OMICRON PTL
XRIO Converter
User Manual
V1.000
Contents
1 General information
The AREVA P132 P139 XRIO converter is designed for testing AREVA P132 P139 feeder protection
relays by using the OMICRON Test Universe 2.30 software or higher. The converter provides all
necessary data for testing the phase overcurrent, thermal overload, earth-fault and unbalance protection
functions of the P132 P139 relays. The converter is tested with the following relay:
AREVA P1323394540NU00G0A
Ser No. 3286650/11/08
Note: This converter is tested with the relay described above. It may also work with other relays from the
P132 or P139 series.
Figure 1: Opening and importing the AREVA P132 P139 XRIO converter
5 Functional range
The AREVA P132 P139 XRIO converter implements the following functions:
DTOC (definite time overcurrent)
IDMT1 (inverse time overcurrent)
IDMT2 (inverse time overcurrent)
SCDD (short circuit direction determination)
THERM (thermal overload protection)
I2> (unbalance protection)
These functions use the RIO interface of the Test Universe software. Consequently, the test modules are
configured automatically.
8 Converter structure
The converter is divided into two sections: the AREVA P132 P139 section and the RIO section. Both
sections consist of several function blocks.
8.2 RIO
The RIO section of the converter contains all specialized RIO functions which are needed to use the more
specialized test modules (like Overcurrent) provided by the OMICRON Test Universe software.
Warning: Do not change any values in this section. The values have been set using the relay settings of
the Relay Parameter Section.
Note: Do not enter the input mask of the RIO-Functions. Changing parameters in this view could disable
formulas in the RIO section.
The AREVA P132 P139 converter constructs the overcurrent characteristic curve out of the setting values
in the Relay Parameter Section which allows using the test modules listed above for testing the relay
functions.
8.4.3 I2>
This function is not completely supported by the converter. The settings are present and also the RIO
function Unbalance protection is prepared. But the I2> elements are not sorted together with the
negative sequence elements of the DTOC or IDMT functions.
Figure 5: Select the Filter for AREVA S-R 103 .txt Settings
After the relay settings have been imported successfully, a message box showing the number of imported
parameters appears.