Zone-1 :
Phase to Phase fault : (Gx + Fx/1000) = [X1/2.5] with 5% tolerance
Similarly X2, KN2 & X3,KN3 to be considered in place of X1,KN1 for Zone-2 & 3
respectively.
Zone-1 :
Phase to Phase fault : (Gr + Fr/1000) = [1/2.5(R1-X1/20)] with 5% tolerance
Zone-1 :
Phase to Phase fault : (Gx + Fx/1000) = [X1/2.5] with 5% tolerance
Zone-1 :
Phase to Phase fault : (Gr + Fr/1000) = [1/2.5(R1-X1/20)] with 5% tolerance
Similarly R2 & R3 to be considered in place of R1 for Zone-2 & 3 for phase to phase
fault and R2E & R3E in place of R1E for phase to ground fault respectively.