(Wind Speed =39.00 m/s. Terrain Category-22 Net Bearing Capaeity of Soil=8.00 Mt/m.1
TYPE OF STRUCTURE :
The structure of the transmission pole is primarily a thin wall, slender, single column structure made of polygonal closed
section of reducing diameter from bottom to top . The pole is consisting of a number of segments along its length and
joined together with slip jointing method . Closed polygonal section is formed by mechanical process from high tensile
grade of steel sheets of required thickness and continuous weld along the length only with no circumferential welded
joints. Circumferential weld is only deposited at its junction with base plate..
The pole is fixed with HD. Bolts on RCC. foundation as per design.
The transmission arrangement is primarily symmetric about the pole axis.
DESIGN BASIS :
The structure of the pole is analysed and designed in two parts, 'Part-A' for steel superstructure and 'Part-B' for the RCC.
foundation. The superstructure has been analysed with the dead load and lateral load due to wind. The dead weight of the
entire structure is too small as compared to its height, thus total seismic force is much less than the forces developed due
to wind. The foundation has been designed considering limit state method on the basis of soil data supplied by the client
and other loading data obtained from the analysis of the the superstructure.
The design calculation has been carried out based on the basic philosophy, that seismic and wind do not occur at the
same point of time. Thus wind being the governing load, has been considered ignoring the negligible seismic load for the
design calculation of the pole and its foundation.
The following code of practices were considered for the design calculations :-
1) IS-1904-1986
2) IS-11233-1985
3) IS-875-1987, Part-III
4) IS-456-2000
5) IS-10178
PART-B
DESIGN PARAMETERS :
N.B. Design Parameters specified in a), e) and g) taken from the general soil test report but suggested to
verify at actual from the specific sites.
1. Foundation Details:
i) Type of Foundation = Shallow Foundation with Square Footing and Square Pedestal
ii) Depth of Foundation below FGL. = 5000.00 mm
iii) Difference between FGL. and top of pedestal . = 300.00 mm
iv) Dimensions of Foundation Base:-
a) Width of the square base 8350.00 mm
b) Depth of base slab 800.00 mm
v) Base Reinforcements =
a) Bottom Bar= 25 mm dia tor bar Both 150 mm c/c
ways @
b) Top Bar= 16 mm dia tor bar Both 150 mm c/c
ways @
2. Pedestal Details:
Type of Foundation = Shallow Foundation with Square Footing and Square Pedestal
a) Total Horizontal shear forces at base of mast, Fx = 28.96 Mt. (Lateral Load)
b) Total Vertical load at base of mast , Fy = 12.31 Mt. (Dead Load+Lateral Load)
c) Total Moment (on vertical plane, at base of mast) , Mz = 637.06 Mtm. (DL+Lateral Load)
NB: Data Taken from analysis Results (Considering Dynamic effect of Wind):
Foundation Diagram
(Db-Dp)/2 Dp (Db-Dp)/2
PLAN
h1 GL.
F.G.L.
N.G.L. h
h2
D
(Db-Dp)/2 Dp (Db-Dp)/2
SECTION
Design Considerations:
NB:
1. THERE IS NO UPLIFT FORCE ACTING ON THE FOUNDATION, THUS UPLIFT CHECK IS NOT REQUIRE
2. FROM STABILITY POINT OF VIEW, FOUNDATION FOR SUCH SINGLE COLUM STRUCTURE/SYSTEM NEED TO BE SO
DESIGNED THAT THE GROSS PRESSURE BELOW THE FOOTING SHALL BE ALWAYS (+)IVE. IN MOST OF THE CASES
THUS SBC VALUE ONLY DOES NOT GOVERN THE FOUNDATION GEOMETRY, WHEREAS THE STABILITY REQUIREMENT
PRIMARILY GOVERNS.
B1/a/iv : DESIGN FOR FOUNDATION REINFORCEMENT :
NB: RCC. Section of footing is exposed to net pressure thus designed with net pressure accordingly.
Depth of footing slab, D = 800.0 mm
Clear Cover to Main Reinforcement of Foundation, c = 50.0 mm
Assumed dia of Foundation main Reinforcement , d1= 25.0 mm
Min. Effective depth of slab at the junction of pedestal with the base, de= 712.5 mm
GL.
p net min = p1 p2
2
-5.71 Mt/m p net max =
10.58 Mt/m2
x y
a Dp a
Dp+de
Db
s= 1712.50 mm
Design Shear Force, Vu1 = 27.651197 Mt./m
276511.97 N/m
Effective area at critical section, As1 = 712500.00 mm
Shear Stress, v 1 = 0.39 N/mm
c1 = 0.49 N/mm
> 0.39 , Hence O.K.
B1/a/v/ii: Two way shear :
4
Sectional moment of inertia for pedestal = Ip = 1.33 m
y p(max) = 1.00 m
3
zp = 1.33 m
2
Cross sectional area of pedestal, Ap = 4.00 m
fck = Characteristic strength of concrete= 20 Mpa
Axial force, Pp = 57.31 Mt
Moment at pedestal bottom, Mp = 767.39 Mtm
Maximum stress in pedestal, p max1 = 589.87 Mt/m (Comp)
Minimum stress in pedestal, p min1 = -561.22 Mt/m (Ten)
Pp
Mp
p min1
p max1
b1 b2
b2= 1.025 m
b1= 0.975 m
B1/b/i : DESIGN FOR PEDESTAL REINFORCEMENT: