Vous êtes sur la page 1sur 56

E.E.E. Dept.

N.I.T.K. - Surathkal

Protection Issues with


Distributed Generation

Dr. K.P.Vittal
Professor
Agenda

Distributed generation

Anti-islanding requirements

Sustainable Feeder Island

System design & protection issues

Anti-islanding protection

References

Conclusive Remarks

K.P.Vittal, EEE Dept., NITK, Mangalore, India, Pin: 575 025, 46 Slides
2
Distributed Generation
K.P.Vittal, EEE Dept., NITK, Mangalore, India, Pin: 575 025, 46 Slides
3
Distributed Generation

Small generators connected to sub-transmission


and distribution systems.
Typically from few hundred KW to few tens of
MW.
Different sources of energy
Wind
Fuel cells
Bio-fuels
Mini hydros
etc..
K.P.Vittal, EEE Dept., NITK, Mangalore, India, Pin: 575 025, 46 Slides
4
Distributed Generation

[2]

K.P.Vittal, EEE Dept., NITK, Mangalore, India, Pin: 575 025, 46 Slides
5
Distributed Generation Overheads

Adds complexity to the system


Radial systems become double ended systems
Changes system fault levels
Load flow direction may also change
Cost of installing distributed generation
Cost of installing generators
Cost of modification in existing systems

K.P.Vittal, EEE Dept., NITK, Mangalore, India, Pin: 575 025, 46 Slides
6
Distributed Generation Merits

Distributed generators provide


Additional capacity to the grid
Environmental friendly power
Better voltage profile at load ends
Better local reactive power support, reducing
losses
Technological advancements in alternative
energy sources provides the momentum
A source of revenue for small entrepreneurs

K.P.Vittal, EEE Dept., NITK, Mangalore, India, Pin: 575 025, 46 Slides
7
Distributed Generation Issues

May require replacement of devices Load break


switches to breakers
Increasing rating of breakers
Re-visiting protection system
Choice of appropriate system grounding that will balance
Loss of sensitivity of protection and
Appearance of transient over voltages
Avoiding islanding

K.P.Vittal, EEE Dept., NITK, Mangalore, India, Pin: 575 025, 46 Slides
8
Anti-islanding requirements
K.P.Vittal, EEE Dept., NITK, Mangalore, India, Pin: 575 025, 46 Slides
9
Anti-islanding requirements

K.P.Vittal, EEE Dept., NITK, Mangalore, India, Pin: 575 025, 46 Slides
10
Anti-islanding requirements

Anti-islanding capability is an important requirement for distributed generators. It refers to


the capability of a distributed generator to detect if it operates in an islanded system and to
disconnect itself from the system in time.

K.P.Vittal, EEE Dept., NITK, Mangalore, India, Pin: 575 025, 46 Slides
11
Anti-islanding requirements

Islanding is not desirable under a scenario when


contract for power is between utility and end
user.
Island is an unregulated power system
Behavior of islanded system is un-predictable
due to lack of proper voltage and/or frequency
control
Can create hazard to utility workers

K.P.Vittal, EEE Dept., NITK, Mangalore, India, Pin: 575 025, 46 Slides
12
Anti-islanding requirements

Re-connection of utility supply is an issue and


will require re-synchronization.
Current industry practice is to disconnect the
DGs from the system when islands are formed
and reconnect them after utility supply is
restored.

Thus anti-islanding schemes are necessary when


having DGs in the system

K.P.Vittal, EEE Dept., NITK, Mangalore, India, Pin: 575 025, 46 Slides
13
Anti-islanding requirements

Anti-islanding schemes should work for islands


at all levels

[2]

K.P.Vittal, EEE Dept., NITK, Mangalore, India, Pin: 575 025, 46 Slides
14
Anti-islanding requirements

Anti-islanding schemes should detect islands at


the shortest possible time that will avoid out-of-
phase reclosing
Should be able to work with all types of DGs and
ratings
Synchronous generators Connected to primary
feeders and can go up to 30MW Due to its large
power rating, it is always a challenge to implement
anti-islanding schemes

K.P.Vittal, EEE Dept., NITK, Mangalore, India, Pin: 575 025, 46 Slides
15
Anti-islanding requirements

Induction generators Connected to primary


feeders with 10 to 20MW Cannot sustain a
island due to high reactive power demand.

Inverter based generator connection few


hundred KW to few MW Sustainability depends
on the design of the inverter and primary system
configuration

Should be a cost effective and reliable solution

K.P.Vittal, EEE Dept., NITK, Mangalore, India, Pin: 575 025, 46 Slides
16
Anti-islanding requirements

Islanding detection methods

Local detection : A Cost effective option but may


not be effective in all situations

Remote detection:

Communication based : Expensive option in


comparison with the cost of DGs

K.P.Vittal, EEE Dept., NITK, Mangalore, India, Pin: 575 025, 46 Slides
17
Sustainable Feeder Island
K.P.Vittal, EEE Dept., NITK, Mangalore, India, Pin: 575 025, 46 Slides
18
Sustainable Feeder Island

Two-to-One rule:
An island with the connected load twice as much as
the islanded generation is not sustainable.
Frequency decline when an island is formed with load
twice as much as generation [Effect shown in fig],

K.P.Vittal, EEE Dept., NITK, Mangalore, India, Pin: 575 025, 46 Slides
19
Sustainable Feeder Island

If the DR is capable of forming a sustainable feeder island it


may require the following system upgrades:
1. If the DR feeder is equipped with a substation circuit
recloser, replace the recloser with a circuit breaker.
2. Add a three-phase voltage transformer (VT) on the load
side of the DR feeder breaker to allow voltage supervision
or sync-check on restoration.
3. Replace the existing protection with:
modern multifunction relay equipped with features such as,
voltage supervision, sync-check, directional over current
element, out-of-step detection, and disturbance monitoring.

K.P.Vittal, EEE Dept., NITK, Mangalore, India, Pin: 575 025, 46 Slides
20
System Design and
Protection Issues
K.P.Vittal, EEE Dept., NITK, Mangalore, India, Pin: 575 025, 46 Slides
21
System Design and
Protection Issues

Distribution equipment ratings


Maximum size of distribution conductor limits the total
rating of DGs (E.g., BC Hydro has a limit of 15MVA on
a 35kV line) [2]

Increase in fault current contributions may necessitate


rating review of fuses, line re-closures and customer
end interface switching devices

Load flow check to verify the thermal ampacity of


primary conductors.
K.P.Vittal, EEE Dept., NITK, Mangalore, India, Pin: 575 025, 46 Slides
22
System Design and
Protection Issues

Review of design of feeder voltage regulators


due to possibility of dual direction power flow

Either block reverse power flow or

Install bi-directional voltage regulating controllers

Review ampere ratings of line voltage regulators

K.P.Vittal, EEE Dept., NITK, Mangalore, India, Pin: 575 025, 46 Slides
23
System Design and
Protection Issues

Interconnection transformer grounding

Trade-off between
Safety of connected single
phase loads and
Sensitivity of ground fault
protection

[2]

K.P.Vittal, EEE Dept., NITK, Mangalore, India, Pin: 575 025, 46 Slides
24
System Design and
Protection Issues

Different Cases of Ground faults influenced by Interconnection


transformer grounding:

Case A: No Grounding
With the high side of
the interconnecting
transformer
ungrounded,
L-G Fault close to
POI but without DR
(or disconnect open)

K.P.Vittal, EEE Dept., NITK, Mangalore, India, Pin: 575 025, 46 Slides
25
System Design and
Protection Issues

Case A: No grounding

Healthy phase over voltage


Equipment / personnel safety
issues

[2]

No protection sensitivity
loss.

[2] IN = 3*246 = 738A

K.P.Vittal, EEE Dept., NITK, Mangalore, India, Pin: 575 025, 46 Slides
26
System Design and
Protection Issues

No grounding

Di-electric stress on equipment such as pole


mounted distribution transformers

Stray flux as a result of excessive saturation


due to over-voltage can cause damage to
non-laminated steel parts of the transformer

K.P.Vittal, EEE Dept., NITK, Mangalore, India, Pin: 575 025, 46 Slides
27
System Design and
Protection Issues

Case B: Solid Grounding


With the high side of
the interconnecting
transformer solidly
grounded,
L-G Fault close to POI
but with DR (or
interconnection swtich
closed)

K.P.Vittal, EEE Dept., NITK, Mangalore, India, Pin: 575 025, 46 Slides
28
System Design and
Protection Issues

Solid Grounding
Concern of loss of sensitivity
of earth fault protection

IN = 3*114 = 342A
[2]

K.P.Vittal, EEE Dept., NITK, Mangalore, India, Pin: 575 025, 46 Slides
29
System Design and
Protection Issues

Solid grounding

No concern of over-voltage

Reduction in earth fault current sensitivity can


affect fault detection

With DG offline and interconnecting transformer


online, situation is much worse

Solution is to take a mid path by using


resistance grounding System dependent
K.P.Vittal, EEE Dept., NITK, Mangalore, India, Pin: 575 025, 46 Slides
30
TRANSIENT OVERVOLTAGES AND
TRANSFER TRIP
K.P.Vittal, EEE Dept., NITK, Mangalore, India, Pin: 575 025, 46 Slides
31
TRANSIENT OVERVOLTAGES AND
TRANSFER TRIP

K.P.Vittal, EEE Dept., NITK, Mangalore, India, Pin: 575 025, 46 Slides
32
TRANSIENT OVERVOLTAGES AND
TRANSFER TRIP

Problem:
A series-resonance phenomenon that can occur when the DR
back feeds to a ground fault on an ungrounded transmission
system.
Utility system and its customers can be subjected to over
voltages higher than line-to-line levels due to this
phenomenon.
Remedy:
Avoidance of series resonance requires delaying the line
tripping at the remote terminal and sending a transfer trip to
the substation DR feeder breaker.
This ensures that the DR is isolated from the system before
tripping of the remote line terminal(s), which provides an
effective grounding to the transmission system.

K.P.Vittal, EEE Dept., NITK, Mangalore, India, Pin: 575 025, 46 Slides
33
Anti-islanding Protection
K.P.Vittal, EEE Dept., NITK, Mangalore, India, Pin: 575 025, 46 Slides
34
Anti-islanding Protection

K.P.Vittal, EEE Dept., NITK, Mangalore, India, Pin: 575 025, 46 Slides
35
Anti-islanding Protection

Limitations of islanding schemes

High implementation cost

Co-ordination requirement between DG

operator and utility

False tripping due to false islanding detection

Non-operation for certain situations

K.P.Vittal, EEE Dept., NITK, Mangalore, India, Pin: 575 025, 46 Slides
36
Anti-islanding Protection

Non-detection zones
System situations when islanding is not
detected
Example Frequency based islanding of a
synchronous DG
Location of island
Daily variation of loads

K.P.Vittal, EEE Dept., NITK, Mangalore, India, Pin: 575 025, 46 Slides
37
Anti-islanding Protection

K.P.Vittal, EEE Dept., NITK, Mangalore, India, Pin: 575 025, 46 Slides
38
Anti-islanding Protection

Communication based anti-islanding techniques


Transfer trip scheme

K.P.Vittal, EEE Dept., NITK, Mangalore, India, Pin: 575 025, 46 Slides
39
Anti-islanding Protection

Communication based anti-islanding techniques


Transfer trip scheme
Monitor all relevant breakers/reclosures and
issue DG tripping when island is formed
Simple with fixed system topology and limited
number of switching device
An expensive proposition and not scalable

K.P.Vittal, EEE Dept., NITK, Mangalore, India, Pin: 575 025, 46 Slides
40
Anti-islanding Protection

Communication based anti-islanding techniques


Using power line signaling

K.P.Vittal, EEE Dept., NITK, Mangalore, India, Pin: 575 025, 46 Slides
41
Anti-islanding Protection

Communication based anti-islanding techniques


Using power line signaling
Inject high frequency signal at the utility bus
Monitor presence of signal at each DG
interconnection and trip when signal is absent
Scalable as each additional DG requires only a
sensing device
Costly as the injector requires an interconnecting
transformer
K.P.Vittal, EEE Dept., NITK, Mangalore, India, Pin: 575 025, 46 Slides
42
Anti-islanding Protection

Local detection based anti-islanding techniques


Frequency based passive detection
Frequency threshold
Rate of change of frequency
Vector shift

K.P.Vittal, EEE Dept., NITK, Mangalore, India, Pin: 575 025, 46 Slides
43
Anti-islanding Protection
Local detection based anti-islanding techniques
Frequency based detection - Performance

K.P.Vittal, EEE Dept., NITK, Mangalore, India, Pin: 575 025, 46 Slides
44
Anti-islanding Protection
Local detection based anti-islanding techniques
Key influencing factors of frequency based
detection
Inertia constant of the DG
Voltage and frequency dependency of loads
Generator controls

K.P.Vittal, EEE Dept., NITK, Mangalore, India, Pin: 575 025, 46 Slides
45
Anti-islanding Protection
Other passive schemes
Voltage monitoring at DG interconnection
A measure of reactive power imbalance
Faster than frequency based
Still not popular due to issues of setting (more
work required)
Change of active power output
Change of reactive power output (more
sensitive than voltage change)

K.P.Vittal, EEE Dept., NITK, Mangalore, India, Pin: 575 025, 46 Slides
46
Anti-islanding Protection
Active schemes
Impedance measurement
Injection of low frequency inter-harmonic current

Advantage immune to power mismatch


Disadvantage interference with other DGs, cost

K.P.Vittal, EEE Dept., NITK, Mangalore, India, Pin: 575 025, 46 Slides
47
Anti-islanding Protection
Active schemes
Varying generator terminal voltage
Vary the generator terminal voltage and measure
the change in reactive power flow change.
Islanded system High change in reactive power
Connected system Low change in reactive power
Voltage regulator does the variation
automatically
Around 1% change with a frequency of 1 to 5 Hz

K.P.Vittal, EEE Dept., NITK, Mangalore, India, Pin: 575 025, 46 Slides
48
Conclusive remarks
K.P.Vittal, EEE Dept., NITK, Mangalore, India, Pin: 575 025, 46 Slides
49
Conclusive remarks

Distributed generation has huge potential to


improve the efficiency of the power system

It does bring with it lot of challenges in design


and protection

Anti-islanding detection is a very key issue

One of the active areas of research today

K.P.Vittal, EEE Dept., NITK, Mangalore, India, Pin: 575 025, 46 Slides
50
References
K.P.Vittal, EEE Dept., NITK, Mangalore, India, Pin: 575 025, 46 Slides
51
References
[1]IEEE Standard for Interconnecting Distributed Resources with Electric Power
Systems, IEEE, Standards Coordinating Committee 21, July 2003.
[2]Mukesh Nagpal, Frank Plumptre, Richard Fulton and Terrence G. Martinich,
Dispersed Generation InterconnectionUtility Perspective, IEEE Trans. On
Industry Applications, Vol. 42, No. 3, May /June 2006, pp864-872.
[3] W. Bower and M. Ropp, "Evaluation Of Islanding Detection Methods For Photovoltaic
Utility", International Energy Agency, Report IEA PVPS T5-09: 2002.
[4] M. A. Referrn, O. Usta, G. Fielding. Protection Against Loss of Utility Grid Supply
for a Dispersed Storage and Generation Unit, IEEE Transactions on Power Delivery,
Vol. 8, No. 3, July 1993. pp 948 - 954.
[5] C. J. Mozina. Interconnection Protection of IPP Generators at Commercial /
Industrial Facilities, IEEE Transactions on Industry Applications, Vol. 37, No. 3,
May / June 2001. pp 681 - 689.
[6] N. Jenkins, R. Allan, P. Crossley, D. Kirschen, and G. Strbac, Embedded Generation,
1st ed. Institute of Electrical Engineers, 2000.
[7] M. Guillot, C. Collombet, P. Bertrand, B. Gotzig. Protection of Embedded
Generation Connected to a Distribution Network and Loss of Mains Detection,
Schneider Electric, France, CIRED 2001, 18-21 June 2001, Conference Publication
No.482 IEE 2001 pp 82 85.

K.P.Vittal, EEE Dept., NITK, Mangalore, India, Pin: 575 025, 46 Slides
52
References

[8] G. Heggie, H Yip, A Multi-Function Relay for Loss of Mains Protection, IEE Colloquium on
System Implications of Embedded Generation and its Protection and Control No. 1998 / 277,
Feb 1998, p.5/1-4.

[9] Cooper Power Systems Product Manual, "UM30SV Vector Jump/Islanding Relay", Electric
Apparatus Literature150-23, 1999.

[10] W. Freitas, Z. Huang and W. Xu, "A Method for Assessing the Effectiveness of Vector Surge
Relays for Distributed Generator Applications," accepted for publication by IEEE Trans. on
Power Delivery (Paper No. TPWRD-00358-2003.R1).

[11] W. Freitas and W. Xu, "False Operation of Vector Surge Relays" IEEE Trans. on Power Delivery,
Volume: 19 , Issue: 1 , Jan. 2004, pp 436 - 438.

[12] M. A. Redfern , J. I. Barret , O. Usta, A New Microprocessor Based Islanding Protection


Algorithm for Dispersed Storage and Generation Units, IEEE Transactions on Power Delivery,
Vol. 10, N 3, July 1995. pp 1249 1254.

K.P.Vittal, EEE Dept., NITK, Mangalore, India, Pin: 575 025, 46 Slides
53
References
[13] S. K. Salman, D. J. King and G. Weller, New Loss of Mains Detection Algorithm for Embedded
Generation Using Rate of Change of Voltage and Changes in Power Factors, Developments in
Power Systems Protection, Conference Publication N 479 IEE 2001.
[14] F. Pai, S. Huang, A Detection Algorithm for Islanding-Prevention of Dispersed Consumer
Owned Storage and Generating Units, IEEE Transactions on Energy Conversion, Vol. 16, No 4,
pp 346 - 351, December 2001 (df/dP).
[15] P. O Kane, B. Fox Loss of Mains Detection for Embedded Generation by System Impedance
Monitoring, Development in Power System Protection, 25 27th March 1997, Conference
Publication No. 434 IEE, 1997, pp 95 98.
[16] J. E. Kim and J. S. Hwang Islanding detection Method of Distributed Generation Units
Connected to Power Distribution System, Proceedings of IEEE PowerCon 2000 International
Conference, Volume: 2 , 4-7 Dec. 2000, pp 643 - 647.
[17] J. Motohashi, Y. Imai, T. Ishikawa, T. Kai, H. Kaneda, T. Fujimoto, T. Ishizuka. Development
of Detecting System of Islanding Operation for Dispersed Synchronous Machine Generator
Interconnected to Distribution line, Meiden Review Magazine, Series 110, 2000 No 1, pp 1019
1022.
[18] Bas Verhoeven, "Probability Of Islanding In Utility Networks Due To Grid Connected
Photovoltaic Power Systems", International Energy Agency, Report IEA PVPS T5-07: 2002.

K.P.Vittal, EEE Dept., NITK, Mangalore, India, Pin: 575 025, 46 Slides
54
Any questions?
Thank you for your kind attention

vittal@nitk.ac.in

Vous aimerez peut-être aussi