Vous êtes sur la page 1sur 7

White Paper

WP00022

The Case for Specifying


Industrial Ethernet Cable
for Harsh Environments

Brian Shuman
Senior Product Engineering
Project Manager
Industrial Cable Belden

Table of Contents Executive Summary


Network uptime is the single most critical concern of industrial automation and control
Executive Summary..................................... 1 applications. Each second of downtime equals money lost through lower production, costly
Realizing Key Business Benefits.............. 2 repairs, or maintenance and worker safety expenses. To maintain high reliability and availability
of systems and data communication, networks must be built on a robust and dependable
Addressing Network Priorities:
infrastructure.
Uptime, Safety and Control........................ 2
Identifying Risks: Top Environmental Today, industrial Ethernet is the principal network infrastructure choice for mission-critical
Factors Facing Industrial Applications.... 2 operations. Built on the same standards-based networking platform as enterprise Ethernet,
Assessing the Impact: which has long reigned as the universal network solution, industrial Ethernet connects the
The Real Costs of Network Failure........... 3 office with the plant floor through a single platform.

Identifying a Solution: This convergence of open, standards-based Ethernet communications enables secure, seamless
Key Considerations..................................... 3 interoperability among manufacturing enterprise networks from corporate offices to the
Comparing Commercial vs. shop floor to remote locations and offers Internet and enterprise connectivity, anytime and
Industrial-Grade Components......... 4
anywhere.
The Proof is in the Testing................ 4
Selecting an Industrial Ethernet And as more smart devices connect to the Internet and produce rapidly growing amounts of
Cable: Fiber or Copper?.................... 5 data through a movement known as the Industrial Internet of Things (IIoT) networks built on
Physical Media Cabling and industrial Ethernet technology ensure flexibility for future expansion and change.
Connectivity......................................... 6
It is also critical to note that while the base technology is the same, enterprise-grade products
Meeting Industrial Ethernet
are not appropriate for use in industrial networks. The industrial applications previously
Standards and Approvals........................... 6
mentioned operate in drastically different environments. Products designed for use in a simple,
Conclusion.................................................... 7 clean and stable office setting will not be able to withstand the harsh, extreme and relentless
conditions found in an industrial setting. Industrial-grade solutions are built with these
extremes in mind and feature unique protections to enable long-standing, reliable operation,
no matter the environment.

This white paper will address the risks and priorities of industrial networking, as well as key
considerations when selecting physical layer products and solutions to support an industrial
Ethernet infrastructure.
Realizing Key Business Benefits Addressing Network Priorities: Identifying Risks: Top Environmental
Uptime, Safety and Control Factors Facing Industrial
In addition to system integration and Applications
interoperability, there are many other key Untimely and costly disruptions can largely
business benefits to a complete, end-to- be prevented through a well-planned and Networks in all industrial operations must
end Ethernet solution from cabling and executed network infrastructure that perform in extreme and often hazardous
connectivity, to active components and incorporates environmentally hardened, environments and every operation has
associated hardware. These benefits include industrial-grade components in the physical, its own set of environmental challenges.
lower overall total cost of ownership (TCO) data link and network layers1. A ruggedly But no matter the conditions, industrial
and higher return on investment (ROI) designed framework enables industrial communications and control networks
through real-time visibility and flexibility, enterprises to carry out their mission-critical are expected to operate consistently
reduced network maintenance and functions by providing the highest possible and reliably by withstanding high
administration costs and labor, and greater levels of: operating temperatures, power or voltage
physical and virtual network security. fluctuations, UV exposure, machine
1. Uptime. Preventing signal transmission vibration, electromagnetic interference
Operational benefits at both the industrial problems is a major factor in ensuring (EMI), mechanical hazards, and other special
facility and enterprise levels include: consistent and dependable network uptime industrial criteria.
and productivity. Whether an operation
Faster and less costly plant upgrades, involves a discrete manufacturing facility, Food and Beverage
expansions and change-outs a processing plant or an airport, keeping To meet stringent hygiene requirements,
operations running smoothly and reliably communications network components
Access to real-time data to improve
assures maximum uptime and peace of face regular, high-intensity cleanings,
overall operations
mind for network managers who want commonly referred to as wash-downs
Faster installation and remote to attain 99.999 percent uptime or better. or splash zones, and must be able to
troubleshooting Any network failure, and subsequent withstand the caustic cleaning chemicals
Real-time inventory visibility and downtime, also results in severe and and high-pressure water. Systems in
increased production capacity extremely costly consequences. the food and beverage industry must
also deal with motion during packaging,
Integration with enterprise resource 2. Safety. Optimum safety is critical to
extreme temperature and moisture/
planning (ERP) for scheduling, planning, protect people and processes in all
humidity from freezers and ovens during
quality tracking and delivery information industrial operations. These applications
processes, like pasteurization, as well
demand fail-safe reliability and
as high noise sensitivity in order to fill
The plant or shop floor is just one example redundancy of data transmissions, as well
precise measurements.
of an industrial setting. The term industry as network components that meet and
is broad and encompasses many diverse exceed the requirements for hazardous Machine Building
operations from discrete manufacturing of environments. To handle the constant, and often
every kind; to the processing of foods and extreme, motion of packaging lines,
3. Control. Industrial facilities rely heavily
beverages, pulp and paper, chemicals, oil, assembly cells and transport belts, this
on their automation, instrumentation and
gas and petrochemicals; to commercial and highly automated equipment must
control data communications to relay
government sites, such as power generation deal with tight spaces, elevated levels
signals between devices, machinery and
plants, wind energy farms, water and of electrical noise, changing electrical
the control system. This communication
wastewater treatment facilities, airports currents, prolonged vibration and
triggers events and functions on a very
and transportation hubs, military bases, vigorous torque. Several environmental
specific and pre-determined schedule, with
ships and shipyards, railyards, tunnels, dams, factors are also at play, such as resistance
little or no margin for error. Continuous
and bridges. Industrial-grade products are to oils and solvents, chemicals, welding
monitoring, management and control
also relevant for other uses, such as sensors spatter, and dust.
drives operational efficiencies and
in the pavement at a stoplight, intelligent
potential cost savings.
parking meter systems, or campus security Chemical Processing
measures, like pan-tilt-zoom cameras and In the chemical processing industry, any
call boxes. While each industry is unique, communications network components
they all share common factors, such as used must be able to withstand many
environmental risks and business priorities. outdoor environmental conditions,
including sunlight, extreme temperatures,

2
Be Certain with Belden

system fails, the cost of replacement parts


and repair represents only a tiny fraction of
the overall costs associated with production
downtime.
Chemical
Many instances of unplanned downtime
in industrial operations can be attributed
to network infrastructure failure, and
that downtime is costly. According to one
Noise survey of manufacturing executives in
Vibration Interference the automotive industry, downtime can
cost companies an average of $22,000 per
minute2.

The indirect costs of Ethernet system failure


in any industry must take into account
lost productivity, delayed downstream
processes, cost of system shut-down and
Extreme start-up, and the potentially devastating
Temperatures loss of service to customers relying on the
facilitys mission-critical output. If a cabling
Moisture system component or Ethernet switch fails,
the repair and labor costs alone could be
15-20 times the cost of the component
itself. Depending on the industry and overall
operating costs, these indirect effects
can send total downtime costs soaring to
UV hundreds of thousands, even millions of
Impact dollars.

In the traditional office environment, you dont have to be concerned about cable exposure to That is why investing in a high-quality,
abrasive chemicals, extreme temperatures, heavy vibration or water and other fluids. Thats not
true in the unforgiving settings where machines, automation and manufacturing equipment live.
rugged Ethernet infrastructure designed
specifically for use in harsh environments
damage from rodents, excessive moisture Given these environmental risks, it is is the obvious business choice one that
from rainfall, mist or fog, and have clear that the networked communications can provide tremendous peace-of-mind to
the ability to operate when buried systems in extreme environments must network engineers and administrators and
underground. be exceptionally rugged and durable. Any the organizations they serve.
physical deterioration or electrical failure
Drive-Thru Restaurant in key data transmission components can Identifying a Solution: Key
Even non-traditional applications require lead to unreliable network performance and Considerations
robust solutions. For example, outdoor safety issues, and may ultimately lead to loss Given many network performance problems
ordering boards at drive-thru restaurants of critical data, costly downtime, or even are due to failure at the physical media layer3
are exposed to temperature extremes, catastrophic failure. it is critical to ensure that components are
humidity, sunlight, corrosive cleaning designed and constructed to withstand the
chemicals, dust, extreme moisture and Assessing the Impact: The Real operational and environmental stressors to
humidity, rainfall, grit, and sludge. The Costs of Network Failure which they are subjected. For each category,
cars that drive by may also expose the multiple factors need to be considered
Maximum productivity with minimal
equipment to oil, gas and caustic fumes. to ensure optimal performance, ease of
downtime is a key goal, and 24/7 network
This application is very similar to the maintenance, and long-term reliability of the
performance and reliability are critical to
connectivity needs at gas station pumps mission-critical network.
achieving that goal. No matter what the
or parking meters on city streets.
industry, if a switch, connector or cabling

3
Comparing Commercial vs. Industrial-Grade electromagnetic interference (EMI) or The standard jacketed COTS cables failed
Components radio-frequency interference (RFI). Plant at -20 C. The industrial-grade cables,
In a typical office, the Ethernet floor vehicles, such as forklifts and protected by high-low temperature jackets,
infrastructure is installed in a relatively moving carts, can accidentally run over did not crack until impacted at -70 C.
clean, quiet environment with cables hidden cables, causing abrasion, crushing or cut-
behind walls, in ceilings or under floors with through. Crushing. An Instron crushing device was
network switches, hardware and connectivity used to determine the point at which a
Even well-made, properly installed COTS
components sheltered in protected areas. cable could no longer reliably support Cat
Ethernet components are not constructed
5e applications. The COTS cable with a PVC
to survive these kinds of hazards. Only
Industrial facilities present a very different jacket failed at 400 pounds applied force.
hardened, industrial-grade components
reality. Here, many, if not most, cables The industrial-grade, black-jacketed armored
are robust enough to withstand the
and connectors are integral to machine cable failed only after 2,250 pounds more
environmental challenges present in every
automation, instrumentation and control than a ton of applied force.
day industrial settings.
systems, which places them in harsh and
potentially hazardous situations. Even the Cut-Through. A chisel-point mandrel on an
The Proof is in the Testing4
best Commercial-Off-The-Shelf (COTS) Instron machine was lowered onto a segment
An office and an industrial setting couldnt
Ethernet systems are not made to handle of cable to test the cables susceptibility to
be more different especially when you
these conditions over time. Extreme being cut-through, leaving the conductor
consider the level of stress placed on
conditions call for ruggedized cables. exposed. The COTS cable shorted out at
Ethernet cabling systems or adverse effects
92 pounds of applied force. The armored
environmental conditions can have on
Consider, for example, the harmful effects industrial cable took 346 pounds applied
active devices. Belden has done extensive
these common environmental conditions can force to pierce the armor; however, the
testing to compare both the physical and
have on network components: conductors did not short until a force of
electrical performance of COTS cables versus
1,048 pounds was applied.
Temperature Extremes. Extreme cold industrial cables. The results of each test
can make COTS cables stiff and brittle, clearly indicate why a commercial-grade High Temperature. Three types of cables
while elevated temperatures can degrade cable is never suitable for the wide variety were placed in a high-temperature oven
the plastic used in the construction of extreme conditions commonly seen in an a COTS Cat 5e cable with standard PVC
of the cables and cause an increase in industrial environment. jacket, an industrial-grade Cat 5e cable
attenuation. Industrial-grade cables can with a PVC jacket, and an industrial-grade
Abrasion. Cables were stretched across a
operate in a far wider temperature range Cat 5e cable with an FEP jacket. The COTS
fixed drum covered with rough sandpaper
(-40 C to +85 C) than COTS cables (0 C cable functioned acceptably at +20 C but,
and moved back and forth for 25 cycle
to +60 C). over time at +60 C, attenuation increased
counts. At that point, the conductors of
to where the cable would not support a
Chemical Exposure. Oils, solvents, the COTS cable could be seen through
run distance of 100 meters. Both of the
chemicals and cleaning solutions can soak breaks in the jacket, which would cause it
industrial-grade cables, even after exposure
into COTS cables, especially under the to lose mechanical and electrical integrity.
to +60 C over time, continued to support
stress of heat, causing the cable jacket to The armored industrial cables were not
the maximum run distance.
swell and lose mechanical strength. compromised.
UV Radiation. Exposure to sunlight can Oil Resistance. Cables were immersed in
Cold Bend. Cables were left in a cold box for
cause COTS cable jackets to decompose containers of oil, then in water, and finally
one hour then wound around a mandrel with
at an accelerated rate, compromising held in a +125 C chamber for 60 days. The
one end of the cable placed under tension
mechanical strength and electrical COTS cable showed signs of deterioration.
from an aluminum weight. When unrolled
performance. The industrial cables jacket did not, because
and inspected, the COTS cable became brittle
the materials and jacket thickness are rated
Physical Hazards. Industrial settings and showed visible cracks. The industrial-
for exposure to oil and other substances,
present many mechanical risks, especially grade high/low temp cable had no visible
even at elevated temperatures.
for machine automation cables and damage.
connectors. Excessive machine movement
UV Exposure. Cables were exposed to
or vibration can result in cables being Cold Impact. An aluminum weight was
fluorescent light that mimicked solar
pulled or stretched with excessive force, dropped to smash against a segment of
radiation levels for 720 hours (30 days).
which can degrade electrical performance cooled cable. Ten samples were inspected at
The COTS cable was not sunlight-resistant
and increase susceptibility to ambient a series of increasingly lower temperatures.
and their jackets showed discoloration,

4
Be Certain with Belden

Selecting an Industrial Ethernet Cable: Fiber or Copper?


Fiber optic Ethernet cables represent the ultimate in future-proofing and are available for indoor or outdoor use,
including burying underground. Typical designs use multimode fibers in a loose tube configuration, usually available
in 2- to 72-fiber constructions.

Other fiber cable considerations include the following:

To handle Gigabit Ethernet light sources and any expanded A basic, COTS fiber optic cable will likely not withstand industrial
bandwidth requirements, some cables use a laser-optimized fiber. conditions a fiber optic Ethernet cable, designed with
ruggedized features to operate in industrial settings, is needed.
For moisture protection, a water-blocking agent should be
included in the cables construction. Ratings include:
In particularly harsh environments, a chlorinated polyethylene UL Type: Optical fiber, nonconductive riser (OFNR)
(CPE) outer jacket will provide additional protection against
cUL Type: OFN FT4
chemicals or abrasion. An armor tape or aluminum/steel armoring
may also be appropriate for extreme environments, including IEEE 383-2003 Flame Test
some burial situations.

Copper Ethernet cables are the more traditional option in industrial installations, available for Cat 5e, Cat 6 or Cat 6a applications.

Other copper cable considerations include: Cat 5e, Cat 6 and Cat 6a twisted pair cables are available using
any number of conductor types, insulations, shielding and
Cat 5e cables are still widely used today, however new jackets.
installations favor the use of Cat 6 cables to meet Gigabit speeds
Armoring is also available for extremely harsh environments.
and increased bandwidth. Cat 6a cables are also an option for
extreme future-proofing.

Additional Selection Criteria Include:

Unshielded or shielded? Unshielded products can be used in Insulation. Most industrial-grade Ethernet cables utilize a
most environments, while shielded products are recommended polyolefin insulation. For extreme temperatures, however, a
for environments with high noise. fluorinated ethylene propylene (FEP) insulation and jacket is
recommended.
Shields. Typically, a foil is used to protect the integrity of the
signal and to screen out any undesirable interference or noise. Jackets. Oil- and sunlight-resistant cables typically have a
However, to provide extra durability and noise protection, a foil/ polyvinyl chloride (PVC) jacket. If the cables are exposed to
braid combination can be used. moisture, a water-blocking agent should be part of the cables
construction, as well as inner and outer polyethylene (PE) jackets
Solid or stranded conductors? Solid conductors are appropriate
if the cable is buried. Gas-resistance calls for an FEP-jacketed
for most installations, while stranded conductors provide extra
cable, while LSZH jackets are available for environments where
flexibility for better handling in small spaces. For robotic/
smoke/flames are a risk, in order to avoid smoke toxicity for
continuous flex applications, use of a cable with a highly
safety reasons. For extreme temperature environments, the
stranded conductor is recommended.
cables should feature an FEP jacket (for an extended operating
Pair conformity/centricity. Bonded-pair cables provide resistance temperature of -70 C to +150 C). And, for continuous flexing
to the rigors of installation by utilizing a manufacturing or robotic applications, which could include the complication of
technique that affixes the insulation of the cable pairs along welding spatter, cables with thermoplastic elastomer (TPE) inner
their longitudinal axes so no gaps can develop between the and outer jackets are recommended.
conductor pairs. A nonbonded-pair cable construction can be
susceptible to pair-gapping during installation (resulting in
impedance mismatches).

5
a precursor to degradation of the jacket Heavy-duty, all dielectric, indoor-/ Industrial-grade connectivity
material. The industrial-grade cables were outdoor-rated optical fiber cabling components, such as IP67- or IP20-rated
rated to resist the effects of sunlight and in single-mode and multimode UTP or FTP patch cords, connectors,
other UV sources and showed no jacket constructions. Many feature water- modular jacks and plug kits, adaptors,
damage. blocking agents for added protection in faceplates, and surface mount boxes.
moisture-laden environments.
Water Immersion. Cables were coiled Extreme Conditions?
Industrial-grade Cat 5e (2-pair and
and submerged in water, and then tested IP67-rated connectors are ideal for use in
4-pair), Cat 6 (4-pair) and Cat 6a (4-pair)
intermittently over a six-month period. The extremely damp/wet environments and
cables with heavy-duty, oil- and UV-
COTS cable showed increased attenuation applications where significant vibration
resistant jackets. Some category cables
as soon as it was immersed in water and could result in intermittent communication
feature a bonded-pair technology, which
continued to degrade over the half-year from connector contact deterioration. The
delivers superior electrical stability in the
immersion. After six months of immersion, connector, approved by the Open Device
harshest of environments.
the industrial-grade cable showed only a Vendor Association (ODVA), is the M12
slight increase in attenuation and the cable Upjacketed and armored cables for more D-code Ethernet connector a 4-pin
still exceeded the Cat 5e requirements. extreme environments. connector that uses Cat 5e or better (2-pair).
Continuous flex cables designed for use
Physical Media Cabling and Connectivity Keep in mind that the IP67 rating is not
with continuous motion machines and
For the physical media layer, there are always used in wet environments or
automation systems.
many solutions available that fully conform applications where vibration is an issue.
to the IEEE 802.3 Local Area Network Low smoke zero halogen (LSZH), water- Some users choose instead to deploy all
(LAN) standard. Selection will depend on blocked and/or burial cables. M12 D-code connectors so that they can
each facilitys network configuration and eliminate control panels.
Cables designed for use with leading
application requirements. These physical
industrial automation networking and
media products may include:
communications protocols, such as
EtherNet/IP (ODVA), Modbus TCP/IP,
PROFINET and Fieldbus HSE.

Meeting Industrial Ethernet Standards and Approvals


Industrial facilities networking products must meet or exceed stringent industrial regulations and ratings.
When designing a network infrastructure, consider these common certifications and ensure any selected
products meet the requirements necessary for the networks vertical market or application.

UL CMR-CMX Outdoor the basic and most common safety standard for communication cable
C(UL) CMG FT-4 the basic and most common safety standard for Canada
UL Verification Cat 5e/6/6a third-party testing of electrical performance
UL Power Limited Tray Cable (PLTC) the basic rating for installation in 300V power trays
UL Tray Cable (TC) the basic rating for installation in 600V power trays

6
Be Certain with Belden

Conclusion specifically for use in harsh and demanding During the product selection process, it is
environments. Components in the physical important to take the time to evaluate the
Most industrial organizations invest
layer are especially vulnerable and costly marketplace and select a qualified supplier
significantly to protect the safety and
to replace. Its also important to keep in capable of providing a top-quality, end-
security of their production processes
mind that Enterprise-grade products are to-end Ethernet framework tailored to the
and to provide workers with safety and
neither designed for, nor intended for use specific application and environmental
protective gear where needed. Doesnt
in, industrial markets or applications; do conditions. As many adopters of industrial
it make good business sense to invest
not risk your network uptime by using Ethernet have already discovered, taking
wisely to preserve, protect and defend the
COTS cables, which cannot stand up to a total system approach will result
network infrastructure that supports all of
harsh environments. Industrial-grade in a more integrated system with all
the facilitys mission-critical information,
products are far more ruggedly engineered products seamlessly matched to deliver
automation and control functions?
and constructed, and they incorporate interoperability and consistently reliable
The most effective and cost-effective design features and materials capable of performance day after day and year after
way to ensure long-term network withstanding the severe environmental year.
performance and reliability is to invest in and physical stressors to which they are
an industrial Ethernet infrastructure with subjected every day.
networking components designed and rated

References
1. OSI Reference Model (Open Systems Interconnection) definition. TechTarget.com. http://searchnetworking.techtarget.com/definition/OSI
2. Downtime Costs Auto Industry $22k/Minute. http://news.thomasnet.com/companystory/downtime-costs-auto-industry-22k-minute-
survey-481017 (March 27, 2006)
3. Source: Datacom Mag, Network Management Special
4. Nine tests published in the Industrial Ethernet User Guide, IEUG002 2008

About Belden
Belden Inc., a global leader in high quality, end-to-end signal transmission solutions, delivers a comprehensive product
portfolio designed to meet the mission-critical network infrastructure needs of industrial, enterprise and broadcast markets.
With innovative solutions targeted at reliable and secure transmission of rapidly growing amounts of data, audio and video
needed for todays applications, Belden is at the center of the global transformation to a connected world. Founded in 1902,
the company is headquartered in St. Louis, USA, and has manufacturing capabilities in North and South America, Europe and
Asia.

For more information, visit us at www.belden.com and follow us on Twitter @BeldenIND.

Belden, Belden Sending All The Right Signals, Hirschmann, GarrettCom, Tofino Security, Lumberg Automation and the Belden logo are
trademarks or registered trademarks of Belden Inc. or its affiliated companies in the United States and other jurisdictions. Belden and other
parties may also have trademark rights in other terms used herein.

Phone: 1.800.BELDEN1 www.belden.com


Copyright 2016, Belden Inc. ETHERNET-FOR-PHYSICAL-LAYER_WP00022_INCA_BDC_0516_A_AG
7