Académique Documents
Professionnel Documents
Culture Documents
Denitions 4
Packaging, transport and storage 6
Maintenance 10
Oil sampling 12
Tan-w measurement 14
Maintenance 18
Oil sampling 19
Maintenance 23
Oil sampling 24
Maintenance 27
Manometer 29
Anti-condensation heater 30
Spark gap device 31
Oil test plug 32
Oil test valve 33
PLC carrier accessories 34
PQSensor 38
Undrilled top plate 40
C2 test outlet 41
Pre-/post-energizing Disposal 42
Troubleshooting 44
Checklist 45
ABB has been producing instrument transformers for more than All instrument transformers supplied by ABB are tailor-made to
60 years. Thousands of our products perform vital functions in meet the needs of our customers. An instrument transformer
electric power networks around the world day after day, all year must be capable of withstanding very high stresses in all climatic
round. Their main applications include revenue metering, control, conditions. We design and manufacture our products for a service
indication and relay protection. life of at least 30 years. Actually, most last even longer.
Thank you for purchasing an ABB outdoor instrument transformer. Please carefully
read the applicable parts of this manual before installing and energizing the instrument
transformer.
The manual should be saved for future reference for the entire service life of the
instrument transformer. The gures in this manual are only intended for illustrative
purposes.
Please contact your local ABB ofce if you have any questions.
4 Denitions | Manual
Rated dynamic current (Idyn) Voltage factor (FV)
The dynamic short-time current is according to IEC, It is important that the voltage transformer, for thermal and
Idyn = 2.5 x Ith and according to IEEE, Idyn = 2.7 x Ith protection reasons, can withstand and reproduce the continuous-
fault overvoltages that can occur in the grid. The overvoltage
Primary reconnection factor is abbreviated as FV. The IEC standard species a voltage
The ampere turns for a current transformer always remain the factor of 1.2 continuously and simultaneously 1.5/30 s. for
same, and consequently, the load capacity (load) remains the systems with effective grounding with automatic fault tripping, and
same. The short-circuit capacity however, may be reduced for the 1.9/8 h for systems with insulated neutral points without automatic
lower ratios. Primary reconnection is available for currents at ratios ground fault systems.
2:1 or 4:2:1.
Accuracy, according to IEC, for measuring windings is fullled
Secondary reconnection between 0.8 and 1.2 x rated voltage and for protection windings
Extra secondary terminals (taps) are run from the secondary up to the voltage factor (1.5 or 1.9 x rated voltage).
winding. The load capacity drops as the ampere turns decrease
on the taps, but the short-circuit capacity remains constant. Each Thermal limit load
core can be individually reconnected. Thermal limit load is the total power the transformer can supply
without excessively high temperature rise. The transformer
Load is engineered so that it can be loaded with the impedance
The external impedance in the secondary circuit in ohms at the corresponding to the load at rated voltage, multiplied by the
specied power factor. It is usually expressed as the apparent square of the voltage factor. This means that at a voltage factor
power in VA -, which is taken up at the rated secondary current. of 1.9/8 h, for example, the limit load = total rated load x 1.92.
It is important to determine the power consumption of connected The transformer cannot be subjected to a higher limit load
meters and relays including the cables. without exceeding the rated load. Consequently, because of load
considerations, it is unnecessary to specify a higher thermal limit
RCT load.
The secondary winding resistance at 75C
Ferro resonance
Instrument security factor (FS) Ferro resonance is a potential source of transient overvoltage.
To protect meters and instruments from being damaged by high Three-phase and single-phase switching, blown fuses, and
currents, an FS factor of 5 or 10 is often specied for measuring broken conductors can result in overvoltage when ferro resonance
cores. This means that the secondary current will increase a occurs between the magnetizing impedance of a transformer
maximum of 5 or 10 times when the rated load is connected. and the system capacitance of the isolated phase or phases. For
FS10 is normally sufcient for modern meters. example, the capacitance could be as simple as a length of cable
connected to the ungrounded winding of a transformer. Another
Accuracy limit factor (ALF) example of ferro resonance occurring is when an inductive voltage
The protection cores must be able to reproduce the fault current transformer is connected in parallel with a large grading capacitor
without being saturated. The overcurrent factor for protection across the gap of a circuit breaker. Ferro resonance is usually
cores is called ALF. ALF of 10 or 20 is commonly used. Both FS known as a series resonance.
and ALF are valid at the rated load only. At a lower load the FS
and ALF will increase.
Manual | Denitions 5
Packaging, transport and storage
General information The wood crate material is approved under SWPP, the Swedish
As far as the height permits, instrument transformers are shipped Wood Packing Program, and fullls the requirements for treatment
vertically in packages of three or as single units; see Figure 1 on and marking stipulated in the FAO standard
the next page. Single units can also be shipped in the horizontal ISPM 15.
position depending on the type of transformer.
The treated crates are marked with the ISPM 15 symbol to
Note! certify that they have been subjected to approved measures. The
Transformers delivered in horizontal creates shall marking is clearly visible on at least two opposite sides of the
always be transported, if transported horizontally, crate.
with the same side up as when delivered.
Transportation
Special optional accessories, such as Roxtec cable entry kits An instrument transformer is packed in an export crate, designed
and certain ground terminals, are kept in the terminal box or are to withstand the stresses of transport and storage. However, the
secured inside the crate together with the primary terminals. following have to be considered during transport:
Dampers, adapters, surge arrester etc. are secured to the bottom - The instrument transformer must be handled with care to
of the crate or packed in a separate crate. The crate materials and avoid mechanical damage.
packing methods for instrument transformer are specied in the - Lifting of the crate is preferably by forklift.
following chapters of this document. If slings are used, make sure that the slings pass outside
the crossbar at the bottom of the crate to avoid the risk
Crate markings of dropping the crate.
The following applies to crates: - Transformers packed vertically must not be tilted more
- A packing list and unpacking instructions are stapled to than 45 during transport or storage.
the inside of the crate.
- All crates transported in the vertical position are marked Caution!
with position tags that are stapled on opposite sides of Transformers delivered in horizontal creates shall
the crate. always be transported, if transported horizontally,
- The center of gravity is marked on two opposite sides of with the same side up as when delivered.
the crate.
- The crate label is painted on all four sides. The gross Unpacking
weight is painted on two opposite sides of the crate. Instructions for unpacking and lifting accompany each
- When transported horizontally, the goods label is stapled transformer. When unpacking, check the contents of the crate
on two sides of the crate, both the long and the short against the packing list attached inside each crate, and inform
side. For vertical transportation the goods label is stapled the nearest ABB representative if there is a discrepancy. Crate
on the two short sides of the crate. damage may be a sign of rough transport. Immediately register all
- The crate is marked with international pictorial markings claims regarding any visible damage to the crates or the contents,
on at least two sides, i.e. ISPM 15, UN3363, Marine as well as any shortages, with the carrier and the appropriate
Pollutant and label of class 9+ label marine pollutants. insurance agent. In the event of damage, it is advisable to take
photos.
Crate disposal
The crates consist of a bottom frame, sides and cover made of Caution!
wood. There are also a number of nails, screws and brackets. Do not install or attempt to repair any transformer
Furthermore, there are strips of felt or foam rubber to protect the showing visible damages.
paint (only applicable for painted units). These components can be
recycled according to local regulations.
Be especially observant of signs of oil leakage and insulator
damage, and that oil is visible in the oil level glass on the
Heat treatment of crates
transformer. Leakage must be immediately localized.
The wooden transport crates have been debarked and heat
treated in conjunction with kiln drying.
1 Example of a single unit packed using a horizontal single package | 2 Example of three units packed using vertical three pack
1 2
Delivery
Check the transformer for any transport damages immediately
CAUTION upon delivery. Damage to packaging may be a sign of rough
FOR YOUR SAFETY handling. Note any damage (it is advisable to take pictures)
DO NOT ATTEMPT TO HANDLE, INSTALL,
USE OR SERVICE THIS PRODUCT
BEFORE READING THE INSTRUCTION
and contact the appropriate insurance company. Check the
MANUAL. transformer. Be especially observant of signs of oil leakage
Failure to read the instruction manual prior and insulator damage and that oil is visible in the oil level glass.
to performing these actions can lead to
serious injury and/or damage. Leakage must be immediately localized.
1 Connection of standard ground terminal (other types can be supplied upon request when an order is placed)
Connecting the primary terminals A connection that is not properly tightened can cause overheating
Primary connections should be made so that static and damage to the transformer. The maximum permitted static
mechanical loads on the primary terminals are minimized. This test load is according to the dimensional drawing for all directions,
is accomplished by using a exible component, either in the in compliance with IEC.
connector or in another part of the primary connection.
A rigid, non-exible connection may result in oil leakage at the Each crate is accompanied with detailed assembly instructions
primary terminals. All connections must be carefully made. for primary terminals; see types in Figures 1-5. Carefully follow the
instructions to avoid damage to the unit.
1 Connection for low current | 2 Connection for high current | 3 Connection for high current with both stud type and ag type shown | 4 Connection for
low current | 5 Connection for rated current
1 2
3 4 5
Transformer damage
Metal, porcelain and epoxy components are checked. Porcelain
components are cleaned as necessary.
Tan-w measurement
Tan-w measurements are recommended after 1520 years of
service, but if high values are noted, measurements should be
made once yearly. Upon request, transformers can be supplied
with a capacitive voltage terminal or DDF terminal that is normally
grounded.
Caution!
High voltages are present at all unconnected taps
when the transformer is in service.
Oil sampling
After a longer period of service (1520 years) or if damage is
suspected after for example, a major operational disturbance, an
oil sample can be extracted for testing of the oils moisture and
gas contents.
Oil sampling and oil lling must be performed in dry weather Submitting oil samples and reports
and with the transformer dry. The transformer must be taken Mark the syringe with the transformers serial number and ll in the
out of service and the transformer top must be grounded. report.
Transformers with coolers are sealed with an overpressure at Return the syringes and the questionnaire in the transport box as
about +20C, and subsequently depressurized at about -10C. soon as possible after sampling to the diagnostics lab, using the
Transformers with coolers for customers who have specied more delivery address stated in the end of the document.
than +40C as the maximum ambient temperature are sealed Reports of analysis results and recommended measures are sent
without overpressure at about 20C. Ensure that tools are at hand by ABB within ten working days from reception of oil samples.
before beginning work. Additional information concerning sampling or analysis results can
be obtained from ABB Instrument Transformers.
Caution!
Never open the oil plug on the oil tank when taking Transformers with metal bellows, i.e. expansion chambers shaped
an oil sample. as cooling anges, may not be opened because of internal
overpressure. Contact ABB AB according to the information
above for oil sampling.
Note!
The transformer normally has a slight overpressure,
Transformers with gas cushion
so be careful to avoid oil spillage when opening.
The transformers have an oil lling hole at the top of the expansion
chamber where oil samples can be taken, see Figure 1-5 on the
Preparation and information
next page, depending on type of expansion system. To take an oil
Before taking the oil sample, the following should be checked:
sample on the current transformer, follow the steps below.
- That the glass syringe is in proper condition, i.e. clean
- First open the oil lling cover.
and dry.
Check the sampling syringe
- Suitable tools are on hand for opening and sealing the
- Carefully insert the hose into the oil lling hole. The hose
transformer.
must be beneath the oil surface.
- That a vessel for surplus oil is on hand to avoid spilling oil
- Flush the syringe with oil from the transformer and empty
onto the ground.
the syringe according to the information above.
- It is recommended that a special oil sampling kit be
- Close the side outlet and ll the syringe again with oil
used, which can be ordered from ABBs diagnostic
from the transformer, taking care not to draw in gas. This
lab. Contact information can be found at the end of the
is the oil sample. Close the valve after sampling.
document.
- Clean the sealing surfaces at the oil lling opening from
spilled oil and foreign matter, and install new o-rings if
Using the syringe supplied by the manufacturer
necessary.
The syringe supplied by the manufacturer has three valve
- Seal the transformer at a torque of 25 Nm.
positions: closed, open through the hose and open to a side
outlet. The plunger may not be touched because of the risk of
drawing air into the syringe. Caution!
The caption for Figure 1-5, on the next page,
The syringe must be ushed with oil to ensure that the oil is describes which of the expansion systems are
sampled and not mixed with air that is still in the hose. This is testable or non-testable through the oil lling hole.
done by extracting oil from the transformer, which is emptied by
changing the valve position and emptying the syringe through Transformers with test plugs or test valves
the side outlet. During the procedure, ensure that no gases are If an instrument transformer is supplied with a oil test plug or oil
extracted from the transformer. test valve there is no need to open the transformer to take an oil
sample. Information on how to use oil test valves and test plugs is
If a slight amount of gas has entered the syringe despite provided in the optional accessories chapter.
preventive measures, hold the syringe upright and slowly press
out the gas with the plunger. If gases have been drawn into the
syringe, this should be noted in the report.
3 4
Before energizing, a tan-w measurement is recommended. Measurements between primary terminals and capacitive
This measurement should be kept as a reference. taps
Measurement for maintenance measurements in the future. - Disconnect the primary terminals from the busbar.
Its important that the same test equipment is used for each - Measure the resistance of one secondary winding.
measurement. - Calculate the actual winding temperature, Ta, of
the winding as Ta = (Ra/Ro)(235-T0)-235 where Ra is
Conditions for measurements the measured winding resistance, R0 is the winding
Field measurements made at ambient air temperatures below resistance measured in the factory routine test and T0 is
10C have proven to produce inconsistent results. Measurements the temperature during the factory routine test.
shall preferably be made at temperatures around 20C. - Check that one end of all secondary windings is
Field measurements shall preferably not be made with rated connected to ground.
frequency to avoid disturbances. (Test equipment, such as DOBLE - Connect the tan-w bridge with point 1 to the voltage
M 4000 that uses a test frequency of 45-75 Hz, is available on terminal, point 2 to the ground/guard terminal and
the market.) The relation between tan-w at 50 Hz and the test point 3 to the current terminal of the test equipment as
frequency, for the range of interest for tan-w = 0.5-1.0%, is described in Figure 1 on the next page.
tan-w50 Hz=ftest tan-wtest/50, where ftest is the test frequency used.
For measurements between primary terminals and capacitive
When making eld measurements it is important to try to taps, a test voltage up to 10 kV can be used depending on the
estimate the temperature of the test object. One way is to test equipment.
measure the secondary winding resistance, just before making
the tan-w measurement, and comparing with the value given at Measurements between capacitive taps and ground
room temperature in the routine test report for the transformer. - Connect one of the primary terminals to ground.
Alternatively, the current transformer can be left non-energized - Measure the resistance of one secondary winding.
until the internal temperature drops to the ambient temperature. - Calculate the actual winding temperature, Ta, of
(For IMB current transformers, this can be expected to take about the winding as Ta = (Ra/Ro)(235-T0)-235 where Ra is
6-12 hours.) the measured winding resistance, R0 is the winding
resistance measured in the factory routine test and T0 is
The measurement can be made in different ways depending on the temperature during the factory routine test.
whether the current transformer is provided with a capacitive tap, - Check that one end of all secondary windings is
DDF terminal or without a special tap. connected to ground.
- Connect the tan-w bridge with point 1 to ground,
Current transformers equipped with capacitive voltage taps point 2 to ground/guard and the current terminal and
It is recommended that measurements be made between the high point 3 to the voltage terminal of the test equipment as
voltage terminals and capacitive tap, but measurements can also described in Figure 1 on the next page.
be made between the capacitive tap and ground.
Measurement between primary terminals to capacitive taps is
preferred, as this will provide information about the main part of
the insulation. Measurement between capacitive taps and ground
only provides information about a small part of the insulation. Test
voltages for measurement between capacitive taps and ground
must be limited to a maximum of 2.5 kV.
Delivery
Immediately check the inductive voltage transformer for any
CAUTION transport damage upon delivery. Damage to packaging may be a
FOR YOUR SAFETY sign of rough handling. Note any damage (it is advisable to take
DO NOT ATTEMPT TO HANDLE, INSTALL,
USE OR SERVICE THIS PRODUCT
BEFORE READING THE INSTRUCTION
pictures) and contact the appropriate insurance company. Check
MANUAL. the transformer. Be especially observant of signs of oil leakage
Failure to read the instruction manual prior and insulator damage and that oil is visible in the oil level glass.
to performing these actions can lead to
serious injury and/or damage. Leakage must be immediately localized.
There are also ground terminals in the terminal box for connection
of appropriate winding terminals and cable screens.
Neutral terminal
The transformer is equipped with an external, so-called neutral
terminal (N-terminal) on the primary winding. Check that it is
grounded to the grounding point in the terminal box.
Caution!
High voltages are present at the neutral terminal
when the voltage transformer is in service.
Mount the primary terminal on the top of the expansion tank, see
Figure 2, with four M10 bolts and washers with a tightening torque
of 45 Nm. Also mount other enclosed components, if any, such as
dampers, adapters etc. This can be done before the transformer
is mounted on the support.
Minimal maintenance is required due to the transformer being Oil level check
hermetically sealed. A visual check is normally sufcient The left side of the oil level glass, located as shown in Figure 1,
when the recommendation is to follow the checklist at the must always be dark, see Figure 2, at all ambient temperatures.
back of the manual. If the right side of the oil level glass is not completely black,
there is oil leakage. This should be localized and corrected as
Check for oil leakage at the following positions: soon as possible. When there is leakage, moisture can enter the
- Oil level glass and oil lling plug transformer.
- Seals at top and bottom ange of the insulator
- Seal between the oil tank and lid Note!
- Secondary terminal box bushing The entire oil level glass must always be dark when
- Oil drain plug (if any) the transformer is in service.
Oil lling
Filling of oil can be necessary when the oil level in the transformer
is one liter low. If oil needs to be lled, contact the manufacturer
for further instructions. Contact information can be found at the
end of the document.
1 Oil level glass location on an inductive voltage transformer 2 Oil level glass indicating empty
Oil sampling and oil lling must be performed in dry weather Reports of analysis results and recommended measures are sent
and with the transformer dry. The transformer must be taken by ABB within ten working days from reception of oil samples.
out of service and the transformer top must be grounded. Additional information concerning sampling or analysis results can
be obtained from ABB Instrument Transformers.
Caution!
Never open the oil plug on the oil tank when taking Transformers with gas cushions
an oil sample. The transformers have an oil lling hole at the side of the
expansion chamber where oil samples can be taken; see Figure 1.
To sample oil on the voltage transformer, follow the steps below.
Note!
- First open the oil lling cover.
The transformer normally has a slight overpressure,
Check the sampling syringe.
so be careful to avoid oil spillage when opening.
- Carefully insert the hose into the oil lling hole. The hose
must be beneath the oil surface.
Preparation and information
- Flush the syringe with oil from the transformer and empty
Before taking the oil sample, the following should be checked:
the syringe according to the information above.
- That the glass syringe is in proper condition, i.e. clean
- Close the side outlet and ll the syringe again with oil
and dry.
from the transformer, taking care not to draw in gas. This
- Suitable tools are on hand for opening and sealing the
is the oil sample. Close the valve after sampling.
transformer.
- Clean the sealing surfaces at the oil lling opening from
- That a vessel for surplus oil is on hand to avoid spilling oil
spilled oil and foreign matter, and install new o-rings if
onto the ground
necessary.
- It is recommended that a special oil sampling kit be
- Seal the transformer at a torque of 25 Nm.
used, which can be ordered from ABBs diagnostic
lab. Contact information can be found at the end of the
Transformers with test plugs or test valves
document.
If an instrument transformer is supplied with a oil test plug or oil
test valve there is no need to open the transformer to take an oil
Using the syringe supplied by the manufacturer
sample. Information on how to use oil test valves and test plugs is
The syringe supplied by the manufacturer has three valve
provided in the optional accessories chapter.
positions: closed, open through the hose and open to a side
outlet. The plunger may not be touched because of the risk of
drawing air into the syringe. 1 Expansion system with exploded view of the oil lling cover
The syringe must be ushed with oil to ensure that the oil is
sampled and not mixed with air that is still in the hose. This is
done by extracting oil from the transformer, which is emptied by
changing the valve position and emptying the syringe through
the side outlet. During the procedure, ensure that no gases are
extracted from the transformer.
Delivery
Check the capacitor voltage transformer for any transport
CAUTION damages immediately upon delivery. Damage to packaging may
FOR YOUR SAFETY be a sign of rough handling. Note any damage (it is advisable to
DO NOT ATTEMPT TO HANDLE, INSTALL,
USE OR SERVICE THIS PRODUCT
BEFORE READING THE INSTRUCTION
take pictures) and contact the appropriate insurance company.
MANUAL. Check the transformer. Be especially observant of signs of oil
Failure to read the instruction manual prior leakage and insulator damage and that oil is visible in the oil level
to performing these actions can lead to
serious injury and/or damage. glass. Leakage must be immediately localized.
All information contained in this manual is based on the latest Connecting secondary terminals in the terminal box
product information available at the time of printing. The right The secondary terminals must be carefully connected. There
is reserved to make changes at any time without notice. are markings on the terminal block. There is a wiring diagram
on the transformers rating plate, inside the terminal box. Each
unused secondary winding must have one end grounded. Ground
terminals are located in the secondary terminal box.
Assembly Mount the primary terminal on the top of the expansion system,
Each transformer should be checked for possible oil leakage, see Figure 2, with four M10 bolts and washers and torque to
porcelain damage and other damage caused by rough handling. 45 Nm. Also mount other enclosed components, if any, such as
Check that the oil level is correct according to the maintenance dampers, adapters etc. This can be done before the transformer
chapter. If not, carefully check for possible oil leakage and contact is mounted on the support.
ABB for further instructions.
Connect the transformers high voltage terminal to the line,
Prior to assembly, ensure that the support structure is at and preferably with a exible aluminum cable so as to minimize the
horizontal. If not, correct with washers. Deformation of the bottom mechanical load on the primary terminal. The maximum permitted
tank may otherwise occur and possibly lead to oil leakage and/or static test load for all directions is according to the dimensional
insulator damage. The tolerance for atness is 1.5 mm. If there is drawing in compliance with IEC.
an upper unit, it is carefully placed on top of the bottom unit.
Low voltage terminal
The low voltage terminal, marked as L, is connected to the ground
Note!
upon delivery. Both the low voltage and chassis terminals are
The same manufacturing number must be on the top
accessible in the transformers terminal box. The cable between
and bottom units.
the L-terminal and the chassis terminal must be disconnected
when carrier equipment is connected.
The upper unit, if any, is secured with the supplied bolts and
washers, see Figure 1, at a tightening torque of 79 Nm for M12
bolts or 121 Nm for M14. The bolts are included in the delivery. If
the apparatus consists of additional units, repeat this procedure.
Pay attention to the orientation of the upper unit since this will
affect the position of the primary terminal.
1 Connection of standard ground terminal (other types can be supplied upon request when an order is placed)
Minimal maintenance is required due to the transformer being tan-w is normally obtained in conjunction with capacitance
hermetically sealed. A visual check is normally measurement. The value of the tan-w varies with age, the test
sufcient with the recommendation of following the checklist method, the selected voltage level and temperature. An absolute
at the back of this manual. reference value can thus not be provided. Consequently, the tan-w
is primarily compared to previous values obtained with equivalent
Check for oil leakage at the following positions: methods and conditions so that any trends can be detected. It
- Oil level glass and oil lling plug is therefore helpful if one or more reference values have been
- Seals above and below the insulator obtained by measuring the tan-w at an earlier stage, for example in
- Drain slots on expansion housing conjunction with commissioning, (rst energizing).
- Seal between oil tank and cover
- Seal between cover and CVD Oil level check of the electromagnetic unit
- Seal between terminal box and oil tank The electromagnetic unit is supplied with an oil level glass which is
- Oil drain plug designed, as seen in Figure 1, with a black and an uncolored side.
Transformer damage The oil level glass must always be dark for electromagnetic units
Metal, porcelain and epoxy components are checked. Porcelain designed as per Figure 2 at all ambient temperatures. If the oil
components are cleaned as necessary. level glass is not completely dark, the transformer should be
checked for leakage and corrected as soon as possible. When
Minor damage to insulator sheds can be repaired on site. there is leakage, moisture can enter the transformer.
Instructions for repair of porcelain and polymer insulators can
be obtained from your ABB representative; see the contact For electromagnetic units designed as per Figure 3, the oil
information at the end of the document. level shall always be visible in the oil level glass at all ambient
temperatures. If the oil level is not visible, the transformer should
Oil lling be checked for leakage and corrected as soon as possible. When
Filling of oil can be necessary when one liter of oil has been there is leakage, moisture can enter the transformer.
extracted from the EMU. If oil needs to be lled, contact the
manufacturer for further instructions. Contact information can be Note!
found at the end of the document. The entire oil level glass must always be dark for
units as in Figure 2, or visible for units as in Figure 3,
Tan-w measurement (capacitor voltage divider only) when the transformer is in service.
After a longer period of service (1520 years) or if a fault is
suspected after for example, a major operational disturbance, Oil sampling (electromagnetic unit only)
the tan-w for the capacitor voltage divider can be measured After a longer period of service (1520 years) or if damage is
electrically. Note that the capacitor voltage divider consists of suspected after for example, a major operational disturbance, an
one or more sections that cannot be opened. Consequently, oil oil sample can be extracted for testing of the oils moisture and
samples cannot be taken. gas contents.
1 Oil level glass indicating empty | 2 Oil level glass location on electromagnetic unit of type EOH | 3 Oil level glass location on electromagnetic unit of
type EOL or EOM
1 2 3
Oil sampling and oil lling must be performed in dry weather Taking an oil sample
and with the transformer dry. The transformer must be taken To take an oil sample, follow the steps below.
out of service and the transformer top must be grounded. - First open the oil lling plug; see Figures 1 and 2 on the
next page.
There is an oil lling plug on the cover of the capacitor voltage - Check the sampling syringe.
transformer's electromagnetic unit where oil samples can be - Carefully insert the hose into the oil lling hole. The hose
taken. Ensure that tools are at hand before beginning work. must be beneath the oil surface.
- Take an oil sample after pre-lling the syringe with oil
Preparation and information according to the instructions above. If a little air has
Before taking the oil sample, the following should be checked: entered the syringe despite preventive measures, hold
- That the glass syringe is in proper condition, i.e. clean the syringe upright and slowly press out the air with the
and dry. plunger. If air has been drawn into the syringe, note this
- Suitable tools are at hand for opening and sealing the in the report.
transformer. - Close the valve after sampling.
- That a vessel for surplus oil is at hand to avoid spilling oil - Clean the sealing surfaces at the oil lling opening from
onto the ground. spilled oil and foreign matter, and install new o-rings if
- It is recommended that a special oil sampling kit be necessary.
used, which can be ordered from ABBs diagnostic - Seal the transformer with a torque of 25 Nm.
lab. Contact information can be found at the end of the
document. Transformers with test valve
- Replacement seals for oil lling plug are at hand. If the instrument transformer is supplied with an oil test plug or oil
test valve there is no need to open the transformer's oil lling plug
Using the syringe supplied by the manufacturer to take an oil sample. Information on how to use oil test valves
The syringe supplied by the manufacturer has three valve and test plugs is provided in the optional accessories chapter.
positions: closed, open through the hose and open to a side
outlet. The plunger may not be touched because of the risk of Submitting oil samples and reports
drawing air into the syringe. Mark the syringe with the transformers serial number and ll in the
report.
The syringe and hose are then ushed with oil from the
transformer oil lling plug; see either Figure 1 or 2 on the next Return the syringes and the questionnaire in the transport box as
page. This ensures that the transformer oil is sampled and not the soon as possible after sampling to the diagnostics lab, using the
oil mixed with air that is still in the hose. Carefully pull the syringe delivery address stated in the end of the document.
and check that only oil is drawn in. Fill the syringe with oil to ush
it. Change the valve position and empty the syringe through the Reports of analysis results and recommended measures are sent
side outlet into the vessel for oil spillage without withdrawing the by ABB within ten working days from reception of oil samples.
hose from the transformer. Additional information concerning sampling or analysis results can
be obtained from ABB Instrument Transformers.
Close the side outlet and ll the syringe again with oil from the
transformer, still without drawing in air. This is the oil sample. Capacitor voltage divider
The capacitor voltage divider, consisting of one or more sections,
If a slight amount of gas has entered the syringe despite may not be opened. Consequently, oil samples cannot be
preventive measures, hold the syringe upright and slowly press taken. As an alternative to oil sampling, the tan-w can instead be
out the gas with the plunger. If gases have been drawn into the measured in conjunction with capacitance measurement.
syringe, this should be noted in the report.
Delivery
Check the coupling capacitor for any transport damages
CAUTION immediately upon delivery. Damage to packaging may be a
FOR YOUR SAFETY sign of rough handling. Note any damage (it is advisable to take
DO NOT ATTEMPT TO HANDLE, INSTALL,
USE OR SERVICE THIS PRODUCT
BEFORE READING THE INSTRUCTION
pictures) and contact the appropriate insurance company. Check
MANUAL. the capacitor. Be especially observant of signs of oil leakage
Failure to read the instruction manual prior and insulator damage. Leakage must be immediately localized.
to performing these actions can lead to
serious injury and/or damage. Instructions for repair of porcelain and polymer insulators can be
obtained from ABB; see the contact information at the end of this
document.
Safety notice
This coupling capacitor should be installed within the design Lifting the coupling capacitor
limitations as described on its rating plate and in these Each package is delivered with detailed lifting instructions that
instructions. Follow your companys safety must be complied with when lifting. Any deviation from the
procedures. This product is intended to be operated and instructions may harm the product.
maintained by qualied persons who are thoroughly trained
and who understand the hazards involved. This publication is Top sections, if so equipped, are packaged separately with up to
written only for such qualied persons and is not intended to three sections in each crate.
be a substitute for adequate training and experience in safety
procedures for this device. The detailed lifting instructions can be sent separately if requested.
Please contact your ABB representative for further information.
WARNING Caution!
DETAILED DESCRIPTIONS OF STANDARD REPAIR
The coupling capacitor must be placed in the vertical
PROCEDURES, SAFETY PRINCIPLES AND SERVICE
position at least 24 hours before energizing.
OPERATIONS ARE NOT INCLUDED. IT IS IMPORTANT
TO NOTE THAT THIS DOCUMENT CONTAINS CERTAIN
WARNINGS AND CAUTIONS REGARDING CERTAIN Assembly
SPECIFIC SERVICE METHODS THAT COULD CAUSE Each coupling capacitor should be checked for possible oil
PERSONAL INJURY TO SERVICE PERSONAL OR COULD leakage, porcelain damage and other damage caused by rough
DAMAGE EQUIPMENT OR RENDER IT UNSAFE. PLEASE handling.
UNDERSTAND THAT THESE WARNINGS CANNOT COVER
ALL CONCEIVABLE WAYS IN WHICH SERVICE, WHETHER Prior to assembly, ensure that the support structure is at and
OR NOT RECOMMENDED BY ABB, MIGHT BE PERFORMED horizontal. If not, correct with washers. Deformation of the adapter
OR POSSIBLE HAZARDOUS CONSEQUENCES OF EACH plate may otherwise occur and possibly lead to oil leakage and
CONCEIVABLE WAY, NOR COULD ABB INVESTIGATE ALL insulator damage. The tolerance for atness is 1.5 mm.
SUCH WAYS. ANYONE USING SERVICE PROCEDURES
OR TOOLS, WHETHER OR NOT RECOMMENDED BY The upper unit, see Figure 1, is secured with the supplied bolts
ABB, MUST THOROUGHLY ENSURE ONESELF THAT and washers at a tightening torque of 79 Nm for M12 bolts or 121
NEITHER PERSONAL NOR EQUIPMENT SAFETY WILL Nm for M14. The bolts are included in the delivery. If the apparatus
BE JEOPARDIZED BY THE SERVICE METHOD OR TOOLS consists of additional units, repeat this procedure. Pay attention to
SELECTED. the orientation of the upper unit since this will affect the position of
the primary terminal.
All information contained in this manual is based on the latest
product information available at the time of printing. The right Connecting the primary terminal
is reserved to make changes at any time without notice. The primary terminal is attached to the bottom of the crate. With
horizontal transport, its placed in the package near the expansion
tank and with vertical transport at the bottom of the crate.
Connect the coupling capacitors high voltage terminal to the line, Check for oil leakage at the following positions:
preferably with a exible aluminum cable so as to minimize the - Seals above and below the insulator
mechanical load on the primary terminal. The maximum permitted
static test load for all directions is according to the dimensional Tan-w measurement
drawing in compliance with IEC. After a longer period of service (1520 years) or if a fault is
suspected after for example, a major operational disturbance, the
Connection of ground terminals tan-w for the coupling capacitor can be measured electrically. Note
As standard the transformer is delivered with a ground clamp that the coupling capacitor consists of one or more sections that
which is to be installed on one of the mounting pads for grounding cannot be opened. Consequently, oil samples cannot be taken.
of the entire apparatus, see standard ground terminal in Figure 3.
In case the ground clamp is not installed on the mounting pad, Tan-w is normally obtained in conjunction with capacitance
upon delivery, the ground clamp is found inside the package.If measurement. The value of the tan-w varies with, age, the test
special, optional, ground bars are ordered, these are found inside method, the selected voltage level and temperature. An absolute
the package. Make sure that the ground terminal, by means of reference value can thus not be provided. Consequently, the tan-w
a separate conductor, is securely connected to ground. Also is primarily compared to previous values obtained with equivalent
make sure that the ground terminal is galvanically connected to methods and conditions so that any trends can be detected. It
the mounting pad of the apparatus, in particular if the oil tanks is therefore helpful if one or more reference values have been
surface is painted or anodized. Note that the ground terminal can obtained by measuring the tan-w at an earlier stage, for example in
be attached on at least two feet. conjunction with commissioning, (rst energizing).
28 Accessories | Manual
The manometer is mounted at the top of the transformer
Manometer and if ordered prior to manufacture, can be supplied on IMB
current transformers and EMF inductive voltage transformers.
The manometer is provided with a quick release coupling and Current transformers with gas cushion type of
delivered separately either inside the terminal box or in a separate expansion system
box at the same location as the transformer. The coupling on the A current transformer equipped with an expansion system of the
transformer is covered by a protective hood. See Figure 1 for an gas cushion type is delivered with atmospheric pressure, i.e. no
example where the manometer is mounted on a transformer. overpressure. A reading of zero on the gauge upon delivery is
normal. When the current transformer is in service at maximum
To connect the manometer to the transformer, rst loosen the ambient temperature, the readings can by as high as 0.15 bar.
M8 bolts and remove the protective hood, then plug in the
manometer. To remove the manometer, pull back the locking Current transformers with metal bellows type of
ring on the quick coupling. Slight oil spillage when removing the expansion system
manometer is normal. If the manometer is removed for a longer A current transformer equipped with an expansion system of
period of time, the coupling on the transformer must be covered the metal bellows type is delivered with an overpressure. The
by the protective hood. Clean the sealing surfaces, check the overpressure depends on the temperature range the current
o-ring and replace if damaged. Mount the protective hood and transformer is designed for (see rating plate). A reading of
tighten the M8 bolts to a torque of 22.5 Nm. -0.25 bar to +0.5 bar is normal upon delivery. When the current
transformer is in service at maximum ambient temperature,
the readings can be up to 0.15 bar higher than on unloaded
transformers.
Caution!
To ensure that the manometer connection is not
damaged during lifting, do not remove the protective
hood until the unit is mounted on the support
structure.
Manual | Accessories 29
Optional accessories
1 Anti-condensation heater mounted inside the secondary terminal box. Point one (1) is the terminal where the auxiliry power supply is to be connected,
according to the specication of the heater, point two (2) is the thermostat, point three (3) is the cable installed after manufacturing and point four (4) is
the heater element.
30 Accessories | Manual
The spark gap device is in the secondary terminal box and if
Spark gap device ordered prior to manufacture, can be supplied on IMB current
transformers.
It is a well known fact that high voltages are induced if a current 1 Secondary terminal box supplied with spark gap devices, as
transformer is operated with open secondary circuits. The shown with point one (1) | 2 View of spark gap device
Beside the risk for injury to personal, the high induced voltage
may cause damage to the current transformer and the excitation
losses in the saturated core may create abnormal heating inside
the transformer.
Adjustment at site
If the setting must be adjusted or for any other reason a check of
the adjustment becomes necessary, follow the four steps below.
- If a protective spark gap device is mounted, see
Figure 1, start by checking the distance using a
thickness gauge.
If the distance is unsatisfactory, continue with the
remaining steps. 1
Manual | Accessories 31
Optional accessories
Before proceeding, be sure to read the oil sampling information To take an oil sample, follow the below steps:
provided in a separate chapter for the pertinent instrument - Remove the protective cover; see Figure 1.
transformer. - Loosen the bolt one turn only.
- Carefully press the needle through the rubber membrane
To take an oil sample through the test plug, see Figures 1, a in the oil test plug; see Figure 2.
syringe is needed with a needle diameter of 0.7 mm (ambient - Close the side outlet and ll the syringe with oil from the
temperature > 0C) or 1.0 mm (ambient temperature < 0C) and transformer, taking care not to draw in gas. This is the oil
a minimum length of 40 mm. The syringe can be ordered from the sample. Close the valve on the syringe after sampling.
manufacturer. - Remove the syringe and tighten the bolt.
Caution! - If gases are drawn into the syringe; position the syringe
To avoid damaging the rubber in the oil test plug, with the needle upwards and carefully evacuate the
the needle must be carefully pressed through the gases after opening the syringe valve. When all gases
membrane. are evacuated close the syringe valve. If the quantity of
oil is not enough repeat the steps above without
evacuating the oil from the syringe.
Note!
- Clean up any oil spills and sealing surfaces.
The rubber in the oil test plug has a service life of
- Check the o-ring and replace if damaged.
approximately 100 needle insertions.
- Tighten the protective cover; see Figure 1.
1 Exploded view of the protective cover over the test plug | 2 Insertion of needle in the test plug. The syringe shall be inserted with the opening upwards
when pressed through the membrane of the test plug
1 2
32 Accessories | Manual
The oil test valve is mounted at the top of the transformer
Oil test valve and can be supplied if specied when ordering prior
to manufacture on IMB current transformers, EMF
inductive voltage transformers and CPB capacitor voltage
transformers.
Before proceeding, be sure to read the oil sampling information 1 Exploded view of test valve | 2 Nut connected to test valve | 3 Using the
provided in a separate chapter for the pertinent instrument syringe with the test valve
1
transformer.
The oil sample when the transformer is supplied with a test valve,
see Figure 1, is taken by following the steps below:
- Loosen the two bolts (in some cases one) and remove
the protective hood; see Figure 1.
- Remove the plug from the test valve; see Figure 1.
- Carefully connect the equipment to the oil test valve.
Note that a tube nut, as seen mounted in Figure 2, is
needed for the connection with a thread diameter of
G3/8". This tube nut is normally not included.
2
- Open the screw on the test valve by turning it clockvise a
quarter turn.
- Flush the syringe with oil from the transformer and empty
the syringe without removing it from the test valve.
- Close the side valve and ll the syringe again with oil
from the transformer, still without drawing in air; see
Figure 3. This is the oil sample.
- Close the valve on the syringe after sampling.
- Close the screw on the test valve by turning it
3
anti-clockvise a quarter turn.
- Clean up any oil spills and sealing surfaces. Ret the
plug. Do not over-tighten the plug; nger tightening is
enough for sealing.
- Check the o-ring and replace if damaged.
- Mount the protective hood and tighten the M8 bolts to a
torque of 22.5 Nm.
Manual | Accessories 33
Optional accessories
accessories transformers.
PLC is mainly used to reliably transmit speech, energy 1 Schematic view of PLC connected to a capacitor voltage devider. Point
management data and power system protection signals through one (1) is the high voltage terminal of the capacitor voltage devider. Point
two (2) is the intermediate voltage bushing towards the electromagnetic
high voltage power transmission lines. All ABB CPB capacitor unit. Point three (3) is the connection between the L-terminal and the
voltage transformers have a low voltage terminal (L-terminal) PLC accessory. Point four (4) is the schematic view of the PLC accessory
in the secondary terminal box where the high frequency carrier which consist of, from the left, a ground switch, an air gap and a drain
signal from a Line Matching Unit (LMU) can be connected. If the coil.
1
Users guide and specications
Although the L-terminal is delivered grounded, do not open or
touch the low voltage terminal (L) while the CVT is energized.
Note that the PLC ground switch, see Figure 1, is designed to
prevent the lid of the terminal box from being opened when the
switch is in Carrier position, i.e. open position. When the PLC
ground switch is in the Grounded position, i.e. closed position,
2
this mechanical interlocking is released and the lid can be opened.
The drain coil is set to 12, 24 or 48 mH, depending on what was
selected upon ordering, and has BIL 10 kV 1.2/50 s insulation.
The corresponding air gap has a protection level, i.e. ash-over
impulse voltage, of maximum 8.5 kV 1.2/50 s with AC ash-over
of at least 2.5 kV RMS.
Note!
If a unit is delivered with the PLC accessories and is
not going to be used for power line communication,
3
no extra steps needs to considered due to the PLC
accessories when installing the unit.
34 Accessories | Manual
Connecting the LMU to the PLC accessory Follow these steps to connect the carrier lead-in cable:
If the supplied PLC accessory is going to be connected to a - Make the necessary arrangement so the lead-in cable is
LMU, the LMU is to be connected to the low voltage terminal inside the secondary terminal box.
(L-terminal), marked with L inside the terminal box, see Figure 1. - Loosen the nuts from for the L-terminal pinscrew marked
with L in the secondary terminal box.
The carrier lead-in cable, from the LMU to the L-terminal, should - Remove the terminal marking.
be of outdoor weather-resistant type. The recommended cable - Attach the lead-in cable to the L-terminal.
type is insulated 16-25 mm2, test voltage 2.5 kV AC wet, BIL 10- - Put the terminal marking back on the L-terminal and
15 kV 1.2/50 s. The choice of coax cable on the modems side tighten the inner nut with a tightning torque of 15 Nm
of the LMU is left to the customer. and the marking's nut with a tightning torque of 10 Nm.
Manual | Accessories 35
Optional accessories
PLC carrier
accessories
Connecting of PLC without PLC accessories included 1 Terminal box without supplied PLC accessories. Cable marked by point
Since modern Line Matching Units (LMU) often contains the PLC one (1) is installed during manufacturing and is the grounding cable to the
L-terminal. | 2 Terminal box without supplied PLC accessories where the
accessories, that could be supplied with the capacitor voltage grounding cable to the L-terminal has been removed. The cable marked
transformer, the PLC accessories might not be necessary even if by point one (1) is the lead-in cable which is connected during installation.
the unit is going to be connected to a LMU. 1
Note!
Advice with the manufacturer of the LMU if it is
compatible with the supplied transformer.
One of the main reasons for the drain coil is to enable a solid
current path for the power frequency current through the CVD
and thus enabling the CVT's functionality, but at the same time,
imposing impedance high enough across the LMU or coupling
device to minimize carrier losses.
36 Accessories | Manual
frequencies (typically between 30500 kHz) but also increase the 1 View of capacitor voltage transformer connected with a line matching
undesired voltage drop at power frequency. Although this voltage unit and with a line trap.
Manual | Accessories 37
Optional accessories
The PQSensor provides an output signal of 63.5 V AC that is In other words, for normal PQSensor applications for monitoring
compatible with all modern power quality recorders and it has up to the 50th harmonic and a required accuracy of +/-5% or
been designed to operate over an extended temperature range of worse, the impact from most PLC equipment (with regard to
-40C to 55C, making it suitable for the harshest environments. their drain coil) in conjunction with normal coupling capacitances
Installation is entirely inside the CVT secondary terminal box, should be negligible.
see Figure 1 on both this and the next page, and does not affect
normal operation of the CVT. As a result, there are no external Additionally, in the opposite direction the PLC equipment should
cabling or xtures on the CVT support structure and the output remain unaffected by the presence of PQSensor. Carrier
voltage is available inside the secondary terminal box together insertion loss due to PQSensor should be insignicant thanks to
with the conventional CVT output voltage. Furthermore, the the low impedance through the MU.
PQSensor is fully factory calibrated and consequently requires
no additional on-site calibration or adjustment. 1 Schematic diagram of the PQSensor connected to a capacitor voltage
transformer
Note!
For additional and more detailed users information,
please refer to separate documents provided with
each PQSensor delivery.
38 Accessories | Manual
1 Illustrative drawing of the PQSensor tted in the terminal box where point one (1) is the Signal Condition Module (SCM) and point two (2) is the
Measurment Unit (MU). The dotted cable (not included in the delivery of the unit) is the connection to the control room which is connected during the
installation of the unit.
Manual | Accessories 39
Optional accessories
The undrilled top plate is always mounted to the top capacitor Limitations
stack in the factory, for both the capacitor voltage transformer and - Maximum screw size is M16.
the coupling capcitor, unless a top plate, drilled for Line Trap (LT), - Minimum bolt circle radius from center of the top plate is
is ordered before manufacturing. The primary terminal is mounted 64 mm.
on the extrusion in the middle of the top plate as shown in - Maximum bolt circle radius from center of the top plate is
Figure 1. If a LT shall be mounted on top of the capacitor voltage 148 mm.
transformer or the coupling capacitor the top plate must be drilled. - Number of drilling points is limited to four (4) points in
This requires the top plate to be removed after delivery and drilled midway of the gusset marked with two (2) in Figure 1.
according to the xturing holes of LT or its pedistal. - Center radius clearance for LT or its pedistal required,
due to extrusion marked with point one (1) in Figure 1 is
1 View of the undrilled top plate. Point one (1) is the mounting extrusion
for the primary terminal and point two (2) is the gusset which can be minimum 55 mm.
drilled.
Note!
Make sure that the pedistal for the line trap can be
used toghether with the undrilled top plate.
Caution!
Make sure that the unit, where the line trap is to
be mounted on, can handle the extra load before
assembly.
40 Accessories | Manual
The C2 test outlet can, if ordered prior to manufacturing, be
C2 test outlet supplied on CPB capacitor voltage transformers.
The C2 test outlet is an accessory for utilities with certain 5. Note! Maximum test voltage on the C2 test outlet is
demands for external access to C2, i.e. the intermediate voltage limited to 12 kV RMS due to voltage stress between the
across the bottom capacitor in the CVD (Capacitor Voltage inserted test pin and the cover lid. This constraint on
Divider) of a CVT; see Figure 1. However, due to practical reasons the intermediate voltage does not however occur during
with regard to actual design of the CVD, the C2 test outlet is normal operation when the test pin is withdrawn and test
located in the EMU (Electromagnetic Unit). In the EMU, the C2 test outlet sealed.
outlet is comprised of a polymeric bushing located on the cover lid 6. Restore the C2 test outlet in the reverse order. Make
at the rear end (opposite side as the oil lling plug). In order to not sure the metallic hexagon plug is tightened to a torque of
jeopardize the insulation of the intermediate voltage during normal 10 Nm torque. The metallic outer capsule is tightened by
operation, the bushing contains a contact socket deep below, hand only. The metallic outer capsule must nevertheless
not just below the cover lid but even sufciently immersed in the be tightened until it makes galvanic contact with the
insulation oil. Consequently this socket is accessible by means of cover lid.
a separate test pin (supplied as part of the C2 test outlet) that is
to be inserted in the C2 test outlet during testing only. To protect
1 This circuit diagram shows the electrical point to which the C2 test out-
the polymeric bushing from accelerated aging due to UV radiation let is connected. In the example; fuses, PGS (Potential Grounding Switch)
from the sun, there is a metallic capsule that covers the bushing and PLC (Power Line Carrier) optional accessories are also shown.
during normal operation. In addition to this capsule, there is a
metallic hexagon plug beneath with an o-ring seal for sealing the
bushing against oil leakage.
Specication
Maximum test voltage 12 kV RMS
Connection interface 4 mm banana type provided. Pin at
one end and socket at the other.
Tightening torque 10 Nm (metallic hexagon plug only)
Usage
1. Make sure the CVT is de-energized and sufciently
grounded before opening or interconnecting the C2 test
outlet to external equipment. Note! This C2 test outlet
must never be put in service while the CVT is in normal
operation.
2. Remove the metallic capsule covering the C2 test outlet
by hand, turning it counterclockwise.
3. Loosen the metallic hexagon plug using a wrench.
Check that the o-ring is intact, otherwise replace it.
Spare o-rings can be ordered from ABB; see the contact
information at the back of this manual.
4. Insert the supplied test pin into the bushing of the
C2 test outlet for interconnection to the utilitys test
equipment.
Manual | Accessories 41
Disposal
After disassembling all components, as seen in Figures 1-4 on the Disposal in general must be carried out in accordance with local
next page, can be recycled as described below. legal provisions, laws and regulations.
1. Oil 9. Porcelain and polymeric
2. Quartz sand 10. Iron Note!
3. Paper 11. Hardening plastic ABB AB, High Voltage Products, Instrument
4. Copper 12. O-rings Transformers can be engaged to uninstall
transformers. There is a charge for this service.
5. Aluminum 13. Glass
6. Stainless steel 14. Wood
7. Zinc-coated iron 15. Thermoplastic
8. Brass 16. Impregnant
Incineration of Faradol 600 and 810 produces no poisonous gases, only water and carbon dioxide. It is therefore suitable to dispose
of the uid and the impregnated components through incineration. The uids however, are toxic to aquatic organisms. The uids must
therefore be handled accordingly. It is thus recommended that the impregnant be incinerated in a plant intended for this purpose.
42 Disposal | Manual
1 Cut-away view of an IMB current transformer | 2 Cut-away view of an EMF inductive voltage transformer | 3 Cut-away view of a CPB capacitor voltage
transformer | 4 Cut-away view of a CCB coupling capacitor
1 5 2 4, 5
13
12 5
4, 5, 12 13
12 12
5 5
9 1, 2
3, 4, 5
5
12
1, 2 12
5
5 3, 4
3, 4, 10, 15 12
12
6
5 8, 11, 12, 15 8, 11, 12, 15
5 5
3 4, 5 4
4, 5
5 5
5
6 5
12 6
5 16 12
11 5 16
11
4, 5
4, 5
5 11
12
3, 4 1
8, 11, 12, 15 5
5 3, 4
5
10 5 12
11
Manual | Disposal 43
Troubleshooting
2. Compensating reactor shorted internally 2. Replace reactor or complete EMU. Reset reactor taps to
same setting as unit being replaced. Corrective action inside
electromagnetic unit is required.
CPB About 7 to 15% lower than normal 1. Tap capacitor section shorted 1. Measure C2 tap to ground capacitance with CVT circuit
voltage disconnected and neutral of primary open. Replace capacitor
if variation from rating plate has increased by 7% or more.
Corrective action inside electromagnetic unit is required.
2. Poorly connected adjustment winding 2. Check the BN connection inside the terminal box, as well as
inside the secondary terminal box. all connection to the adjustment winding. Note that breaking the
seal to the adjustment winding cover needs to be approved by
the manufacturer.
CPB Distorted output voltage 1. Heavy load on secondary exceeding 1. Reduce load.
EMF thermal load.
2. Damping circuit, i.e. Rd and Ld, in contact 2. Open lter at d1-d2 terminals. Measure d1-d2 resistance.
with or too close to tank or core. First wind- Value according to rating plate. If open circuit or higher
ing only. value check for loose wires. Lower value check for shorted
components.
3. Step-down transformer arcing or partially 3. Replace EMU. Set taps to same setting as unit being
shorted replaced
CPB Lower than normal voltage, more than 1. Heavy load on secondary exceeding 1. Reduce load
EMF -1.2% thermal load.
1) Some measures require breaking warrant seals. During the warranty period, please obtain authorization from your ABB representative prior to taking
corrective measures.
44 Troubleshooting | Manual
Checklist
Prior to energizing
What to check When Applies to Check for
External package damage A IMB, CPB, CCB, EMF Broken bracing, signs of rough handling
Signs of oil leakage A,B,C IMB, CPB, CCB, EMF Visible oil spillage
Transformer damage B,C IMB, CPB, CCB, EMF Damage to insulator and terminals
Corrosion on primary and ground B IMB, CPB, CCB, EMF Corrosion on the contact surface. If present
terminals remove the same.
Oil level B,C IMB, CPB, EMF Oil visible in level glass
Tan-w measurement C IMB, CPB, EMF On-site reference value
After energizing
What to check When Applies to Check for
Signs of oil leakage D,E IMB, CPB, CCB, EMF Visible oil spillage
Transformer damage D,E IMB, CPB, CCB, EMF Damage to insulator and terminals
Oil level D,E IMB, CPB, CCB, EMF Oil visible in level glass
Tan-w measurement E IMB, CPB, CCB, EMF Trends and change of values. Values depend on
age, voltage level, test method and temperature
Insulation test on secondary E IMB, CPB, EMF Values depend on age, voltage level, test method
windings and temperature
Oil sample and gas analysis E IMB, CPB, EMF Content of critical gases indicating possible
damage
Denitions
A After arrival of the transformer at the destination
B Upon unpacking
C Immediately before energizing
D During periodic routine checks according to established schedule for the S/S
E After 15-20 years
Manual | Checklist 45
Customer notes
Publication 1HSE96002-12en, revision E, 2015-01-28, Manual, Outdoor instrument transformer, Photo: Hasse Eriksson
Instrument transformers
Order department ABB AB is certied according to ISO 9001, ISO 14001
PPHC/IO and OHSAS 18001.
SE-771 80 Ludvika
Sweden Note! ABB AB is working to continuously to improve
its products. We therefore reserve the right to change
Phone: +46 240 78 20 00 designs, dimensions and data without prior notice.
Fax: +46 240 78 27 02
E-mail: order_it@se.abb.com
ABB AB
Diagnostics lab
PPTOR/AD
SE-771 80 Ludvika
Sweden
E-mail: diagnostics@se.abb.com
Phone: +46 240-78 20 00
ABB AB
Instrument transformers
Marketing department
PPHC/M
SE-771 80 Ludvika
Sweden
www.abb.com