Vous êtes sur la page 1sur 2

Assembly Instructions for cable gland:

321/R Exe IIC Gb / Extb IIIC Db


AI 452 / Issue D - 03/16

Operating temperature range -60C +100C Certification Details


Gland Type: 321/R Exe IIC Gb, Extb IIIC Db
If an Exe IP cap is fitted (Sizes Os to C2 only) and access is Baseefa06ATEX0059X II 2 GD IP66
required for fitment of a cable, undo Item 1 fully until IECEx BAS06.0016X
you gain access to the cap. Remove the cap from the EAC C RU C-GB.05.B.00750
cable gland seal and replace Item 1.1 against the seal c CSA us No: 1205533 (LR 78713-10)
(Item 1.2) and reassemble Item 1 onto Item 2 then Class 1 Zone 1 AExe II, Zone 21 AExtD
continue with the cable preparation. Class 1 Div 2 ABCD, Class II Div2 Groups EFG, Class III

If the cap is required, please check that the cable gland


is sufficiently tight to seal and retain the cap.
1. Backnut
Optional Exe IP Cap 1.1 Compression Spigot
(Sizes Os to C2 only)
1.2 Seal
1 2. Entry

1.1

1.2

Cable Preparation Gland Preparation

II II

5mm minimum
2 recommended

1
1

A
A B
Allow sufficient length of cable, II, to suit equipment. Unless already screwed into the equipment, hold the entry in
If required, fit shroud. position with a spanner/wrench to prevent rotation and tighten
Pass cable through the cable gland as shown above. the backnut using a wrench/spanner until resistance is felt
between the seal and cable. Then turn the back nut through a
Note : If the equipment has a threaded entry, it may be further half to one full turn to complete the inner seal.
advisable to screw the cable gland into the equipment to
prevent twisting of the cable after Step B To ease wiring inside the equipment it may be beneficial to strip
the outer sheath of the cable as shown above.

IMPORTANT: Support the cable to prevent it from twisting

Connection Solutions www.ehawke.com


Hawke International is a division of Hubbell Ltd. UK Office Sales: +44 (0) 161 830 6698
Registered No. 669157 in England. Registered Office: Oxford Street West, Technical: +44 (0) 161 830 6697
Cannon Place, 78 Cannon Street, London EC4N 6AF. Ashton-Under-Lyne, Fax: +44 (0) 161 830 6648
A member of the Hubbell Group of Companies Lancashire. OL7 0NA. UK E-mail: sales@ehawke.com AI 452 - Issue D / Page 1 of 2
C
Using a suitably sized Phillips head screw driver, carefully tighten
each of the cable clamp screws alternatley until the screws are
tight (torque figure 1.5Nm to 3Nm).

Fit shroud if required

DETAIL A

CABLE GLAND SELECTION TABLE


Cable Acceptance Details
Compressed
Hexagon
Length
Size Entry Thread Size Outer Sheath Dimensions
Ref. Standard Alternative
Seal Seal (S) Across Across IMPORTANT NOTE:
Metric NPT Flats Corners When used in Increased Safety applications, these cable
Min. Max. Min. Max.
glands may be used with braided cables where the braid
Os M20 3.2 8.0 - - 52.0 24.0 26.5 and the outer sheath pass into the enclosure. The braid must
then be suitably terminated within the enclosure. Braided
O M20 6.5 11.9 - - 52.0 24.0 26.5
cable is classed as unarmoured cable in the EN/IEC 60079
series standards for Exe applications.
A M20 or 10.0 14.3 9.0 13.4 52.0 30.0 32.5

B M25 1 or 13.0 20.2 9.5 15.4 54.0 36.0 39.5

C M32 1 or 1 19.5 26.5 15.5 21.2 61.0 46.0 50.5

C2 M40 1 or 1 25.0 32.5 22.0 28.0 67.0 55.0 60.6

Sizes Os and O are available with an M16 thread size. If M16 entry is used on O size cable
glands the maximum cable inner sheath diameter is limited to 10.9mm.

SCHEDULE OF LIMITATIONS - Baseefa ATEX / IECEx: EC Declaration of Conformity in accordance with European Directive
1. This cable gland has an operating temperature range of -60C to +100C. 94/9/EC (until 19th April 2016) and
EU Declaration of Conformity in accordance with European Directive
2. A seal must be formed between the equipment and the cable gland to 2014/34/EU (from 20th April 2016)
maintain the appropriate degree of protection against ingress of dust, Manufacturer: Hawke International
solid objects and water. Address: Oxford Street West, Ashton-under-Lyne, OL7 0NA, United Kingdom

Equipment: Range of Group II Increased Safety Cable Glands Type: 321/R


NOTES - c CSA us: Provisions of the Directive fulfilled by the Equipment:
1. The cable used must have extruded sealing (solid polymeric) completely Group II Category 2GD Exe IIC Gb, Extb IIIC Db IP66
surrounding the core (insulation and conductor), allowing for no holes or
ventilation through the inner jacket or along the cores. Notified Body for EC-Type Examination: SGS-Baseefa 1180 Buxton UK
2. The 321/R series cable gland connectors, when used in Class 1 Division 2 EC-type Examination Certificate: Baseefa06ATEX0059X
Classified areas, are not suitable to be interfaced with an explosion proof
enclosure containing arcing and sparking devices, unless installed in Notified Body for production: SGS-Baseefa 1180 Buxton UK
conjunction with an approved explosion proof sealing fitting.
Harmonised Standards used:
3. These glands are suitable for use with Certified Marine Shipboard EN 60079-0:2012, EN60079-7:2007, EN60079-31:2014.
armoured / unarmoured cables constructed to CSA Standard 245 and
IEEE45 / IEC 600092-353 Standards, or certified equivalent), for use on On behalf of the above named company, I declare that, on the date the equipment
Shipboards and Offshore Rigs / Platforms. accompanied by this declaration is placed on the market, the equipment conforms
with all technical and regulatory requirements of the above listed directives.
4. Must comply with Canadian Electrical Code and National Electric Code
requirements for threaded entries.
.
5. For Exe applications, a sealing washer or thread sealant may be required A. Tindall
between the enclosure and the gland to maintain the IP rating of the Technical Manager
enclosure.

6. This cable gland may only be installed when temperature is above -5C.
After completion of the installation, the assembly is then suitable for -60C
to +100C.

AI 452 - Issue D / Page 2 of 2