Condensateurs Propivar

Propivar capacitors
Condensadores Propivar

Notice dutilisation
User manual
Gua de utilizacin
Attention Cette notice dnit les vrications effectuer pour sassurer du respect des
conditions standards dutilisation, dinstallation et de maintenance des batteries
de condensateurs MT.
Lapplication des conditions de garantie est subordonne au respect de lensemble

! de ces rgles (ou, pour des applications spciques, lobtention de notre


accord crit).
Les condensateurs accompagns de ce document doit tre installs et utiliss par
un personnel comptent et familier avec les rgles de scurit lectrique dnies
dans chaque pays.
Ce document ne remplace en aucun cas les formations et habilitations lectriques
ainsi que les procdures de scurit que doit suivre le personnel intervenant sur des
quipements lectriques telles que dnies dans le pays.

LE NON RESPECT DE CES INSTRUCTIONS, EXPOSE AU DANGER DE MORT


OU DES BLESSURES GRAVES.

1. Rception du matriel @ nos marchandises voyagent toujours aux risques et prils soit du destinataire soit
du client selon lincoterm ngoci.
@ nous dclinons toute responsabilit quant aux manquants ou aux avaries
imputables au transporteur.
Le cas chant :
1 Ne pas refuser le colis.
2 Emettre des rserves manuscrites sur le bordereau. Vrier les dgts ventuels.
3 En cas de dgts, mettre des rserves circonstancies par lettre recommande
auprs du transporteur.
@ dballer le matriel avec prcaution pour faire des constats internes au colis et
faire des photos en cas de problme.
@ raliser des photos et donner des explications prcises concernant les problmes
rencontrs et les circonstances.
@ vrier quil ny a pas de fuite de liquide dilectrique avant dballage.
@ sassurer quaucun colis nest manquant et que le matriel na subi aucun choc
nuisible son isolement et son fonctionnement
@ vrier que les caractristiques lectriques portes sur le marquage signaltique
correspondent celles dnies sur le bon de commande
@ en cas de non conformit, rappeler, sur la rclamation, la rfrence du bordereau
dexpdition.

2. Manutention @ dballer les quipements sur le lieu dinstallation


@ utiliser de prfrence un chariot lvateur
DB108739

@ viter les chocs et les dformations.

3. Stockage @ stocker les appareils dans un local sec, ar, labri de la pluie, des projections
deau, des agents chimiques et des poussires
@ temprature de stockage : -20 C +45 C.
@ humidit relative moyenne de stockage : < 95 %

4. Garantie Nos produits sont contrls en usine. Toute modication remet en cause la garantie.

5. Plaque signaltique Vrier que les caractristiques de lquipement livr sont conformes celles de la
commande :
PB100046

@ Cn : capacit nominale (en mF)


@ Imp : nom du liquide dimprgnation
@ Qn : puissance ractive (en kvar)
@ Un : tension nominale (en V)
@ Std : norme de rfrence
@ Ui : niveau disolement (en kV)
@ T : classe de temprature (en C)
@ Fn : frquence nominale (en Hz)
@ nombre de bornes
@ avec/sans rsistance de dcharge interne : avec sans XXXXX
@ avec/sans fusibles internes : avec sans XXXXX

2 3657801AC.indd
Franais
6. Conditions dinstallation Lutilisation des condensateurs tempratures trs leves, rduit la dure de vie
des condensateurs. Il faut donc veiller au respect des tempratures au voisinage
des condensateurs xes par la norme CEI 60871, (sauf dans le cas dune
spcication particulire prcise de la part du client, il faudra alors se rfrer aux
plans contractuels) :

Symbole Maximum Moyenne sur 24h Moyenne sur 1 an Minimum


A 40 C 30 C 20 C -25 C
B 45 C 35 C 25 C -25 C
C 50 C 40 C 30 C -25 C
D 55 C 45 C 35 C -25 C

Dans le cas d'une spcication particulire convenue avec le client


la commande, se rfrer aux plans contractuels.

@ avant linstallation, il est ncessaire de sassurer que les conditions dinstallation


correspondent aux caractristiques du matriel livr
@ il faut notamment vrier les points suivants :
_ la temprature ambiante du condensateur doit correspondre la classe de
temprature indique sur les plans contractuels
_ laltitude dinstallation doit tre infrieure 1000 m. Dans le cas dune
spcication particulire convenue avec le client la commande, se rfrer aux
plans contractuels
_ aucune prsence dautres contraintes particulires de service (pollution,
atmosphre corrosive ou agressive, humidit leve, zone sismique, etc.)
_ la tension du rseau doit rester dans les limites admissibles indiques ci-dessous.

7. Limites de fonctionnement Les limites de longues dures


Surtension Dure maximale
1,10 Un 12 h par 24 h
1,15 Un 30 mn par 24 h
1,20 Un 5 mn
1,3 Un 1 mn

Les transitoires
Surtension de manuvre < 22 x Un.
Surintensit de manuvre < 100 x In.
Le taux dharmonique
Pour les cas standards, Ieff < 1,30 x In.
Pour les cas spciques ou dots de self anti-harmoniques (SAH), se rfrer aux
plans contractuels.

3657801AC.indd 3
8. Instructions de montage @ pour les manutentions voir la paragraphe "2. Manutention"
@ en aucun cas, des efforts doivent tre exercs sur les parties ou lments des
DB114155

condensateurs
@ sassurer que les condensateurs sont monts correctement : verticalement ou sur
"chant" (voir gure gauche)
@ sassurer quun espace de 100 mm minimum est respect entre condensateurs
@ le couple de serrage des connexions doit tre : 3 daN.m pour les bornes rsine
@ il est interdit de manipuler les condensateurs par les bornes
@ vrier que les raccordements sont dimensionns pour un courant de 1,43 x In
(raccordements non rigides, de prfrence)
@ il est impratif de tenir la batterie de condensateurs loigne des sources de
chaleur (inductances, transformateurs, etc.), an de respecter les limites de
tempratures indiques pour ce matriel dans les plans contractuels
@ si ce matriel est install lintrieur, sassurer que les locaux sont sufsamment
ventils (ou climatiss) pour permettre lvacuation des pertes dissipes indiques
sur les plans contractuels.

9. Protection Condensateurs monophass


Ces condensateurs doivent tre assembls en montage "double-toile", avec une
L1
protection de courant dsquilibre (TC + relais, voir schma gauche).
DB114154

Le choix des seuils de protection de dsquilibre doit tre valid par notre service
technique.

Condensateurs triphass (triangle) ou 3 condensateurs


monophass monts en triangle
Une protection par des fusibles HPC limiteurs est obligatoire. La dtermination du
L2 calibre des fusibles doit prendre en compte les courants denclenchement ainsi que
L les courbes de fusion-fusible et rupture cuve-condensateur.
Le calibre doit tre suprieur 1,8 In.

Dans tous les cas


Choix des appareils de manuvre
@ lappareillage de manuvre doit tre adapt la commande spcique des
batteries de condensateurs. Des appareils de manuvre sans ramorages doivent
tre utiliss. Nous contacter en cas de doute ou de problme.
@ dans le cas dutilisation de disjoncteurs vide comme appareil de manuvre,
il est ncessaire de mettre en place des protections pour limiter les surtensions en
cas de ramorage. Nous contacter en cas de doute ou de problme.
Limitation des courants
Des selfs de choc doivent tre prvues pour limiter les courants denclenchement :
@ lorsque plusieurs batteries se trouvent en parallle sur le mme jeu de barres
@ lorsque les courants denclenchement dpassent les valeurs acceptables par les
diffrents composants (condensateurs, disjoncteurs, contacteurs,)

Il est recommand dinstaller une protection de surtension dans la batterie


de condensateurs an de respecter les limites de surtensions indiques dans le
paragraphe "7. Limites de fonctionnement".

4 3657801AC.indd
Franais
10. Scurit SEULS DES PERSONNELS QUALIFIES PEUVENT INSTALLER, MANUVRER
ET MAINTENIR CES EQUIPEMENTS.

En plus des rgles gnrales concernant les interventions sur des matriels

! lectriques, les rgles spciques suivantes sont respecter :


@ aprs une dconnexion, les condensateurs ne doivent jamais tre renclenchs
avant un temps de scurit minimum de 300 secondes (cela doit inclure les
dconnexions accidentelles telles que microcoupures, pertes temporaires de la
source auxiliaire, )
@ un dispositif de scurit doit interdire laccs des personnes aux condensateurs
pendant les dix minutes qui suivent la dconnexion, ainsi que les manuvres
pendant toute la dure de lintervention
@ avant toute intervention, les bornes des condensateurs doivent tre raccordes et
maintenues la terre pendant toute sa dure
@ ne jamais reconnecter un condensateur sans avoir pralablement effectu une
mesure de capacit de celui ci et procd au remplacement de(s) lment(s)
dfectueux.

LE NON RESPECT DE CES INSTRUCTIONS, EXPOSE AU DANGER DE MORT


OU DES BLESSURES GRAVES.

11. Vrication la mise Avant la mise sous tension


@ vrier le fonctionnement de la chane de protection
sous tension @ mesurer la tension rseau
@ mesurer la capacit par phase de la batterie de condensateurs.

Aprs la mise sous tension


@ mesurer la temprature ambiante (condensateurs) aprs 12 h de fonctionnement
@ mesurer la tension rseau
@ mesurer le courant efcace absorb par la batterie de condensateurs.

12. Maintenance Vrications annuelles


@ vrier le serrage des connexions
@ vrier la propret des isolateurs
@ vrier les valeurs de U, I, C batterie et C condensateurs
@ mesurer la temprature ambiante pour les condensateurs
@ vrier le fonctionnement des chanes de protection.

Dfauts et remdes
Claquage dun condensateur triphas
Il se manifeste par la fusion dun ou plusieurs fusibles HPC. Lidentication du
condensateur dfectueux se fait par mesure de capacit (variation de capacit
> 10 % = dfectueux). Dans ce cas le remplacement immdiat du condensateur
et des trois fusibles HPC est impratif.
Claquage dun condensateur monophas
Il se manifeste par un dclenchement de protection de dsquilibre.
Lidentication se fait par une mesure de capacit de chaque condensateur
(variation de capacit > 10 % = dfectueux). Dans ce cas, le remplacement
immdiat du condensateur est impratif (un rquilibrage de la batterie est parfois
ncessaire, nous consulter).
NB : en cas de fusibles internes, on recommande aussi le remplacement des condensateurs
dont la capacit a vari de plus de 4 5 %.

13. Fin de vie Condensateurs moyenne tension


Les condensateurs de nos gammes, contiennent un liquide dilectrique non PCB.
Toutefois, sagissant dun dchet industriel, leur mise au rebut doit tre effectue par
une socit habilite.

En cas de doute ou de problme, consulter le constructeur.

3657801AC.indd 5
Important This manual denes the checks to be performed to ensure compliance with standard
conditions of use, installation and maintenance of MV capacitor banks.
Application of the terms of warranty is dependent on compliance with all these rules
(or, for specic applications, on obtaining our written agreement).

! The capacitor bank accompanied by this document must be installed and operated
by competent personnel familiar with the electrical safety rules dened in each
country.
This document in no case replaces training and accreditation in electrical
engineering and the safety procedures that must be followed by personnel working
on electrical equipment as dened in the country.

FAILURE TO COMPLY WITH THESE INSTRUCTIONS EXPOSES PERSONNEL


TO DANGER OF DEATH OR SEVERE INJURY.

1. Equipment acceptance @ our goods always travel at the cost and risks either of the recipient or the customer
depending on the negotiated Incoterm
@ we decline all liability for missing goods or damage attributable to the carrier.
Where applicable :
1 Do not reject the package.
2 Express reservations in handwriting on the slip. Check any damage.
3 In the event of damage, express detailed reservations by registered letter to the
carrier.
@ unpack the material with precaution to notice the internal damages of the package
and take picture in case of problems
@ carry out photographs and make precise explanations concerning the
encountered problems and the circumstances
@ check that there is no dielectric liquid leakage before unpacking
@ make sure that no package is missing and that the equipment has not sustained
any impact that could harm its insulation or operation.
@ check that the electrical characteristics marked on th nameplate correspond to
those dened on the order form
@ in case of nonconformity, mark the consignment note reference on the claim.

2. Handling @ unpack the equipment at the installation location


@ preferably use a lift truck
DB108739

@ avoid impacts and strain.

3. Storage @ store the equipment in a dry, ventilated room, sheltered from rain, water splashes,
chemical agents and dust
@ storage temperature: -20 C to +45 C
@ storage mean relative humidity < 95 %.

4. Warranty Our products are inspected in factory. Any alteration may compromise the warranty.

5. Nameplate Check that the characteristics of the equipment delivered are in conformity with the
characteristics indicated on the order form:
PB100046

@ Cn: Nominal capacity (mF)


@ Imp: Name of impregnation liquid
@ Qn: Reactive power (kvar)
@ Un: Nominal voltage (V)
@ Std: Reference standard
@ Ui: Insulation level (kV)
@ T: Temperature class (C)
@ Fn: Nominal frequency (Hz)
@ number of terminals
@ With/without internal discharge resistor: with without XXXXX
@ With/without internal fuses: with without XXXXX

6 3657801AC.indd
6. Installation conditions The use of capacitors at very high temperatures shortens capacitor service life.
One should therefore make sure to comply with the temperatures in the vicinity of the
capacitors set by standard IEC 60871 (except where a particular specication has
been dened by the customer, therefore, refer to the contractual drawings):

Symbol Maximum Mean over 24h Mean over 1 an Minimum

English
A 40 C 30 C 20 C -25 C
B 45 C 35 C 25 C -25 C
C 50 C 40 C 30 C -25 C
D 55 C 45 C 35 C -25 C

In the case of a particular specication agreed with the customer at ordering,


refer to the contractual drawings.

@ prior to installation, it must be ensured that the conditions of installation match the
characteristics of the equipment supplied
@ the following points should be checked in particular:
_ the capacitor ambient temperature must correspond to the temperature class
indicated on the contractual drawings
_ the installation altitude must be less than 1000 m. In the case of a particular
specication agreed with the customer at ordering, refer to the contractual drawings
_ there must be no other particular operating constraints (pollution, corrosive or
aggressive atmosphere, high humidity, seismic zone, etc.)
_ the network voltage must remain within the permissible limits shown below.

7. Operating limits Long duration limits


Overvoltage Maximum duration
1.10 Un 12 h per 24 h period
1.15 Un 30 mn per 24 h period
1.20 Un 5 mn
1.3 Un 1 mn

Transients
Operating overvoltage < 22 x Un.
Operating overcurrent < 100 x In.
Harmonic content
For standard cases, rms current < 1.30 x In.
For special cases or for devices tted with detuned reactors, refer to the contractual
drawings.

3657801AC.indd 7
8. Assembly instructions @ for handling, see the section on "2. Handling"
@ in no case, efforts must be carried out on the parts or elements of the condensers
DB114155

@ make sure that the capacitors are mounted correctly: upright or edgewise
(see diagram on the left)
@ ensure that a space of at least 100 mm is left between capacitors
@ the tightening torque of connections should be 3 daN.m for resin terminals
@ it is strongly recommended not to handle the capacitors by the terminals
@ check that the connections are sized for a current of 1.43 x In (preferably non-rigid
connections)
@ it is essential to keep the capacitor bank well away from heat sources (inductors,
transformers, etc.), so as to comply with the temperature limits for this equipment
stated on the contractual drawings
@ if this equipment is installed indoors, ensure that the premises are adequately
ventilated (or air-conditioned) to remove the dissipated losses stated on the
contractual drawings.

9. Protection Single-phase capacitors


These capacitors should be assembled in a "double-star" mounting, with unbalance
L1
current protection (CT + relay, see diagram on the left).
DB114154

The choice of unbalance protection thresholds must be validated by our technical


department.

Three-phase capacitors (delta) or 3 delta connected


single-phase capacitors
Protection by limiting HRC fuses is compulsory. When determining fuse rating,
L2 inrush currents and fuse blowing and tank/capacitor breaking curves must be taken
L into consideration. The rating should be upper than 1.8 In.

In all cases
Choice of operating devices:
@ the switchgear must be suited to the specic capacitor bank operating
mechanism. Re-strike free switchgear should be used. Contact us in case of doubts
or problems.
@ where vacuum circuit-breakers are used as switchgear, protection devices must
be installed to limit surge in the event of re-striking. Contact us in case of doubts or
problems.
Limitation of current
Surge reactors must be tted to limit inrush currents:
@ when several banks are connected in parallel on the same busbar
@ when inrush currents exceed values acceptable by the various components
(capacitors, circuit-breakers, contactors, etc.).

It is recommended to install an overvoltage protection device in order to comply with


the overvoltage limits indicated in the section on operating limits'

8 3657801AC.indd
10. Safety ONLY QUALIFIED PERSONNEL MAY INSTALL, OPERATE AND MAINTAIN
THIS EQUIPMENT.

In addition to the general rules concerning operations on electrical devices,

! the following specic rules must be complied with:


@ following disconnection, capacitors must never be re-energized before a safety

English
period of at least 300 s has elapsed (this must include accidental disconnections
such as brownouts, temporary loss of the auxiliary supply source, etc.)
@ a safety device must prevent poeple from accessing to the capacitors during the
ten minutes following disconnection, as well as switching while servicing operations
are in progress
@ before any servicing operation, the capacitor terminals must be earthed and kept
earthed while such operations are in progress
@ never reconnect a capacitor bank without rst performing a capacitance
measurement in each capacitor and replacing any defective part(s).

FAILURE TO COMPLY WITH THESE INSTRUCTIONS EXPOSES PERSONNEL


TO DANGER OF DEATH OR SEVERE INJURY.

11. Checks on energizing Before energizing


@ check operation of the protection circuits
@ measure network voltage
@ measure capacitance per phase of the capacitor bank.

After energizing
@ measure ambient temperature (capacitors) after 12 hours operation
@ measure network voltage
@ measure the rms current drawn by the capacitor bank.

12. Maintenance Annual checks


@ check connection clamping
@ check insulator cleanliness
@ check bank U, I, C and capacitor C values
@ measure ambient temperature for the capacitors
@ check operation of the protection circuits.

Faults and solutions


Disruptive breakdown of a three-phase capacitor
Revealed by blowing of one or more HRC fuses. The faulty capacitor is identied by
measuring the capacitance (capacitance uctuation greater than 10 % = faulty).
In this case, the capacitor and the three HRC fuses must be replaced immediately.
Disruptive breakdown of a single-phase capacitor
Revealed by unbalance protection tripping. The faulty capacitor is identied by
measuring the capacitance of each capacitor (capacitance uctuation greater than
10 % = faulty). In this case, the capacitor must be replaced immediately
(rebalancing of the bank may be necessary; please consult us).
Note: for internal fuses, we also recommend replacing capacitors with a capacitance uctuation
of more than 4 or 5 %.

13. End of life Medium voltage capacitors


Our capacitor ranges contain a non-PCB dielectric liquid.
However, since this constitutes industrial waste, these capacitors must be disposed
of by an accredited company.

In case of doubts or problems, consult the manufacturer.

3657801AC.indd 9
Atencin Este manual dene las vericaciones que deben efectuarse para asegurarse de que
se cumplan las condiciones estndares de utilizacin, instalacin y mantenimiento
de las bateras de condensadores de MT.
La aplicacin de las condiciones de garanta est subordinada al respeto del

! conjunto de estas normas (o, para aplicaciones especcas, a la obtencin de un


acuerdo escrito por nuestra parte).
La batera de condensadores acompaada por este documento debe ser instalada y
utilizada por un personal competente y familiarizado con las normas de seguridad
elctrica denidas en cada pas.
Este documento no sustituye en ningn caso a las formaciones y habilitaciones
elctricas as como los procedimientos de seguridad que debe seguir el personal
que acta sobre equipos elctricos tal y como se denen en el pas.
EL INCUMPLIMIENTO DE ESTAS INSTRUCCIONES CONLLEVA PELIGRO DE
MUERTE O DE HERIDAS GRAVES.

1. Recepcin del material @ nuestras mercancas viajan siempre a riesgo y ventura o bien del destinatario
o bien del cliente segn el incoterm negociado
@ nos eximimos de cualquier responsabilidad en cuanto a los incumplimientos
o a defectos imputables al transportista. En tal caso:
1 No rechazar el paquete
2 Emitir reservas manuscritas en el albarn. Vericar los daos eventuales
3 En caso de daos, emitir reservas detalladas mediante carta certicada
al transportista.
@ desembalar el material con precauciones para hacer la constatacin interno
y hacer fotos en casa de problema
@ realizar fotos y hacer explicaciones precisas de los problemas encontrados
y de sus circunstancias
@ vericar la ausencia de fuga de liquido dielctrico antes de desembalar
@ asegurarse que ningn paquete est ausente y que el material no ha sufrido
ningn golpe perjudicial para su aislamiento y funcionamiento
@ vericar que las caractersticas elctricas indicadas en el marcado de las
caractersticas corresponden a las denidas en el orden de pedido
@ en caso de no conformidad, indicar, en la reclamacin, la referencia del albarn
de entrega.

2. Manutencin @ desembalar los equipos en el lugar de instalacin


@ utilizar preferentemente una carretilla elevadora
DB108739

@ evitar los golpes y las deformaciones.

3. Almacenamiento @ almacenar los condensadores en un local seco, ventilado, protegido de la lluvia,


de las salpicaduras de agua, de los agentes qumicos y del polvo
@ temperatura de almacenamiento: -20 C a +45 C
@ humedad relativa media de almacenamiento: < 95 %.

4. Garanta Nuestros productos estn controlados en fbrica. Cualquier modicacin afecta a la


garanta.

5. Placa de caractersticas Vericar que las caractersticas del equipo suministrado cumplen las del pedido:
@ Cn: capacidad nominal (en mF)
PB100046

@ Imp: nombre del lquido de impregnacin


@ Qn: potencia reactiva (en kvar)
@ Un: tensin nominal (en V)
@ Std: norma de referencia
@ Ui: nivel de aislamiento (en kV)
@ T: clase de temperatura (en C)
@ Fn: frecuencia nominal (en Hz)
@ nmero de bornes
@ con/sin resistencia de descarga interna: con sin XXXXX
@ con/sin fusibles internos: con sin XXXXX

10 3657801AC.indd
6. Condiciones de instalacin El uso de los condensadores a temperaturas muy elevadas reduce el periodo
de vida de los mismos. Por tanto es necesario asegurarse del respeto de las
temperaturas en la cercana de los condensadores jadas por la norma CEI 60871
(excepto en el caso de una especicacin particular indicada por parte del cliente,
en cuyo caso se deber consultar los planos contractuales):

Smbolo Mximo Media en 24h Media en 1 ao Minimo


A 40 C 30 C 20 C -25 C
B 45 C 35 C 25 C -25 C
C 50 C 40 C 30 C -25 C
D 55 C 45 C 35 C -25 C

Espaol
En caso de una especicacin especial acordada con el cliente en el momento
del pedido, consultar los planos contractuales.

@ antes de la instalacin, es necesario asegurarse de que las condiciones de


instalacin correspondan a las caractersticas del material suministrado
@ se deben vericar en particular los puntos siguientes:
_ la temperatura ambiente del condensadore debe corresponder a la clase de
temperatura indicada en los planos contractuales
_ la altitud de instalacin debe ser inferior a 1000 m. En caso de una especicacin
particular acordada con el cliente en el momento del pedido,
consultar los planos contractuales
_ la ausencia de otros requisitos particulares de servicio (contaminacin, atmsfera
corrosiva o agresiva, humedad elevada, zona ssmica,)
_ la tensin de la red debe mantenerse dentro de los lmites admisibles siguientes.

7. Lmites de funcionamiento Los lmites de largas duraciones


Sobretensin Duracin mxima
1,10 Un 12 h por 24 h
1,15 Un 30 mn por 24 h
1,20 Un 5 mn
1,3 Un 1 mn

Los transitorios
Sobretensin de maniobra < 22 x Un.
Sobreintensidad de maniobra < 100 x In.
La tasa de armnicos
Para los casos estndares, Ieff < 1,30 x In.
Para los casos especcos o dotados de inductancias anti-armnicos, consultar los
planos contractuales.

3657801AC.indd 11
8. Instrucciones de montaje @ para las manutenciones, ver el prrafo "2. Manutencin"
@ en ningn caso, se debe someter a fuerzas a los condensadores
DB114155

@ asegrese de que los condensadores estn montados correctamente:


en posicin vertical o lateral (ver esquemas a la izquierda)
@ asegrese de que haya un espacio de 100 mm mnimo entre condensadores
@ el par de apriete de las conexiones debe ser: 3 daN.m para las bornes resinas
@ se desaconseja fuertemente manipular los condensadores por los bornes
@ vericar que las conexiones estn dimensionadas para una corriente de 1,43 x In
(conexiones no rgidas, preferentemente)
@ es obligatorio mantener la batera de condensadores alejada de las fuentes de
calor (inductancias, transformadores, etc.), con el n de respetar los lmites de
temperatura indicados para este material en los planos contractuales
@ si este material est instalado en interior, asegrese de que los locales estn
sucientemente ventilados (o climatizados) para permitir la evacuacin de las
prdidas disipadas indicadas en los planos contractuales.

9. Proteccin Condensadores monofsicos


Estos condensadores deben ser ensamblados en montaje "doble-estrella", con una
proteccin de corriente de desequilibrio (TI + rels, ver esquema a la izquierda).
L1
DB114154

La seleccin de los umbrales de proteccin de desequilibrio debe ser validada por


nuestro servicio tcnico.

Condensadores trifsicos (tringulo) o 3 condensadores


monofsicos montados en tringulo
Una proteccin por fusibles limitadores de alto poder de ruptura es obligatoria.
La determinacin del calibre de los fusibles debe tener en cuenta las corrientes de
L2 conexin as como las curvas de fusin-fusible y rotura cuba-condensador.
L El calibre debe ser superior a 1,8 In.

En cualquier caso
Eleccin de aparato de maniobra
@ la aparamenta de maniobra deber estar adaptada al mando especco de las
bateras de condensadores. Se deben utilizar aparatos de maniobra sin recebados.
Contactarnos en caso de duda o de problema.
@ si se utilizan interruptores automticos en vaco como aparato de maniobra, es
necesario instalar protecciones para limitar las sobretensiones en caso de
recebado. Contactarnos en caso de duda o de problema.
Limitacin de corriente
Se deben prever inductancias de choque para limitar las corrientes de conexin:
@ cuando varias bateras se encuentran en paralelo en el mismo juego de barras
@ cuando las corrientes de conexin sobrepasan los valores aceptables por los
diferentes componentes (condensadores, interruptores automticos,
contactores,).

Se recomienda instalar una proteccin de sobretensin con el n de respetar los


lmites de sobretensin indicados en el prrafo "lmites de funcionamiento".

12 3657801AC.indd
9. Seguridad NICAMENTE PERSONAS CUALIFICADAS PUEDEN INSTALAR, MANIOBRAR
Y MANTENER ESTOS EQUIPOS.

Adems de las normas generales referentes a las actuaciones sobre materiales

! elctricos, se deben cumplir las normas especcas siguientes:


@ despus de una desconexin, los condensadores no deben nunca
reengancharse antes de un tiempo de seguridad mnimo de 300 segundos
(esto debe incluir las desconexiones accidentales tales como microcortes, prdidas
provisionales de la fuente auxiliar,)
@ un dispositivo de seguridad debe prohibir el acceso de las personas a los
condensadores durante los diez minutos que siguen a la desconexin
@ antes de cualquier actuacin, los bornes de los condensadores deben ser

Espaol
conectados y mantenidos a tierra durante todo el tiempo de la actuacin
@ nunca volver a conectar un condensador sin haber realizado previamente una
medicin de capacidad en cada condensador y efectuado la sustitucin del o de los
elementos defectuosos.

EL INCUMPLIMIENTO DE ESTAS INSTRUCCIONES CONLLEVA UN PELIGRO


DE MUERTE O DE HERIDAS GRAVES.

10. Vericacin de la puesta Antes de la puesta en tensin


@ vericar el funcionamiento de las cadenas de proteccin
en tensin @ medir la tensin de la red
@ medir la capacidad par fase de la batera de condensadores.

Despus de la puesta en tensin


@ medir la temperatura ambiente (condensatores) despus de 12 horas de
funcionamiento
@ medir la tensin de la red
@ medir la corriente ecaz absorbida por la batera de condensadores.

11. Mantenimiento Vericaciones anuales


@ vericar el apriete de las conexiones
@ vericar la limpieza de los aisladores
@ vericar los valores de U, I, C batera y C condensadores
@ medir la temperatura ambiente para la batera de condensadores
@ vericar el funcionamiento de las cadenas de proteccin.

Fallos y soluciones
Fallo de un condensador trifsico
Se maniesta por la fusin de uno o varios fusibles de alto poder de ruptura.
La identicacin del condensador defectuoso se realiza por la medicin de la
capacidad (variacin de la capacidad > al 10 % = defectuoso). En este caso, es
necesario reemplazar inmediatamente el condensador y los tres fusibles de alto
poder de ruptura.
Fallo de un condensador monofsico
Se maniesta por un disparo de la proteccin de desequilibrio.
La identicacin se realiza mediante la medicin de la capacidad de cada
condensador (variacin de capacidad > al 10 % = defectuoso).
En este caso, es necesario reemplazar inmediatamente el condensador
(un nuevo equilibrado de la batera es a veces necesario, consltenos).
Nota: en caso de fusibles internos, se recomienda tambin la sustitucin de los condensadores
cuya capacidad haya variado en ms del 4 al 5 %.

12. Final de vida Condensadores de media tensin


Los condensadores de nuestras gamas contienen un lquido dielctrico libre de PCB.
Sin embargo, al tratarse de un residuo industrial, su desecho deber efectuarlo una
empresa autorizada.

En caso de duda o de problema, consultar al constructor.

3657801AC.indd 13
Notes

14 3657801AC.indd
Notes

3657801AC.indd 15
2008 - Schneider Electric - Tous droits rservs

Schneider Electric Industries SAS En raison de l'volution des normes et du matriel, les caractristiques indiques par le texte
Rectiphase et les images de ce document ne nous engagent qu'aprs conrmation par nos services.
399 rue de la Gare
74370 Pringy Ce document a t imprim sur du papier cologique.
France
Tl. : 33 (0)4 50 66 95 00 Ralisation : Schneider Electric
Fax : 33 (0)4 50 27 24 19 Publication : Sedoc
http://www.schneider-electric.com Impression : Schneider Electric

N UG 3 657 801 AC