7) Calculation for size of the pressure vessel

Q=3M3/H,H=27M
a Flowrate (Cut-in) : 1.60 L/s
b Flowrate (Cut-Out) : 0.80 L/s
c Head (Cut-in) : 16.00 meters , 2.0
d Head (Cut-Out) : 27.00 meters , 3.0
e No. of Start/Stop per hour : 20 s/s per hour
f No.of Pump : 2 pump(s)

Cut out (absolute pressure ) - Cut in((absolute pressure )


Acceptance Factor = --------------------------------------------------------
Cut out ( absolute presssure )
4.00 - 3.00
= --------------------------------------------- =
4.00

Cut-in flowrate + Cut-Out flow


ii) Mean flowrate = -------------------------------------------------------------------------------
2
1.60 + 0.80
= ----------------------------------------------------------------------------
2
3600 sec
=
iii) System operating ----------------------------------------------------------------------
time per pump=
per cycle in an hour no. of s/s per hour x no. of pumps

Based on
iv) 85%
of the time water charging in the pressure vessel and
15% of the time water discharging out from the pressure vessel in a cyc

Therefore Pressure vessel storage time = 15%


= 13.5 Secs

Mean Flowrate x Storage Time (Effective Cap


v) Therefore the total capacity of = --------------------------------------------- =
Acceptance Factor

Therefore we select 1 nos. 100 litres of GT-tanks Model


has the overall capacity of 100 litres.
ssure vessel

bar
bar

n((absolute pressure )
-----
re )

0.25

Cut-Out flowrate
------------------------------------------------------

0.80
------------------------- = 1.20 L/s
3600
----------------------------------------------- = 90secs
20 x 2

pressure vessel in a cycle.

x 90 secs

1.20 x 14
--------------------------------------------------- = 65 litres
0.25

GT-tanks Model