Vous êtes sur la page 1sur 44

Motors | Automation | Energy | Transmission & Distribution | Coatings

DWB
Molded Case Circuit Breaker
UL 489 Listed
Molded Case
Circuit Breaker
Summary
Introduction 04

Selection Guide 06

Accessories 08

Internal Accessories 11

External Accessories 13

Technical Data 17

Installation and Connections 18

Trip Curves 20

Dimmensions - Inch (mm) 35


www.weg.net

DWB
Molded Case Circuit Breaker
UL 489 Listed

DWB400
In 200...400

DWB250
In 80...250

DWB160
In 20...100

4 DWB - Molded Case Circuit Breaker - UL 489 Listed


www.weg.net

Introducing the WEG DWB Series of Molded Case Circuit Breakers now available with UL 489
certification. With its three compact frames, the DWB UL provides protection from 20 to 400
amperes in two versions: Standard 80% rated and Premium 100% rated.

The DWB UL also counts with two levels of short circuit interrupting capacity, and common1)
internal accessories that simplify field installation and minimize inventory variations.

UL Interrupting Rating (kA)


MCCB DWB160 DWB250 DWB400
Type C J J P J P
@ 240 V ac 35 50 50 100 50 100
@ 480Y/277 V ac 10 14 14 35
@ 480 V ac 18 35

Current Ratings and Trip Units


Reference code Rated current In (A) Trip unit Curve

20, 25, 30, 40, 50,


DWB160 Fixed thermal Fixed magnetic2) (10 x In)
60, 70, 80, 90, 100

Ir
80-100, 100-125, 120-150,
DWB250 Adjustable thermal (0.8...1 x In) Fixed magnetic (10 x In)
160-200, 200-250

Ir
160-200, 180-225, 200-250,
DWB400 220-275, 240-300, 260-325, Adjustable thermal (0.8...1 x In) Adjustable magnetic (510 x In)
280-350, 320-400
Im

Note: 1) For DWB400, contact and alarm blocks only.


2) Circuit breakers with rated currents of 20 and 25 A, the magnetic trip point is 300 A.

DWB - Molded Case Circuit Breaker - UL 489 Listed 5


www.weg.net

Selection Guide
DWB160 for Distribution - Standard 80% Rated - Fixed Thermal and Fixed Magnetic Trip Unit
Interrupting ratings (kA) Reference code
Rated current (A) Magnetic trip point (A)
240 V ac 480Y/277 V ac 3 poles
DWB160CE
20 300 35 10 DWB160CE20-3DX
25 300 35 10 DWB160CE25-3DX
30 300 35 10 DWB160CE30-3DX
40 400 35 10 DWB160CE40-3DX
50 500 35 10 DWB160CE50-3DX
60 600 35 10 DWB160CE60-3DX
70 700 35 10 DWB160CE70-3DX
80 800 35 10 DWB160CE80-3DX
90 900 35 10 DWB160CE90-3DX
100 1000 35 10 DWB160CE100-3DX
DWB160JE
20 300 50 14 DWB160JE20-3DX
25 300 50 14 DWB160JE25-3DX
30 300 50 14 DWB160JE30-3DX
40 400 50 14 DWB160JE40-3DX
50 500 50 14 DWB160JE50-3DX
60 600 50 14 DWB160JE60-3DX
70 700 50 14 DWB160JE70-3DX
80 800 50 14 DWB160JE80-3DX
90 900 50 14 DWB160JE90-3DX
100 1000 50 14 DWB160JE100-3DX

DWB250 for Distribution - Standard 80% Rated - Adjustable Thermal and Fixed Magnetic Trip Unit
Interrupting ratings (kA) Reference code
Current range (A) Magnetic trip point (A)
240 V ac 480Y/277 V ac 3 poles
DWB250JE
80-100 1000 50 14 DWB250JE100-3DF
100-125 1250 50 14 DWB250JE125-3DF
120-150 1500 50 14 DWB250JE150-3DF
160-200 2000 50 14 DWB250JE200-3DF
200-250 2500 50 14 DWB250JE250-3DF
DWB250PE
80-100 1000 100 35 DWB250PE100-3DF
100-125 1250 100 35 DWB250PE125-3DF
120-150 1500 100 35 DWB250PE150-3DF
160-200 2000 100 35 DWB250PE200-3DF
200-250 2500 100 35 DWB250PE250-3DF

DWB400 for Distribution - Standard 80% Rated - Adjustable Thermal and Magnetic Trip Unit
Interrupting ratings (kA) Reference code
Current range (A) Magnetic trip point (A)
240 V ac 480 V ac 3 poles
DWB400JE
160-200 1600-2000 50 18 DWB400JE200-3DA
180-225 1800-2250 50 18 DWB400JE225-3DA
200-250 2000-2500 50 18 DWB400JE250-3DA
220-275 2200-2750 50 18 DWB400JE275-3DA
240-300 2400-3000 50 18 DWB400JE300-3DA
260-325 2600-3250 50 18 DWB400JE325-3DA
280-350 2800-3500 50 18 DWB400JE350-3DA
320-400 3200-4000 50 18 DWB400JE400-3DA
DWB400PE
160-200 1600-2000 100 35 DWB400PE200-3DA
180-225 1800-2250 100 35 DWB400PE225-3DA
200-250 2000-2500 100 35 DWB400PE250-3DA
220-275 2200-2750 100 35 DWB400PE275-3DA
240-300 2400-3000 100 35 DWB400PE300-3DA
260-325 2600-3250 100 35 DWB400PE325-3DA
280-350 2800-3500 100 35 DWB400PE350-3DA
320-400 3200-4000 100 35 DWB400PE400-3DA

Notes: Wiring terminals (lugs) built-in for DWB160 and supplied as standard with DWB250 and DWB400. Lugs are also available as an accessory for DWB250
and DWB400, see the section Accessories.

6 DWB - Molded Case Circuit Breaker - UL 489 Listed


www.weg.net

Selection Guide
DWB160 for Distribution - Premium 100% Rated - Fixed Thermal and Fixed Magnetic Trip Unit
Interrupting ratings (kA) Reference code
Rated current (A) Magnetic trip point (A)
240 V ac 480Y/277 V ac 3 poles
DWB160CH
20 300 35 10 DWB160CH20-3DX
25 300 35 10 DWB160CH25-3DX
30 300 35 10 DWB160CH30-3DX
40 400 35 10 DWB160CH40-3DX
50 500 35 10 DWB160CH50-3DX
60 600 35 10 DWB160CH60-3DX
70 700 35 10 DWB160CH70-3DX
80 800 35 10 DWB160CH80-3DX
90 900 35 10 DWB160CH90-3DX
100 1000 35 10 DWB160CH100-3DX
DWB160JH
20 300 50 14 DWB160JH20-3DX
25 300 50 14 DWB160JH25-3DX
30 300 50 14 DWB160JH30-3DX
40 400 50 14 DWB160JH40-3DX
50 500 50 14 DWB160JH50-3DX
60 600 50 14 DWB160JH60-3DX
70 700 50 14 DWB160JH70-3DX
80 800 50 14 DWB160JH80-3DX
90 900 50 14 DWB160JH90-3DX
100 1000 50 14 DWB160JH100-3DX

DWB250 for Distribution - Premium 100% Rated - Adjustable Thermal and Fixed Magnetic Trip Unit
Interrupting ratings (kA) Reference code
Current range (A) Magnetic trip point (A)
240 V ac 480Y/277 V ac 3 poles
DWB250JH
80-100 1000 50 14 DWB250JH100-3DF
100-125 1250 50 14 DWB250JH125-3DF
120-150 1500 50 14 DWB250JH150-3DF
160-200 2000 50 14 DWB250JH200-3DF
200-250 2500 50 14 DWB250JH250-3DF
DWB250PH
80-100 1000 100 35 DWB250PH100-3DF
100-125 1250 100 35 DWB250PH125-3DF
120-150 1500 100 35 DWB250PH150-3DF
160-200 2000 100 35 DWB250PH200-3DF
200-250 2500 100 35 DWB250PH250-3DF

DWB400 for Distribution - Premium 100% Rated - Adjustable Thermal and Magnetic Trip Unit
Interrupting ratings (kA) Reference code
Current range (A) Magnetic trip point (A)
240 V ac 480 V ac 3 poles
DWB400JH
160-200 1600-2000 50 18 DWB400JH200-3DA
180-225 1800-2250 50 18 DWB400JH225-3DA
200-250 2000-2500 50 18 DWB400JH250-3DA
220-275 2200-2750 50 18 DWB400JH275-3DA
240-300 2400-3000 50 18 DWB400JH300-3DA
260-325 2600-3250 50 18 DWB400JH325-3DA
280-350 2800-3500 50 18 DWB400JH350-3DA
320-400 3200-4000 50 18 DWB400JH400-3DA
DWB400PH
160-200 1600-2000 100 35 DWB400PH200-3DA
180-225 1800-2250 100 35 DWB400PH225-3DA
200-250 2000-2500 100 35 DWB400PH250-3DA
220-275 2200-2750 100 35 DWB400PH275-3DA
240-300 2400-3000 100 35 DWB400PH300-3DA
260-325 2600-3250 100 35 DWB400PH325-3DA
280-350 2800-3500 100 35 DWB400PH350-3DA
320-400 3200-4000 100 35 DWB400PH400-3DA

Notes: Wiring terminals (lugs) built-in for DWB160 and supplied as standard with DWB250 and DWB400. Lugs are also available as an accessory for DWB250
and DWB400, see the section Accessories.

DWB - Molded Case Circuit Breaker - UL 489 Listed 7


www.weg.net

Accessories
Overview of DWB160 and Accessories

10

2 3

1
11

5 6 8
9

1 - Molded case circuit breaker DWB160


2-A  uxiliary switch BC, alarm switch AL, alarm/contact block BCAL
3 - Undervoltage-trip release BS, shunt trip release BD
4 - Wiring terminal (lug) PC (built-in)
5 - Escutcheon MP DWB160
6 - Mechanical interlock BLIM DWB160 3P
7 - Lock-OFF device PLW DWB160 3P
8 - Panel door rotary operating handle MRX
9 - Panel door rotary operating handle MR
10 - DIN rail base BFR DWB160 3P UL
11 - Flange handle FH

8 DWB - Molded Case Circuit Breaker - UL 489 Listed


www.weg.net

Accessories
Overview of DWB250 and Accessories

2 3

7 8

5 6

1 - Molded case circuit breaker DWB250


2 - Auxiliary switch BC, alarm switch AL, alarm/contact switch BCAL
3 - Undervoltage release BS, shunt release BD
4 - Wiring terminal (lug) PC (supplied as standard)
5 - Escutcheon MP DWB250
6 - Mechanical interlock BLIM DWB250 3P
7 - Lock-OFF device PLW DWB250
8 - Panel door rotary operating handle MR
9 - Flange handle FH

DWB - Molded Case Circuit Breaker - UL 489 Listed 9


www.weg.net

Accessories
Overview of DWB400 and Accessories

2 3

8
7
5 6

1 - Molded case circuit breaker DWB400


2 - Auxiliary switch BC, alarm switch AL, alarm/contact switch BCAL
3 - Undervoltage release BS, shunt release BD
4 - Wiring terminal (lug) PC (supplied as standard)
5 - Escutcheon MP DWB400
6 - Mechanical interlock BLIM DWB400 3P
7 - Lock-OFF device PLW DWB400
8 - Panel door rotary operating handle MR
9 - Flange handle FH

10 DWB - Molded Case Circuit Breaker - UL 489 Listed


www.weg.net

Internal Accessories
Auxiliary Switches and Alarm Switches
The auxiliary switch and alarm switch have the function to signal remotely the status of circuit breakers power contacts.
There are 3 types of switches available:

BC Auxiliary Switch (Auxiliary Contact Block)


JJ 
Indicates the main contacts status open (OFF) / closed (ON) through a changeover
contacts (SPDT or form C contact)

AL Alarm Switch (Alarm Contact Block)


JJ Indicates circuit breakers trip due to overload, short-circuit, shunt trip or undervoltage-trip
release conditions through a changeover contact (SPDT or form C contact)
JJ The contact opens when the circuit breaker is reset

JJ Offers provisions for audio or visual indication of the under the conditions described above

BCAL
Ensemble comprised of an auxiliary switch + alarm switch The BCAL switch makes
JJ

both functions described above

Reference code
Internal accessory Number of contacts
DWB160 DWB250 DWB400
1 changeover BC-1 DWB
Auxiliary switch BC
2 changeover BC-2 DWB
Alarm switch AL 1 changeover AL-1 DWB
Auxiliary switch and alarm switch BCAL 1BC + 1AL BCAL-2 DWB
Electrical characteristics
Rated voltage Type of load Switching capacity (A)
125 V ac Resistive 6
250 V ac Resistive 6

Notes: Use BCAL switches when applications require auxiliary switch and alarm switch fitted in the same circuit breaker.
Not applicable for motor switching.

Using BC and AL Switches


BC, AL and BCAL switches already come with built-in terminal blocks. These terminal blocks accept wires of 20 to 16 AWG
(0.5 to 1.5 mm2) and tightening torque of 6.9 lb.in (0.8 N.m).

Wiring Diagrams

ON OFF TRIP

12 12
11 22 11 22
BC
21 14 21 14
24 24
82 82
AL 81 81
84 84

DWB - Molded Case Circuit Breaker - UL 489 Listed 11


www.weg.net

Internal Accessories
Shunt and Undervoltage Release
Voltage releases function to trip remotely the circuit breaker. They are often used for remote emergency stop purpose.

BD Shunt Release
JJ 
When energized by a pulse or maintained signal of voltage, the shunt release trips the
circuit breaker (trip position).
The shunt release works from 70 to 110% of the rated voltage (0.70 x Un <Ue <1.1 x Un)
JJ 
This release features a device to keep it not energized after the tripping pulse

BS Undervoltage Release
JJ 
Trips the circuit breaker when the voltage drops below 35% of the rated voltage (Ue
<0.35 x Un)
JJ 
When voltage is between 35 to 70% of the rate voltage, it may open the circuit breaker
(0.35 x Un <Ue <0.7 x Un)
JJ 
After the operation of BS release, circuit breaker can only be closed if supply voltage is
above 85% of the rated voltage (Ue >0.85 x Un)
JJ 
The BS undervoltage release along with an emergency stop push button makes possible
the fail-safe operation of the circuit breaker

Internal accessory Rated voltage - Ue Reference code


Undervoltage release BS BS DWB160-250
Shunt release BD BD DWB160-250
24 / 48 / 60 / 110-130 / 220-250 V ac/dc
Undervoltage release BS BS DWB400
Shunt release BD BD DWB400

To Complete the Reference Code, Replace " " with the Appropriate Voltage Code
E26 E27 E28 E10 E15
24 V ac/dc 48 V ac/dc 60 V ac/dc 110-130 V ac/dc 220-250 V ac/dc

Note: Other voltages upon request.

Using BD and BS Releases


BD and BS releases already come with built-in terminal blocks. These terminal blocks accept wires of 20 to 16 AWG
(0.5 to 1.5 mm2) and tightening torque of 6.9 lb.in (0.8 N.m). After BD or BS releases have operated, the circuit breaker have to
be reset before being closed again.
Wiring Diagrams

C1 D1
BD BS

C2 D2
Maximum Configurations - Internal Accessories
Internal accessory DWB160 DWB250 DWB400
Auxiliary switch 2 11) 2 11) 2 11) 2 11) 2 11) 2 11)
Alarm switch 0 11) 0 11) 0 11) 0 11) 0 11) 0 11)
Shunt release 1 1 0 0 1 1 0 0 1 1 0 0
Undervoltage release 0 0 1 1 0 0 1 1 0 0 1 1

Note: 1) Use BCAL switches when applications require auxiliary switch and alarm switch fitted in the same circuit breaker.

12 DWB - Molded Case Circuit Breaker - UL 489 Listed


www.weg.net

External Accessories
Panel Door Operating Handles
The panel door operating handles allow external operation of a circuit breaker installed in an electrical panel. WEG has
3 options to better fit according to customer needs.

MR Panel Door Rotary Operating Handles


JJ 
Degree of protection UL-type 1, 3R (IP55)
JJ 
When in ON position, panel door cannot be opened, unless a tool is used to bypass the
panel door locking system, allowing thermometry of the panel
JJ 
Circuit breaker and panel door padlocking in OFF position using 1 to 3 padlocks. MR allows
padlocks with diameters of 0.19...0.31 inches (5...8 mm)
JJ 
Handle shaft length can be adjusted up to 16.93 inches (430 mm)
JJ 
Available in 2 color versions: black handle/gray background and red handle/yellow
background
JJ 
Padlocks are not supplied

Rotary opeating Reference code


Handle color /
handle + Thermometry Degree of Shaft length Handle length
background
mechanism + feature protection (inch / mm) (inch / mm) DWB160 DWB250 DWB400
color
shaft
5.12 / 130 MR DWB160 130
Black / gray
16.93 / 430 MR DWB160 430
1.77 / 45
5.12 / 130 MR DWB160 130 E
Red / yellow
UL-type 1, 16.93 / 430 MR DWB160 430 E
MR Yes
3R, 12 (IP55) 5.12 / 130 MR DWB250 130 MR DWB400 130
Black / gray
16.93 / 430 MR DWB250 430 MR DWB400 430
3.15 / 80
5.12 / 130 MR DWB250 130 E MR DWB400 130 E
Red / yellow
16.93 / 430 MR DWB250 430 E MR DWB400 430 E

Handle color / Reference code


Thermometry Handle length
Rotary handle Degree of protection background
feature (inch / mm) DWB160 DWB250 DWB400
color
Black / gray RH DWB160
1.77 / 45
Red / yellow RH DWB160 E
RH Yes UL-type 1, 3R, 12 (IP55)
Black / gray RH DWB250-400
3.15 / 80
Red / yellow RH DWB250-400 E

Shaft length Reference code


Shaft Suitable for
(inch / mm) DWB160 DWB250 DWB400
5.12 / 130 ESB DWB160-400 130
ESB RH
16.93 / 430 ESB DWB160-400 430

Reference code
Mechanism Suitable for
DWB160 DWB250 DWB400
MRH RH MRH DWB160 MRH DWB250 MRH DWB400

DWB - Molded Case Circuit Breaker - UL 489 Listed 13


www.weg.net

External Accessories
Panel Door Operating Handles

MRX Panel Door Rotary Operating Handles


JJ 
Higher degree of protection UL-type 4x (IP66 for DWB160)
JJ 
When in ON position, panel door cannot be opened, unless a tool is used to bypass the
panel door locking system, allowing thermometry of the panel
JJ 
Circuit breaker and panel door padlocking in OFF position using 1 to 3 padlocks. MRX
allows padlocks with diameters of 0.16...0.31 inches
(4...8 mm)
JJ 
Handle shaft length can be adjusted up to 16.93 inches (430 mm)
JJ 
Available in 2 color versions: black handle/gray background and red handle/yellow
background
JJ 
Padlocks are not supplied

Rotary opeating handle + Shaft length Handle color / Reference code


Thermometry feature Degree of protection
mechanism + shaft (inch / mm) background color DWB160
5.12 / 130 MRX DWB160 130
Black / gray
16.93 / 430 MRX DWB160 430
MRX Yes UL-type 4x (IP66)
5.12 / 130 MRX DWB160 130 E
Red / yellow
16.93 / 430 MRX DWB160 430 E

Reference code
Rotary handle Thermometry feature Degree of protection Handle color / background color
DWB160
Black / gray RHX DWB160
RHX Yes UL-type 4x (IP66)
Red / yellow RHX DWB160 E

Shaft length Reference code


Shaft Suitable for
(inch / mm) DWB160
5.12 / 130 ESX DWB160 130
ESX RHX
16.93 / 430 ESX DWB160 430

Reference code
Mechanism Suitable for
DWB160
MRH RHX MRH DWB160

Note: Degree of protection rating (IP) according to IEC 60529.

14 DWB - Molded Case Circuit Breaker - UL 489 Listed


www.weg.net

External Accessories
Panel Door Operating Handles

FH Flange Handles
JJ Degree of protection UL-type 1, 12, 3R, 4 and 4x available
JJ 
When in ON position, panel door cannot be opened, unless a tool is used to bypass the panel door locking system,
allowing thermometry of the panel
JJ 
Flexible cable length up to 72 inches (1828 mm)
JJ 
Allows padlocking in OFF position using padlocks
JJ 
Padlocks are not supplied

Reference code
Flange handle Thermometry feature Degree of protection
DWB160 DWB250 DWB400
FHU Yes UL-type 1, 12, 3R, 4 FHU DWB160-250 FHU DWB400
FHX Yes UL-type 4, 4x FHX DWB160-250 FHX DWB400

Reference code
Flexible cable Length (inch) Suitable for
DWB160 DWB250 DWB400
36 FC DWB160-250 36i FC DWB400 36i
48 FC DWB160-250 48i FC DWB400 48i
FC FHU, FHX
60 FC DWB160-250 60i FC DWB400 60i
72 FC DWB160-250 72i FC DWB400 72i

Reference code
Mechanism Suitable for
DWB160 DWB250 DWB400
MFH FHU, FHX MFH DWB160 MFH DWB250 MFH DWB400

DWB - Molded Case Circuit Breaker - UL 489 Listed 15


www.weg.net

External Accessories
Changeover Device
Manual-operated changeovers are used to make safe switching of two different circuits.

BLIM Mechanical Interlock


JJ 
Provides safe operation in a manual-operated changeover system
JJ 
Makes the mechanical interlock of 2 circuit breakers of the same frame size, preventing both
MCCBs to be in ON position
JJ 
Interlock is assembled directly to the front cover of the circuit breakers
JJ 
It can be padlocked in 2 positions: MCCB1 ON and MCCB2 OFF, MCCB1 OFF and MCCB2 ON
JJ 
BLIM allows padlocks with diameters of 0.16...0.31 inches (4...8 mm)
JJ 
It is possible to interlock 3 MCCBs side-by-side using 2 BLIMs
JJ Padlocks are not supplied

External accessory MCCB Reference code


DWB160 BLIM DWB160 3P
Mechanical interlock BLIM DWB250 BLIM DWB250 3P
DWB400 BLIM DWB400 3P

Accessory for Connection and Installation


Depending on the application and local standards, the MCCB may be installed and connected through bus bars or cables.
Given these requirements, the DWB range of circuit breakers have the specific connection accessory to comply with.

PC Wiring Terminals (Lugs)


JJ 
Provides the means for connecting the circuit breaker to the power source and the load
JJ 
PC is supplied with 3 pieces that are suitable for either line or load terminals
JJ Built-in on DWB160 in the 6 terminals

External Supplied with Minimum cross-section Maximum cross-section Tightening torque


MCCB Reference code
accessory (units) (AWG / mm) (AWG / mm) (lb.in / N.m)
DWB250 4 / 16 (1 cable) 250 kcmil / 120 (1 cable) 221.2 / 25 PC DWB250 3P
Wiring terminal PC 3
DWB400 3/0 / 95 (1 cable) 500 kcmil / 240 (1 cable) 266 / 30 PC DWB400 3P

DIN Rail Base External accessory MCCB Reference code


JJ Quick assembly of DWB160 on 35 mm DIN rails
JJ 
DIN rail base DWB160 BFR DWB160 3P UL
Fast replacement when panel is under maintenance

Escutcheons and Lock-OFF Devices

MP Escutcheons
JJ 
Escutcheons are frames for cutouts in panel doors
JJ 
It makes possible the external switching of the MCCB through the front door when the circuit
breakers is installed close to the panel door, maintaining the degree of protection
JJ 
Degree of protection IP40
JJ 
See section Dimensions for cutout details

External accessory MCCB Reference code


DWB160 3P MP DWB160
Escutcheon MP DWB250 3P MP DWB250
DWB400 3P MP DWB400

Note: Degree of protection rating (IP) according to IEC 60529.

PLW Lock-OFF Devices


JJ 
The PLW is a fixed-type device that is installed on the front of the MCCB ensuring the MCCB locking in OFF position
JJ 
It can be padlocked using 1 to 3 padlocks. PLW allows padlocks with diameters of 0.16...0.31 inches (4...8 mm)
JJ 
Padlocks are not supplied

External accessory MCCB Reference code


DWB160 3P PL DWB160 3P
Lock-OFF device PLW DWB250 3P PL DWB250
DWB400 3P PL DWB400

16 DWB - Molded Case Circuit Breaker - UL 489 Listed


www.weg.net

Technical Data

Reference code DWB160 DWB250 DWB400


Frame size 160 250 400
Electrical characteristics according to UL 489
Rated operational voltage - Ue V ac (60 Hz) 480Y/277 480Y/277 480
Maximum rated continuous current - In (40 C) A 100 250 400
MCCB rating design 80%, 100%1)
160-200, 180-225, 200-250,
Rated current - In (40 C) A 20, 25, 30, 40, 50, 60, 70, 80, 90, 100 80-100, 100-125, 120-150,160-200, 200-250 220-275, 240-300, 260-325,
280-350, 320-400
Number of poles 3 3 3
Short-circuit breaking capacity levels C J J P J P
kA rms
240 V ac 35 50 50 100 50 100
UL interrupting rating - max RMS symmetrical
480Y/277 V ac 10 14 14 35
480 V ac 18 35
Number of operations 10000 6000 6000
Mechanical lifespan (C-O)
Operations per hour 360 240 240
Number of operations 6000 1000 1000
Electrical lifespan (C-O) @ 480 V ac
Operations per hour 360 240 240
Protection
Against short-circuit & overload (fixed thermomagnetic) Yes No No
Against short-circuit & overload (adjustable thermal and fixed magnetic) No Yes No
Against short-circuit & overload (adjustable thermal and magnetic) No No Yes
Accessories
Auxiliary switch BC Yes Yes Yes
Alarm switch AL Yes Yes Yes
Internal Auxiliary and alarm switches BCAL Yes Yes Yes
Shunt trip release BD Yes Yes Yes
Undervoltage-trip release BS Yes Yes Yes
Mechanical interlock BLIM Yes Yes Yes
Lock-OFF device PLW Yes Yes Yes
External
Escutcheons MP Yes Yes Yes
Wiring terminal (lug) PC Built-in Standard Standard
Panel door rotary operating handle MRX Yes No No
Handles Panel door rotary operating handle MR Yes Yes Yes
Flange handle FH/FHX Yes Yes Yes
Installation and connections
Suitable for reverse connection Yes Yes Yes
Maximum cross-section 3 AWG 250 kcmil 500 kcmil

Cables - Cu2) Minimum cross-section 10 AWG 4 AWG 3/0 AWG


Tightening lb.in (N.m) 57.2 (6.5) 221.2 (25) 266 (30)
torque
Tightening
Busbar lb.in (N.m) - 70 (8) 177 (20)
torque
Dimensions (W x D x H) Inches (mm) 3.07 x 2.87 x 6.30 (78 x 73 x 160) 4.17 x 2.99 x 7.83 (105 x 80 x 200) 4.22 x 3.9 x 10.08 (107 x 99 x 256)
Weight 3 poles Pounds (kg) 2.09 (0.95) 3.97 (1.8) 7.85 (3.56)

Notes: 1) For DWB160: suitable for continuous operation at 100 percent of rating only if used in a circuit breaker enclosure in a cubicle space 23.6 by 15.7 by 7.9 inches
(600 by 400 by 200 mm) or equivalent.
For DWB250: suitable for continuous operation at 100 percent of rating only if used in a circuit breaker enclosure in a cubicle space 31.5 by 23.6 by 11.8 inches
(800 by 600 by 300 mm) or equivalent.
F
 or DWB400: suitable for continuous operation at 100 percent of rating only if used in a circuit breaker enclosure in a cubicle space 47.2 by 23.6 by 15.8 inches
(1200 by 600 by 400 mm) or equivalent.
2) Use only 90 C rated wire with ampacity based on 75 C rated conductors.

DWB - Molded Case Circuit Breaker - UL 489 Listed 17


www.weg.net

Installation and Connections


Minimum Mounting Distances

DWB160

DWB250

DWB400
Recommended mounting distances (inch / mm)

A 1.97 / 50 1.97 / 50 2.76 / 70


A

B 0.79 / 20 0.79 / 20 1.18 / 30


C

C 0.79 / 20 0.79 / 20 1.18 / 30


Recommended distances between circuit breakers
for side by side assembly (inch / mm)
D

D 0.394 / 10 0.394 / 10 0.394 / 10

Recommended distances between circuit breakers


for vertical assembly (inch / mm)

E 3.54 / 90 5.91 / 150 7.09 / 180


E


90

90
90

Mounting position
90

Drilling for fixing the circuit breakers (inch / mm)

See section dimensions See section dimensions See section dimensions

DWB160/DWB250

Dimensions of fixing screw to


M4 x 2.99 / 76 (2 pieces) M4 x 2.99 / 76 (2 pieces) M5 x 1.97 / 50 (4 pieces)
the plate (inch / mm)
Surpass of the fixing screw in
relation to the circuit breaker (inch / mm)
H

H 0.315 / 8 0.236 / 6 0.59 / 15

Tightening torque - fixing screw (lb.in / N.m) 35.2 / 4 35.2 / 4 25 / 2.5

18 DWB - Molded Case Circuit Breaker - UL 489 Listed


www.weg.net

Installation and Connections


Conductor Installation
Reference code Tightening torque (lb.in / N.m) Conductor - Inch (mm)
1.55 A/mm
1,000 A/in 35...240 mm
4 AWG...250 kcmil

0.78 (19.5)
0.3
3
(8.5
)
DWB250 70 / 8

0.37
0.3

(9.5)
3
) (8.5)
(8
31
0.
ax
M

0.47
(12)
Max 0.47
0.94
(24) (12)
Max
0.94
(24)

1.55 A/mm
1,000 A/in 95...240 mm
1.06 (27) 3/0 AWG...500 kcmil

0.3
5
DWB400 177 / 20 (9)
0.47

0.3
1
(8)
2)
(1
47
0.
ax
M
0.47
(12)
Max 0.43
0.94
(24) (11)
Max
0.91
(23)

Thermal Dissipation
Distribution MCCB
Rated current - In A 20 25 30 40 50 60 70 80 90 100 125 150 200 250 275 300 325 350 400
Watts/pole
DWB160 1 2 4 4 5 8 4 5 6 7
Power loss
DWB250 14 19 17 14 20
DBW400 14 20 20 19 19 30 30

Deratings
50 F / 59 F / 68 F / 77 F / 86 F / 95 F / 104 F / 113 F / 122 F / 131 F / 140 F /
Temperature derating
10 C 15 C 20 C 25 C 30 C 35 C 40 C 45 C 50 C 55 C 60 C
DWB160 (x In) 1.16 1.12 1.09 1.07 1.02 1.02 1 0.97 0.95 0.91 0.88
DWB250 (x In) 1.15 1.13 1.10 1.08 1.05 1.02 1 0.98 0.95 0.92 0.88
DWB400 (x In) 1.16 1.13 1.10 1.08 1.05 1.02 1 0.98 0.94 0.90 0.88

Altitude derating 6500 ft / 2000 m 9800 ft / 3000 m 13100 ft / 4000 m 16400 ft / 5000 m
Rated current - In % 100 98 93 90
Rated operational voltage - Ue V ac 4801) 4801) 4801) 4001)

Notes: 1) For DWB160 and DWB250, consider Wye connection.

DWB - Molded Case Circuit Breaker - UL 489 Listed 19


www.weg.net

Trip Curves
DWB160 - Fixed Thermal and Fixed Magnetic (20100 A)

20000
20,000
Characteristic trip curve.
DWB160
DWB160 Characteristic trip curve.
The curves shown are for cold state and three pole
10000
10,000 The curves shown are for cold state and three pole
loaded. For hot state the time values are
loaded. For hot 25%
approximately stateofthe time
the values are
presented onapproximately
the cold
state25% of the presented on the cold state curve.
curve.
5000
5,000
ForFor
oneone pole
pole load,
load, thethe
timetimemay
mayrise
rise up
up to
to 20%.
20%.
ForFor
twotwo
polepole
load,load,
thethe
timetime mayrise
may riseup
uptoto10%.
10%

2000
2,000

1000
1,000

500
500

200
200

100
100

50
50

20
20
t t(s)
(s)

10
10

55

22

11

0.5
0.5

0.2
0.2
A: 12
25 A: 12 xx In
In 20 A:
A: 15
15 xx In
In
20
0.1
0.1

0.05
0.05 From 30
From 30 to
to 100
100 A:
A :10
10xxIn
In

0.02
0.02

0.01
0.01
11 1.3
1.3 22 33 44 55 66 7
7 8
8 10
10 12
12 15
15 20
20 30
30 40
40 50
50

xx InIn

20 DWB - Molded Case Circuit Breaker - UL 489 Listed


www.weg.net

Trip Curves
DWB250 - Adjustable Thermal and Fixed Magnetic (80250 A)

20000
20,000

DWB250
DWB250 Characteristic
The
Thecurves
trip curve.trip curve.
Characteristic
curvesshown
shownarearefor
for cold state
state and
andthree
threepole
pole
10000
10,000
loaded.loaded.
For hotForstate
hotthe time
state thevalues are are
time values
approximately 25%
approximately 25%of of
thethepresented
presentedononthe
thecold
cold
state curve.
5000
5,000
For For
oneone
polepole
load,
load,
state curve.
thethe
timetimemay
mayrise up to
rise up to 20%.
20%.
For For
twotwo
polepole
load, thethe
load, timetimemay
mayrise up to 10%.
rise up 10%.

2000
2,000

1000
1,000

500
500

200
200
Maximum
Maximum current adjustment:11xxInIn
current adjustment:

100
100

50
50

20
20
t(s)
t (s)

10
10

Minimum
Minimum current adjustment:0.8
current adjustment: 0.8x xInIn
55

22

11

0.5
0.5

0.2
0.2
10
10 xx In
In

0.1
0.1

0.05
0.05

0.02
0.02

0.01
0.01
1 1 1.3
1.3 2
2 33 44 55 66 77 88 10
10 20
20 30
30 40
40 50
50

x xIn
In

DWB - Molded Case Circuit Breaker - UL 489 Listed 21


www.weg.net

Trip Curves
DWB400 - Adjustable Thermal and Magnetic (200...400 A)

20000
20,000
Characteristic trip curve.
10000
10,000
DWB400
DWB400 The
Characteristic trip curve.
curves shown are for cold state and three pole
The curves shown are for cold state and three pole
loaded. For hot state the time values are
loaded. For hot state the time values are approximately
approximately 25% of the presented on the cold
25% of the presented on the cold state curve.
5000
5,000 state
Forcurve.
one pole load, the time may rise up to 20%.
For For
onetwo
pole load, the time may rise up 20%.
pole load, the time may rise up to 10%
For two pole load, the time may rise up 10%.

2000
2,000

1000
1,000

500
500

200
200
Maximumcurrent
Maximum currentadjustment:
adjustment:1 x1lnxIn
100
100

50
50

20
20
t (s)t (s)

10
10
Minimumcurrent
Minimum currentadjustment:
adjustment:0.80.8
x lnxIn

55

22

11
Maximum magnetic
Maximum magnetic
Minimum
Minimum magnetic
magnetic
0,5
0.5
adjustment:
adjustment: 55xxIn
ln
adjustment:10
adjustment: 10xxIn
ln

0,2
0.2

0,1
0.1

0,05
0.05

0,02
0.02

0,01
0.01
11 1,3
1.3 2
2 33 44 55 66 7
7 8
8 10
10 20
20 30
30 40
40 50
50

xx IIn n

22 DWB - Molded Case Circuit Breaker - UL 489 Listed


www.weg.net

Trip Curves
DWB160 - Short-Circuit Limiting Curves @ 240 V ac

50
50

40
40
DWB160
DWB160 -- UL
UL240
240V V

30
30

20
20

10
10
(k)
IpIp (k)

77

55

44

33

22

11
11 22 33 44 55 77 10
10 20
20 30
30 40
40 50
50 70
70 100
100

IsIs(kA)
(kA)

DWB - Molded Case Circuit Breaker - UL 489 Listed 23


www.weg.net

Trip Curves
DWB160 - Short-Circuit Limiting Curves @ 480Y/277 V ac

30
30

DWB160 - UL
DWB160 - UL480Y/277
480Y/277 Vac V ac

20
20

J
C
10
10

77
Ip Ip(k)
(k)

55

44

33

22

11
11 22 33 4
4 55 77 10
10 20
20

IsIs(kA)
(kA)

24 DWB - Molded Case Circuit Breaker - UL 489 Listed


www.weg.net

Trip Curves
DWB250 - Short-Circuit Limiting Curves @ 240 V ac

50
50

40
40 DWB250 - UL 240 V

30
30

P
J
20
20

10
10
IpIp(k)
(k)

77

55

44

33

22

11
11 22 33 44 55 77 10
10 20
20 30
30 40
40 50
50 70
70 100
100 200
200

IsIs(kA)
(kA)

DWB - Molded Case Circuit Breaker - UL 489 Listed 25


www.weg.net

Trip Curves
DWB250 - Short-Circuit Limiting Curves @ 480Y/277 V ac

50
50

40
40
DWB250
DWB250 UL
- UL-480Y/277
480Y/277 Vac V ac

30
30

20
20

10
10
Ip Ip(k)
(k)

77

55

44

33

22

11
11 22 33 44 55 77 10
10 20
20 30
30 40
40 50
50 70
70 100
100

IsIs(kA)
(kA)

26 DWB - Molded Case Circuit Breaker - UL 489 Listed


www.weg.net

Trip Curves
DWB400 - Short-Circuit Limiting Curves @ 240 V ac

50
50

P
40
40 DWB400
DWB400 --UL
UL240240V
V

J
30
30

20
20

10
10
Ip (k)
Ip (k)

77

55

44

33

22

11
11 22 3
3 44 55 77 10
10 20
20 30
30 40
40 50
50 70
70 100
100 200
200

IsIs(kA)
(kA)

DWB - Molded Case Circuit Breaker - UL 489 Listed 27


www.weg.net

Trip Curves
DWB400 - Short-Circuit Limiting Curves @ 480 V ac

50
50

40
40
DWB400
DWB400 -- UL
UL480
480V
V

30
30

20
20
P

10
10
Ip Ip(k)
(k)

77

55

44

33

22

11

11 22 33 44 55 77 10
10 20
20 30
30 40
40 50
50 70
70 100
100

Is Is(kA)
(kA)

28 DWB - Molded Case Circuit Breaker - UL 489 Listed


www.weg.net

Trip Curves
DWB160 - I2t @ 240 V ac

1000
1,000

700
700
DWB160
DWB160 -- UL
UL240
240V V

J
500
500 C
400
400

300
300

200
200

100
100

70
70

50
50
I t (10 AAs)

40
40
2 s)

30
It (10
3

30
2

20
20

10
10

77

55
44
33

22

11
11 22 33 44 55 77 10
10 20
20 25
25 30
30 40
40 50
50 70
70

IsIs(kA)
(kA)

DWB - Molded Case Circuit Breaker - UL 489 Listed 29


www.weg.net

Trip Curves
DWB160 - I2t @ 480Y/277 V ac

1000
1,000

700
700
DWB160 - -UL
DWB160 UL 480Y/277
480Y/277 V acV ac
J

500
500 C
400
400

300
300

200
200

100
100

70
70

50
50
t (10 A As)

40
40
2 s)

30
It I(10

30
3
2

20
20

10
10

77

55
44
33

22

11
11 22 33 44 55 77 10
10 14
14 20
20

IsIs(kA)
(kA)

30 DWB - Molded Case Circuit Breaker - UL 489 Listed


www.weg.net

Trip Curves
DWB250 - I2t @ 240 V ac

2000
2,000

DWB250
DWB250 -- UL
UL240
240V V

1000
1,000 P
J
700
700

500
500

400
400

300
300

200
200

100
100

70
70
I t (10 AAs)

50
s)

50
2
It (10

40
3

40
2

30
30

20
20

10
10

77

55
44
33

22

11
11 22 33 44 55 77 10
10 20
20 30
30 40
40 50
50 70
70 100
100 150
150

IsIs(kA)
(kA)

DWB - Molded Case Circuit Breaker - UL 489 Listed 31


www.weg.net

Trip Curves
DWB250 - I2t @ 480Y/277 V ac

2000
2,000
P
DWB250 - UL
DWB250 - UL480Y/277
480Y/277 VacV ac

1000
1,000
J
700
700

500
500

400
400

300
300

200
200

100
100

70
70
I t (10 AAs)

50
s)

50
2
It (10

40
3

40
2

30
30

20
20

10
10

77

55
44
33

22

11
11 22 33 44 55 77 10
10 14
14 20
20 30
30 35
35 50
50

Is Is(kA)
(kA)

32 DWB - Molded Case Circuit Breaker - UL 489 Listed


www.weg.net

Trip Curves
DWB400 - I2t @ 240 V ac

5000
5,000

DWB400
DWB400 --UL
UL240
240V
V

P
2000
2,000 J

1000
1,000

700
700
500
500
400
400
300
300

200
200
I t (10 As)

100
100
2 A s)

70
3
It (10

70
2

50
50
40
40
30
30

20
20

10
10

77
55
44
33

22

11
11 22 33 44 55 77 10
10 20
20 30
30 40
40 50
50 70
70 100
100 150
150

Is Is(kA)
(kA)

DWB - Molded Case Circuit Breaker - UL 489 Listed 33


www.weg.net

Trip Curves
DWB400 - I2t @ 480 V ac

10000
10,000

DWB400 - UL
DWB400 - UL480V
480 V

P
2000
2,000

1000
1,000

700
700

500
500
400
400

300
300

200
200
I t (10 AAs)
2 s)

100
100
It (10
3

70
2

70

50
50
40
40

30
30

20
20

10
10

77
55
44
33

22

11
11 22 33 44 55 77 10
10 18
18 30
30 35
35 50
50
Is (kA)
Is (kA)

34 DWB - Molded Case Circuit Breaker - UL 489 Listed


www.weg.net

Dimensions - Inch (mm)


Circuit Breakers

DWB160 Drilling for Fixing

0.984
(25)
2x
M4
6.25 (158.8)
4.01 (102)
1.77 (45.2)

3.93 (100)
1.49 (38.1)
0.883
(22.4)

2.62 (66.8)
0.984 0.984
(25) (25) 2.58 (65.7)
2.77 (70.4)
3.06 (77.9)
2.91 (74)
3.04 (77.4)
3.63 (92.4)

DWB250 Drilling for Fixing

1.37
(35)

2xM
4
5.31 (135)

0.886
(22.5)
7.79 (198.1)
1.77 (45)

2.38 (60.6)

3.28 (83.6)

4.88 (124)

1.37 1.37
(35) (35) 2.68 (68.3)
4.16 (105.8) 2.94 (74.8)

3.07 (78)

3.26 (83)

4.20 (106.8)

DWB400 Drilling for Fixing

4x 1,38
M5
38 35
5 44xx 1.38
1,38
MM5 (35)
5 35
7,83
199

103,2
4,06

(51.6)
(103.2)

2.03
2,03
51,6
12,72
323
(323)
4.06103,2

(199)
7.83
4,06

7,83
199

103,2
2,03
51,6
12,72

4,06
323
12.72

12,72
323
(168.5)
6.63
168,5
6,63
3,31
84,1

168,5
6,63
(84.1)
3.313,31
84,1

3,31
84,1

3.90
3,90
(99.1)
99,1
4.33
4,33
(109.9)
109,9
3,90 4.50
4,50
99,1 (114.4)
114,4
4.19
(106.5) 5.07
5,07
4,33 (128.8)
128,8
109,9
4,50
114,4
5,07
128,8
DWB - Molded Case Circuit Breaker - UL 489 Listed 35
www.weg.net

Dimensions - Inch (mm)


Accessories

BLIM - Mechanical Interlock

2 x Frame 160 + BLIM DWB160 3P Drilling for Fixing

4.13 (105)
0.984 (25)
4x
M4
6.25 (158.8)

3.93 (100)
1.06
3.06 (77.9) (27.1) 4.04 (102.6)

7.20 (182.9)

2 x Frame 250 + BLIM DWB250 3P Drilling for Fixing


4.27 (108.5) 4.92 (125.1)
1.37
4

(35)
x
M
4
7.79 (198.1)

4.88 (124)

0.760
4.16 (105.8) (19.3)

9.09 (230.9)
1

2 x Frame 400 + BLIM DWB400 3P Drilling for Fixing

4.61
4,61
(117)
117
44xxM 1.38
1,38
M5
5 (35)
35
103,2
4,06

(51.6)
12,72

2.03
323

2,03
51,6

(168.5)
(103.2)

6.63
168,5
103,2
4.06

6,63
4,06

(199)
7.83
7,83
199
12.72

116,9
(323)

4,60
12,72
323

2,03
51,6

0.10
168,5
6,63

0,10 3.90
3,90
(2.5)
2,5 (99.1)
99,1
(116.9)
116,9
4.60

4.33
4,60

4,33
(109.9)
109,9
4.50
4,50
(114.4)
114,4

5.07
5,07
(128.8)
128,8
8.79 0,10 3,90
5.63
5,63
(223.3) 2,5 99,1 (142.9)
142,9
4,33
109,9
4,50
114,4
36 DWB - Molded Case Circuit Breaker - UL 4895,07Listed
128,8

5,63
142,9
www.weg.net

Dimensions - Inch (mm)


Accessories
MR - Panel Door Rotary Operating Handles

Frame 160 + MRX DWB160 Panel Door Cutout


25.4...127
(1...5)
)
5
4x
9 7(
0.1
0.126
(3.2)
6.25 (158.8)

1.90 (48.5)
0.965
(24.5)
86
0.8 2.5)
2
(
16.93
(430)

0.984...1102
2.05 (52.3) (25...28)

3.06 (77.9) 4.71 (119.7) 1.90 (48.5)

Frame 160 + MR DWB160 Panel Door Cutout


)
5
25.4...127 (2 x
97
(1...5) 0.1
6.25 (158.8)
1.64 (41.7)

1.22 (31)

2.09 (53)
16.93 (430) 45

1.77 (45)

3.06 (77.9) 4.72 (119.9)

Frame 250 + MR DWB250 Panel Door Cutout

25.4...127 97
(1...5) 0.1 5)
x
(2
7.79 (198.1)
(41.7)
1.64

1.22 (31)

2.08 (53)

16.93
(430)
45

1.77 (45)

4.16 (105.8) 5.11 (129.8)

Frame 400 + MR DWB400


4x 1,38
M5
35
4x 1,38
M5
35
(103.2)
7,83

323 (323)
199

103,2
4,06

12,72
323
7,83
199

(84.1) 4.06103,2
4,06

12.72
12,72

(168.5)
6.63 168,5
6,63
3,31
84,1

168,5
6,63
3.313,31
84,1

3.90 (99.1)
3,90
99,1

4.19 (106.5) 13.1713,17


(334.4)
334,4
3,90
99,1
13,17
334,4

DWB - Molded Case Circuit Breaker - UL 489 Listed 37


Y

11
34,8
34,8

www.weg.net
194,1

194,1
A
X X
Y

11
108
Y

11
322,1

100,1
124

A
Y X X

322,1
108
Dimensions - Inch (mm)

17,4

124

A
B X X X

108
out - DWB250
X X
201

201
Accessories Y

Y
FH - Flange Handle B

Panel door Cutout - DWB250


B
Y Frame 160 + FH DWB160-250 Panel door Cutout - DWB250
7,87

A UP
7,87
7

49,3
Lenghts 36", 48", 60", 72".
26,6
75,7
2.98 (75.7)

A DOWN
49,3
1.94 (49.3)
Y
26,6
1 (26.6)

Y
Y
11

B MAX
Y
194,1

X X
108

119

194,1 (194.1)

41,8
7.64
322,1

Y
11

Y 0.99
X
41,8
(41.8)
(322.1)
(100.1)

12.68

(11)
3.94
201

0
100,1

322,1
(17.4)
0.69

0.43
A
76

17,4

X X
108

11
119

MENSION
YY
XX XX
7.9201(201)

FHU/FHX - 60'' 7,87 FHU/FHX - 72''


25.79 30.79
1.0676 (76)

4.25108(108)
119 (119)

24.79 29.79
AA

Y
23.79 28.79 B XX XX
kg kg
4.69

MASSA BRUTA/GROSS WEIGHT MASSA LQUIDA/NET WEIGHT ESCALA/SCALE


22.79 27.79
21.79 26.79
20.79 25.79 00
0.31
7,87 RESUMO DE MODIFICAES EXECUTADO VERIFICADO LIBERADO DATA
19.79 24.79 Panel door Cutout - DWB160 ECM LOC VER
(7.87) SUMMARY OF MODIFICATIONS EXECUTED CHECKED RELEASED DATE
18.79 23.79 RODRIGOGL
Y EXEC
FH Flange Handles
VERIF/CHECKED
YY
LIBER/RELEASED BB 00

SWD - A2
Table 2 MAXIMUM "B" DIMENSION DT LIBER/REL DT 07.08.2014 FOL/SHEET 1 2
Enclousure Propriedade da WEG. Proibida reproduo sem autorizao prvia./ WEG's property. Forbidden reproduction without previous authorization.
Depth FHU/FHX - 36'' FHU/FHX - 48'' FHU/FHX - 60'' FHU/FHX - 72''
10 15.79 10.79 25.79 30.79 Panel door
Panel door cutout
Cutout - DWB160
- DWB160
12 14.79 12.79 Y 24.79
Y 29.79
Lenghts 36", 48", 60",1672". 13.79 16.79 23.79 28.79
Lenghts 36, 48, 60, 72 MASSA BRUTA/GROSS WEIGHT kg MASS
18 12.79 18.79 22.79 27.79
20 - 20.79 21.79 Table 226.79 MAXIMUM "B" DIMENSION
24Table 1 - Maximum "A" Dimension- 20.79 25.79
Enclousure
30
Enclousure 36" - 48" 60"- 72 19.79 Depth24.79 FHU/FHX - 36'' FHU/FHX - 48'' FHU/FHX - 60'' FHU/FHX - 72'' ECM LOC
RESUMO DE MODIFICAES
SUMMARY OF MODIFICATIONS
36Depth Up Down- Up Down Up Down - Up Down 18.79 23.79 EXEC RODRIGOGL
10 15.79 10.79 25.79 30.79 FH Flange Handles
10 10 21 11 25 17 31 20 34 12 14.79 12.79 24.79 29.79 VERIF/CHECKED
12Table 110 23 12 26 17 31 19 33 16 13.79
Maximum A dimension (inches)
16.79 23.79 28.79 LIBER/RELEASED
16 10 20 12 23 17 28 36
19 30 18
48
12.79 18.79
60
22.79 27.79
72
DT LIBER/REL DT 07.08.2014
Enclousure depth
18 10 20 12 23 Up17 28 19 30 Down 20 Up - Down 20.79 Up 21.79 Down 26.79 UpPropriedade da WEG. Proibida reproduo
Down sem autorizao prvia./ WEG's property. Forbidden reproduction witho
20 10 - - 11 21 1016 26 18 28 21 24 11 - 25 - 17 20.79 31 25.79 20 34
24 12 - - - - 1014 26 16 28 23 30 12 - 26 - 17 19.79 31 24.79 19 33
30 16 - - - - 1011 24 13 26 20 36 12 - 23 - 17 18.79 28 23.79 19 30
36 18 - - - - 10 6 21 8 22 20 12 23 17 28 19 30
20 - - 11 21 16 26 18 28
24 - - - - 14 26 16 28
30 - - - - 11 24 13 26
36 - - - - 6 21 8 22

Table 2 Maximum B dimension (inches)


Enclousure depth FHU/FHX-36 FHU/FHX-48 FHU/FHX-60 FHU/FHX-72
10 15.79 10.79 25.79 30.79
12 14.79 12.79 24.79 29.79
16 13.79 16.79 23.79 28.79
18 12.79 18.79 22.79 27.79
20 - 20.79 21.79 26.79
24 - - 20.79 25.79
30 - - 19.79 24.79
36 - - 18.79 23.79

38 DWB - Molded Case Circuit Breaker - UL 489 Listed


34,8

www.weg.net

194,1
Y

11
100,1

322,1
17,4

124

A
X X

108

119
X X

Dimensions - Inch (mm) 201

Accessories Panel door Cutout - DWB250

5 Y 6 7 8 9 10
FH - Flange Handle 7,87

A UP
75,7 Frame 250 + FH DWB160-250
49,3 1 2 3 4 5 6 7
26,6 2.98
75,7
(75.7)

A DOWN
Y 1.94 (49.3)
49,3

1 (26.6)
26,6
A
Y
Y

B MAX
194,1 (194.1)
194,1

1.37
34,8
(34.8)

(11)
7.64

41,8

0.43
YY
100,1

11
322,1

3.94100,1(100.1)

B
17,4

12.68322,1(322.1)
11

Y
0.6917,4(17.4)

4.88124 (124)

X X
108

119

4.25108(108)
4.69119 (119)
201

XX XX

AA
A
76

X X
108

XX XX
119
7.9 (201)
201

7,87

Y Y
Y
B
C B
B

Panel door Cutout - DWB160


Panel
Panel doordoor cutout - DWB250
Cutout - DWB250
Y
Y
Y
0.317,87(7.87)
Table 2 MAXIMUM "B" DIMENSION
ximum "A" Dimension Enclousure
48" 60" 72 Depth FHU/FHX - 36'' FHU/FHX - 48'' FHU/FHX - 60'' FHU/FHX - 72''
Lenghts 36", 48", 60", 72".
Up Down Up Down Up Down Lenghts 36, 48, 60, 72.
10 15.79 10.79 75,7 25.79 30.79
11 25 17 31 20 34 12 14.79 12.79 24.79 29.79
12 26 17 31 19 33 Table161 13.79 16.79 Maximum 49,3 A dimension28.79(inches)
23.79 Table 2 Maximum B dimension (inches)
12 23 17 28 19 30 18 12.79 18.79 22.79 27.79 MASSA BRUTA/GROSS WEIGHT kg MASSA LQUIDA/NET WEIGHT kg ESCALA/SCALE
12 23 D 17 28 19 30 Enclousure 20 - 36 20.79 48
26,6 21.79 60
26.79 72 Enclousure
11 21 16 26 18 28 FHU/FHX-36 FHU/FHX-48 FHU/FHX-60 FHU/FHX-72
- - 14 26 16 28
depth 24 Up - Down - Up Down
20.79 Up 25.79 Down Up Down depth RESUMO DE MODIFICAES EXECUTADO VERIFICADO LIBERADO
30 - - 19.79 24.79 ECM LOC
- - 11 24 13 26 10 36 10 - 21 - 11
Y 25
18.79 17 23.79 31 20 34 10 15.79 EXEC
10.79 RODRIGOGL
25.79
SUMMARY OF MODIFICATIONS
30.79 EXECUTED CHECKED RELEASED

- - 6 21 8 22 FH Flange Handles
12 10 23 12 26 17 31 19 33 12 14.79 VERIF/CHECKED 12.79 24.79 29.79
00
16 10 20 12 23 17 28 19 30 16 13.79 LIBER/RELEASED
16.79 07.08.2014
23.79 28.79 1 2
DT LIBER/REL DT FOL/SHEET
18 10 20 12 23 17 28 19 30 18 12.79 Propriedade da WEG. Proibida reproduo
18.79 22.79
sem autorizao prvia./ WEG's property. Forbidden reproduction without previous authorization. 27.79
20 - - 11 21 16 26 18 28 20 - 20.79 21.79 26.79
24 - - - - 14 26 16 28 24 - - 20.79 25.79
E 30 - - - - 11 24 13 26 30 - - 19.79 24.79
194,1

36 - - - - 6 21 8 22 36 - - 18.79 23.79
1,831
46,5

Frame 400 + FH DWB400 41,8


100,1

322,1
17,4

11

2,362
60 1,16
0,2 1,831 Y
68 X
46,5 X 29,5
6,8
0,433
11

201

F 1.8311,831
(46.5) 9,17
2.362
46,5 R233 1.16
A

2,362
(60)
76

X X 60 1,16
(29.5)
108

0,2 29,5
68
119

6,8
9 7
0,433

(RR229,.1
11

31 0.
(11)

(620,268
17
0,3 ,4
8 7,87
33)
33 2,362
60 1,16
.86,8)68 29,5
0.433
4,252

3,819

4,685

0,433

31
108

119

11
97

0,3 ,4
7,874

8
200

9,17
F

R233 Y
4,252

3,819

4,685
119

108

119
(200)

97

B
31
F

0.30,338.1,44)
108(108)

119(119)
97 (97)

( 8
(281.6)
7,874
200

11.09
11,09
281,6
7.874

11,09
281,6
4.2524,252
3,819

4,685
3.819
4.685
FF

Panel door Cutout - DWB160


G 4x 10
-24 UNC
Y
Lenghts 36", 48", 60", 72". E
11,09
281,6

E
Table 2 MAXIMUM "B" DIMENSION
4xTable 1NUNC
410U-24
C
Maximum "A" Dimension
4x 10 -2 36" 48" 60"
EE
72
Enclousure
Depth FHU/FHX - 36'' FHU/FHX - 48'' FHU/FHX - 60'' FHU/FHX - 72''
Enclousure
Depth Up Down Up Down Up Down Up Down 10 15.79 10.79 25.79 30.79
10 10 21 11 25 17 31 20 34 12 14.79 12.79 24.79 29.79
12 10 23 12 26 17 31 19 33 16 13.792 16.79 23.79 (inches) 28.79
Table
16 1 10 20Maximum 12 23 17E28dimension
19 30 (inches) Table Maximum F dimension E MAX MASSA BRUTA/GROSS WEIGHT
18 12.79 18.79 22.79 27.79
Enclousure
18 10 20 12 23 17 28 19 30 20 Enclousure
- 62 20.79
cable 72
21.79cable 26.79
20 - - 11FHU-60 21 16 26 18 28 FHU-72
H depth
24 - - - - 14 26 16 28
24 depth- Up - Down Up20.79 Down 25.79
HX - 72'' 30 - - 19.79 24.79 F UP ECM
10
30 - - - 25 - 11 24 13 26 30 36 10 - 17 - 31 2018.79 34 23.79 EXEC R
30.79 36
12 - - - 24 - 6 21 8 22 29 12 17 31 19 33 VERIF/CHECKED
29.79 16 23 28 16 17 28 19 30 LIBER/RELEASED
28.79
F DOWN

27.79 18 22 27 18 MASSA BRUTA/GROSS17


WEIGHT 28 19 30 kg MASSA LQUIDA/NET WEIGHT kg ESCALA/SCALE DT LIBER/REL DT 0
Propriedade da WEG. Proibida reproduo sem
26.79 20 21 26 20 16 26 18 28
00
25.79 24 20 25 24 14 26 16 28
RESUMO DE MODIFICAES EXECUTADO VERIFICADO LIBERADO DATA
24.79 30 19 24 30 ECM
11 LOC
24 13 26OF MODIFICATIONS
SUMMARY EXECUTED CHECKED RELEASED DATE
VER
23.79
36 18 23 36 EXEC
6 RODRIGOGL
21 8 22 Handles
FH Flange
VERIF/CHECKED
LIBER/RELEASED 00
SWD - A2

DT LIBER/REL DT 07.08.2014 FOL/SHEET 1 2


DWB - Molded Case Circuit Breaker - UL 489 Listed
Propriedade da WEG. Proibida reproduo sem autorizao prvia./ WEG's property. Forbidden reproduction without previous authorization. 39
www.weg.net

Dimensions - Inch (mm)


Accessories

PLW - Lock-OFF Devices

Frame 160 + PLW DWB160 3P Panel Door Cutout


2.32 (59)
0.984
(25)

2x
23 ) M4
0.3 8.2
x
(3
6.25 (158.8)

3.93 (100)
3.06 (77.9) 3.68 (93.6)

Frame 250 + PLW DWB250 Panel Door Cutout

1.49 (38)

1.37
2

(35)
xM
4

23 )
0.3 8.2
x
(3
4.88 (124)

4.16 (106)
4.08 (104)

Frame 400 + PLW DWB400 Panel Door Cutout


4x 1,38
M5
35

44xxM 1.38
1,38
M5 5 (35)
35
7,83
199

103,2
4,06

12,72
323

(51.6)
2.03
2,03
51,6
(103.2)
4.06
103,2

(199)
4,06

7.83
7,83
12.72

199
(323)

103,2
12,72

4,06
323

(168.5)

12,72
2,03
51,6

323
6.63
168,5
6,63
3,31
84,1

168,5
6,63
(84.1)
3.31
3,31
84,1

3,31
84,1

3.903,90
(99.1)
99,1
4,33
4.33 109,9
(109.9)
4,50
4.50114,4
(114.4)
5,07
4.19 (106.5) 3,90 5.07128,8
(128.8)
99,1
4,33
109,9
4,50
40 DWB - Molded Case Circuit Breaker
114,4
5,07
- UL 489 Listed
128,8
www.weg.net

Dimensions - Inch (mm)


Accessories

MP - Escutcheons

MP DWB160 1.22
(31)
1.97
(50)

(46.7)

2.48
1.84

(63)
2.99
(76)

0.12

(2.8
0.11
(3)

MP DWB250 )
1.44
2.19 (36.50)
(55.5)
2.99

(46.7)

2.48
(76)

(63)
1.84

7
3 0.12
(2.8
0.11

(3)
)

1,47
MP DWB400
37,3

1.47
1,47
(37.3)
37,3

3,15
80
(120.5)

3,15
3.15
143,6

120,5
4.74
3,80
96,5
5,65

4,74

3,15 (80)
80 80
(143.6)
(96.5)

143,6

120,5
3.80

5.65
3,80
96,5
5,65

4,74
143,6

120,5
3,80
96,5
5,65

4,74

(6.1)
6,1
0.24
0,24

0.32
0,32
6,1

(8.2)
0,24

8,2

0,32
8,2

DWB - Molded Case Circuit Breaker - UL 489 Listed 41


6,1
,24
www.weg.net

1 2 3 4 5

Dimensions - Inch (mm)


1 1 2 2 3 3 4 4 5 5
Accessories

BFR - DIN Rail Base

BFR DWB160 3P UL

1,78
45,2
3 4 5 6

1,78
45,2

1,78
45,2
(1.78)
45.2
100,1
3,94

117,5
4,62
100,1

100,1
(100.1)
3,94

3,94

117,5

117,5
3.94

(117.5)
4,62

4,62
4.62
1,78
45,2

0,05
0,98 1,27
24,90
0,25
6,3
117,5
4,62

0,05
0,38 0,05
(0.05)
0,98
(0.98) 0,98 1,27
9,7 1,27
1.27
24,90
24.90 24,90
0,25 0,25
(0.25)
6,3 6,3
6.3

0,38 0,38
(0.38)
9,7 9.7
9,7

2,76
(2.76) 0,05
70
70 1,27
0,25
6,3
2,76 2,76 0,38
70 70 9,7 BFR DWA160

03/08/2012 1:1 mm [inche

BFR DWA160 BFR DWA160

03/08/2012 03/08/2012 1:1 1:1 mm [inches

BFR DWA160

03/08/2012 1:1 mm [inches]


A3

42 DWB - Molded Case Circuit Breaker - UL 489 Listed


www.weg.net

The Global Solution with electric machines and automation for industry
and energy systems
WEG, one of the largest global manufacturers of Electric Motors with Quality and Efficiency recognized
in different industrial areas worldwide, is also present in Energy, Transmission and Distribution, Coatings
and Industrial Automation sectors, and produces and offers a wide range of electric components for
Motor Control and Protection and Electric Circuit Protection.

Motor Protection and Starters Pushbuttons and Pilot Lights


JJ Modular contactors up to 800 A (AC-3) JJ IP66 pushbuttons and pilot lights
JJ Compact contactors up to 22 A (AC-3) JJ 
Flush, guarded, extended or mushroom illuminated
JJ Control relays or non illuminated pushbuttons
JJ Motor protective circuit breakers up to 100 A JJ 
Selector switches lever or knob illuminated or non
JJ Enclosed starters (plastic or metallic enclosures) illuminated or with key
JJ Customized starters for OEM applications JJ Emergency pushbuttons (according EN 418)

JJ Overload relays JJ Contact blocks with positive break system

JJ Double pushbutton

Electrical Circuit Protection JJ Pilot lights with LED technology


JJ Miniature circuit breakers up to 125 A JJ Customized descriptions
JJ Molded case circuit breakers up to 1600 A (3P and 4P) JJ Decentralized control stations - PBW
JJ Air circuit breakers up to 6300 A

JJ D gL-gG fuses up to 63 A Smart Relay


JJ NH gL-gG fuses up to 630 A JJ Low voltage electric motor management system
JJ NH aR fuses up to 1000 A JJ Compact and modular concept

JJ Switch-disconnectors for door or base mounting up to 160 A JJ 


Full motor protection and monitoring through current
JJ 
Residual current circuit breaker up to 100 A (30 or 300 mA) and voltage measurements
JJ Surge supressors JJ Multiple operating modes including PLC functions

JJ 
Easy network module change via exclusive drawer
Electrical Connections system (Modbus, DeviceNet, Profibus modules)
JJ Terminal blocks with screw type connection JJ USB communication
JJ Terminal block with spring type connection
JJ Free WLP programming software
JJ Terminal blocks for fuses

JJ Busbar and busbar connectors Electronic Relays


JJ Identifiers for terminals and cables JJ Timing, monitoring and level relays
JJ Printing system JJ 22.5 mm width frame

JJ LED for status indication

Capacitors JJ 
Multifunction three-phase monitoring relays
JJ Power factor compensation and timer relays
JJ Lighting

JJ Motor-run

DWB - Molded Case Circuit Breaker - UL 489 Listed 43


WEG Worldwide Operations

ARGENTINA COLOMBIA JAPAN SPAIN


San Francisco - Cordoba San Cayetano - Bogota Yokohama - Kanagawa Coslada - Madrid
Phone: +54 3564 421484 Phone: +57 1 4160166 Phone: +81 45 5503030 Phone: +34 91 6553008
info-ar@weg.net info-co@weg.net info-jp@weg.net wegiberia@wegiberia.es

Cordoba - Cordoba ECUADOR MALAYSIA SINGAPORE


Phone: +54 351 4641366 El Batan - Quito Shah Alam - Selangor Singapore
weg-morbe@weg.com.ar Phone: +593 2 5144339 Phone: +60 3 78591626 Phone: +65 68589081
ceccato@weg.net info@wattdrive.com.my info-sg@weg.net
Buenos Aires
Phone: +54 11 42998000 FRANCE MEXICO Singapore
ventas@pulverlux.com.ar Saint-Quentin-Fallavier - Isre Huehuetoca - Mexico Phone: +65 68622220
Phone: +33 4 74991135 Phone: +52 55 53214275 watteuro@watteuro.com.sg
AUSTRALIA info-fr@weg.net info-mx@weg.net
Scoresby - Victoria SCANDINAVIA
Phone: +61 3 97654600 GERMANY Tizayuca - Hidalgo Mlnlycke - Sweden
info-au@weg.net Trnich - Kerpen Phone: +52 77 97963790 Phone: +46 31 888000
Phone: +49 2237 92910 info-se@weg.net
AUSTRIA info-de@weg.net NETHERLANDS
Markt Piesting - Wiener Oldenzaal - Overijssel UK
Neustadt-Land Balingen - Baden-Wrttemberg Phone: +31 541 571080 Redditch - Worcestershire
Phone: +43 2633 4040 Phone: +49 7433 90410 info-nl@weg.net Phone: +44 1527 513800
watt@wattdrive.com info@weg-antriebe.de info-uk@weg.net
PERU
BELGIUM Homberg (Efze) - Hesse La Victoria - Lima UNITED ARAB EMIRATES
Nivelles - Belgium Phone: +49 5681 99520 Phone: +51 1 2097600 Jebel Ali - Dubai
Phone: +32 67 888420 info@akh-antriebstechnik.de info-pe@weg.net Phone: +971 4 8130800
info-be@weg.net info-ae@weg.net
GHANA PORTUGAL
BRAZIL Accra Maia - Porto USA
Jaragu do Sul - Santa Catarina Phone: +233 30 2766490 Phone: +351 22 9477700 Duluth - Georgia
Phone: +55 47 32764000 info@zestghana.com.gh info-pt@weg.net Phone: +1 678 2492000
info-br@weg.net info-us@weg.net
INDIA RUSSIA and CIS
CHILE Bangalore - Karnataka Saint Petersburg Minneapolis - Minnesota
La Reina - Santiago Phone: +91 80 41282007 Phone: +7 812 363 2172 Phone: +1 612 3788000
Phone: +56 2 27848900 info-in@weg.net sales-wes@weg.net
info-cl@weg.net VENEZUELA
Hosur - Tamil Nadu SOUTH AFRICA Valencia - Carabobo
CHINA Phone: +91 4344 301577 Johannesburg Phone: +58 241 8210582
Nantong - Jiangsu info-in@weg.net Phone: +27 11 7236000 info-ve@weg.net
Phone: +86 513 85989333 info@zest.co.za
info-cn@weg.net ITALY
Cinisello Balsamo - Milano
Changzhou Jiangsu Phone: +39 2 61293535
Phone: +86 519 88067692 info-it@weg.net
info-cn@weg.net
The values shown are subject to change without prior notice.

For those countries where there is not a WEG own operation, find our local distributor at www.weg.net.
Cod: 50066667 | Rev: 00 | Date (m/y): 07/2016

WEG Group - Automation Business Unit


Jaragu do Sul - SC - Brazil
Phone: +55 47 3276 4000
automacao@weg.net
www.weg.net

Vous aimerez peut-être aussi