Vous êtes sur la page 1sur 37

Main-Remote Installation Products Overview Page 1 of 37

DESCRIPTION 16/1551-LZA 701 0003 Uen A

Main-Remote Installation Products Overview


Copyright

Copyright Ericsson AB 2009. All rights reserved.

Disclaimer

No part of this document may be reproduced in any form without the written permission of the
copyright owner.

The contents of this document are subject to revision without notice due to continued progress in
methodology, design and manufacturing. Ericsson shall have no liability for any error or damage of
any kind resulting from the use of this document.

Contents
1 Introduction

2 Main-Remote RBS Systems


2.1 WCDMA RBS Systems
2.2 GSM RBS Systems
2.3 External Units

3 Power Systems
3.1 PBC-02 Systems
3.2 SSC-01

4 Site Transmission
4.1 TMR 9302
4.2 MPH

5 Cables
5.1 Optical Cables
5.2 Power Cables
5.3 Jumper Cables
5.4 TG Synchronization Cables for GMS
5.5 RET Control Cables
5.6 Grounding Kit Cables

6 Installation Materials
6.1 Antenna Support Products
6.2 Cable Support and Accessories
6.3 Tools and Instruments
6.4 Miscellaneous Products

7 Type Sites
7.1 Type Site 1 - Outdoor Greenfield Site
7.2 Type Site 2 - Greenfield Shelter Site
7.3 Type Site 3 - Rooftop Indoor Site
7.4 Type Site 4 - Rooftop Outdoor Site

file://C:\Users\Dell\AppData\Local\Temp\ALEX_TMP\1027\alex0372.htm 6/21/2013
Main-Remote Installation Products Overview Page 2 of 37

7.5 Type Site 5 - Rooftop Shelter Site


7.6 Type Site 6 - Rooftop Outdoor Site

8 Terms and Abbreviations

file://C:\Users\Dell\AppData\Local\Temp\ALEX_TMP\1027\alex0372.htm 6/21/2013
Main-Remote Installation Products Overview Page 3 of 37

1 Introduction
This document is an overview of products for a main-remote site.

The products can be used, for example, at the following site types:

Greenfield
Rooftop
Indoor/In-building

For further information see documents;

Installation Material Overview, EN/LZT 751 0049


Implementation Team Products Overview, EN/LZT 751 0065
Optical Interface Link, 15/1531-LZA 701 0003

2 Main-Remote RBS Systems


This section describes the units in WCDMA and GSM Main-Remote RBS systems.

The main-remote system contains a Main Unit (MU) and one or more Remote Radio Units (RRU).
The MU supplies power to the system and the RRUs contains the radio equipment. Each RRU is
installed near the antenna and connected directly to the MU by an Optical Interface Link (OIL)
cable. The short distance between the RRU and the antenna reduces feeder loss, thereby lowering
power consumption.

2.1 WCDMA RBS Systems

2.1.1 RBS 3518 Main Unit

file://C:\Users\Dell\AppData\Local\Temp\ALEX_TMP\1027\alex0372.htm 6/21/2013
Main-Remote Installation Products Overview Page 4 of 37

Figure 1 RBS 3518 Main Unit

Table 1 RBS 3518 Main Unit Specifications

Dimensions (WDH) 483102381 mm


Weight 33 kg
Operating temperature -33C to +50C
Input power options -48 V DC
100250 V AC
Typical power consumption 0.10 kW (DC)
0.11 kW (AC)
Optical interface LC
DC power interface Screw terminal
AC power interface Screw terminal
Installation options Floor, wall, pole, or tower
Capacity Up to six RRUs

file://C:\Users\Dell\AppData\Local\Temp\ALEX_TMP\1027\alex0372.htm 6/21/2013
Main-Remote Installation Products Overview Page 5 of 37

2.1.2 RBS 3418 Main Unit, Indoor

Note that the RBS 3418 main unit also is a part of the RBS 3018.

Figure 2 RBS 3418 Main Unit

Table 2 RBS 3418 Main Unit Specifications

Dimensions (WDH) 483271177 mm


Max. weight 20.5 kg
Operating temperature +5C to +50C
Input power options -48 V DC
+24 V DC
100250 V AC
Typical power consumption 0.10 kW (-48 V DC)
0.12 kW (+48 V DC)
0.12 kW (+24 V AC)
Optical interface LC
DC power interface Screw terminal
AC power interface Screw terminal
Installation options 19-inch rack
Capacity Up to six RRUs
Space requirement in 19-inch rack 4-5 U

2.1.3 RRU22 20 W

file://C:\Users\Dell\AppData\Local\Temp\ALEX_TMP\1027\alex0372.htm 6/21/2013
Main-Remote Installation Products Overview Page 6 of 37

Figure 3 RRU22 20 W

Table 3 RRU22 20 W Specifications

Dimensions (WDH) 365286470 mm


Max. weight 29.2 kg
Operating temperature -33C to +50C
Input power options -48 V DC
100250 V AC (with external PSU)
Typical power consumption 0.14 kW (DC)
1.09 kW (AC)
Optical interface ODC
DC power interface ODC
AC power interface Screw terminal in external PSU
RF interface 7-16
RET interface 4-pin N12
Installation options Wall, pole, or tower
Capacity One carrier 20 W or
Two carriers 10 W

2.1.4 RRU22 40 W

file://C:\Users\Dell\AppData\Local\Temp\ALEX_TMP\1027\alex0372.htm 6/21/2013
Main-Remote Installation Products Overview Page 7 of 37

Figure 4 RRU22 40 W

Table 4 RRU22 40 W Specifications

Dimensions (WDH) 365292571 mm


Max. weight 33.6 kg
Operating temperature -33C to +50C
Input power options -48 V DC
100250 V AC
Typical power consumption 0.23 kW (DC)
0.26 kW (AC)
Optical interface ODC
DC power interface ODC
AC power interface Screw terminal in external PSU
RF interface 7-16
RET interface 7-16 (RF interface)
Installation options Wall, pole, or tower
Capacity One carrier 40 W or
Two carriers 20 W

2.1.5 RRUW-01 60 W

file://C:\Users\Dell\AppData\Local\Temp\ALEX_TMP\1027\alex0372.htm 6/21/2013
Main-Remote Installation Products Overview Page 8 of 37

Figure 5 RRUW-01 60 W

Table 5 Remote Radio Unit Wideband (RRUW) -01 60 W Specifications

Dimensions (WDH) 383169636 mm


Weight 20 kg
Operating temperature -33C to +50C
Input power -48 V DC
100250 V AC
Typical power consumption 0.22 kW
Optical interface LC
DC power interface Screw terminal
AC power interface Screw terminal
RF interface 7-16
RET interface 8-pole DIN
Installation options Wall, pole, or tower
Capacity One carrier 60 W or
Two carriers 30 W

file://C:\Users\Dell\AppData\Local\Temp\ALEX_TMP\1027\alex0372.htm 6/21/2013
Main-Remote Installation Products Overview Page 9 of 37

2.2 GSM RBS Systems

2.2.1 RBS 2111 Main Unit, MU 12

Figure 6 RBS 2111 Main Unit

Table 6 RBS 2111 Main Unit Specifications

Dimensions (WDH) 460143373 mm


Weight 6.8 kg
Operating temperature -33 C to +50 C
Input power options -48 V DC
100250 V AC (with external PSU)
Typical power consumption 0.01 kW
0.09 kW with heater
Optical interface SC
DC power interface Screw terminal
AC power interface Screw terminal
Installation options Wall, pole, tower, or 19-inch rack
Capacity Up to three RRUs
Space requirement in a 19-inch rack 2U

2.2.2 RRUN

file://C:\Users\Dell\AppData\Local\Temp\ALEX_TMP\1027\alex0372.htm 6/21/2013
Main-Remote Installation Products Overview Page 10 of 37

Figure 7 RRUN

Table 7 RRUN Specifications

Dimensions (WDH) 372239433 mm


Weight 16.5 kg
Operating temperature -33 C to +50 C
Input power -48 V DC
100250 V AC (with external PSU)
Typical power consumption 0.16 kW (GSM 800/900)
0.18 kW (GSM 1800/1900)
Optical interface SC
DC power interface Screw terminal
AC power interface Screw terminal in external PSU
RF interface N-type
Installation options Wall, pole, or tower
Capacity 2 Transceivers (TRX)

file://C:\Users\Dell\AppData\Local\Temp\ALEX_TMP\1027\alex0372.htm 6/21/2013
Main-Remote Installation Products Overview Page 11 of 37

2.3 External Units

2.3.1 RETU

Figure 8 RETU

Table 8 Remote Electrical Tilt Unit (RETU) Specifications

Dimensions (WDH) 5060178 (KRY 121 63/1)


5958251 (KRY 121 67/x)
Antenna connection interface Screw terminal
RRU interface 4 pole connector
Installation On the antenna
Description Adjusts electrical down tilt in an antenna by
mechanically turning the antenna phase shifters

2.3.2 PSU

file://C:\Users\Dell\AppData\Local\Temp\ALEX_TMP\1027\alex0372.htm 6/21/2013
Main-Remote Installation Products Overview Page 12 of 37

Figure 9 PSU

Table 9 Power Supply Unit (PSU) Specifications

Specification PSU (RRU PSU (RRUW-01) PSU-AC-1 (RRUN)


22)
Application RRU22 RRUW-01 RRUN
Dimensions 18068330 230390140 mm 25532070 mm
(WDH) mm
Weight 3.8 kg 3.8 kg 5.6 kg
Operating -33 C to -33 C to +50 C -33 C to +50 C
temperature +50 C
Input power 100250 V 100250 V AC 100250 V AC
AC
Output power -48 V DC -48 V DC -48 V DC
AC interface ODC (AC) ODC (AC) Screw terminal
DC interface ODC Open end Screw terminal
Description Converts incoming AC power to DC power

2.3.3 ACCU

Figure 10 ACCU

Table 10 Alternating Current Connection Unit (ACCU) Specifications

Application RRUW-01 and RRU22 with external PSU


Dimensions 110180130 mm
(WDH)
Max. weight 1.6 kg
Operating -33 C to +50 C
temperature
Input/output power 100250 V AC
AC input interface Screw terminal
AC output interface ODC (AC)
Description Distributes over current protected power to the PSU; required in outdoor
sites with PSU

file://C:\Users\Dell\AppData\Local\Temp\ALEX_TMP\1027\alex0372.htm 6/21/2013
Main-Remote Installation Products Overview Page 13 of 37

3 Power Systems

3.1 PBC-02 Systems

Figure 11 Wall mounted PBC-02 Main Unit, Battery Unit (BU) 2, and Pole-Mounted PBC-02 Main
Unit with PBC-02 Battery Unit (Double Unit) 1

Table 11 Power and Battery Cabinet-02 (PBC-02) Unit Specifications

Specification PBC-02 MU PBC-02 BU2 PBC-02 MU + PBC-02 MU +


BU1 (Double BU1 + BU2
Unit)
Dimensions 450220570 450220570 450400570 450400570 +
(WDH mm) 450220570
Max. weight 54 kg incl. 65 kg incl. 119 kg incl. 184 kg incl.
battery battery battery battery
Operating temperature -33 C to +45 C
Input Power 90275 V AC
Output voltage -48 V DC
Max. power consumption 1.35 kW 1.35 kW
Battery capacity 13 Ah 26 or 39 Ah 26 or 39 Ah 52 or 65 Ah
Cooling Convection
Installation options Wall or pole

file://C:\Users\Dell\AppData\Local\Temp\ALEX_TMP\1027\alex0372.htm 6/21/2013
Main-Remote Installation Products Overview Page 14 of 37

3.2 SSC-01

The Site Support Cabinet (SSC) is an outdoor cabinet that supports both the RBS 2111 MU and the
RBS 3418 MU. It can hold all power equipment, batteries, up to two MUs, and includes space for
transmission equipment. The SSC is a flexible product that can be ordered according to the needs
of customer. See document SSC-01 Technical Product Description, 11/1551-LZA 701 0003, for
more information.

Figure 12 SSC-01

Table 12 SSC-01 Specifications

Dimensions (WDH) 6508701400 mm


Max. weight 515 kg
Operation temperature -33 C to +50 C
Output voltage -48 V DC
Typical power consumption at ambient temperature +25 C 1.6 TW
Batteries Max. 200 Ah
Cooling Air condition
Space Up to 13 U
Capacity GSM 34 or
WCDMA 61 or
GSM 32 + WCDMA 31

file://C:\Users\Dell\AppData\Local\Temp\ALEX_TMP\1027\alex0372.htm 6/21/2013
Main-Remote Installation Products Overview Page 15 of 37

4 Site Transmission

4.1 TMR 9302

Figure 13 TMR 9302

Table 13 Transmission Rack (TMR) 9302 Specifications

Dimensions (WDH) 445470740 mm


Weight 27 kg (excluding microwave equipment)
Space 6U, holds up to AMM 6p
Operating temperature -25 C to +55 C
Input power -48 V DC
100250 V AC (with external PSU)
Max. power consumption 420 W
Cooling Fans
Installation options Wall or pole

4.2 MPH

file://C:\Users\Dell\AppData\Local\Temp\ALEX_TMP\1027\alex0372.htm 6/21/2013
Main-Remote Installation Products Overview Page 16 of 37

Figure 14 MPH

Table 14 Modem Protective Housing (MPH) Specifications

Dimensions (WDH) 340135620 mm


Weight 12 kg (excluding microwave equipment)
Space Can be used to house an AMM 1p or AMM 2p
Operating temperature -25 C to +50 C (-25 C to +55 C for 2 MMU2)
Input power options -48 V DC
+24 V DC
100250 V AC (with external PSU)
Max. power consumption 200 W
Cooling Cooling fins
Installation options Wall or pole

5 Cables

5.1 Optical Cables

file://C:\Users\Dell\AppData\Local\Temp\ALEX_TMP\1027\alex0372.htm 6/21/2013
Main-Remote Installation Products Overview Page 17 of 37

Figure 15 Optical Cable Connector Types without Protective Covers

Table 15 Optical Cable Specifications

Application Connector Length (m) Product Number(1)


RRU22 to LCODC 1, 5, 10, 20, 50, 70, 80, TSR 899 113/L
RBS 3018, 100, 150, 200, 250, 350,
RBS 3418, or 500
RBS 3518
RRUW-01 to LCLC 5, 10, 20, 50, 70, 100, RPM 253 3577/L
RBS 3018, 150, 250
RBS 3418, or
RBS 3518
RRUN to SCSC 20, 50, 100, 500 TSR 899 088/L
RBS 2111
Adapter when replacing LCODC (f) 1 RPM 253 4388/1000
RRU22 with RRUW-01
Extension cable RRU22 ODCODC (f) 10, 25 TSR 899 145/L
Cascade RRUW-01 to LCLC 2, 5, 10, 20, 100 RPM 253 2895/L
RRUW-01
Cascade RRUW-01 to LCODC 2, 5, 10, 20 RPM 253 2788/L
RRU22
(1) L = defined length of cable.

5.2 Power Cables

Figure 16 Power Cable Connectors Without Protective Covers

file://C:\Users\Dell\AppData\Local\Temp\ALEX_TMP\1027\alex0372.htm 6/21/2013
Main-Remote Installation Products Overview Page 18 of 37

DC Power Cables

The cables dimensions are 26 mm2 for cable lengths up to 60 m and


210 mm2 for cable lengths up to 100 m.

Table 16 DC Power Cable Specifications

Application Connector Length (m) Product Number(1)


RRU22 ODC to open end 0.5, 10, 25, 50, RPM 119 0261/L (2)
80, 100
RRUW-01 Open end to open 100, 300 TFL 492 325/L
RRUN end (210 mm cable drum)
RRUW-01 Open end to open 100, 200, 500 TFL 492 324/L
RRUN end (26 mm cable drum)
Adapter when replacing RRU22 Open end to ODC 1.5 RPM 919 662/01500
with RRUW-01 (f)
(1) L = defined length of cable.
(2) 26 mm2 up to 60 m, 210 mm2 up to 100 m

AC Power Cables

Table 17 AC Power Cable Specifications

Application Connector Length (m) Product Number(1)


PSU (indoor Open-end to 0.5, 5 RPM 119 0474/L
RRU22/RRUW-01) ODC
ACCU (outdoor Open end to 0.5, 10, 25, 50, RPM 119 0552/L
(RRU22/RRUW-01) open end 100
PSU-AC (RRUN)
(1) L = defined length of cable.

5.3 Jumper Cables

Figure 17 Jumper Cable Connectors Without Protective Covers

Table 18 Jumper Cable Specifications

Application Connector Length (m) Dimension Product Number

file://C:\Users\Dell\AppData\Local\Temp\ALEX_TMP\1027\alex0372.htm 6/21/2013
Main-Remote Installation Products Overview Page 19 of 37

(1)

RRU22 7-16(m) to 7-16(m) 1, 2, 3, 5, 1/2" TSR 951 70/L


RRUW-01 7.5, 10
7-16(m) to 7-16(m) 1, 2, 3, 5 1/2" TSR 951 331/L
RRUN N-type to 7-16(m) 1.5 1/4" RPM 119 342/4
N-type to 7-16(m) 4 1/4" RPM 119 0245/4
(1) L = defined length of cable.

file://C:\Users\Dell\AppData\Local\Temp\ALEX_TMP\1027\alex0372.htm 6/21/2013
Main-Remote Installation Products Overview Page 20 of 37

5.4 TG Synchronization Cables for GMS

Figure 18 TG Synchronization Cable Connectors Without Protective Covers

Table 19 Transceiver Group (TG) Synchronization Cable Specifications

Application Connector Length Product Number(1)


MU-01, MU-03, MU-11 to ODC to ODC 5.5, 25 RPM 119 0408/L
MU-01, MU-03, MU-11
MU-01, MU-03, MU-11 to ODC to open end 4, 25 RPM 119 0413/L
MU-12 or outdoor macro RBS
MU-01, MU-03, MU-11 to ODC to 4, 25 RPM 119 0417/L
indoor macro RBS (not DXU-31) 9-pin D-sub
MU-01, MU-03, MU-11 to ODC to RJ45 6, 25 RPM 119 0418/L
RBS 2216 V1 (DXU-31)
MU-12 to Open end to open 4, 5.5, 25 RPM 119 0584/L
MU-12 or outdoor macro RBS end
MU-12 to Open end to 9-pin 4, 25 RPM 119 0586/L
indoor macro RBS (not DXU-31) D-sub
MU-12 to Open end to RJ45 6, 25 RPM 119 0587/L
RBS 2216 V1 (DXU-31)
(1) L = defined length of cable.

5.5 RET Control Cables

Figure 19 RET Control Cables

Table 20 RET Control Cable Specifications

file://C:\Users\Dell\AppData\Local\Temp\ALEX_TMP\1027\alex0372.htm 6/21/2013
Main-Remote Installation Products Overview Page 21 of 37

Application Connector Length (m) Product Number(1)


RRU22 (20W) 8-pole DIN to 4-pin 1.5, 2.5, 3.5, 15 TSR 484 31/L (Black)
M12
RRU22 (20W) 8-pole DIN to 4-pin 1.5, 2.5, 3.5, 15 TSR 484 32/L (Gray)
M12
RRUW-01 8-pole DIN to 8-pole 1, 2, 3, 15 1/TSR 484 21/L (Black)
DIN
RRUW-01 8-pole DIN to 8-pole 1, 2, 3, 15 1/TSR 484 22 (Gray)
DIN
(1) L = defined length of cable.

5.6 Grounding Kit Cables

Table 21 Grounding Cable Kit Specifications

Application Connector Length (m) Product number


Indoor cabinets M8 cable lug 2 5/NTM 201 201/2
M8 cable lug 1 5/NTM 201 201/3
M8 cable lug 2 5/NTM 201 201/4
Outdoor cabinets M8 cable lug 40 9/NTM 201 230/1

6 Installation Materials

6.1 Antenna Support Products

file://C:\Users\Dell\AppData\Local\Temp\ALEX_TMP\1027\alex0372.htm 6/21/2013
Main-Remote Installation Products Overview Page 22 of 37

Figure 20 Antenna Support

A: Freestanding Tripod 5.5 m

Table 22 Freestanding Tripod 5.5 m Specifications

Product number NTM 201 3167/1


Description Freestanding tripod antenna support; the construction is
preferably balanced with concrete blocks 50050050 mm
(not supplied).
Tube length 5500 mm

file://C:\Users\Dell\AppData\Local\Temp\ALEX_TMP\1027\alex0372.htm 6/21/2013
Main-Remote Installation Products Overview Page 23 of 37

Tube diameter 114 mm


Weight 135 kg, excluding concrete blocks
Max. wind load (at 55 m/s) Max 1.5 m2

B: Freestanding Antenna Support 2 m

Table 23 Freestanding Antenna Support 2 m Specifications

Product number NTM 201 1205/1


Description Freestanding antenna support; the construction is balanced
with supplied concrete blocks
Tube length 2000 mm
Tube diameter 60 mm
Weight 112 kg, incl. concrete blocks.
Max. wind load (at 55 m/s) Max 0.6 m2

C: Freestanding Antenna Support 3 m

Table 24 Freestanding Antenna Support 3 m Specifications

Product number NTM 201 3164/1


Description Freestanding antenna support with adjustable shut support;
the construction is preferably balanced with concrete blocks
50050050 mm (not supplied).
Tube length 3000 mm
Tube diameter 76 mm
Weight 122 kg, excluding concrete blocks
Max. wind load (at 55 m/s) Max 1.0 m2

D: Freestanding Antenna Support For Wall

Table 25 Freestanding Antenna Support For Wall Specifications

Product number NTM 201 3163/1


Description A freestanding rooftop antenna support for easy and fast
installation; the construction is balanced with supplied
concrete blocks.
Tube length 1200 mm
Weight 131 kg, incl. concrete blocks
Tube diameter 60 mm
Max. wind load (at 55 m/s) Max 0.6 m2

E: 3-Sector Antenna Mount

Table 26 3-Sector Antenna Mount Specifications

Product number SXK 107 2150/1


Description The product is designed to install 3 sector antennas on one

file://C:\Users\Dell\AppData\Local\Temp\ALEX_TMP\1027\alex0372.htm 6/21/2013
Main-Remote Installation Products Overview Page 24 of 37

single pole.
Weight 6.6 kg
Max. wind load (at 55 m/s) Max 1.0 m2

F: Antenna Support for Tower Installation

Table 27 Antenna Support for Tower Installation Specifications

Product number SXK 107 2126/1


Description The product is to be used in pairs when fastening antenna
tubes on tower legs.
The tubes delivers in three lengths:
- SXA 120 729/16, 60 mm, 1.6 m
- SXA 120 215/29, 75 mm, 2,9 m
- SXA 120 216/40, 90 mm, 4 m
Weight 8 kg

file://C:\Users\Dell\AppData\Local\Temp\ALEX_TMP\1027\alex0372.htm 6/21/2013
Main-Remote Installation Products Overview Page 25 of 37

G: Antenna Support Kit 3 m

Table 28 Antenna Support Kit Specifications

Product number SXK 107 2022/1


Description Basic antenna support kit for wall or roof; 3 m tube with
support.
Weight 43.6 kg
Max. wind load (at 55 m/s) Max 1.0 m2

H: Antenna Support Kit for Wall

Table 29 Antenna Support Kit for Wall Specifications

Product number SXK 107 2146/1


SXK 107 2146/2
Description A light non penetrating rooftop antenna support kit. Comes in
two versions; one for walls with a thickness 100490 mm, and
one for walls with a thickness of 5001000 mm.
Tube length 1500 mm
Tube diameter 60 mm
Weight 14 kg / 15.5 kg
Max. wind load (at 55 m/s) Max 0.6 m2

6.2 Cable Support and Accessories

Cable Tube

file://C:\Users\Dell\AppData\Local\Temp\ALEX_TMP\1027\alex0372.htm 6/21/2013
Main-Remote Installation Products Overview Page 26 of 37

Figure 21 Cable Tubes

Table 30 Cable Tube Specifications

Position in Figure A B
Product number NTM 201 3727/1 NTM 201 3811/1
Tube length 8.5 m (51.7 m) 25 m
Tube diameter 40/35 mm for all 3 sectors 50/40 mm for all 3 sectors
Weight 3.5 kg 19 kg
Installation Ladder, wall, tower Ladder, wall, tower
possibilities
Description Straight split tubes, incl. Flexible cable tube kit, incl. pull wire and
fastening material fastening material

Cable Support Kit

file://C:\Users\Dell\AppData\Local\Temp\ALEX_TMP\1027\alex0372.htm 6/21/2013
Main-Remote Installation Products Overview Page 27 of 37

Figure 22 Cable Support Kit

Table 31 Cable Support Kit Specifications

Product number NTM 201 3728/1


Description Support kit for three fiber cables and three power cables

file://C:\Users\Dell\AppData\Local\Temp\ALEX_TMP\1027\alex0372.htm 6/21/2013
Main-Remote Installation Products Overview Page 28 of 37

6.3 Tools and Instruments

Figure 23 Tools and Instruments

Table 32 Tool and Instrument Specifications

Position Product Product Compatible Description


in Figure Number Connector Types
A Fiber Check Tool LPK 112 102/1 LC, SC, ODC Used to verify with visible
light if fiber is ok or not
B Ferrule End-face LTT 601 154/1 LC, SC Used to clean fiber ends
Cleaner
C OTDR LPB 102 111/1 LC, SC Optical Site Master with
power meter for
measurement of OIL cable
and optical transmission;
Testing distance up to
2.5 km.

6.4 Miscellaneous Products

Cable Winder Box

file://C:\Users\Dell\AppData\Local\Temp\ALEX_TMP\1027\alex0372.htm 6/21/2013
Main-Remote Installation Products Overview Page 29 of 37

Figure 24 Three Cable Winder Boxes

Table 33 Cable Winder Box Specifications

Product Number NTM 201 3729/1


Description Holds excess fiber cable (up to 30 m)
Dimensions 280440 mm
Weight 1.1 kg
Installation options Wall, tower, 19-inch rack, stackable

Label Set for Cables

Table 34 Cable Label Set Specifications

Specification WCDMA GSM


Product NTM 201 3767/1 NTM 201 3767/2
Number
Description Complete set of labels for fiber, power and RF cables
Max. sectors 6 3

Earth Grounding

Table 35 Earth Grounding Specifications

Product number Description


9/NTM 201 230/2 Earth grounding rod for installation into the ground
NTM 201 3326/1 Earth grounding bar for towers and city sites

Fiber Connection Box

Table 36 Fiber Connection Box Specifications

Product Description
number
NCD 901 37/1 Outdoor fiber connection box for distribution to three RRUs, incl. three LC duplex

file://C:\Users\Dell\AppData\Local\Temp\ALEX_TMP\1027\alex0372.htm 6/21/2013
Main-Remote Installation Products Overview Page 30 of 37

adapters

Indoor Cable Chute

Figure 25 Indoor Cable Chute

Table 37 Indoor Cable Chute Specifications

Product number NTM 201 3730/1


Dimensions (WH) 2540 mm
Chute length 22 m
Weight 1.1 kg
Installation possibilities Ladder, wall
Description To protect fiber cables

7 Type Sites

7.1 Type Site 1 - Outdoor Greenfield Site

file://C:\Users\Dell\AppData\Local\Temp\ALEX_TMP\1027\alex0372.htm 6/21/2013
Main-Remote Installation Products Overview Page 31 of 37

Figure 26 Outdoor Greenfield Site

Table 38 Outdoor Greenfield Site Specifications

Position Product Number Description


in
Figure
A NTM 201 3728/1 Cable
support kit
B NTM 201 3727/1 Outdoor
cable tube
kit
C NTM 201 3729/1 Overlength
box kit
D SXK 107 2126/1 Antenna
Support Kit
E SXA 120 729/16 Tube, 1.6 m

7.2 Type Site 2 - Greenfield Shelter Site

file://C:\Users\Dell\AppData\Local\Temp\ALEX_TMP\1027\alex0372.htm 6/21/2013
Main-Remote Installation Products Overview Page 32 of 37

Figure 27 Greenfield Shelter Site

Table 39 Greenfield Shelter Site Specifications

Position in Figure Product Number Description


A NTM 201 3448/2 Cable sealing
B NTM 201 3730/1 Indoor cable chute
C NTM 201 3604/2 19-inch rack frame, 48 U
D NTM 201 3729/1 Overlength box kit

file://C:\Users\Dell\AppData\Local\Temp\ALEX_TMP\1027\alex0372.htm 6/21/2013
Main-Remote Installation Products Overview Page 33 of 37

7.3 Type Site 3 - Rooftop Indoor Site

Figure 28 Rooftop Indoor Site

Table 40 Rooftop Indoor Site Specifications

Position in Figure Product Number Description


A NTM 201 3605/1 19-inch rack frame, 16U
B NTM 201 3729/1 Overlength box kit
C NTM 201 3811/1 Tube kit
D SXK 107 21 46/1 Antenna support for wall
E NTM 201 3164/1 Freestanding antenna support

file://C:\Users\Dell\AppData\Local\Temp\ALEX_TMP\1027\alex0372.htm 6/21/2013
Main-Remote Installation Products Overview Page 34 of 37

7.4 Type Site 4 - Rooftop Outdoor Site

Figure 29 Rooftop Outdoor Site

Table 41 Rooftop Outdoor Site Specifications

Position in Figure Product Number Description


A NTM 201 3167/1 Antenna support, freestanding
B SXK 107 2150/1 3 sector antenna installation kit

7.5 Type Site 5 - Rooftop Shelter Site

file://C:\Users\Dell\AppData\Local\Temp\ALEX_TMP\1027\alex0372.htm 6/21/2013
Main-Remote Installation Products Overview Page 35 of 37

Figure 30 Rooftop Shelter Site

Table 42 Rooftop Shelter Site Specifications

Position in Figure Product Number Description


A NTM 201 3604/2 19-inch rack frame, 48 U
B SXK 107 2126/1 Tower installation support
C SXA 120 729/16 Tube, 1.6 m

7.6 Type Site 6 - Rooftop Outdoor Site

file://C:\Users\Dell\AppData\Local\Temp\ALEX_TMP\1027\alex0372.htm 6/21/2013
Main-Remote Installation Products Overview Page 36 of 37

Figure 31 Rooftop Outdoor Site

Table 43 Rooftop Outdoor Site Specifications

Position in Figure Product Number Description


A NTM 201 1205/1 Antenna support
B NTM 201 3811/1 Tube kit

8 Terms and Abbreviations


ACCU Alternating Current Connection Unit
BU Battery Unit
MPH Modem Protective Housing
MU Main Unit
ODC Outdoor Connector
OIL Optical Interface Link
PBC-02 Power and Battery Cabinet-02
PSU Power Supply Unit

file://C:\Users\Dell\AppData\Local\Temp\ALEX_TMP\1027\alex0372.htm 6/21/2013
Main-Remote Installation Products Overview Page 37 of 37

RETU Remote Electrical Tilt Unit


RRU Remote Radio Units
RRUN RRU for GSM
RRUW Remote Radio Unit Wideband
SSC Site Support Cabinet
TG Transceiver Group
TMR Transmission Rack
TRX Transceivers

file://C:\Users\Dell\AppData\Local\Temp\ALEX_TMP\1027\alex0372.htm 6/21/2013

Vous aimerez peut-être aussi