Vous êtes sur la page 1sur 2

Quick checking C.

A 6411
of earth loops C.A 6413
C.A 6415
EARTH
CLAMPS

mA
CHAUVIN
ARNOUX
A n active element in electrical
protection, the earthing
is usually made up of several
can also be used to
measure the leak
currents flowing into the
links to the equipotential ground. To further optimize
surface (surface of the earth), thus your testing operations, the
forming multiple loops. To complement C.A 6413 and 6415 models
the traditional continuity and earth also possess an alarm function
measurements, the C.A 6411, 6413 and (buzzer if threshold exceeded) and
6415 offer the advantage of quick earth a measurement logging function. In
testing in total safety (the electrical the event of low earth resistances, the C.A 6411, 6413 and 6415 models
installation remains connected to earth,
even during the test). These clamps
C.A 6415 allows measurements from
one tenth of an Ohm upwards. Resistance measurement
mA Current measurement
Remaining battery charge life
Calibre (1) Resolution Accuracy (2) (1) Automatic calibre change
(2) In the reference conditions Battery indicator
0.10 to 1.00 (3) 0.01 (2 % + 0,02 ) (3) Calibre only available

1.0 to 50.0 0.1 (1.5 % + 0.1 ) on the C.A 6415 model Automatic shutdown inhibited
Resistance 50.0 to 100.0 0.5 (2.0 % + 0.5 )
measurement 100 to 200 1 (3.0 % + 1 )
Holding of display
200 to 400 5 (6.0 % + 5 ) 2 Buzzers active
400 to 600 10 (10 % + 10 )
600 to 1200 50 - measure Significant eddy currents
1 to 300 mA 1 mA (2.5 % + 2 mA)
RMS current
0.300 A to 3.000 A 1 mA (2.5 % + 2 mA) Jaws not closed properly
measurement
3.00 A to 30.00 A 10 mA (2.5 % + 20 mA)
C.A 6411 and 6413 models

01 53 42 12 30
Resistance under 1
General specifications 1
clamp C.A 6413 and 6415 models
Clamping diameter: 32 mm
Temperature of use: -10 to +55 C Alarm function
Storage temperature: -30 to +70 C MEM Recording in memory
Relative humidity: 0 to 75% RH
R Reading memory
IP 30 as per EN 60529
Dimensions : 235 x 100 x 55 mm
C.A 6413 and 6415 models:
Alarm threshold adjustable from 1 to 199
Memory capacity: 99 measurements.
ON
A OFF
Electrical specifications

906 111 770 - Ed. 1 - 08/99 - Non contractual document. Confirm specifications before ordering.
Complies with EN 61010-2-032
Dual insulation, class 2
150 V, cat. III, pollution level 2 To order
Max. over-intensity: 100 A AC constant C.A 6411 model
Measurement frequency: C.A 6411 . . . . . . . . . . . . . . . . . . P01.1220.01 ON
C.A 6413 . . . . . . . . . . . . . . . . . P01.1220.02 OFF Start/stop + autotest
1689 Hz (C.A 6411 and C.A 6413)
2400 Hz (C.A 6415) C.A 6415 . . . . . . . . . . . . . . . . . P01.1220.03 Resistance measurement
Each earth clamp is delivered
Charge life: with 9 V alkaline battery in a carrying case with one 9 V battery A Current measurement
(Cd/Ni battery accepted): and a users manual.
1000 thirty-second measurements Calibration loop
(C.A 6411 and C.A 6413) ON
CL1 . . . . . . . . . . . . . . .P01.1223.01 MEM AL A OFF
1500 thirty-second measurements (C.A 6415)
Your distributor

C.A 6413 and 6415 models


ON
OFF Start/stop + autotest

Resistance measurement
A Current measurement
MEM Recording of measurement
AL Alarm activation and adjustment