Thepurposeofaloadbanktestistosimulaterealworldscenariosthatcanbeusedtoconfirmproperfunctionality.
Loadbanksareprovidedtosimulateelectricalload,asitisimportanttotestvariouselectricalapparatusinits
installedlocation.Whiletheequipmentundertest(EUT)mayhavebeentestedatthefactory,theinstallation
variables(Eg.altitude,ambienttemperature,airintake,fuel,exhaust,coolingsystemsandcontractor/sub
contractorworkmanshipquality)canbesignificantlyaffectedbytheinstallation.Theproperuseofaloadbankcan
beusedtoeffectivelytesttheoperatingcapabilityofthecompletesystem,asdeliveredfromthemanufacturer.
Aloadbankisadevicewhichdevelopsanelectricalload,appliestheloadtoanelectricalpowersourceand
convertsordissipatestheresultantpoweroutputofthesource.
Thepurposeofaloadbankistoaccuratelymimictheoperationalorrealloadthatapowersourcewillseein
actualapplication.However,unliketherealload,whichislikelytobedispersed,unpredictableandrandomin
value,aloadbankprovidesacontained,organizedandfullycontrollableload.
Consequently,aloadbankcanbefurtherdefinedasaselfcontained,unitized,systematicdevicethatincludesload
elementswithcontrolandaccessorydevicesrequiredforoperation.
Whereastherealloadisservedbythepowersourceandusestheenergyoutputofthesourceforsome
productivepurpose,theloadbankservesthepowersource,usingitsenergyoutputtotest,supportorprotectthe
powersource.
Contents
1 Applications
2 Loadbanktypes
2.1 Resistiveloadbank
2.2 Reactiveloadbanks
2.2.1 Inductiveloadbanks
2.2.2 Capacitiveloadbanks
2.3 Resistive/Reactiveloadbanks
3 Alternativeloadbanks
3.1 Electronicloadbanks
3.2 WaterCooledloadbanks
3.3 MediumVoltageloadbanks
3.4 ServerSimulatingloadbanks
3.5 Nonlinearloadbanks
3.6 400Hzloadbanks
3.7 Regenerativeloadbanks
3.8 Resonantloadbanks
4 LoadBankManufacturers
Applications
http://wiki.openelectrical.org/index.php?title=Load_Bank_Testing 1/6
5/1/2017 LoadBankTestingOpenElectrical
Loadbanksareusedinavarietyofapplications,including:
Factorytestingofturbinesandenginedieselgeneratorsets
Reductionofwetstackingproblems
Periodicexercisingofstandbyenginegeneratorsets
BatteryandUPSsystemtesting
Groundpowertesting
Loadoptimizationinprimepowerapplications
Removalofcarbonbuilduponpistonrings
Loadrejectiontest
Loadbanktypes
Thethreemostcommontypesofloadbanksareresistive,inductive,andcapacitive.Bothinductiveandcapacitive
loadscreatewhatisknownasreactanceinanACcircuit.Reactanceisacircuitelement'soppositiontoan
alternatingcurrent,causedbythebuildupofelectricormagneticfieldsintheelementduetothecurrentandisthe
"imaginary"componentofimpedance,ortheresistancetoACsignalsatacertainfrequency.Capacitivereactance
isequalto1/(2fC),andinductivereactanceisequalto2fL.Theunitofreactanceistheohm.Inductive
reactanceresiststhechangetocurrent,causingthecircuitcurrenttolagvoltage.Capacitivereactanceresiststhe
changetovoltage,causingthecircuitcurrenttoleadvoltage.
Resistiveloadbank
Aresistiveloadbank,themostcommontype,providesequivalentloadingforbothgeneratorsandprimemovers.
Thatis,foreachkilowatt(orhorsepower)ofloadappliedtothegeneratorbytheloadbank,anequalamountof
loadisappliedtotheprimemoverbythegenerator.Aresistiveloadbank,therefore,removesenergyfromthe
completesystem:loadbankfromgeneratorgeneratorfromprimemoverprimemoverfromfuel.Additional
energyisremovedasaconsequenceofresistiveloadbankoperation:wasteheatfromcoolant,exhaustand
generatorlossesandenergyconsumedbyaccessorydevices.Aresistiveloadbankimpactsuponallaspectsofa
generatingsystem.
Theloadofaresistiveloadbankiscreatedbytheconversionofelectricalenergytoheatviahighpowerresistors
suchasgridresistors.Thisheatmustbedissipatedfromtheloadbank,eitherbyairorbywater,byforcedmeans
orconvection.
Inatestingsystem,aresistiveloadsimulatesrealliferesistiveloads,suchasincandescentlightingandheating
loadsaswellastheresistiveorunitypowerfactorcomponentofmagnetic(motors,transformers)loads.
Themostcommontypeuseswireresistance,usuallywithfancooling,andthistypeisoftenportableandmoved
fromgeneratortogeneratorfortestpurposes.Sometimesaloadofthistypeisbuiltintoabuilding,butthisis
unusual.
Rarelyasaltwaterrheostatisused.Itcanbereadilyimprovised,whichmakesitusefulinremotelocations.
Reactiveloadbanks
Inductiveloadbanks
Aninductiveloadincludesinductive(laggingpowerfactor)loads.
http://wiki.openelectrical.org/index.php?title=Load_Bank_Testing 2/6
5/1/2017 LoadBankTestingOpenElectrical
Aninductiveloadconsistsofanironcorereactiveelementwhich,whenusedinconjunctionwitharesistiveload
bank,createsalaggingpowerfactorload.Typically,theinductiveloadwillberatedatanumericvalue75%thatof
thecorrespondingresistiveloadsuchthatwhenappliedtogetheraresultant0.8powerfactorloadisprovided.That
istosay,foreach100kWofresistiveload,75kVArofinductiveloadisprovided.Otherratiosarepossibleto
obtainotherpowerfactorratings.Aninductiveloadisusedtosimulateareallifemixedcommercialloads
consistingoflighting,heating,motors,transformers,etc.Witharesistiveinductiveloadbank,fullpowersystem
testingispossible,becausetheprovidedimpedancesuppliescurrentsoutofphasewithvoltageandallowsfor
performanceevaluationofgenerators,voltageregulators,loadtapchangers,conductors,switchgearandother
equipment.
Capacitiveloadbanks
Ancapacitiveloadincludescapacitive(leadingpowerfactor)loads.
Acapacitiveloadbankorcapacitorbankissimilartoaninductiveloadbankinratingandpurpose,exceptleading
powerfactorloadsarecreated,soreactivepowerissuppliedfromtheseloadstothesystem,henceimprovesthe
powerfactor.Theseloadssimulatecertainelectronicornonlinearloadstypicaloftelecommunications,computer
orUPSindustries.
Resistive/Reactiveloadbanks
Theseareacombinationofprimarilyresistiveandinductiveloadelementssuitableforperformingpowerfactor
testing.Resistive/reactivecombinationloadbanksareusedtotesttheenginegeneratorsetatitsratedpowerfactor
andinthemajorityofcasesthiswillbe0.8powerfactor.
Thereactivecomponentoftheloadwillhaveacurrentthatlagsthevoltage.Theresultingpowerisdescribedin
twoterms,theKW,orrealpowerandtheKVAorapparentpower.
Sincethecurrentlagsthevoltageinthereactiveloadthetotalpowerisnotthedirectsumofthetwobuttheir
vectorsum.Thatvectoristhephaseangledifferencebetweenthevoltageandthecurrent.Thecombinationof
resistiveandreactivecurrentintheloadwillallowforthefullnameplateKVAratingofthegeneratorwindingsto
betested.EventhoughthegeneratorsetisproducingmoreKVAitisactuallynotproducingmoreKW.Thereal
powerorhorsepowerrequiredfromtheengineisessentiallythesame.
Alternativeloadbanks
Electronicloadbanks
Anelectronicloadbanktendstobeafullyprogrammable,airorwatercooleddesignusedtosimulateasolidstate
loadandtoprovideconstantpowerandcurrentloadingoncircuitsforprecisiontesting.
Theseunitstendtobesomewhatrare,butaregreatfortestinglabstoperformconstantpower,voltageandcurrent
loadtests.
WaterCooledloadbanks
Oftentimes,situationsrequirecustomerstotestpowersupplies,namelygeneratorsandUPSsystems,inlocations
thatarenotconducivetonormalforcedaircooledloadbanks,eitherduetoenvironmentorphysicalconstraints.
Forexample,aUPSsystemthatisunderground,locatedinaparkinggarageorlocatedontopofarooftop.
http://wiki.openelectrical.org/index.php?title=Load_Bank_Testing 3/6
5/1/2017 LoadBankTestingOpenElectrical
Inthesesituations,verylongrunsofcablesometimesmorethen300'+maybeused,butdueincreasedresistance
andsubsequentvoltagedrop,mayposeandaddtotheexistingchallenge.
Inadditiontotheabovescenario,watercooledloadbankscanbeusedtoprovideheatedwatertosimulatewater
basedserverandorchillers
Sothisleavesuswithanopenloop,watercycleloadcell,wherebychilledwaterissuppliedtoadevicewith
heatingelements.Aneasywaytoenvisionthisistothinkofitasanexpensivehotwaterheater.
MediumVoltageloadbanks
Thenotionofusingmediumvoltageloadbankforportabletestingpurpose,cameaboutfromthinkingoutside
thebox.Theextralogisticscostsfortransporting,craningintopositionandconnectingthelowvoltagecable,
becamerathertedious.
Amediumvoltageloadbankisjustlikeanyotherloadbankinthatitcontainsresistors,reactorsorcapacitors.
However,thevoltageratingsaregreaterthan600VACandbelow69,000VAC.
Mediumvoltageloadbanksareoftenusedforcommissioningpowerplants,maritimeelectricalsystems,standby
generatorsystemsandsubstations,essentiallythesameaslowvoltageloadbanks,theonlydifferencebeingthe
voltage.
Thealternatemethodoftestingwithoutmediumvoltageloadbanksistouselowvoltageloadbankswithstep
downtransformersusedtoservethelowvoltageloadbanks.
Typicallyitisalwaysadvantageoustotestwithmediumvoltageloadbanksversusjustusinglowvoltageload
banks,astheaddedlogisticsandprocurementcostsforlowvoltageloadbanksarefarmoreexpensive.
ServerSimulatingloadbanks
Thesearetypicallyrackmountableandusedtosimulatetruehotaisle/coldaislecontainmentsystems,heat
andairflow.Thesesimulatephysicalserversasinstalledatadatacenterbywayofheatdischarge,electrical
resistanceandairflow.Theresultantheatoutputoftheloadbanksareofabenefitinthattheyareusedtoload
computerroomairconditioners,whilstcreatinganelectricalloadtotheprimaryandstandbysystemsinthedata
center.
Nonlinearloadbanks
Aloadisconsiderednonlinearifitsimpedancechangeswiththeappliedvoltage.Thechangingimpedance
meansthatthecurrentdrawnbythenonlinearloadwillnotbesinusoidalevenwhenitisconnectedtoa
sinusoidalvoltage.Thesenonsinusoidalcurrentscontainharmoniccurrentsthatinteractwiththeimpedanceof
thepowerdistributionsystemtocreatevoltagedistortionthatcanaffectboththedistributionsystemequipment
andtheloadsconnectedtoit.
Inthepast,nonlinearloadswereprimarilyfoundinheavyindustrialapplicationssuchasarcfurnaces,large
variablefrequencydrives(VFD),heavyrectifiersforelectrolyticrefining,etc.Theharmonicstheygeneratedwere
typicallylocalizedandoftenaddressedbyknowledgeableexperts.
Timeshavechangedandharmonicproblemsarenowcommoninnotonlyindustrialapplicationsbutin
commercialbuildingsaswell.Thisisdueprimarilytonewpowerconversiontechnologies,suchastheSwitch
modePowerSupply(SMPS),whichcanbefoundinvirtuallyeverypowerelectronicandpowerconversion
http://wiki.openelectrical.org/index.php?title=Load_Bank_Testing 4/6
5/1/2017 LoadBankTestingOpenElectrical
device.Namelywindfarmsarenotoriousforthisandrequirespecialconsiderationsduetotehextraharmonic
content.
400Hzloadbanks
Thesearenormallyusedonaircraftandshipbasedsystemsthatrequirecommissioningortestingbeforebeing
placedinservice.400Hzsystemsareusedwhereweightisimportantbecausethemagneticcorescanbe
smaller/lighter.Thisappliestotransformersaswellsincealowerinductance(smallercore/numberofturns)canbe
usedthanrequiredbylowerfrequencies.
Itisworthytonotethatresistorsratedfor60Hzcanoperateatthehighervalueof400Hzwithoutaproblem,but
inductorsandcapacitorscannot.
Regenerativeloadbanks
Reversepower/regenerativepowerprotectionofgeneratorbysensingpowerdirection,magnitudeandautomatic
additiontoactasapowersink.
Theseareseenprimarilyusedtocaptureanddissipateregenerativepowerfromlargemotorsandarefoundinthe
followingsettings:
Cranesandrigs
Mining
Cablelayingvessels
Elevators
Resonantloadbanks
Resonantloadsarebecomingincreasinglyprevalentduetosolarinverterantiislandingtestingand
commissioningperIEEEonphotovoltaicsystems.Thesearecomprisedofanexactbalanceofresistive,capacitive
andinductiveloadsina1:1:1,or1:2.5:2.5ratiossoastoprovideaspecificqualityfactor.
Manysolarinvertersaredesignedtobeconnectedtoautilitygrid,andwillnotoperatewhentheydonotdetectthe
presenceofthegrid.Theycontainspecialcircuitrytopreciselymatchthevoltageandfrequencyofthegrid.
Traditionalutilityelectricpowersystemsweredesignedtosupportaonewaypowerflowfromthepointof
generationthroughatransmissionsystemtodistributionlevelloads.Thesesystemswerenotoriginallyintendedto
accommodatethebackfeedofpowerfromdistributedgenerationsystemsatthedistributionlevel.
Islandingreferstotheconditioninwhichadistributedgeneratorcontinuestopoweralocationeventhough
electricalgridpowerwhentheelectricutilityisnolongerpresent.Islandingcanbedangeroustoutilityworkers,
whomaynotrealizethatacircuitisstillpowered,anditmaypreventautomaticreconnectionofdevices.For
thatreason,distributedgeneratorsmustdetectislandingandimmediatelystopproducingpowerthisisreferredto
asantiislanding.
LoadBankManufacturers
Hereisabrieflistingofcommonlyknownloadbankmanufacturers:
Avtron
Loadtec
Cannon
http://wiki.openelectrical.org/index.php?title=Load_Bank_Testing 5/6
5/1/2017 LoadBankTestingOpenElectrical
Hawthorne
CrestchicUK
Northbridge
Froment
Simplex
Note:Thislistingisbynowaycompleteorabsolute.
Retrievedfrom"http://wiki.openelectrical.org/index.php?title=Load_Bank_Testing&oldid=549"
Category: ElectricalTesting
Thispagewaslastmodifiedon18February2017,at04:00.