Académique Documents
Professionnel Documents
Culture Documents
QF17A QF17C
Dual Mount Dual Mount
Features Applications
Hydraulic-magnetic technology Residential and commercial applications requiring high
100% rating capability, independent of ambient temperature sensitivity earth leakage protection from electrical shock
VC 8035 compliant and fire hazards
VDE and CCC approved, CE certified Earth leakage protection (IEC / EN 60947-2)
UL recognised (UL 1053, UL 1077) Telecom / datacom equipment
Ratings 5 to 63 A Lighting control
Earth leakage sensitivity 30 mA UPS equipment
Single pole plus switched neutral earth leakage protection Alternative energy equipment
Switch versions fitted with short circuit protection Mobile power generation equipment
Available in various currents and time delays Railway signalling equipment
Precision tripping characteristics Industrial equipment
Compact 26 mm wide module
Trip indication with mid-trip position
Reset immediately after overload
Suitable to use for electrical isolation
Shell designed for easier installation onto busbar
Auxiliary Switch,Trip Alarm & Combo: Optional Accessories
Features Rear studs (factory fitted)
Auxiliary switch Handle lock
Auxiliary switch + trip alarm Surface mounting clips
Trip alarm Busbar
AC and DC voltages Escutcheon blank
UL 489 listed (auxiliary switch: 6 A 250 V AC, Safety blank
0.5 A 80 V DC)
IEC 60947-5-1 approved (auxiliary switch: 6 A 240 V AC,
0.5 A 110 V DC; trip alarm: 6 A 240 V AC, 0.5 A 110 V DC)
Factory fitted
Attached to right hand side of circuit breaker
Compact 6.5 mm width
A005438
Auxiliary Module
Auxiliary Switch DIN and CBI Mini Rail mounted
Trip Alarm CBI Mini Rail mount only
Auxiliary Switch / Trip Alarm Combo CBI Mini Rail mount only
No Medium
Q Dual Current Sensitivity Voltage No special Future
Requirement Type F 1 pole + N Overload Auxiliary delay
Frame Mount Rating 63 A 30 mA 240 V AC termination use
Switch curve 2
1500
OPERATING
CHARACTERISTICS
10000
CURVE 2
1000
100
Tripping Time (Seconds)
10
0.1
Maximum
0.01
Minimum
0.001
100
1000
105
130
150
200
300
400
500
1500
2000
2500
3000
4000
5000
% Rated Current
* The published time delay curves are generated at 30oC ambient temperature with the Circuit Breaker mounted in the up-right position. The must hold, must trip and instantaneous
trip current values are not affected by temperature, although delay time for the other operating current values may have to be adjusted using the temperature compensation curve which
is available on request.
1,000
100
Impeaence (m )
10
Maximum
1
Minimum
0.1
0 5 10 15 20 25 30 35 40 45 50 55 60 65
Amp rating
QF17-SERIES-DAT Data Sheet
OCT 2016 Page 5 of 6
low voltage