waterflow detection valve) must be alarm line will automatically drain back
maintained at a minimum temperature Operation through the orifice which is also pro-
of 40F/4C. vided in the trim of the waterflow de-
Upon operation of the alarm check, dry tection valve.
Item 11. A single Water Motor Alarm pipe, deluge, or preaction valve to
may be connected to the alarm lines which the Model WMA-1 Water Motor The Water Motor Alarm does not have
from a maximum of three separate fire Alarm is connected, water will flow to to be reset after an operation. How-
protection systems. However, when the Water Motor and through the Inlet ever, if the alarm was silenced during
two or three alarm lines are intercon- Nozzle. As water flows through the In- operation by closing of an alarm con-
nected, each alarm line must be pro- let Nozzle, a high velocity jet is formed trol valve, the alarm control valve must
vided with a 3/4 inch (P/N 52-271-1- which impinges on the Impeller, caus- be reopened after the fire protection
001) Model WM-1 Y-Strainer and a 3/4 ing the Impeller and the Striker to ro- system is restored to service.
inch (P/N 52-403-1-005) Check Valve tate. With each rotation, the free swing-
with 3/32 inch orifice. The strainers ing Striker Ring hits the Gong and
must be located at the alarm outlet in sounds the alarm. The spent water is
the trim of each of the waterflow detec- then drained through the 1 inch outlet.
tion valves. The check valves must be
located between each strainer and the The alarm will sound as long as water
interconnection with the alarm line is flowing into the system and flowing
from another system. to the Water Motor Alarm. Water in the
TFP921 Page 3 of 4
ing onto the Sleeve. Securely tighten must be given to the owner and the fire IN NO EVENT SHALL TYCO FIRE
the Striker Shaft Bearing using a pair department, central control station, or PRODUCTS BE LIABLE, IN CON-
of channel locks on the 1-1/2 inch (38 other signal station to which the TRACT, TORT, STRICT LIABILITY OR
mm) hex end. alarms are connected. UNDER ANY OTHER LEGAL THE-
Step 11. Spin the Striker by hand and If the alarm was silenced during opera- ORY, FOR INCIDENTAL, INDIRECT,
verify that it spins freely (without any tion, the alarm control valve must be SPECIAL OR CONSEQUENTIAL
sign of binding). If not, make the nec- reopened immediately after the fire DAMAGES, INCLUDING BUT NOT
essary adjustments. protection system is restored to serv- LIMITED TO LABOR CHARGES, RE-
ice. GARDLESS OF WHETHER TYCO
Step 12. Install the gong and securely FIRE PRODUCTS WAS INFORMED
tighten the Cap Nut. The identification The Model WMA-1 Water Motor Alarm ABOUT THE POSSIBILITY OF SUCH
sign lettering must be orientated hori- must be maintained and serviced in DAMAGES, AND IN NO EVENT
zontally, accordance with the following instruc-
SHALL TYCO FIRE PRODUCTS LI-
Step 13. Test the Water Motor Alarm tions:
ABILITY EXCEED AN AMOUNT
by opening the alarm test valve in the Step 1. The Model WMA-1 Water Mo- EQUAL TO THE SALES PRICE.
trim of the water flow detection valve. tor Alarm does not require any regu-
The alarm must be clear and steady. If larly scheduled maintenance. Rotating THE FOREGOING WARRANTY IS
not, make the necessary adjustments. parts do not require lubrication. It is MADE IN LIEU OF ANY AND ALL
recommended, however, that fire OTHER WARRANTIES EXPRESS
NOTE alarms be periodically operated, i.e., OR IMPLIED, INCLUDING WARRAN-
Testing of the Water Motor Alarm may inspected, to verify that they generate TIES OF MERCHANTABILITY AND
result in operation of other associated a clear and steady sound. Any impair- FITNESS FOR A PARTICULAR PUR-
alarms. Consequently, notification ment must be be immediately cor- POSE.
must be given to the owner and the fire rected.
department, central control station, or
other signal station to which the
Step 2. The inspection should be
made quarterly or more frequently, as
Ordering
alarms are connected. may be necessary in the case of loca-
tions subject to vandalism. The Y-
Information
Strainer and Sump are to be cleaned
Care and out after each operation of the Water
Orders for the WMA-1, Optional Drain
Trim, and replacement parts must in-
Motor Alarm and after the alarm line
Maintenance piping has been drained.
clude the description and Part Number
(P/N).
The following procedures and inspec- The Complete Model WMA-1 Alarm
tions should be performed as indi-
cated, in addition to any specific re-
Limited Assembly includes the Model WMA-1
Water Motor Alarm, Model WM-1
quirements of the NFPA, and any
impairment must be immediately cor-
Warranty Strainer, and Standard Inlet Trim.
WMA-1 Alarm Assemblies:
rected. Products manufactured by Tyco Fire
Specify: Model WMA-1 Alarm Assem-
The owner is responsible for the in- Products are warranted solely to the
bly with Red Finish Gong,
spection, testing, and maintenance of original Buyer for ten (10) years P/N 52-630-1-001.
their fire protection system and de- against defects in material and work-
vices in compliance with this docu- manship when paid for and properly or
ment, as well as with the applicable installed and maintained under normal Specify: Model WMA-1 Alarm Assem-
standards of the National Fire Protec- use and service. This warranty will ex- bly with Aluminum Finish Gong,
tion Association (e.g., NFPA 25), in pire ten (10) years from date of ship- P/N 52-630-2-001
addition to the standards of any ment by Tyco Fire Products. No war- Optional Drain Trim:
authority having jurisdiction. The in- ranty is given for products or
stalling contractor or product manufac- components manufactured by compa- Specify: Optional Drain Trim for Model
turer should be contacted relative to nies not affiliated by ownership with WMA-1 Water Motor Alarm,
any questions. Tyco Fire Products or for products and P/N 52-630-2-002.
It is recommended that automatic components which have been subject Separately Ordered Alarm Control
sprinkler systems be inspected, to misuse, improper installation, corro- Valve:
tested, and maintained by a qualified sion, or which have not been installed, Specify: UL/FM 3/4 Inch Ball Valve,
Inspection Service in accordance with maintained, modified or repaired in ac- P/N 92-300-1-006.
local requirements and/or national cordance with applicable Standards of Separately Ordered Parts for
codes. the National Fire Protection Associa- Multiple Systems:
tion, and/or the standards of any other Specify: Model WM-1 Y-Strainer, P/N
NOTES Authorities Having Jurisdiction. Mate- 52-271-1-001. (1 required for two sys-
Before closing a fire protection system rials found by Tyco Fire Products to be tem, 2 required for 3 systems.)
main control valve for maintenance defective shall be either repaired or
replaced, at Tyco Fire Products sole Specify: 3/4 Inch Check valve with
work on the fire protection system that 3/32 Inch Orifice, P/N 52-403-1-005 (2
it controls, permission to shut down option. Tyco Fire Products neither as-
sumes, nor authorizes any person to required for two system, 3 required for
the affected fire protection systems 3 systems.)
must first be obtained from the proper assume for it, any other obligation in
authorities and all personnel who may connection with the sale of products or Replacement Parts for
be affected by this decision must be parts of products. Tyco Fire Products Water Motor Alarm:
notified. shall not be responsible for sprinkler (Specify description) for use with
system design errors or inaccurate or Model WMA-1 Water Motor Alarm,
Testing of the Water Motor Alarm may P/N (see Figure 1).
result in operation of other associated incomplete information supplied by
alarms. Consequently, notification Buyer or Buyers representatives.
TYCO FIRE PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446