Académique Documents
Professionnel Documents
Culture Documents
fully edited. Content may change prior to final publication. Citation information: DOI
10.1109/TPWRD.2015.2457831, IEEE Transactions on Power Delivery
1
AbstractThird order high-pass harmonic filter has been II. ACCEPTED DESIGN EQUATIONS
widely used in industry. However, technically-sound design
As explained earlier, four equations (or conditions) are
method has not been well established for the filter. This letter
presents a complete design method along with simple design required to determine four component parameters (C1, C2, L
formulas. Comparative case studies show that the proposed and R). Two conditions are well understood and accepted by
design method will result in minimal fundamental frequency loss industry and research community:
for the filter and a significantly smaller auxiliary filter capacitor. Condition 1: The reactive power output of the filter shall be
equal to the required amount QF. This condition yields the
Index TermsPassive filters, 3rd order filter, harmonics. following design equation:
I. INTRODUCTION C1 QF / 1V 2 (1)
C2
minimization to establish the 3rd design equation. The
L fundamental frequency power loss of the filter is as follows:
R
0885-8977 (c) 2015 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See
http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI
10.1109/TPWRD.2015.2457831, IEEE Transactions on Power Delivery
2
The above optimization problem can be solved using the procedure is very simple. The proposed design method has
following KKT optimality condition [5]: been compared with the design result using the condition of
C2 C1 and with the actual filter installation documented in
f ( R* , C2* ) 1g1 ( R* , C2* ) 2g 2 ( R* , C2* )
(6) [3] for a HVDC link (Corisca tapping substation). The same
3g3 ( R* , C2* ) 0 design input data are used for the comparison. They are QF=10
Mvar, V= 90 kV, a%=53.5 for 7th harmonic, ZS=j22.5 . The
where ( R* , C2* ) is the optimal solution and 1 , 2 and 3 are harmonic losses are calculated assuming 1.5% background
KKT multipliers which should be nonnegative. voltage harmonics for the 3rd to 13th harmonics.
Through extensive mathematical operations, an analytical The results are shown in Table I and Fig. 3. It can be seen
solution for the above problem has been found. It is shown that the proposed design method results in much less power
below. This results in the 3rd design equation: loss. In addition capacitor C2 is significant smaller, which
leads to reduced cost and space for the filter.
C2 C1 L / ( R2C1 L) (7)
TABLE I: DESIGN RESULTS FOR DIFFERENT DESIGN METHODS
VF (H ) 1 a%VF0 (H ) (9) 0
0 10 20 30 40 50
Harmonic Order
Fig. 3. Comparison of filter impedance characteristic.
The above design equation can be solved analytically for
the case where the system impedance can be approximated as a
VI. CONCLUSIONS
reactance in the form of Z S (H ) jnH X S , where XS is the
This letter has proposed a design concept for the 3rd order
short-circuit reactance of the system and nH H / 1 . This
high-pass filter. A complete and simple design method in
condition can be met for many industrial facilities which are terms of four design formulas has been established
supplied by a service transformer. The reactance of the service accordingly. Case study results have shown that the proposed
transformer dominates Z S . For such systems, the resulting method can result in minimal fundamental frequency loss for
design equation is: the filter and a significantly smaller filter capacitor C2.
0885-8977 (c) 2015 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See
http://www.ieee.org/publications_standards/publications/rights/index.html for more information.