Setting Calculation

India Mylapor Substation 230kV Inter


Project
Connection Line Settings Calculation

Relay Type PCS-924, PCS-9611

Document Version R1.00

SUBQ Code SUBQ00383520

Date 2014-1-16

NR Electric Co., Ltd.


Setting Calculation

Table of Contents

Table of Contents ................................................................................ i


1 Primitive Parameters ...................................................................... 1
2 Settings Calculation........................................................................ 2
3 Settings List .................................................................................... 4
3.1 PCS-924 Settings (Mylapor) ............................................................................4
3.2 PCS-9611 Settings (Mylapor) ..........................................................................4

4 Manual Version History .................................................................. 7

NR Electric Co., Ltd. i


Setting Calculation

ii NR Electric Co., Ltd.


Setting Calculation

1 Primitive Parameters

LINE NAME 230kV inter-connection line


SUBSTATION NAME 230kV Mylapor
Terminal Mylapor
Sl. SYSTEM PARTICULARS
No Line Parameters Details
1 Rated Line Voltage in kV 230kV
2 Line Length in kms 0.17 km
3 Positive sequence impedance of line Ohm/km 0.035+ j 0.120 Ohm/km
4 Zero sequence of line in Ohm/km 0.0239+j 0.0959 Ohm/km
Mutual Zero sequence impedance in Ohm/km for parallel
5 0
lines
6 Maximum load current in normal operating condition 570A
7 Minimum power factor 0.95
8 Minimum Voltage in kV during maximum power transfer 95% of the rated voltage
9 CT ratio Adopted 800/1A
10 VT ratio 230kV/110V

Equivalent Impedance of the system 230kV Mylapor

The short-circuit current should be calculated from the system to 230kV busbar at 230kV Mylapor
substation.

Operation mode 3-phase fault 1-phase fault

Maximum operation mode (MVA) 8830 7858

Equivalent Impedance of the system 230kV INTER CONNECTION

The short-circuit current should be calculated from the system to 230kV busbar at 230kV Mylapor
substation (old substation, via Bay206).

Operation mode 3-phase fault 1-phase fault

Maximum operation mode (MVA) 8922 7926

NR Electric Co., Ltd. 1


Setting Calculation

2 Settings Calculation
a) Current Differential Protection

The pick up current setting of current differential protection takes 1.2 times of maximum load
current, current differential protection will not blocked by CT circuit failure.

The minimum differential current for an internal fault can approximately takes 7858MVA, the
sensitivity coefficient for the pick up current setting is:

It can meet the sensitivity requirement.

b) Phase overcurrent protection

Only one stage of phase overcurrent protection is configured, the current setting should be larger
than the maximum load current, the time delay takes 0.8s, phase overcurrent protection is
controlled by voltage controlled element and not controlled by direction element.

c) Earth fault protection

Only one stage of earth fault protection is configured, the primary current takes 300A, the time
delay takes 1.8s, earth fault protection is not controlled by direction element.

d) SOTF protection

Phase SOTF overcurrent protection is enabled.

The current setting can be set the same as that of phase overcurrent protection, the time delay
takes 0.1s.

2 NR Electric Co., Ltd.


Setting Calculation

Zero-sequence SOTF overcurrent protection is enabled.

The zero-sequence current setting can be set the same as that of earth fault protection, the time
delay takes 0.1s.

e) 50BF protection

The current setting should be larger than the maximum load current, i.e.:

f) VT/CT circuit supervision

NR Electric Co., Ltd. 3


Setting Calculation

3 Settings List

Note!

All the settings are the recommended settings, for system parameters are not available, all
the settings have not been check.

For other settings that not listed in this section, please set them according to the actual
condition on site.

3.1 PCS-924 Settings (Mylapor)

System settings
No. Item Range Value
1 Active_Grp [1 - 10] 1
2 Opt_SysFreq [0 - 1] Hz 50
3 PrimaryEquip_Name [xxxx - xxxx] Mylapor
4 CT1.I1n [100 - 65500] A 800
5 CT2.I1n [100 - 65500] A 800
6 CT3.I1n [100 - 65500] A 800
7 I1n_Base [100 - 65500] A 800
8 I2n_Base [1.000 - 5.000] A 1
Diff settings
No. Item Range Value
1 87S.I_Biased [0.05 - 30] A 0.855
2 87S.I_Alm [0.05 - 30] A 0.1
3 87S.Slope [0.3 - 1.0] 0.75
4 87S.En [0 - 1] 1
5 87S.En_CTS_Blk [0 - 1] 0
Trip logic settings
No. Item Range Value
1 t_Dwell_Trp [0 - 10] s 0.04
2 t_Dwell_TT [0 - 10] s 0.04

3.2 PCS-9611 Settings (Mylapor)

System settings
No. Item Range Value
1 Active_Grp [1 - 10] 1
2 Opt_SysFreq [0 - 1] 50
3 PrimaryEquip_Name [xxxx - xxxx] Mylapor

4 NR Electric Co., Ltd.


Setting Calculation

4 Prot.I1n [0 - 20000] A 800


5 Prot.I2n [1 - 5] A 1
6 Measmt.I1n [0 - 20000] A
7 Measmt.I2n [1 - 5] A
8 Neu1.I1n [0 - 20000] A
9 Neu1.I2n [1 - 5] A
10 Prot.U1n [0.1 - 500] KV 230
11 Prot.U2n [100 - 200] V 110
12 Syn.U1n [0.1 - 500] KV
13 Syn.U2n [10 - 200] V
14 Opt_3I0 [0 - 1] 1
15 Opt_PwrDir [0 - 3] 0
OC settings
No. Item Range Value
1 50/51P.U2_VCE [2 - 70] V 4.4
2 50/51P.Upp_VCE [2 - 120] V 77
3 50/51P.RCA [-180 - 179] deg -45
4 50/51P.En_VTS_Blk [0 - 1] 0
5 50/51P.K_Hm2 [0.05 - 1.0] 0.2
6 50/51P.I_Rls_HmBlk [0.05 - 150.0] 30
7 50/51P.Opt_Hm_Blk [1 - 3] 1
8 50/51P1.I_Set [0.05 - 150] A 1.069
9 50/51P1.t_Op [0 - 100] s 0.8
10 50/51P1.En_VCE [0 - 1] 1
11 50/51P1.Opt_Dir [0 - 2] 0
12 50/51P1.En_Hm_Blk [0 - 1] 0
13 50/51P1.En [0 - 1] 1
14 50/51P1.OutMap [0 - 1048575] 00700
EF1 settings
No. Item Range Value
1 50/51G.RCA [-180 - 179] deg -135
2 50/51G.En_VTS_Blk [0 - 1] 0
3 50/51G.K_Hm2 [0.05 - 1.0] 0.2
4 50/51G.3I0_Rls_HmBlk [0.05 - 150.0] 30
5 50/51G1.3I0_Set [0.05 - 150] A 0.375
6 50/51G1.t_Op [0 - 100] s 1.8
7 50/51G1.Opt_Dir [0 - 2] 0
8 50/51G1.En_Hm_Blk [0 - 1] 0
9 50/51G1.En [0 - 1] 1
10 50/51G1.OutMap [0 - 1048575] 00700
SOTF settings

NR Electric Co., Ltd. 5


Setting Calculation

No. Item Range Value


1 50BF.I_Set [0.05 - 25] A 0.855
2 50BF.t_Op [0 - 100] s 0.3
3 50BF.t_ReTrp [0 - 100] s 0.05
4 50BF.Opt_LogicMode [1 - 4] 4
5 50BF.En [0 - 1] 1
6 50BF.En_ReTrp [0 - 1] 0
7 50BF.OutMap [0 - 1048575] 03800
8 50BF.OutMap_ReTrp [0 - 1048575] 00000
SOTF settings
No. Item Range Value
1 SOTF.t_En [0 - 100] s 0.4
2 SOTF.Opt_Mode [0 - 1] 0
3 50PSOTF.I_Set [0.05 - 150] A 1.069
4 50PSOTF.t_Op [0 - 100] s 0.1
5 50PSOTF.En [0 - 1] 1
6 50PSOTF.OutMap [0 - 1048575] 00700
7 50GSOTF.3I0_Set [0.05 - 150] A 0.375
8 50GSOTF.t_Op [0 - 100] s 0.1
9 50GSOTF.En [0 - 1] 1
10 50GSOTF.OutMap [0 - 1048575] 00700
Superv settings
No. Item Range Value
1 CTS.3I0_Set [0.05 - 150] A 0.08
2 CTS.3U0_Set [0.1 - 120] V 4.4
3 CTS.En [0 - 1] 1
4 VTS.I_Set [0.05 - 150] A 0.784
5 VTS.I2_Set [0.05 - 150] A 0.1
6 VTS.En [0 - 1] 1
7 VTS.En_SynVT [0 - 1] 0

6 NR Electric Co., Ltd.


Setting Calculation

4 Manual Version History


In the latest version of the setting calculation, several descriptions on existing values have been
modified.

Setting calculation version and modification history records

Setting Calculation Corresponding


Version Chinese Date Description of change
Source New Version
R1.00 R1.01 2014-1-16 Form the original manual.