Vous êtes sur la page 1sur 9

Type KAVR 100, 130: Multi-shot auto-reclose

and check synchronising relay

KAVR 100 and 130 are multi-shot auto-reclose relays with integral check synchronising for application to feeders switched by a single
circuit breaker. They are intended for use on transmission, sub-transmission and distribution systems

As a part of the K range of relays, the KAVR can be integrated into an overall protection and control system by utilising its integral
serial communications facility

Features Models available The KAVR 130 can be set so that a


single phase fault initiates a single phase
Number of reclosures selectable KAVR 100 auto-reclose cycle. If the fault evolves
between 1 and 4 3 phase tripping only onto all three phases before the relays
dead time has elapsed, a three phase
Optional single phase reclosure on KAVR 130
trip will result.
the first shot Single and 3 phase tripping
Integral synchronism check function An integral maintenance alarm counts
Application the number of operations of the circuit
for auto-reclose and manual circuit
breaker. It provides an alarm and a
breaker closure
subsequent lockout, if the preset
The KAVR 100 provides 1, 2, 3 or 4
Selectable undervoltage blocking and thresholds are exceeded. Additional
shot reclosure of a circuit breaker
differential voltage blocking features counters indicate the number of relosures
following a fault on an overhead line.
which may be attempted before lockout
Maintenance alarm and lockout The first shot can be selected to be either
occurs.
high speed or delayed three phase
Independently adjustable timers with
reclosure. The KAVR 130 has separate counters for
wide setting ranges
each phase and will also register the
Flexible operating logic options via The KAVR 130 is specifically designed
total number of single phase and three
software function links for transmission and sub-transmission
phase reclosures attempted.
lines where there is a need for single-
Measurement of line and busbar phase auto-reclosure. In addition to the
voltage, system frequency, and phase cycles available on the KAVR 100, it Check synchronising
angle slip frequency gives the option of high speed single-
phase auto-reclose for the first shot. The relay checks that the two parts of the
Remote communications via
system are in synchronism by measuring
K-Bus The check synchronising function ensures the angle and the slip frequency
Integral event recorder accessible that the two parts of the system are between the line voltage and the bus
from remote PC sufficiently in synchronism before being voltage. Auto-reclose is blocked if these
connected together. This function can values exceed the phase angle and slip
Comprehensive self-checking and also be used with manual switching and frequency settings.
alarms is operable even when the auto-reclose
function is out of service. Manual closure is blocked if these values
exceed the system angle and system slip
settings.
Functions
Selectable undervoltage and differential
KAVR 100/130

voltage measurements are available to


Auto-reclose
block closure if the line and bus voltages
The auto-reclose cycle is initiated by the are not compatible.
operation of the associated protective
To allow the circuit breaker to be closed
relay. Flexible scheme logic is provided
to allow the relay to be used for a wide onto an uncharged line; live line/dead
range of applications. bus; dead line/dead bus and dead
line/live bus detectors are included.
These allow reclosure when the voltage
on the line and/or the bus VT is below a
preset value.

466
Scheme logic Ancillary Functions Test features

The KAVR uses ladder logic A number of features are provided to


(Figure 1) to implement the scheme. Measurement enable the relay to be thoroughly tested
It presents this in the form of contacts, during commissioning, routine
coils, counters and timers that are The relay can display the magnitude of maintenance and fault finding
implemented in the software. In the line and bus voltages, line voltage operations:
operation, the left side of the ladder is frequency and slip frequency. The
analogous to a positive supply rail, with The measurement functions allow
measurements can be selected by the
the right side being negative. The the analogue input and its associate
user to be displayed as either primary or
program then acts as an imaginary secondary quantities. wiring to be checked.
current flowing left to right, acting upon Primary display quantities are based on The on/off states of the digital
the components on the rungs of the the VT ratios set in the relay. These inputs and relay outputs can be
ladder as appropriate. Changes to the
quantities can provide a default setting displayed.
scheme can be made by the user, by
on the LCD situated on the relay
opening or closing software function
frontplate. Power-on diagnostics and self
links, to match it to a particular
application. Full details of the scheme monitoring
logic used are included in the relevant Event records
logic diagram. Power-on diagnostic tests are carried out
(See additional information.) Fifty events are stored in a non-volatile by the relay when it is energised.
buffer. Software is available to enable
Inputs and outputs the events to be downloaded to a PC. These tests include checks on the timer,
microprocessor, memory and the
KAVR has 8 opto-isolated inputs which Any change of state of a control input or analogue input circuity.
may be assigned by the user to any of output relay, local setting change or
the available scheme inputs listed in the Continuous self-monitoring, in the form
operation of a control function, is stored
relevant scheme description. of watchdog circuity, memory checks
in the relay with a resolution of 1ms.
and analogue input module tests, is also
Alarms are also stored as events.
There are 8 programmable outputs, each performed. In the event of a failure, the
comprising a relay with 1 normally open relay will either lock out or attempt a
contact, which may also be assigned by recovery, depending on the type of
the user. failure detected.

A dedicated watchdog contact with 1


normally open and 1 normally closed
contact is also available.

Typical application diagrams (Figures 4


and 5) show the input and output
functions assigned as factory default
settings.

User controls
External inputs
User controls are provided, via the user
interface, to: Break Sotware
switch auto reclosing in and out of relay coil
service
reset the relay from lockout Make
Sotware
reset Successful AR or Function link relay contact Timer Output
CB Failed to close indication

Make
In addition on the KAVR 130 they may
KAVR 100/130

be used to:
select single phase, three phase or
single/three phase reclosing Figure 1 Example of ladder logic

467
1 Figure 2

Communications terminal arrangement

54
56

K-Bus
Screened 2 core cable

Relay 32 Relay 4 Relay 3 Relay 2 Relay 1


Figure 3

Basic communications system

Protocol converter
KAVR 100/130

KITZ

RS232 K-Bus

Desktop
p
computer PC

468
Hardware Description User Interface Software is available with each KITZ to
provide access to the relay to read and
The relay is housed in a Midos size 4 change settings. Additional software
case, suitable for either rack or panel Front panel user interface entitled Protection Access Software &
mounting as shown in Toolkit which provides access to the
The features of the relay can be event recorder, together with other
Figure 6.
accessed through a menu-driven system. additional functions, is also available.
A highly integrated 16-bit micro- The menu is arranged in the form of a
controller uses digital signal processing table, into each column of which related Each relay is directly addressable over
techniques to analyse power system items (menu cells) are grouped. the bus to allow communication with the
quantities and implement scheme logic. PC.
The user can move around the menu by
The micro-controller performs all of the
means of the keys on the frontplate. This It should be noted that protection
major software functions such as input
can be done with the cover in place, but tripping and blocking signals are not
signal processing, scheme logic, output
any change to the settings requires the routed via the K-Bus. Separate
relay control and handling of the
cover to be removed. conventional cabling is used for these
operator interface.
functions. Where appropriate, the
The relay has 2 analogue inputs and 8 isolated 48V dc supply available on
Remote access user interface
opto-isolated digital inputs. The internal each relay is used to energize its opto-
VTs are used to isolate, step-down and The menu table can also be accessed via isolators via external contacts.
condition the input from the line VTs. the remote communications facility. This
Their output signals are then converted allows all of the menu cells in a column Communications protocol
into digital data for further processing. to be displayed simultaneously on the
screen of a PC. Changes to the menu cell The communications protocol used with
The front plate contains a 2 x 16 can be made from the PC keyboard. K-Series relays is designated Courier.
character, alphanumeric liquid crystal
The Courier language has been
display (LCD) and 4 pushbuttons to
developed specifically for the purpose of
provide local access to the relays menu. Relay interconnection
developing generic PC programs that
There are also 3 light emitting diodes
The relays are interconnected via a will, without modification, communicate
(LED) for visual indication of the relays
shielded, twisted wire pair known as K- with any device using the Courier
status.
Bus. Up to 32 relays may be connected language.
Standard Midos terminal blocks are in parallel across the bus.
In the Courier system, all information
located at the rear of the relay providing
The K-Bus is connected through a resides in the relay.
connections for all input and output
protocol converter known as KITZ, either Each time communication is established
circuits such as dc supply, ac voltage
directly or via a modem, to the RS-232 with the relay, the requested information
and a K-Bus communications port.
port of the PC. The KITZ provides signals is loaded to the PC.
over the bus which are RS-485 based
The protocol includes extensive error
and transmits at64 kbits/s. The K-Bus
checking routines to ensure that the
connection is shown in Figure 2.
system remains reliable and secure.
This system allows up to 32 relays to be
accessed through one RS-232
communications port.
A pictorial representation of this is
shown in Figure 3.

Password protection

Password protection is provided on settings which alter the configuration of the


KAVR 100/130

relay, any accidental change to which could seriously affect the ability of the relay
to perform its intended function, ie. enable/disable settings, protection function
characteristic selection, scheme logic settings and system VT ratios.

469
KAVR 100/130

470
A B C

A 13 4
A.C./D.C. +
SUPPLY WD 6 RELAY HEALTHY
14
C B VX - 3
PHASE ROTATION A B C 21
WD 5 RELAY FAILED

30
N 22
23 RL0 32 AR IN PROGRESS

A B C n 34
24
25 RL1 36 CB CLOSE
N a b c
38
26 RL2 40 AR LOCKOUT/OUT OF SERVICE
n 27
42
a b c
28 RL3 44 BLOCK INST PROTECTION
17
29

18 RL4 31 MAINTENANCE ALARM

19
KAVR100 33
CASE EARTH
RL5 35 MAINTENANCE LOCKOUT
1 20
29 30 37
3 4 31 32 46 RL6 EXCESS FAULT FREQUENCY
5 6 CB AUX SWITCH L0 39
33 34
7 8 35 36 41
9 10 48
37 38 INST PROTECTION L1 RL7 43 CB FAILED TO CLOSE
39 40
13 14 1
41 42 50
MAIN PROTECTION L2
43 44
17 18 45 46 52 CASE EARTH
19 20 LOGIC INPUT COMMON (1) CONNECTION
47 48
21 22 49 50 45
SPRING CHARGED L3
23 24 51 52 54
Figure 4

25 26 53 54 47
MANUAL CB CLOSE L4
55 56 56 K-BUS COMMUNICATIONS PORT
27 28
SCN 49
NON AR PROTECTION L5 SCN

MODULE TERMINAL BLOCKS 51


VIEWED FROM REAR BLOCK AR L6
(WITH INTEGRAL CASE
EARTH STRAP) 7
53
RESET LOCKOUT L7 +
NOTE 1. +48V FIELD VOLTAGE
8
55 -
(a) C.T. SHORTING LINKS MAKE LOGIC INPUT COMMON (2)
BEFORE (b) & (c) DISCONNECT.
(b) SHORT TERMINALS BREAK BEFORE (c).
(c) LONG TERMINAL.
(d) NOTE 2. EARTH CONNECTIONS ARE TYPICAL ONLY.
PIN TERMINAL (P.C.B. TYPE)
Typical application diagram KAVR100
Figure 5

A B C

A 13 4
A.C./D.C. +
SUPPLY WD 6 RELAY HEALTHY
14
C B VX - 3
PHASE ROTATION A B C 21
WD 5 RELAY FAILED

30
N 22
23 RL0 32 AR IN PROGRESS

A B C n 34
24
25 RL1 36 CB CLOSE
N a b c
38
26 RL2 40 AR LOCKOUT/OUT OF SERVICE
n 27
Typical application diagram KAVR130

42
a b c
28 RL3 44 SYNC CHECK OK FOR MAN. CL
17
29

18 RL4 31 INHIBIT D.E.F./CB POLE DISCR.

19
KAVR130 33
CASE EARTH
RL5 35 INHIBIT P.S.B.
1 20
29 30 37
3 4 31 32 46 RL6 ENABLE 1 PH TRIPPING
5 6 CB AUX SWITCH L0 39
33 34
7 8 35 36 41
9 10 48
37 38 AR INIT. PROT A PH L1 RL7 43 CB TRIP
39 40
13 14 1
41 42 50
AR INIT. PROT B PH L2
43 44
17 18 45 46 52 CASE EARTH
19 20 LOGIC INPUT COMMON (1) CONNECTION
47 48
21 22 49 50 45
AR INIT. PROT C PH L3
23 24 51 52 54

25 26 53 54 47
CB SPRING CHARGED/
L4
AIR/GAS PRESSURE K-BUS COMMUNICATIONS PORT
27 28 55 56 56
SCN 49
"BLOCK AR" FROM PROT. L5 SCN

MODULE TERMINAL BLOCKS 51


VIEWED FROM REAR RESET LOCKOUT L6
(WITH INTEGRAL CASE
EARTH STRAP) 7
53
MANUAL CB CLOSE L7 +
NOTE 1. +48V FIELD VOLTAGE
8
55 -
(a) C.T. SHORTING LINKS MAKE LOGIC INPUT COMMON (2)
BEFORE (b) & (c) DISCONNECT.
(b) SHORT TERMINALS BREAK BEFORE (c).
(c) LONG TERMINAL.
(d) NOTE 2. EARTH CONNECTIONS ARE TYPICAL ONLY.
PIN TERMINAL (P.C.B. TYPE)

471
KAVR 100/130
Technical Data Phase angle settings Voltage settings
Check synchronism Undervoltage 22V to 132V
Relay ratings 5 to 90 Differential voltage 0.5V to 22V
System synchronism Line/bus dead voltage
Inputs: 5 to 90 5V to line/bus live voltage
AC voltage Line/bus live voltage
Slip frequency settings Line/bus dead voltage to 132V
Vn (nominal)
63.5/110V Check synchronism :
0.001Hz to 2.0Hz Transformer ratios
Operating range
System synchronism Voltage transformers
0 to 327V
0.001Hz to 2.0Hz 1:1 to 9999:1
Maximum withstand
375V
Time settings Digital inputs
Auxiliary voltage Vx Opto-isolated inputs
24/125V or KAVR100
Eight energised from 48V field
48/250V ac or dc Dead time 1 0.01s to 300s
voltage
Dead time 2 1.00s to 300s
Frequency Nominal rating 50V dc
50/60Hz Dead time 3 1.00s to 9999s
Off voltage 12V
Dead time 4 1.00s to 9999s
Frequency range On voltage35V
46Hz to 65Hz Reclaim time 1.00s to 600s
Check synchronism delay
Contacts
Output: 0.1s to 99s
Output relays Eight single make
System synchronism delay
Field voltage Contact ratings
0.1s to 99s
48V dc (current limit: 60mA)
Check synchronism window Make and carry for 0.2s 30A
0.01s to 600s Carry continuously 5A
Burdens
Auto-reclose inhibit after Break 50W resistive
AC voltage manual close 0.01s to 300s 25W inductive
0.02VA at 110V phase/neutral (L/R = 0.04s at 300V max)
Close pulse 0.01s to 10s
Auxiliary voltage
KAVR130 Durability
The burden on the auxiliary
Dead time 1 0.01s to 300s Loaded contact
supply depends upon the number
of output relays and control Dead time 2 1.00s to 9999s 10,000 operations minimum.
inputs energised. Dead time 3 1.00s to 9999s Unloaded contact
Dead time 4 1.00s to 9999s 1000,000 operations minimum
No. of No. of Typical Single phase dead time 1
output control burden 0.01s to 5s Communications port (K-Bus)
relays inputs Language Courier
Reclaim time 1.00s to 600s
DC 0 0 2.5 6.0W Check synchronism delay Transmission mode Synchronous
supply 0.10s to 99s
2 2 4.0 8.0W Signal levels RS485
System synchronism delay
8 8 5.5 12W Message format HDLC
0.10s to 99s
AC 0 0 6.0 12VA Data rate 64 kbits/s
KAVR 100/130

Check synchronism window


supply
2 2 6.0 14VA 0.01s to 9999s Connection Multidrop (32 units)
Auto-reclose inhibit after
8 8 13 23VA Cable type Screened
manual close 0.01s to 600s
twisted pair of wires
Close pulse 0.01s to 5s
Cable length 1000m (maximum)
Connector Screw terminals (M4)
Isolation 2kV rms for 1 minute

472
High voltage withstand DC supply interruption Atmospheric environment
IEC 60255-11:1979
Dielectric withstand Temperature
IEC 60255-5:1977 The unit will withstand a 10ms IEC 60255-6:1988
interruption in the auxiliary supply,
2kV rms for 1 minute between all Storage and transit
under normal operating conditions,
case terminals (except terminal 1) 25C to+70C
without de-energising.
connected together and the case
Operating 25C to +55C
earth/terminal 1. AC ripple on DC supply
IEC 60255-11: 1979 IEC 60068-2-1:1990 Cold
2kV rms for 1 minute between
terminals of independent The unit will withstand 12% ac ripple IEC 60068-2-2:1974 Dry heat
circuits,including contact circuits. on the dc supply.
Humidity
1.5kV rms for 1 minute across open EMC Compliance IEC 60068-2-3:1969
contacts of output relays 56 days at 93% RH and 40C
89/336/EEC
0 to 8.
Enclosure protection
Compliance with the
1kV rms for 1 minute across the IEC 60529:1989
EuropeanCommission Directive on
open contacts of the watchdog relay. IP50 (dust protected)
EMC is claimed via the technical
High voltage impulse Construction File route.
IEC 60255-5: 1977 Mechanical environment
EN 50081-2:1994
Three positive and three negative EN 50082-2:1995 Vibration
impulses of 5kV peak, 1.2/50s, IEC 60255-21-1:1988
Generic Standards were used to
0.5J between all terminals and all Response Class 1
establish conformity.
terminals (except terminal 1) and case Endurance Class 1
earth/terminal 1. Product Safety
Shock and Bump
7 72/23/EEC IEC 60255-21:1988-2:1988
Electrical environment Shock Response Class 1
Compliance with the European
Shock Withstand Class 1
High frequency disturbance Commission Low Voltage Directive.
Bump Class 1
IEC 60255-22-1:1988 Class III
EN61010-1: 1993/A2:1995
Seismic
2.5kV peak between independent EN60950:1992/A3: 1995
IEC255-21-3 1993 Class 1
circuits.
Compliance is demonstrated by
2.5kV peak between independent reference to generic safety
circuits and case earth. standards. Case
1.0kV peak across terminals of the The relay is housed in a size 4 Midos
same circuit. case as shown in Figure 6.
Fast transient disturbance
52
IEC 60255-22-4:1992 Class III
97 4 holes 4.4
23.5
2kV, 5kHz applied directly to all
inputs.
IEC 60801-4: 1988 Level 4 All dimensions in mm.
168 159
4kV, 2.5kHz applied directly to
auxiliary voltage, watchdog and trip
capacitor.
Push button
4kV, 2.5kHz, via capacitor clamp to projection 10 max. 99
all inputs. Panel cut-out:
Flush mounting fixing details.
Electrostatic discharge
IEC 60255-22-2:1989 Class III 32 212
25 min.
8kV discharge in air with cover in
KAVR 100/130

place.
IEC 60801-2:1991 Level 2 177 157 max.
4kV point contact discharge with
cover removed.
Reset
103 11
Flush mounting.

Figure 6 Case outlines size 4

473
Additional Information
Glossary
KAVR/KAVS/KVTR service manual
R8505 Courier K-Bus
KAVR100 scheme description A communications language The 64 kbps twisted pair cable
R6523 developed to provide generic used to connect Courier
control, monitoring, data compatible devices and
KAVR130 scheme description extraction and setting changes transfer Courier data.
R6539 on remote devices (primarily
on protective relays) within the KITZ
KAVR100 logic diagram The interface unit which
08 KAVR100 01 (11 sheets) substation environment.
converts between K-Bus and
KAVR130 logic diagram IEC60870-5 FT1.2 format
08 KAVR130 01 (12 sheets) data, which is used to transfer
Courier data over modems
KAVR130 service manual and RS232 connections.
R8523

Information required with order

Relay type KAVR

Models available:

Three phase tripping 1 0 0


Single and three phase tripping 1 3 0

Configuration:

Standard 0 1

Case size:

Size 4 MiDOS flush mounting L 1

Auxiliary voltage:

24/125V 2
48/250V 5

Transformer ratings:

Vn = 57.7 / 120V In = 0A J
KAVR 100/130

Language:

English E

Issue:

474

Vous aimerez peut-être aussi