Académique Documents
Professionnel Documents
Culture Documents
Electrical heat-tracing for process The XTV family of self-regulating, It can also be used for frost protection
temperature maintenance applications parallel circuit heating cables is used of large pipes and for applications
up to 120C which may be subject to for process temperature maintenance requiring high temperature exposure
steam cleaning. of pipes and vessels. capability.
High temperature
fluoropolymer outer jacket
High temperature
fluoropolymer insulation
Spacer
Application
Area classification Hazardous, Zone 1, Zone 2 (Gas), Zone 21, Zone 22 (Dust)
Ordinary
Traced surface type Carbon steel
Stainless steel
Painted or unpainted metal
Chemical resistance Organics and corrosives
For aggressive organics and corrosives consult your local Tyco Thermal Controls representative
Supply voltage
230 Vac (Contact your local Tyco Thermal Controls representative for data on other voltages)
Approvals
The XTV heating cables are approved for use in hazardous areas by PTB and Baseefa Ltd.
PTB 09 ATEX 1118 X & Baseefa06ATEX0184X
II 2G Ex e II T* & II 2D Ex tD A21 IP66 T*
IECEx PTB 09.0059X & IECEx BAS 06.0044X
Ex II 2G Ex e II T* & Ex II 2D Ex tD A21 IP66 T*
*See approval schedule
The XTV heating cables are approved by DNV for use on ships and mobile offshore units.
DNV Certificate No. E-8934
The products also have the required approvals for use in Kazakhstan, Russia and many other
countries. Contact your local Tyco Thermal Controls representative for more details.
Specifications
Maximum maintain or continuous 120C
exposure temperature (power on)
Maximum intermittent exposure 215C (20 bar saturated steam)
temperature (power on) Maximum cumulative exposure 1000 hours
Temperature classification T2: 20XTV2-CT-T2
T3: 4XTV2-CT-T3, 8XTV2-CT-T3, 12XTV2-CT-T3, 15XTV2-CT-T3
in accordance with European Standard EN 60079-30-1 5.1.13 and international standards.
Based on systems approach* T3-T6
*Raychem XTV heat-tracing cables are approved for the listed temperature classifications by
using the principles of stabilized design (as per system classification approach) or the use of a
temperature limiting device. Use TraceCalc design software or contact Tyco Thermal Controls.
Minimum installation temperature 60C
Minimum bend radius at 20C: 13 mm
at 60C: 51 mm
Thermal output rating
Nominal power output at 230 Vac on A 20XTV2-CT-T2 80
W/m
insulated steel pipes B 15XTV2-CT-T3
70
C 12XTV2-CT-T3
D 8XTV2-CT-T3 60 A
E 4XTV2-CT-T3
50
B
40
C
30
D
20
E
10
0 20 40 60 80 100 120
Pipe temperature (C)
Ordering details
Part description 4XTV2-CT-T3 8XTV2-CT-T3 12XTV2-CT-T3 15XTV2-CT-T3 20XTV2-CT-T2
Part No. 002735-000 325059-000 427089-000 214999-000 849015-000
Components
Tyco Thermal Controls offers a full range of components for power connections, splices and end seals.
These components must be used to ensure proper functioning of the product and compliance with electrical requirements.
AT-TS thermostats provide temperature the temperature sensor is defect possible. Connection kits need to be
control in safe area. The temperature (sensor break or sensor short-circuit). ordered separately. The thermostat is
set point can be checked through The temperature sensor has a length available in 2 temperature ranges.
a window in the lid. LEDs are of 3 meter and can be shortened for
providing an indication when cables ambient sensing operating. Direct
are energized (Heating ON) or when connection of the heating cable is
HEATING CABLES
30
60
0
90
12
0
COMPONENTS
CONRTROL AND MONITORNING
AT-TS-13 AT-TS-14
General
Area of use Ordinary area, outdoors Ordinary area, outdoors
Supply voltage 230 Vac +10% 15% 50/60 Hz 230 Vac +10% 15% 50/60 Hz
Max. switching current 16 A, 250 Vac 16 A, 250 Vac
Max. conductor size 2.5 mm2 2.5 mm2
Switching differential 0.6 K to 1 K 0.6 K to 1 K
Switching accuracy 1 K at 5C (calibration point) 2 K at 60C (calibration point)
Switch type SPST (normally open) SPST (normally open)
Adjustable temperature range 5C to +15C 0C to +120C
Housing
Temperature setting inside inside
Exposure temperature 20C to +50C 20C to +50C
Ingress protection IP65 according to EN 60529 IP65 according to EN 60529
Entries 1 x M20 for supply cable ( 8-13 mm) 1 x M20 for supply cable ( 8-13 mm)
1 x M25 for heating element ( 11-17 mm) 1 x M25 for heating element ( 11-17 mm)
1 x M16 for the sensor 1 x M16 for the sensor
ACCESSORIES
AT-TS-13 AT-TS-14
Temperature sensor
Type PTC KTY 83-110 PTC KTY 83-110
Length sensor cable 3m 3m
Diameter sensor cable 5.5 mm 5.5 mm
Diameter sensor head 6.5 mm 6.5 mm
Sensor material PVC Silicone
Max. exposure temperature sensor cable 80C 160C
The sensor cable may be extended to a maximum of 100 m using a 2-conductor
wirE with a cross-section of 1.5 mm2. The sensor cable should be shielded if it is
laid in cable ducts or in the vicinity of high-voltage carrying cables. The shield of the
extension cable should be grounded at the controller end only.
Output parameters
Alarm on LED Green LED: Heating Cable ON Green LED: Heating Cable ON
Red LED: Sensor break Red LED: Sensor break
Red Led: Sensor short-circuit Red Led: Sensor short-circuit
Ordering details
Part description AT-TS-13 AT-TS-14
PN (Weight) 728129-000 (0.44 kg) 648945-000 (0.44 kg)
Accessories
PA Reducer Reducer M25 (M)/M20 (F) Reducer M25 (M)/M20 (F)
PN 184856-000 184856-000
Spare temperature sensor HARD-69 HARD-69
(AT-TS-13 and AT-TS-14) (Max. exposure temperature 160C)
PN (Weight) 133571-000 (180 g) 133571-000 (180 g)
AT-TS-13 or AT-TS-14
max.
C 16A
5 1 2
3
6 8 9 4
Temperature sensor
Heating system
Temperature sensor
Heating system
*Two- or four-pole electrical protection by circuit-breaker may be needed for local circumstances, standards and regulations
**Depending on the application, one- or three-pole circuit-breakers or contactors may be used
***Optional: Potential-free circuit-breaker for connection to the BMS
Tyco, Alliance Integrated Systems, AMC, AutoMatrix, AutoSol, BTV, CapaciSense, Chemelex, DHSX, DigiTrace, DigiTrace logo,
DigiTrace Supervisor, Duoterm, ElectroMelt, EM2XR, FHSM, FHSC, FlexFit, FlexiClic, Flowguard, FreezeTrace, FreezGard,
Frostex, Flostex Plus, Frostguard, FroStop, FSE, Gardian, HAK, Handvise, HBTV, HCCL, HotCap, HQTV, HTPG, HTPI, HWAT,
HXTV, IceStop, Interlock, Isocable, Isodrum, Isoheat, Isomantle, Isopad, Isopad Frostguard, Isopad logo, Isopanel, Isotape,
Isotherm, JBM, JBS, K-Flex, K-Flex logo, KHE, KHH, KHL, KHP, KTV, Labsafe, LBTV, LHC, LHFV, LHRV, Metabond, Mini
WinterGard, Miser WinterGard, MoniTrace, Multi-plus, NGC, PetroTrace, PLI, PolyMatrix, Pyro CiC, PyroFLX, Pyromaster, Pyropak,
2012 Tyco Thermal Controls LLC
Pyrosil, PyroSizer, Pyrotenax, Pyrotenax Designer, Pyrotenax logo, QTVR, QuickNet, QuickNet logo, QuickStat, QuickTerm,
RayClic, RaySol, RayStat, Retro WinterGard, RHS, RHSC, RHSM, RMM2, SBF, SBV, SC, SHC, Sheathmaster, ShowerGuard, SLBTV,
Smart heat for Comfort and Safety, SnoCalc, SnoCalc logo, STS, System 500, System 1850, System 1850-SE, System 2000,
System 2200, T2, T2 logo, T2Blue, T2QuickNet, T2Red, T2Reecta, TankCalc Plus, TempBus, Thermoheat, ThermoLimit, Thermo-
Line, Total Care in Heat-tracing, Touch, Trac-Loc, Trac Calc, TraceCalc Net, TraceCalc Net logo, TraceCalc Pro logo, TraceGuard 277,
TraceMaster, Tracer, Tracer logo, TRACERLYNX, TRACERLYNX logo, TraceStat, TraceTek, TraceTek logo, TruckPak, VLBTV, VLKTV, VPL,
We manage the heat you need, WinterGard, WinterGard logo, WinterGard Plus, WinterGard Wet, XL-ERATE, XL-ERATE logo, XL-Trace, XTV
and Zero EMI are registered and/or unregistered trademarks of Tyco Thermal Controls LLC or its afliates.
Important: All information, including illustrations, is believed to be reliable. Users, however, should independently evaluate the
suitability of each product for their particular application. Tyco Thermal Controls makes no warranties as to the accuracy or
completeness of the information, and disclaims any liability regarding its use. Tyco Thermal Controls' only obligations are those
in the Tyco Thermal Controls Standard Terms and Conditions of Sale for this product, and in no case will Tyco Thermal Controls
or its distributors be liable for any incidental, indirect, or consequential damages arising from the sale, resale, use, or misuse of
the product. Specifications are subject to change without notice. In addition, Tyco Thermal Controls reserves the right to make
changeswithout notification to Buyerto processing or materials that do not affect compliance with any applicable specification.