 6.4 x In 10%
In 0.1 Increments
.5 .5
.5 Fixed
Instantaneous
Override
.3 .3
.3
Available Flat Response
Short Delay Time Settings
.2 0.1 to 0.5 seconds .2
in 0.01 second increments

.1
.1 .1

Application
.05 Determines .05
End of Curve

.03 .03

.02 .02

.01 .01
10,000

20,000

30,000

40,000

50,000
60,000
70,000
80,000
100
50

90
20

40

70
80

3000

4000

5000
6000
7000
8000
9000
30

60

1000

2000
3

7
8

10
2

4
1

5
6

CURRENT IN MULTIPLES OF PLUG RATING In AMPERES Curve No. SC-6344-96

October 1997
Application Data
29-167R
Page 18

AB DE-ION Circuit Breakers


R-Frame Circuit Breakers Equipped with 1600A Digitrip OPTIM Trip Units; Ground Fault or Ground Fault Alarm Only
CURRENT IN MULTIPLES OF RATING PLUG In

10
.4
.2

.3

.5
.6
.7
.8
.9

4
.1

5
6
7
8
9
1
2 HOURS

10,000
Circuit Breaker Time/Current Curves (Ground Current)
Series CT R - Frame Circuit Breakers
Equipped With 1600A Digitrip Optim Trip Units
5,000 Response: GROUND FAULT TRIP OR GROUND FAULT ALARM ONLY
1 HOUR

Available Rating Plugs

Maximum Ampere Rating Plug Ground Fault


3,000 Ampere Rating Catalog Pickup Range
Rating (In) Number Amperes

2,000
1600 1600 ORPL16A160 400 -1200
1250 ORPL16A125 312.5 -1200
1200 ORPL16A120 300 -1200
1000 ORPL16A100 250 -1000
800 ORPL16A080 200 - 800

1,000

500

300

200
Interrupting Rating @ 50/60 Hz RMS Sym. Amperes (kA)

Breaker UL / CSA

100 Type Volts 240 480 600


RD, CRD 125 65 50
1 MINUTE

kA
RDC, CRDC 200 100 65

IEC 947-2

Volts 240 415 690


50
Rating I CU I CS I CU I CS I CU I CS
RD, CRD 135 100 70 50 25 13
kA
RDC, CRDC 200 100 100 50 35 18
30
U IMP = 8kV Utilization Category A

Notes
20 1) For field testing primary injection methods, follow NEMA AB4-1991 publications.
2) Calibration response in short delay pickup range is the same for 1, 2, or 3 poles in series.
3) There is a memory effect that can act to shorten the long delay. The memory effect
comes into play if a current above the long delay pickup value exists for a time and then
is cleared by the tripping of a downstream device or the circuit breaker itself. A
subsequent overload will cause the circuit breaker to trip in shorter time than normal.
The amount of time reduction is inverse to the amount of time that has elapsed since the
previous overload. Approximately five minutes is required between overloads to
10 completely reset the memory.
4) The end of the curve is determined by the interrupting rating of the circuit breaker.
TIME IN SECONDS

See above tabulation.


5) Ground fault level is electronically limited to a maximum of 1200 Amperes.
Available Ground Fault 6) For phase current curves, see SC-6336-96, SC-6337-96, SC-6338-96, SC-6339-96,
SC-6340-96, SC-6341-96, SC-6342-96, SC-6343-96, and SC-6344-96.
Pickup Settings 10% 7) The ground fault settings have conventional 100%, +/- 10% as the pickup points.
5 in 0.1 increments 8) For additional curve tolerances contact Cutler-Hammer.
9) Total clearing times shown include the response times of the trip unit, the breaker opening,
and the extinction of the arcing current.

1.0
2

.5

1 1
.2

.5 .5
.5 .5

Available Flat Response


.3 Ground Fault Time Settings .3
.3 0.1 to 0.5 seconds .3
in 0.01 second increments
.2 .2

.1 I2t Slope for .1


.1 Ground Fault .1
Time Settings

.05 Availaible I2t Response .05


Ground Fault Time Settings
Flat Shape for 0.1 to 0.5 seconds
Ground Fault in 0.01 second increments
.03 Time Settings .03

.02 .02

.01 .01
10

10
.4

.4
.2

.3

.5
.6
.7
.8
.9

.2

.3

.5
.6
.7
.8
.9
4

4
.1

5
6
7
8
9

5
6
7
8
9
1

CURRENT IN MULTIPLES OF RATING PLUG In Curve No. SC-6345-96

October 1997
Application Data
29-167R
Page 19

AB DE-ION Circuit Breakers


R-Frame Circuit Breakers Equipped with 2000A Digitrip OPTIM Trip Units; Ground Fault or Ground Fault Alarm Only
CURRENT IN MULTIPLES OF RATING PLUG In

10
.4
.2

.3

.5
.6
.7
.8
.9

4
.1

5
6
7
8
9
1
2 HOURS

10,000
Circuit Breaker Time/Current Curves (Ground Current)
Series CT R - Frame Circuit Breakers
Equipped With 2000A Digitrip Optim Trip Units
5,000 Response: GROUND FAULT TRIP OR GROUND FAULT ALARM ONLY
1 HOUR

Available Rating Plugs

Maximum Ampere Rating Plug Ground Fault


3,000 Ampere Rating Catalog Pickup Range
Rating (In) Number Amperes

2,000
2000 2000 ORPL20A200 500 -1200
1600 ORPL20A160 400 -1200
1250 ORPL20A125 312.5 -1200
1200 ORPL20A120 300 -1200
1000 ORPL20A100 250 -1000

1,000

500

300

200

Interrupting Rating @ 50/60 Hz RMS Sym. Amperes (kA)

Breaker UL / CSA
100
Type Volts 240 480 600
1 MINUTE

RD, CRD 125 65 50


kA
RDC, CRDC 200 100 65

IEC 947-2
50
Volts 240 415 690

Rating I CU I CS I CU I CS I CU I CS
RD, CRD 135 100 70 50 25 13
30 RDC, CRDC
kA
200 100 100 50 35 18

U IMP = 8kV Utilization Category A

20 Notes
1) For field testing primary injection methods, follow NEMA AB4-1991 publications.
2) Calibration response in short delay pickup range is the same for 1, 2, or 3 poles in series.
3) There is a memory effect that can act to shorten the long delay. The memory effect
comes into play if a current above the long delay pickup value exists for a time and then
is cleared by the tripping of a downstream device or the circuit breaker itself. A
subsequent overload will cause the circuit breaker to trip in shorter time than normal.
10 The amount of time reduction is inverse to the amount of time that has elapsed since the
previous overload. Approximately five minutes is required between overloads to
completely reset the memory.
TIME IN SECONDS

4) The end of the curve is determined by the interrupting rating of the circuit breaker.
See above tabulation.
Available Ground Fault 5) Ground fault level is electronically limited to a maximum of 1200 Amperes.
Pickup Settings 10% 6) For phase current curves, see SC-6336-96, SC-6337-96, SC-6338-96, SC-6339-96,
SC-6340-96, SC-6341-96, SC-6342-96, SC-6343-96, and SC-6344-96.
5 in 0.1 increments 7) The ground fault settings have conventional 100%, +/- 10% as the pickup points.
8) For additional curve tolerances contact Cutler-Hammer.
9) Total clearing times shown include the response times of the trip unit, the breaker opening,
and the extinction of the arcing current.
3

1.0
2

.5

1 1
.2

.5 .5
.5 .5

Available Flat Response


.3 Ground Fault Time Settings .3
.3 0.1 to 0.5 seconds .3
in 0.01 second increments
.2 .2

.1 I2t Slope for .1


.1 Ground Fault .1
Time Settings

Availaible I2t Response


.05 Ground Fault Time Settings .05
0.1 to 0.5 seconds
Flat Shape for in 0.01 second increments
Ground Fault
.03 Time Settings .03

.02 .02

.01 .01
10

10
.4

.4
.2

.3

.5
.6
.7
.8
.9

.2

.3

.5
.6
.7
.8
.9
4

4
.1

5
6
7
8
9

5
6
7
8
9
1

CURRENT IN MULTIPLES OF RATING PLUG In


Curve No. SC-6346-96

October 1997
Application Data
29-167R
Page 20

AB DE-ION Circuit Breakers


R-Frame Circuit Breakers Equipped with 2500A Digitrip OPTIM Trip Units; Ground Fault or Ground Fault Alarm Only
CURRENT IN MULTIPLES OF RATING PLUG I n

10
.4
.2

.3

.5
.6
.7
.8
.9

4
.1

5
6
7
8
9
1
2 HOURS

10,000
Circuit Breaker Time/Current Curves (Ground Current)
Series CT R - Frame Circuit Breakers
Equipped With 2500A Digitrip Optim Trip Units
5,000 Response: GROUND FAULT TRIP OR GROUND FAULT ALARM ONLY
1 HOUR

Available Rating Plugs

Maximum Ampere Rating Plug Ground Fault


3,000 Ampere Rating Catalog Pickup Range
Rating (In) Number Amperes

2,000
2500 2500 ORPL25A250 625 -1200
2000 ORPL25A200 500 -1200
1600 ORPL25A160 400 -1200

1,000

500

300

200

Interrupting Rating @ 50/60 Hz RMS Sym. Amperes (kA)

100 Breaker UL / CSA


1 MINUTE

Type Volts 240 480 600


RD 125 65 50
kA
RDC 200 100 65

50 IEC 947-2

Volts 240 415 690

Rating I CU I CS I CU I CS I CU I CS
30 RD 135 70 25
100 50 13
kA
RDC 200 100 100 50 35 18

U IMP = 8kV Utilization Category A


20
Notes
1) For field testing primary injection methods, follow NEMA AB4-1991 publications.
2) Calibration response in short delay pickup range is the same for 1, 2, or 3 poles in series.
3) There is a memory effect that can act to shorten the long delay. The memory effect
comes into play if a current above the long delay pickup value exists for a time and then
is cleared by the tripping of a downstream device or the circuit breaker itself. A
10 subsequent overload will cause the circuit breaker to trip in shorter time than normal.
The amount of time reduction is inverse to the amount of time that has elapsed since the
previous overload. Approximately five minutes is required between overloads to
TIME IN SECONDS

completely reset the memory.


4) The end of the curve is determined by the interrupting rating of the circuit breaker.
Available Ground Fault See above tabulation.
Pickup Settings 10% 5) Ground fault level is electronically limited to a maximum of 1200 Amperes.
5 6) For phase current curves, see SC-6336-96, SC-6337-96, SC-6338-96, SC-6339-96,
in 0.01 increments SC-6340-96, SC-6341-96, SC-6342-96, SC-6343-96, and SC-6344-96.
7) The ground fault settings have conventional 100%, +/- 10% as the pickup points.
8) For additional curve tolerances contact Cutler-Hammer.
9) Total clearing times shown include the response times of the trip unit, the breaker opening,
and the extinction of the arcing current.
3

2 1.0

1 1

.2

.5 .5
.5 .5

Available Flat Response


.3 Ground Fault Time Settings .3
0.1 to 0.5 seconds
in 0.01 second increments
.2 .2

.1 .1
.1 I2 t Slope for .1
Ground Fault
Time Settings

Availaible I2t Response


.05 Ground Fault Time Settings .05
0.1 to 0.5 seconds
Flat Shape for in 0.01 second increments
Ground Fault
.03 Time Settings .03

.02 .02

.01 .01
10

10
.4

.4
.2

.3

.5
.6
.7
.8
.9

.2

.3

.5
.6
.7
.8
.9
4

4
.1

5
6
7
8
9

5
6
7
8
9
1

CURRENT IN MULTIPLES OF RATING PLUG In


Curve No. SC-6347-96

October 1997

Vous aimerez peut-être aussi