Vous êtes sur la page 1sur 94

Applied Commercial Air Conditioning

From installation to maintenance and repair, LG runs more


than 60 global air conditioning academies, each provides
training for air conditioning professionals.

LG Electronics is a division of the LG Group founded in 1947. LG air


conditioners were first manufactured in 1968. With inverter driven residential
and commercial air conditioning equipment and controls, LG is among
the worlds largest volume compressor and HVAC manufacturers with 8
production sites.

2
Establishment Growth Expansion

47 5 8 6 8 8 5 8 6 90 9 5 98 00 01 04 08 0
19 19 19 19 19 19 19 19 20 20 20 20 20
r r ics rs r ) )
hed h ed n er s n er s io ne s so on or che
d
ne o ne a les nta rnia d
blis blis itio iti o dit pre tr
lec ess lau
n
dit
io
diti s
er uni ts tla
(A s o f lifo
Ca reate
sta Est
a nd d n om con con ion hed sale nits
pE co on co
yc G E pr em air dit llion blis al
rn
the ion
c
ou LG
E air ir c air tar o L om yst air con 0 mi sta l glob ning
u
Gr t ra w o d t roll c Fs tial me r E Sou divis
LG f ir s er t e
i n d o
G
r
nge
sc VR
d e n fra
al a i
f 1 r a
te tot dit io d (
e ning
as In v w st
L ha G LG si re u o e n t n lish
o re ir s t f ir s
t
Fir e c st L Firs
t f re ictu nn g C firs air co tab ditio
dK s f am Fir ro dp st a inin stry r Es on
re as yn elle uce he Tra du illion nte ir C
c tu re a o re an 1s od hig US ed in 00 m Ce LG A
fa Ko ed
K m p #
In tr rld s
ch g
nu Co ed wo
1 inin
Ma or t ach Rea Tra
E xp Re ved US
hie
Ac

3
Variable Refrigerant Flow (VRF) technology was introduced as a system
to minimize losses found in conventional HVAC systems. An air cooled VRF
system is engineered to minimize or remove ductwork, large distribution
fans, water pumps and piping, giving back plenum and floor space. A
modular design of a VRF system provides exceptional dehumidification and
temperature control by rapidly adapting to changing loads. The modular
design results in superior energy savings giving occupants the choice to
condition only the zones being used. Energy efficient and easy to design,
install, and maintain, a VRF system has the lowest life cycle cost of any
system on the market today.

4
6 Why LG Multi V?

18 Outdoor Units

42 Indoor Units

78 Controls & Accessories

5
Multi V is engineered to bring together efficiency and easy
installation. With an LG Multi V your residence or building
consumes less energy.

6
Why LG MultiV?

With the use of inverters and dual compressor outdoor units, the LG Multi V system
DEHUMID
DIFFICATIO
ON offers superior load matching, preventing constant cycling or large temperature
AND COMFORT swings. Tight temperature control through precise load matching ensures maximum
CONTRO
OL comfort, efficient operation, and superior dehumidification.

Work without distraction. Sleep without noise. With indoor units that can operate
QU I E T at sound levels as low as 23dB(A) and outdoor units that operate as low as 50dB(A)
and lower with night quiet operation, Multi V creates a comfortable environment so
quiet its almost undetectable. For additional sound level control, a night quiet mode
can be set to limit fan speed during off peak hours.

peak

Day Night

am pm pm pm am am am

Based on single frame Multi V Plus II and Sync II

Sound Pressure MINI Plus II Sync II


(dBA)

Normal 50 58 58
Step 1 46 47 47
Step 2 43 44 44
Step 3 40 41 41
Based on single frame outdoor unit

With controls that alternate compressors and protect against oil migration, coil
QUALITTY AND icing and short cycling, the Multi V offers unmatched quality and reliability. LG also
RELIA
ABILLITT Y has expertise in compressor design, motors, and printed circuit boards resulting in
superior quality control. Multi V is backed up with a 2 year parts and additional 4 year
compressor warranty.

7
Why LG Multi V?

Without using water piping or large distribution ducts, the Multi V system removes
EFFICIE
ENT DESIG
GN losses that are unavoidable in other systems. In addition, the use of optimized scroll
or rotary compressors, specially designed heat exchangers, and inverter technology,
the Multi V system minimizes energy consumption to levels previously unattainable by
non-VRF systems. The modular design offers comfort on demand allowing the choice
to use the system only in the zones where it is needed further promoting reduced
energy consumption.

OFF
OFF

ON
OFF
ON

Multi V indoor units are available in a wide range of styles to fit any interior design.
STT YLISSH DESIG
GN With indoor unit choices including cassettes that mount flush to the ceiling, ducted
units that hide completely concealed in the ceiling, and mirror finished wall mounted
units that fit into any dcor, the LG Multi V system offers unparalleled aesthetic design.

Mirror

Ceiling Suspended
4-Way Ceiling Cassette

Ducted
Floor Standing

2-Way Ceiling Cassette

8
Why LG Multi V?

Multi V outdoor units can be adapted to a wide range of building types and sizes
ADAPTABLE AND including but not limited to schools, hotels, hospitals, offices, and residences.
FLLEXIBLLE Their light weight and small footprint allows them to be moved without expensive
cranes easily fitting into most service elevators and set in place with minimal
requirements for structural reinforcements. Its modular design means Multi V can
be commissioned in stages so tenants can move in as each floor or even each
room is completed.

Imagine a split system that allows you to minimize components by reaching an area
of the building that might otherwise require a second system. The Multi V system is
capable of the longest piping lengths and largest elevation differences in the industry,
allowing maximum flexibility in placement of outdoor condensing units and indoor
units. Whether your building is a high rise condominium or hotel, or a sprawling school
or office complex, this system will reach even the farthest corners and elevations.

Multi V : 738ft longest equivalent

Multi V : Conventional Conventional


328ft vertical

The LG Multi V system uses refrigerant piping to move heat resulting in smaller
SM
MALLER CHASES space requirements compared to water piping or air ducts. This will help reduce the
AND PLENUMS overall construction and material cost of your building and give back leasable space.
Flexible and logical placement of system components, shorter pipe lengths, and
fewer joints lowers installed cost and minimizes potential for leaking.

Conventional

9
Why LG Multi V?

The LATS Multi V design and layout software provides an intuitive method of laying
IN
NTUITIIVE DESIG
GN out a Multi V Mini, Plus II or Sync II system. LATS Multi V checks piping lengths
and elevations, and assists the sizing of indoor and outdoor units by calculating
capacity based on design conditions. LATS Multi V is the industrys only software
that can import AutoCAD drawings and lay out the Multi V system to scale.
When the user finishes the AutoCAD system layout, all of the piping lengths will
be calculated and a drawing file with the Multi V system can be exported.

10
Why LG Multi V?

LG stands behind efficiency and performance with proof. You will find Multi V in the
ENERGY EnergyPro building energy simulation software from EnergySoft . EnergyPro is
MODELIN
NG approved by the California Energy Commission and can be used for documentation
with the California Title 24 Standards as well as energy codes throughout the United
States including ASHRAE 90.1 and LEED . The software accurately models energy
consumption based on building design, orientation, location, and other design
conditions taking into account your specific utility rate structure.

11
Why LG Multi V?

The architectural and engineering community is adopting a balanced design


SUSTAINABILITY approach that considers energy and water consumption, repetitive maintenance
costs, the impact of development on the environment, and the buildings initial cost
as equally important factors in developing high performance, sustainable buildings
that will increase building value.

The American Society of Heating, Refrigerating, and Air Conditioning Engineers


(ASHRAE) and the U.S. Green Building Council (USGBC) have been instrumental
in developing and documenting voluntary best practice standards that provide
the construction industry an all encompassing balanced approach for developing
sustainable buildings.

ASHRAE Standards provide best practices for safe refrigerant handling, proper
building ventilation, controlling building temperature and relative humidity, energy
and water efficiency. The USGBC has developed holistic design standards for
constructing new and retrofitting existing buildings known as LEED - Leadership
in Energy and Environmental Design. The LEED Green Building Rating System is a
voluntary, consensus based program for developing high performance, sustainable
buildings. Based on well founded scientific standards, LEED emphasizes state of
the art strategies for sustainable site development, water and energy conservation
as well as a guide for selecting construction materials that are easily renewable and
manufactured to promote indoor environmental quality.

The LEED rating system provides a complete framework for assessing building
performance and meeting sustainability goals. Based on a system of prerequisites
and credits, often referring to ASHRAE Standards, LEED projects earn points
during the certification process and then are awarded one of four available certification
levels: Certified, Silver, Gold, and Platinum. The LEED rating system does not endorse
products, but sets performance criteria to award prerequisites and points toward certification.

12
12
Why LG Multi V?

The Multi V variable refrigerant flow air conditioning system is engineered for sustainable
green building and provides opportunities for designers to claim numerous LEED
prerequisites and points.

1.T h e Multi V system uses environmentally friendly refrigerant R410A.


2.Unlike traditional applied air conditioning systems using chilled water or condenser
water, the air-to-air Multi V system does not use water or evaporative cooling
that requires make-up water nor does it require any water treatment
chemicals.
3.The Multi V system offers exceptional energy performance by using state of
the art controls, high efficiency variable speed condenser and evaporator
fan assemblies, and a combination of variable and constant speed
compressors that provide unmatched unloading performance.
4.The modular design of the Multi V system uses multiple indoor units allowing the
designer to provide individualized control for each occupant.
5. LGs family of local, central, building management controllers, and communication
gateways make it easy to monitor energy usage and control the Multi V system
operations based on building usage or indoor air quality.

13
13
Why LG Multi V?

Installation and Commissioning Support


COMMISSSIOO N I NG LG is committed to the success of every Multi V project. Proper installation is
AND important to operation and system longevity. Installation and commissioning

TR
ROUBLESSHOOTING training that is conducted at our state of the art training centers will provide the
knowledge and tools to properly install Multi V systems. For on site startup and
commissioning, our technical staff or an approved technical agent will be on hand
to record system operation to start the warranty validation process.

LGMV (LG Monitoring View) Service Tool


Aligning with LGs commitment to quality, the LGMV service tool provides the user
a window into the inner workings of our very sophisticated operating systems. From
a laptop computer, this tool is used to monitor low side and high side pressures,
status of liquid injection, hot gas by-pass valves, operating frequency of the inverter
compressor and condenser fan motors, electronic expansion valve (EEV) position
and super heat values for all connected indoor units. The software provides an
accurate picture of an operating system without the need to manually check system
temperatures, access the refrigerant circuit for system pressures, or perform time
consuming resistance and voltage tests. This service tool provides the most effective
troubleshooting method for LG Multi V equipment.

Easy to maintain
Though highly advanced, Multi V equipment is simple to maintain, mainly consisting
of cleaning filters. Fan motors use permanently lubricated ball bearings. The
nonmetallic condenser fan blades dont rust and attenuate vibration. The specially
designed louvered fin coils are as quick and easy to clean as any outdoor unit coil on
the market today. The control compartment is hinged and swings open for access to
mechanical system components. LGMV software provides a window into the system
for the technician to quickly check operating conditions as part of an annual or semi-
annual maintenance program.

14
Why LG Multi V?

15
Why LG Multi V?

At LG, we are committed to excellence in Multi V design and installation training. We


TRAININ
NG offer complete training for engineers, architects, installers and servicers to ensure
every Multi V installation is successful.

Engineers and Architects


We have designed a comprehensive workshop tailored to specifying engineers and
architects. Training includes a complete product and controls introduction which
explains advanced features and benefits of the LG Multi V system. A live tutorial
covers the setup and use of the LATS Multi V design and layout software. A
standard feature of all LG training is open forum interaction between the facilitator
and all attendees.

16
Why LG Multi V?

Installers and Commissioners


The installation and commissioning course addresses installation, piping, and wiring of
Multi V systems. In depth technical topics are covered such as sequence of operation
for Multi V Mini, Plus II and Sync II synchronous heating and cooling systems. Lab
activities are designed to reinforce classroom discussion, including topics such as
V-Net controls. Time is also set aside to work hands on with the commissioning
and troubleshooting software, LGMV, on operating equipment in our state of the
art training lab.

17
OUTDOOR UNITS

18
19
Outdoor Units

The oil injection mechanism ensures a reliable oil film


OI L on moving parts even at low speed operation allowing
MANAGEMENT the inverter compressor to safely operate down to 25
Hz. Also, concern over oil migration is minimized. The
compressor discharge is specially designed to minimize the
amount of oil leaving the compressor. Oil that may leave
the compressor is then brought back to the compressor
using an oil separator after the discharge and the most
dependable oil return control algorithms available.

With compressors optimized around R410A and the


INVERTER latest inverter technology, the LG Multi V system
TECHNOLOGY precisely matches the load. This helps prevent constant
cycling resulting in tight temperature control, superior
dehumidification, and optimized system efficiency.
Occupants will stay comfortable while reducing utility
costs.

Multi V takes advantage of a digitally controlled(DC) inverter and constant speed


DUAL compressor combination that maximizes efficiency while precisely matching load.
COMPRESSORS Every compressor runs most efficiently at full load. The inverter drive on the first
compressor matches the load exactly, recapturing the efficiency of a partially loaded
compressor while eliminating compressor cycling. The constant speed compressor
will run in more heavily loaded conditions taking the majority of the load running
in its most efficient operating range. This inverter and constant speed compressor
combination adds redundancy to the system and also allows for lower load operation
than a single inverter design.

Inverter

DC Inverter Constant speed


Compressor Compressor

20
Outdoor Units

All Multi V outdoor units use louvered fin coils engineered to


F I N D E S I GN increase surface area enabling more efficient heat transfer.
The louvered fin coil decreases compressor lift reducing
energy consumption without adding difficulty to coil cleaning.

All Multi V outdoor unit coils have a corrosion resistant


GoldFin GoldFin coating standard from the factory. Corrosion
shortens coil life and adds a barrier to efficient heat transfer.
GoldFin will promote sustainable efficiency and coil life by
helping to prevent corrosion caused by everyday pollutants.

21
Why
Why
hy LG
LG Multi
M
Muulti V?
V?

Outdoor Units
LG Multi V consists of three distinct products that will fit any application. With
the longest and most flexible piping in the industry, the Multi V system can
reduce installed cost by reaching that last zone in the building that would
otherwise require an additional outdoor unit and piping network.

Ton 3 4 4.4 6.5 8 9.5 11 12.5 14.5 16

MBh 36 47 53 76 96 115 134 154 173 192

208V/230V-60Hz-1
pg. 34

208V/230V-60Hz-3
pg. 35

460V-60Hz-3
pg.37

208V/230V-60Hz-3
pg. 39

460V-60Hz-3
pg. 41

22
Outdoor Units

17.5 19 20.5 22.5 24 25.5 27 28.5 30 32 33.5 35 36.5 38

211 230 250 270 290 310 330 350 370 390 410 430 450 470

23
Outdoor Units

Multi V Mini is a two pipe heat pump system that is available in


MULTI V MINI capacities of 3, 4 and 4.4 tons. This system is best suited for applications
with up to 9 zones that require either heating or cooling with indoor
units totaling up to 5.7 tons of capacity. Multi V Mini outdoor units
are available in 208/230V single phase which suits small buildings and
residences.
Heating: -4F to 60F (wet bulb)
Cooling: 23F to 118F (dry bulb)

* For more information see page 33

24
Outdoor
Outdo
O
Ou
Outd
Out
u Units

Piping length (equivalent) Elevation


Total 984 ft. Outdoor above indoor 164 ft.
Longest 574 ft. Indoor above outdoor 131 ft.
From first branch 131 ft. Indoor maximum separation 49 ft.

25
Outdoor Units

The Multi V Plus II is a two pipe heat pump system that is


available in capacities from 6.3 to 38.2 tons. This system is
MULTI V best suited for applications that require either heating or
PLUS II cooling greater than 4 tons, such as large office buildings with
a common exposure, hotel ballrooms, and meeting areas.
Multi V Plus II outdoor units are available in 208/230V and
460V three phase and can be applied to applications up to
0.16 in. external static pressure.
Heating: -4F to 60F (wet bulb)
Cooling: 23F to 110F (dry bulb)

* For more information see page 34

26
Outdoor Units

Piping length (equivalent) Elevation


Total 3280 ft. Outdoor above indoor 328 ft.
Longest 738 ft. Indoor above outdoor 328 ft.
From first branch 295 ft. Indoor maximum separation 49 ft.

27
Outdoor Units

The Multi V Sync II unit is a three pipe heat pump system that
MULTI V is available in capacities from 6.3 to 38.2 tons. This system
is best suited for diverse loads that require simultaneous
SYNC II heating and cooling in different zones with a load greater
than 4 tons, such as hotel guest rooms, high rise residences,
multiple tenant shopping, or any building that can utilize
exposures from opposite sides or interior and exterior zones
on the same system. Multi V Sync II outdoor units are
available in 208/230V and 460V three phase and can be
applied to applications up to 0.16 in. external static pressure.
Heating: -4F to 60F (wet bulb)
Cooling: 23F to 110F (dry bulb)
Simultaneous: 14F to 81F (dry bulb)

* For more information see page 38

28
Outdoor Units

Piping length (equivalent) Elevation


Total 3280 ft. Outdoor above indoor 328 ft.
Longest 738 ft. Indoor above outdoor 328 ft.
From first branch 295 ft. Indoor maximum separation 49 ft.

29
Outdoor Units

There is no better way to maximize efficiency than to increase condensing heat


HEAT RECOVERY exchanger surface area and reject heat to zones that would otherwise require an
additional system. Multi V Sync II is a three pipe system with heat recovery units
that can turn some indoor units into zoned condensers providing heat while leaving
others in cooling mode. Water cooled systems recover heat and send it to the central
plant to preheat domestic hot water. Heat recovery with the Multi V Sync II system
provides full heating in its operating range to nearby zones in the same system. By
pairing interior with exterior zones or eastern with western exposures, this system
takes full advantage of building diversity. Heat can be moved from zones requiring
cooling to zones that need heat, providing ultimate individual comfort control with
minimal power consumption. In addition, under rapidly changing conditions, the
Multi V Sync II heat recovery units will change between heating and cooling in just
three minutes.

Simultaneous heating and cooling

Conventional
All units in same mode

30
Outdoor Units

The Multi V Sync II system combines the best features of heat recovery VRF systems.
INSTALL ATION Condensate drains are not required for Multi V heat recovery units. Heat recovery
units that can serve 2, 3, or 4 zones are strategically placed in series or in parallel
to maximize piping reach while minimizing material and labor costs. Piping, fittings,
branches, headers, hangers, insulation, joints, nitrogen, and labor hours can be
greatly reduced resulting in significantly lower installed cost.

Configured for fully independent heating and cooling


Series and/or parallel configuration
Short piping
Few joints
No heat recovery unit condensate drains
Fast 3 minute mode change

Home Run Heat Recovery

Configured for fully independent heating and cooling


Series configuration only
Lengthy homerun piping
May require heat recovery unit condensate drain

Single Port Heat Recovery

Configured for fully independent heating and cooling


Parallel configuration only
Many heat recovery units for independent heating and cooling
Numerous joints

31
Outdoor Units

Outdoor Units ARU N 053 G S 2


Family
ARU = Multi V Outdoor Unit
(Refrigerant R410A)

Type

Nominal Capacity
036 = 36,000 Btu/h 173 = 173,000 Btu/h 330 = 330,000 Btu/h
047 = 47,000 Btu/h 192 = 192,000 Btu/h 350 = 350,000 Btu/h
053 = 53,000 Btu/h 211 = 211,000 Btu/h 370 = 370,000 Btu/h
076 = 76,000 Btu/h 230 = 230,000 Btu/h 390 = 390,000 Btu/h
096 = 96,000 Btu/h 250 = 250,000 Btu/h 410 = 410,000 Btu/h
115 = 115,000 Btu/h 270 = 270,000 Btu/h 430 = 430,000 Btu/h
134 = 134,000 Btu/h 290 = 290,000 Btu/h 450 = 450,000 Btu/h
154 = 154,000 Btu/h 310 = 310,000 Btu/h 470 = 470,000 Btu/h

Electrical Connection

Airflow Configuration
S = Side Discharge
T = Top Discharge

Generation
2 = Second

Heat Recovery Units PRHR 04 0A


Family
PRHR = Multi V Heat Recovery Unit
(Refrigerant R410A)

Configuration
02 = up to 2 indoor units
03 = up to 3 indoor units
04 = up to 4 indoor units

Generation
0A = Original

32
Outdoor
Outdoor
door Units

Note :
1. Capacities are based on the following conditions:
Cooling-Indoor temp. 80F DB / 67F WB Heating-Indoor temp. 70F DB
Outdoor temp. 95F DB Outdoor temp. 47F DB / 43F WB
Interconnecting Piping Length 25ft (7.5m) Interconnecting Piping Length 25ft(7.5m)
Level Difference of 0ft (0m) Level Difference of 0ft (0m)
2. Capacities are net capacities.
3. Due to our policy of innovation some specifications may be changed without notification.

208-230V/60Hz/1
Model ARUN GS2 036 047 053
Ton 3 4 4.4
Cooling Btu/h 38,000 48,000 53,000
kW 11.1 14.1 15.5
Capacity
Heating Btu/h 42,000 53,500 59,000
kW 12.3 15.7 17.3
Cooling kW 3.4 5.1 5.9
Power Input
Heating kW 3.7 5.3 6.2
Cooling EER 11.10 9.50 9.00
Efficiency
Heating COP 3.33 2.96 2.79
Power Supply V / Hz / 208-230 / 60 / 1 208-230 / 60 / 1 208-230 / 60 / 1
inch 37.4 54.3 13.0 37.4 54.3 13.0 37.4 54.3 13.0
Dimensions(WHD)
mm 950 1380 330 950 1380 330 950 1380 330
Ibs 234 234 234
Net Weight
kg 106 106 106
Casing Color Warm Gray Warm Gray Warm Gray
Sound Pressure (Cooling/Heating)1 dB(A) 50/52 51/53 52/54
Type Propeller Propeller Propeller
Fan
Air Flow Rate2 cfm 3885 3885 3885
Type DC INV Rotary DC INV Rotary DC INV Rotary
Compressor
Number of compressor 1 1 1
Heat Exchanger GoldFinTM GoldFinTM GoldFinTM
Refrigerant Type R410A R410A R410A
lb 6.6 6.6 6.6
Refrigerant Charge
kg 3.0 3.0 3.0
Control EEV EEV EEV
Maximum Number of Indoor Units 6 8 9
* Sound pressure levels as tested in an anechoic chamber under Korea Standard KSA0701.

33
Outdoor Units

Note :
1. Capacities are based on the following conditions
Cooling-Indoor temp. 80F DB / 67F WB Heating-Indoor temp. 70F DB
Outdoor temp. 95F DB Outdoor temp. 47F DB / 43F WB
Interconnecting Piping Length 25ft (7.5m) Interconnecting Piping Length 25ft(7.5m)
Level Difference of 0ft (0m) Level Difference of 0ft (0m)
2. Capacities are net capacities
3. Due to our policy of innovation some specifications may be changed without notification
4. When the calculated refrigerant charge is over 209lb(95kg), multiple outdoor system must be divided into smaller independent systems.
So, each system contains less than 209lb(95kg) refrigerant charge.

208-230V/60Hz/3
Model ARUN BT2 Single Frame 076 096 115
Ton 6.5 8.0 9.5
Cooling Btu/h 76,400 95,900 114,700
kW 22.4 28.0 33.6
Capacity
Heating Btu/h 86,000 107,500 129,000
kW 25.2 31.5 37.8
Cooling kW 6.2 7.8 10.6
Power Input
Heating kW 7.0 8.8 11.1
Power Supply V / Hz / 208-230 / 60 / 3 208-230 / 60 / 3 208-230 / 60 / 3
50 3/8 x 63 5/16 x 50 3/8 x 63 5/16 x 50 3/8 x 63 5/16 x
inch
Dimensions(WHD) 28 11/16 28 11/16 28 11/16
mm 1280 1607 730 1280 1607 730 1280 1607 730
Ibs 628 628 628
Net Weight
kg 285 285 285
Casing Color Warm Gray Warm Gray Warm Gray
Sound Pressure* dB(A) 58 58 58
Type Propeller fan Propeller fan Propeller fan
Fan Air Flow Rate
cfm 6,700 6,700 6,700
(High)
Type DC Scroll DC Scroll DC Scroll
Compressor
Number of compressor 2 2 2
Heat Exchanger GoldFinTM GoldFinTM GoldFinTM
Refr igerant Type R410A R410A R410A
lb 17.6 17.6 17.6
Refrigerant Charge
kg 8 8 8
Control EEV EEV EEV
Maximum Number of Indoor Units 13 16 19

* Sound pressure levels as tested in an anechoic chamber under Korea Standard KSA0701

34
Outdoor Units

208-230V/60Hz/3
Dual Frame 154 173 192 211 230
Model ARUN BT2 076 096 096 115 115
Combination
076 076 096 096 115
Ton 12.5 14.5 16.0 17.5 19.0
Cooling Btu/h 152,900 172,000 191,100 210,200 229,300
kW 44.8 50.4 56.0 61.6 67.2
Capacity
Heating Btu/h 172,000 193,500 225,000 236,500 258,000
kW 50.4 56.7 63.0 69.3 75.6
Cooling kW 12.4 14.0 15.6 18.4 21.2
Power Input
Heating kW 14.0 15.8 17.6 19.9 22.2
Power Supply V / Hz / 208-230 / 60 /3 208-230 / 60 / 3 208-230 / 60 / 3 208-230 / 60 / 3 208-230 / 60 / 3
(50 3/8 x 63 5/16 x (50 3/8 x 63 5/16 x (50 3/8 x 63 5/16 x (50 3/8 x 63 5/16 x (50 3/8 x 63 5/16 x
inch
Dimensions(WHD) 28 11/16) x 2 28 11/16) x 2 28 11/16) x 2 28 11/16) x 2 28 11/16) x 2
mm (1280 1607 730) x 2 (1280 1607 730) x 2 (1280 1607 730) x 2 (1280 1607 730) x 2 (1280 1607 730) x 2
Ibs 628+628 628+628 628+628 628+628 628+628
Net Weight
kg 285 285+285 285+285 285+285 285+285
Casing Color Warm Gray Warm Gray Warm Gray Warm Gray Warm Gray
Sound Pressure* dB(A) 61 61 61 61 61
Type Propeller fan Propeller fan Propeller fan Propeller fan Propeller fan
Fan Air Flow Rate
cfm 13,400 13,400 13,400 13,400 13,400
(High)
Type DC Scroll DC Scroll DC Scroll DC Scroll DC Scroll
Compressor
Number of compressor 2+2 2+2 2+2 2+2 2+2
Heat Exchanger GoldFinTM GoldFinTM GoldFinTM GoldFinTM GoldFinTM
Refrigerant Type R410A R410A R410A R410A R410A
lb 17.6 + 17.6 17.6 + 17.6 17.6 + 17.6 17.6 + 17.6 17.6 + 17.6
Refrigerant Charge
kg 8+8 8+8 8+8 8+8 8+8
Control EEV EEV EEV EEV EEV
Maximum Number of Indoor Units 26 29 32 35 39
* Sound pressure levels as tested in an anechoic chamber under Korea Standard KSA0701

208-230V/60Hz/3
Triple Frame 250 270 290 310 330 350

Model ARUN BT2 096 096 096 115 115 115


Combination 076 096 096 096 115 115
076 076 096 096 096 115
Ton 20.5 22.5 24 25.5 27 28.5
Cooling Btu/h 248,400 267,500 286,600 305,700 324,800 343,900
kW 72.8 78.4 84 89.6 95.2 100.8
Capacity
Heating Btu/h 279,500 301,000 322,500 343,900 365,400 386,900
kW 81.9 88.2 94.5 100.8 107.1 113.4
Cooling kW 20.2 21.8 23.4 26.2 29.0 31.8
Power Input
Heating kW 22.8 24.6 26.4 28.7 31 33.3
Power Supply V / Hz / 208-230 / 60 / 3 208-230 / 60 / 3 208-230 / 60 / 3 208-230 / 60 / 3 208-230 / 60 / 3 208-230 / 60 / 3
(50-3/8 x 63-5/16 x (50-3/8 x 63-5/16 x (50-3/8 x 63-5/16 x (50-3/8 x 63-5/16 x (50-3/8 x 63-5/16 x (50-3/8 x 63-5/16 x
inch
Dimensions(WHD) 28-11/16) x 3 28-11/16) x 3 28-11/16) x 3 28-11/16) x 3 28-11/16) x 3 28-11/16) x 3
mm (1280 x 1607 x 730) x 3 (1280 x 1607 x 730) x 3 (1280 x 1607 x 730) x 3 (1280 x 1607 x 730) x 3 (1280 x 1607 x 730) x 3 (1280 x 1607 x 730) x 3
Ibs 628 + 628 + 628 628 + 628 + 628 628 + 628 + 628 628 + 628 + 628 628 + 628 + 628 628 + 628 + 628
Net Weight
kg 285 + 285 + 285 285 + 285 + 285 285 + 285 + 285 285 + 285 + 285 285 + 285 + 285 285 + 285 + 285
Casing Color Warm Gray Warm Gray Warm Gray Warm Gray Warm Gray Warm Gray
Sound Pressure* dB(A) 63 63 63 63 63 63
Type Propeller fan Propeller fan Propeller fan Propeller fan Propeller fan Propeller fan
Fan Air Flow Rate
cfm 20100 20100 20100 20100 20100 20100
(High)
Type DC Scroll DC Scroll DC Scroll DC Scroll DC Scroll DC Scroll
Compressor
Number of compressor 2+2+2 2+2+2 2+2+2 2+2+2 2+2+2 2+2+2
Heat Exchanger GoldFinTM GoldFinTM GoldFinTM GoldFinTM GoldFinTM GoldFinTM
Refrigerant Type R410A R410A R410A R410A R410A R410A
lb 17.6 + 17.6 + 17.6 17.6 + 17.6 + 17.6 17.6 + 17.6 + 17.6 17.6 + 17.6 + 17.6 17.6 + 17.6 + 17.6 17.6 + 17.6 + 17.6
Refrigerant Charge
kg 8+8+8 8+8+8 8+8+8 8+8+8 8+8+8 8+8+8
Control EEV EEV EEV EEV EEV EEV
Maximum Number of Indoor Units 42 45 49 52 55 58

* Sound pressure levels as tested in an anechoic chamber under Korea Standard KSA0701

35
Outdoor Units

Note :
1. Capacities are based on the following conditions
Cooling-Indoor temp. 80F DB / 67F WB Heating-Indoor temp. 70F DB
Outdoor temp. 95F DB Outdoor temp. 47F DB / 43F WB
Interconnecting Piping Length 25ft (7.5m) Interconnecting Piping Length 25ft(7.5m)
Level Difference of 0ft (0m) Level Difference of 0ft (0m)
2. Capacities are net capacities
3. Due to our policy of innovation some specifications may be changed without notification
4. When the calculated refrigerant charge is over 209lb(95kg), multiple outdoor system must be divided into smaller independent systems.
So, each system contains less than 209lb(95kg) refrigerant charge.

460V/60Hz/3
Model ARUN DT2 Single Frame 076 096 115 134 154
Ton 6.5 8.0 9.5 11.0 12.5
Cooling Btu/h 76,400 95,900 114,700 133,800 152,900
kW 22.4 28.0 33.6 39.2 44.8
Capacity
Heating Btu/h 86,000 107,500 129,000 150,500 172,000
kW 25.2 31.5 37.8 44.1 50.4
Cooling kW 5.28 7.16 9.08 11.85 14.00
Power Input
Heating kW 5.73 7.33 9.05 10.60 12.40
Power Supply V / Hz / 460 / 60 / 3 460 / 60 / 3 460 / 60 / 3 460 / 60 / 3 460 / 60 / 3

50 3/8 x 63 5/16 x 50 3/8 x 63 5/16 x 50 3/8 x 63 5/16 x 50 3/8 x 63 5/16 x 50 3/8 x 63 5/16 x
inch
Dimensions(WHD) 28 11/16 28 11/16 28 11/16 28 11/16 28 11/16

mm 1280 1607 730 1280 1607 730 1280 1607 730 1280 1607 730 1280 1607 730
Ibs 529 628 628 628 628
Net Weight
kg 240 285 285 285 285
Casing Color Warm Gray Warm Gray Warm Gray Warm Gray Warm Gray
Sound Pressure* dB(A) 58 58 58 58 58
Type Propeller fan Propeller fan Propeller fan Propeller fan Propeller fan
Fan Air Flow Rate
cfm 6,700 6,700 6,700 6,700 6,700
(High)
Type DC Scroll DC Scroll DC Scroll DC Scroll DC Scroll
Compressor
Number of compressor 1 2 2 2 2
Heat Exchanger GoldFinTM GoldFinTM GoldFinTM GoldFinTM GoldFinTM
Refrigerant Type R410A R410A R410A R410A R410A
lb 17.6 17.6 17.6 17.6 17.6
Refrigerant Charge
kg 8 8 8 8 8
Control EEV EEV EEV EEV EEV
Maximum Number of Indoor Units 13 16 19 23 26

* Sound pressure levels as tested in an anechoic chamber under Korea Standard KSA0701

36
Outdoor Units

460V/60Hz/3
Dual Frame 173 192 211 230 250 270 290 310
Model ARUN DT2 096 115 134 154 134 134 154 154
Combination
076 076 076 076 115 134 134 154
Ton 14.5 16.0 17.5 19.0 20.5 22.5 24.0 25.5
Cooling Btu/h 172,000 191,100 210,200 229,300 248,400 267,500 286,600 305,700
kW 50.4 56.0 61.6 67.2 72.8 78.4 84.0 89.6
Capacity
Heating Btu/h 193,500 225,000 236,500 258,000 279,500 301,000 322,500 343,900
kW 56.7 63.0 69.3 75.6 81.9 88.2 94.5 100.8
Cooling kW 12.44 14.36 17.13 19.28 21.16 23.08 25.85 28
Power Input
Heating kW 12.61 14.33 15.88 17.68 19.73 21.45 23 24.8
Power Supply V / Hz / 460 / 60 / 3 460 / 60 / 3 460 / 60 / 3 460 / 60 / 3 460 / 60 / 3 460 / 60 / 3 460 / 60 / 3 460 / 60 / 3
(50 3/8 x 63 5/16 (50 3/8 x 63 5/16 (50 3/8 x 63 5/16 (50 3/8 x 63 5/16 (50 3/8 x 63 5/16 (50 3/8 x 63 5/16 (50 3/8 x 63 5/16 (50 3/8 x 63 5/16
inch
x 28 11/16) x 2 x 28 11/16) x 2 x 28 11/16) x 2 x 28 11/16) x 2 x 28 11/16) x 2 x 28 11/16) x 2 x 28 11/16) x 2 x 28 11/16) x 2
Dimensions(WHD)
(1280 1607 (1280 1607 (1280 1607 (1280 1607 (1280 1607 (1280 1607 (1280 1607 (1280 1607
mm
730) x 2 730) x 2 730) x 2 730) x 2 730) x 2 730) x 2 730) x 2 730) x 2
Ibs 628 + 529 628 + 529 628 + 529 628 + 529 628 + 628 628 + 628 628 + 628 628 + 628
Net Weight
kg 285 + 240 285 + 240 285 + 240 285 + 240 285 + 285 285 + 285 285 + 285 285 + 285
Casing Color Warm Gray Warm Gray Warm Gray Warm Gray Warm Gray Warm Gray Warm Gray Warm Gray
Sound Pressure* dB(A) 61 61 61 61 61 61 61 61
Type Propeller fan Propeller fan Propeller fan Propeller fan Propeller fan Propeller fan Propeller fan Propeller fan
Fan Air Flow Rate
cfm 13,400 13,400 13,400 13,400 13,400 13,400 13,400 13,400
(High)
Type DC Scroll DC Scroll DC Scroll DC Scroll DC Scroll DC Scroll DC Scroll DC Scroll
Compressor
Number of compressor 2+1 2+1 2+1 2+1 2+2 2+2 2+2 2+2
Heat Exchanger GoldFinTM GoldFinTM GoldFinTM GoldFinTM GoldFinTM GoldFinTM GoldFinTM GoldFinTM
Refrigerant Type R410A R410A R410A R410A R410A R410A R410A R410A
lb 17.6 + 17.6 17.6 + 17.6 17.6 + 17.6 17.6 + 17.6 17.6 + 17.6 17.6 + 17.6 17.6 + 17.6 17.6 + 17.6
Refrigerant Charge
kg 8+8 8+8 8+8 8+8 8+8 8+8 8+8 8+8
Control EEV EEV EEV EEV EEV EEV EEV EEV
Maximum Number of Indoor Units 29 32 35 39 42 45 49 52
* Sound pressure levels as tested in an anechoic chamber under Korea Standard KSA0701

460V/60Hz/3
Triple Frame 330 350 370 390 410 430 450 470
134 134 154 154 154 154 154 154
Model ARUN DT2
Combination 115 134 134 154 154 154 154 154
076 076 076 076 096 115 134 154
Ton 27 28.5 30.0 32.0 33.5 35.0 36.5 38.0
Cooling Btu/h 324,800 343,900 363,100 382,200 401,700 420,500 439,600 458,700
kW 95.2 100.8 106.4 112 117.6 123.2 128.8 134.4
Capacity
Heating Btu/h 365,400 386,900 408,400 429,900 451,500 473,00 494,500 516,000
kW 107.1 113.4 119.7 126 132.3 138.6 144.9 151.2
Cooling kW 26.1 28.98 33.01 33.28 35.16 37.08 39.85 42
Power Input
Heating kW 25.38 26.93 30.33 30.53 32.13 33.85 35.4 37.2
Power Supply V / Hz / 460 / 60 / 3 460 / 60 / 3 460 / 60 / 3 460 / 60 / 3 460 / 60 / 3 460 / 60 / 3 460 / 60 / 3 460 / 60 / 3
(50-3/8 x 63-5/16 (50-3/8 x 63-5/16 (50-3/8 x 63-5/16 (50-3/8 x 63-5/16 (50-3/8 x 63-5/16 (50-3/8 x 63-5/16 (50-3/8 x 63-5/16 (50-3/8 x 63-5/16
inch
x 28-11/16) x 3 x 28-11/16) x 3 x 28-11/16) x 3 x 28-11/16) x 3 x 28-11/16) x 3 x 28-11/16) x 3 x 28-11/16) x 3 x 28-11/16) x 3
Dimensions(WHD)
(1280 x 1607 x (1280 x 1607 x (1280 x 1607 x (1280 x 1607 x (1280 x 1607 x (1280 x 1607 x (1280 x 1607 x (1280 x 1607 x
mm
730) x 3 730) x 3 730) x 3 730) x 3 730) x 3 730) x 3 730) x 3 730) x 3
Ibs 628 + 628 + 529 628 + 628 + 529 628 + 628 + 529 628 + 628 + 529 628 + 628 + 628 628 + 628 + 628 628 + 628 + 628 628 + 628 + 628
Net Weight
kg 285 + 285 + 240 285 + 285 + 240 285 + 285 + 240 285 + 285 + 240 285 + 285 + 285 285 + 285 + 285 285 + 285 + 285 285 + 285 + 285
Casing Color Warm Gray Warm Gray Warm Gray Warm Gray Warm Gray Warm Gray Warm Gray Warm Gray
Sound Pressure* dB(A) 63 63 63 63 63 63 63 63
Type Propeller fan Propeller fan Propeller fan Propeller fan Propeller fan Propeller fan Propeller fan Propeller fan
Fan Air Flow Rate
cfm 20100 20100 20100 20100 20100 20100 20100 20100
(High)
Type DC Scroll DC Scroll DC Scroll DC Scroll DC Scroll DC Scroll DC Scroll DC Scroll
Compressor
Number of compressor 2+2+1 2+2+1 2+2+1 2+2+1 2+2+2 2+2+2 2+2+2 2+2+2
Heat Exchanger GoldFinTM GoldFinTM GoldFinTM GoldFinTM GoldFinTM GoldFinTM GoldFinTM GoldFinTM
Refrigerant Type R410A R410A R410A R410A R410A R410A R410A R410A
lb 17.6 + 17.6 + 17.6 17.6 + 17.6 + 17.6 17.6 + 17.6 + 17.6 17.6 + 17.6 + 17.6 17.6 + 17.6 + 17.6 17.6 + 17.6 + 17.6 17.6 + 17.6 + 17.6 17.6 + 17.6 + 17.6
Refrigerant Charge
kg 8+8+8 8+8+8 8+8+8 8+8+8 8+8+8 8+8+8 8+8+8 8+8+8
Control EEV EEV EEV EEV EEV EEV EEV EEV
Maximum Number of Indoor Units 55 58 61 64 64 64 64 64

* Sound pressure levels as tested in an anechoic chamber under Korea Standard KSA0701

37
Outdoor Units

Note :
1. Capacities are based on the following conditions
Cooling-Indoor temp. 80F DB / 67F WB Heating-Indoor temp. 70F DB
Outdoor temp. 95F DB Outdoor temp. 47F DB / 43F WB
Interconnecting Piping Length 25ft (7.5m) Interconnecting Piping Length 25ft(7.5m)
Level Difference of 0ft (0m) Level Difference of 0ft (0m)
2. Capacities are net capacities
3. Due to our policy of innovation some specifications may be changed without notification
4. When the calculated refrigerant charge is over 209lb(95kg), multiple outdoor system must be divided into smaller independent systems.
So, each system contains less than 209lb(95kg) refrigerant charge.

208-230V/60Hz/3
Model ARUB BT2 Single Frame 076 096 115
Ton 6.5 8.0 9.5
Cooling Btu/h 76,400 95,900 114,700
kW 22.4 28.0 33.6
Capacity
Heating Btu/h 86,000 107,500 129,000
kW 25.2 31.5 37.8
Cooling kW 6.2 7.8 10.6
Power Input
Heating kW 7.0 8.8 11.1
Power Supply V / Hz / 208-230 / 60 / 3 208-230 / 60 / 3 208-230 / 60 / 3
50 3/8 x 63 5/16 x 50 3/8 x 63 5/16 x 50 3/8 x 63 5/16 x
inch
Dimensions(WHD) 28 11/16 28 11/16 28 11/16
mm 1280 1607 730 1280 1607 730 1280 1607 73 0
Ibs 628 628 628
Net Weight
kg 285 285 285
Casing Color Warm Gray Warm Gray Warm Gray
Sound Pressure* dB(A) 58 58 58
Type Propeller fan Propeller fan Propeller fan
Fan Air Flow Rate
cfm 6,700 6,700 6,700
(High)
Type DC Scroll DC Scroll DC Scroll
Compressor
Number of compressor 2 2 2
Heat Exchanger GoldFinTM GoldFinTM GoldFinTM
Refrigerant Type R410A R410A R410A
lb 17.6 17.6 17.6
Refrigerant Charge
kg 8 8 8
Control EEV EEV EEV
Maximum Number of Indoor Units 13 16 19
* Sound pressure levels as tested in an anechoic chamber under Korea Standard KSA0701

38
Outdoor Units

208-230V/60Hz/3
Dual Frame 154 173 192 211 230
Model ARUB BT2 076 096 096 115 115
Combination
076 076 096 096 115
Ton 12.5 14.5 16.0 17.5 19.0
Cooling Btu/h 152,900 172,000 191,100 210,200 229,300
kW 44.8 50.4 56.0 61.6 67.2
Capacity
Heating Btu/h 172,000 193,500 225,000 236,500 258,000
kW 50.4 56.7 63.0 69.3 75.6
Cooling kW 12.4 14 15.6 18.4 21.2
Power Input
Heating kW 14 15.8 17.6 19.90 22.20
Power Supply V / Hz / 208-230 / 60 / 3 208-230 / 60 / 3 208-230 / 60 / 3 208-230 / 60 / 3 208-230 / 60 / 3
(50 3/8 x 63 5/16 x 28 (50 3/8 x 63 5/16 x 28 (50 3/8 x 63 5/16 x 28 (50 3/8 x 63 5/16 x 28 (50 3/8 x 63 5/16 x 28
inch
Dimensions(WHD) 11/16) x 2 11/16) x 2 11/16) x 2 11/16) x 2 11/16) x 2
mm (1280 x 1607 x 730) x 2 (1280 x 1607 x 730) x 2 (1280 x 1607 x 730) x 2 (1280 x 1607 x 730) x 2 (1280 x 1607 x 730) x 2
Ibs 628+628 628+628 628+628 628+628 628+628
Net Weight
kg 285 285+285 285+285 285+285 285+285
Casing Color Warm Gray Warm Gray Warm Gray Warm Gray Warm Gray
Sound Pressure* dB(A) 61 61 61 61 61
Type Propeller fan Propeller fan Propeller fan Propeller fan Propeller fan
Fan Air Flow Rate
cfm 13,400 13,400 13,400 13,400 13,400
(High)
Type DC Scroll DC Scroll DC Scroll DC Scroll DC Scroll
Compressor
Number of compressor 2+2 2+2 2+2 2+2 2+2
Heat Exchanger GoldFinTM GoldFinTM GoldFinTM GoldFinTM GoldFinTM
Refrigerant Type R410A R410A R410A R410A R410A
lb 17.6+17.6 17.6+17.6 17.6+17.6 17.6+17.6 17.6+17.6
Refrigerant Charge
kg 8+8 8+8 8+8 8+8 8+8
Control EEV EEV EEV EEV EEV
Maximum Number of Indoor Units 26 29 32 35 39

* Sound pressure levels as tested in an anechoic chamber under Korea Standard KSA0701

208-230V/60Hz/3
Triple Frame 250 270 290 310 330 350

Model ARUB BT2 096 096 096 115 115 115


Combination 076 096 096 096 115 115
076 076 096 096 096 115
Ton 20.5 22.5 24.0 25.5 27.0 28.5
Cooling Btu/h 248,400 267,500 286,600 305,700 324,800 343,900
kW 72.8 78.4 84 89.6 95.2 100.8
Capacity
Heating Btu/h 279,500 301,000 322,500 343,900 365,400 386,900
kW 81.9 88.2 94.5 100.8 107.1 113.4
Cooling kW 20.2 21.8 23.4 26.2 29.0 31.8
Power Input
Heating kW 22.8 24.6 26.4 28.7 31 33.3
Power Supply V / Hz / 208-230 / 60 / 3 208-230 / 60 / 3 208-230 / 60 / 3 208-230 / 60 / 3 208-230 / 60 / 3 208-230 / 60 / 3
(50-3/8 x 63-5/16 x (50-3/8 x 63-5/16 x (50-3/8 x 63-5/16 x (50-3/8 x 63-5/16 x (50-3/8 x 63-5/16 x (50-3/8 x 63-5/16 x
inch
Dimensions(WHD) 28-11/16) x 3 28-11/16) x 3 28-11/16) x 3 28-11/16) x 3 28-11/16) x 3 28-11/16) x 3
mm (1280 x 1607 x 730) x 3 (1280 x 1607 x 730) x 3 (1280 x 1607 x 730) x 3 (1280 x 1607 x 730) x 3 (1280 x 1607 x 730) x 3 (1280 x 1607 x 730) x 3
Ibs 628 + 628 + 628 628 + 628 + 628 628 + 628 + 628 628 + 628 + 628 628 + 628 + 628 628 + 628 + 628
Net Weight
kg 285 + 285 + 285 285 + 285 + 285 285 + 285 + 285 285 + 285 + 285 285 + 285 + 285 285 + 285 + 285
Casing Color Warm Gray Warm Gray Warm Gray Warm Gray Warm Gray Warm Gray
Sound Pressure* dB(A) 63 63 63 63 63 63
Type Propeller fan Propeller fan Propeller fan Propeller fan Propeller fan Propeller fan
Fan Air Flow Rate
cfm 20100 20100 20100 20100 20100 20100
(High)
Type DC Scroll DC Scroll DC Scroll DC Scroll DC Scroll DC Scroll
Compressor
Number of compressor 2+2+2 2+2+2 2+2+2 2+2+2 2+2+2 2+2+2
Heat Exchanger GoldFinTM GoldFinTM GoldFinTM GoldFinTM GoldFinTM GoldFinTM
Refrigerant Type R410A R410A R410A R410A R410A R410A
lb 17.6 + 17.6 + 17.6 17.6 + 17.6 + 17.6 17.6 + 17.6 + 17.6 17.6 + 17.6 + 17.6 17.6 + 17.6 + 17.6 17.6 + 17.6 + 17.6
Refrigerant Charge
kg 8+8+8 8+8+8 8+8+8 8+8+8 8+8+8 8+8+8
Control EEV EEV EEV EEV EEV EEV
Maximum Number of Indoor Units 42 45 49 52 55 58

* Sound pressure levels as tested in an anechoic chamber under Korea Standard KSA0701

39
Outdoor Units

Note :
1. Capacities are based on the following conditions
Cooling-Indoor temp. 80F DB / 67F WB Heating-Indoor temp. 70F DB
Outdoor temp. 95F DB Outdoor temp. 47F DB / 43F WB
Interconnecting Piping Length 25ft (7.5m) Interconnecting Piping Length 25ft(7.5m)
Level Difference of 0ft (0m) Level Difference of 0ft (0m)
2. Capacities are net capacities
3. Due to our policy of innovation some specifications may be changed without notification
4. When the calculated refrigerant charge is over 209lb(95kg), multiple outdoor system must be divided into smaller independent systems.
So, each system contains less than 209lb(95kg) refrigerant charge.

460V/60Hz/3
Model ARUB DT2 Single Frame 076 096 115 134 154
Ton 6.5 8.0 9.5 11.0 12.5
Cooling Btu/h 76,400 95,900 114,700 133,800 152,900
kW 22.4 28.0 33.6 39.2 44.8
Capacity
Heating Btu/h 86,000 107,500 129,000 150,500 172,000
kW 25.2 31.5 37.8 44.1 50.4
Cooling kW 5.28 7.16 9.08 11.85 14.00
Power Input
Heating kW 5.73 7.33 9.05 10.60 12.40
Power Supply V / Hz / 460 / 60 / 3 460 / 60 / 3 460 / 60 / 3 460 / 60 / 3 460 / 60 / 3

50 3/8 x 63 5/16 x 50 3/8 x 63 5/16 x 50 3/8 x 63 5/16 x 50 3/8 x 63 5/16 x 50 3/8 x 63 5/16 x
inch
Dimensions(WHD) 28 11/16 28 11/16 28 11/16 28 11/16 28 11/16

mm 1280 1607 730 1280 1607 730 1280 1607 730 1280 1607 730 1280 1607 730
Ibs 529 628 628 628 628
Net Weight
kg 240 285 285 285 285
Casing Color Warm Gray Warm Gray Warm Gray Warm Gray Warm Gray
Sound Pressure* dB(A) 58 58 58 58 58
Type Propeller fan Propeller fan Propeller fan Propeller fan Propeller fan
Fan Air Flow Rate
cfm 6,700 6,700 6,700 6,700 6,700
(High)
Type DC Scroll DC Scroll DC Scroll DC Scroll DC Scroll
Compressor
Number of compressor 1 2 2 2 2
Heat Exchanger GoldFinTM GoldFinTM GoldFinTM GoldFinTM GoldFinTM
Refrigerant Type R410A R410A R410A R410A R410A
lb 17.6 17.6 17.6 17.6 17.6
Refrigerant Charge
kg 8 8 8 8 8
Control EEV EEV EEV EEV EEV
Maximum Number of Indoor Units 13 16 19 23 26

* Sound pressure levels as tested in an anechoic chamber under Korea Standard KSA0701

40
Outdoor Units

460V/60Hz/3
Dual Frame 173 192 211 230 250 270 290 310
Model ARUB DT2 096 115 134 154 134 134 154 154
Combination
076 076 076 076 115 134 134 154
Ton 14.5 16.0 17.5 19.0 20.5 22.5 24.0 25.5
Cooling Btu/h 172,000 191,100 210,200 229,300 248,400 267,500 286,600 305,700
kW 50.4 56.0 61.6 67.2 72.8 78.4 84.0 89.6
Capacity
Heating Btu/h 193,500 225,000 236,500 258,000 279,500 301,000 322,500 343,900
kW 56.7 63.0 69.3 75.6 81.9 88.2 94.5 100.8
Cooling kW 12.44 14.36 17.13 19.28 21.16 23.08 25.85 28
Power Input
Heating kW 12.61 14.33 15.88 17.68 19.73 21.45 23 24.8
Power Supply V / Hz / 460 / 60 / 3 460 / 60 / 3 460 / 60 / 3 460 / 60 / 3 460 / 60 / 3 460 / 60 / 3 460 / 60 / 3 460 / 60 / 3
(50 3/8 x 63 5/16 (50 3/8 x 63 5/16 (50 3/8 x 63 5/16 (50 3/8 x 63 5/16 (50 3/8 x 63 5/16 (50 3/8 x 63 5/16 (50 3/8 x 63 5/16 (50 3/8 x 63 5/16
inch
x 28 11/16) x 2 x 28 11/16) x 2 x 28 11/16) x 2 x 28 11/16) x 2 x 28 11/16) x 2 x 28 11/16) x 2 x 28 11/16) x 2 x 28 11/16) x 2
Dimensions(WHD)
(1280 1607 (1280 1607 (1280 1607 (1280 1607 (1280 1607 x (1280 1607 (1280 1607 (1280 1607
mm
730) x 2 730) x 2 730) x 2 730) x 2 730) x 2 730) x 2 730) x 2 730) x 2
Ibs 628+529 628+529 628+529 628+529 628+628 628+628 628+628 628+628
Net Weight
kg 285+240 285+240 285+240 285+240 285+285 285+285 285+285 285+285
Casing Color Warm Gray Warm Gray Warm Gray Warm Gray Warm Gray Warm Gray Warm Gray Warm Gray
Sound Pressure* dB(A) 61 61 61 61 61 61 61 61
Type Propeller fan Propeller fan Propeller fan Propeller fan Propeller fan Propeller fan Propeller fan Propeller fan
Fan Air Flow Rate
cfm 13,400 13,400 13,400 13,400 13,400 13,400 13,400 13,400
(High)
Type DC Scroll DC Scroll DC Scroll DC Scroll DC Scroll DC Scroll DC Scroll DC Scroll
Compressor
Number of compressor 2+1 2+1 2+1 2+1 2+2 2+2 2+2 2+2
Heat Exchanger GoldFinTM GoldFinTM GoldFinTM GoldFinTM GoldFinTM GoldFinTM GoldFinTM GoldFinTM
Refrigerant Type R410A R410A R410A R410A R410A R410A R410A R410A
lb 17.6 + 17.6 17.6 + 17.6 17.6 + 17.6 17.6 + 17.6 17.6 + 17.6 17.6 + 17.6 17.6 + 17.6 17.6 + 17.6
Refrigerant Charge
kg 8+8 8+8 8+8 8+8 8+8 8+8 8+8 8+8
Control EEV EEV EEV EEV EEV EEV EEV EEV
Maximum Number of Indoor Units 29 32 35 39 42 45 49 52
* Sound pressure levels as tested in an anechoic chamber under Korea Standard KSA0701

460V/60Hz/3
Triple Frame 330 350 370 390 410 430 450 470
134 134 154 154 154 154 154 154
Model ARUB DT2
Combination 115 134 134 154 154 154 154 154
076 076 076 076 096 115 134 154
Ton 27.0 28.5 30.0 32.0 33.5 35.0 36.5 38.0
Cooling Btu/h 324,800 343,900 363,100 382,200 401,700 420,500 439,600 458,700
kW 95.2 100.8 106.4 112 117.6 123.2 128.8 134.4
Capacity
Heating Btu/h 365,400 386,900 408,400 429,900 451,500 473,000 494,500 516,000
kW 107.1 113.4 119.7 126 132.3 138.6 144.9 151.2
Cooling kW 26.1 28.98 33.01 33.28 35.16 37.08 39.85 42
Power Input
Heating kW 25.38 26.93 30.33 30.53 32.13 33.85 35.4 37.2
Power Supply V / Hz / 460 / 60 / 3 460 / 60 / 3 460 / 60 / 3 460 / 60 / 3 460 / 60 / 3 460 / 60 / 3 460 / 60 / 3 460 / 60 / 3
(50-3/8 x 63-5/16 (50-3/8 x 63-5/16 (50-3/8 x 63-5/16 (50-3/8 x 63-5/16 (50-3/8 x 63-5/16 (50-3/8 x 63-5/16 (50-3/8 x 63-5/16 (50-3/8 x 63-5/16
inch
x 28-11/16) x 3 x 28-11/16) x 3 x 28-11/16) x 3 x 28-11/16) x 3 x 28-11/16) x 3 x 28-11/16) x 3 x 28-11/16) x 3 x 28-11/16) x 3
Dimensions(WHD)
(1280 x 1607 x (1280 x 1607 x (1280 x 1607 x (1280 x 1607 x (1280 x 1607 x (1280 x 1607 x (1280 x 1607 x (1280 x 1607 x
mm
730) x 3 730) x 3 730) x 3 730) x 3 730) x 3 730) x 3 730) x 3 730) x 3
Ibs 628 + 628 + 529 628 + 628 + 529 628 + 628 + 529 628 + 628 + 529 628 + 628 + 628 628 + 628 + 628 628 + 628 + 628 628 + 628 + 628
Net Weight
kg 285 + 285 + 240 285 + 285 + 240 285 + 285 + 240 285 + 285 + 240 285 + 285 + 240 285 + 285 + 240 285 + 285 + 240 285 + 285 + 240
Casing Color Warm Gray Warm Gray Warm Gray Warm Gray Warm Gray Warm Gray Warm Gray Warm Gray
Sound Pressure* dB(A) 63 63 63 63 63 63 63 63
Type Propeller fan Propeller fan Propeller fan Propeller fan Propeller fan Propeller fan Propeller fan Propeller fan
Fan Air Flow Rate
cfm 20100 20100 20100 20100 20100 20100 20100 20100
(High)
Type DC Scroll DC Scroll DC Scroll DC Scroll DC Scroll DC Scroll DC Scroll DC Scroll
Compressor
Number of compressor 2 + 2 +1 2 + 2 +1 2 + 2 +1 2 + 2 +1 2 + 2 +2 2 + 2 +2 2 + 2 +2 2 + 2 +2
Heat Exchanger GoldFinTM GoldFinTM GoldFinTM GoldFinTM GoldFinTM GoldFinTM GoldFinTM GoldFinTM
Refrigerant Type R410A R410A R410A R410A R410A R410A R410A R410A
lb 17.6 + 17.6 + 17.6 17.6 + 17.6 + 17.6 17.6 + 17.6 + 17.6 17.6 + 17.6 + 17.6 17.6 + 17.6 + 17.6 17.6 + 17.6 + 17.6 17.6 + 17.6 + 17.6 17.6 + 17.6 + 17.6
Refrigerant Charge
kg 8+8+8 8+8+8 8+8+8 8+8+8 8+8+8 8+8+8 8+8+8 8+8+8
Control EEV EEV EEV EEV EEV EEV EEV EEV
Maximum Number of Indoor Units 55 58 61 64 64 64 64 64

* Sound pressure levels as tested in an anechoic chamber under Korea Standard KSA0701

41
INDOOR UNITS

42
pg. 52
Mirror

Wall Mounted pg. 54

1-Way Ceiling pg. 56


Cassette

2-Way Ceiling pg. 58


Cassette

4-Way Ceiling pg. 60


Cassette

Ducted pg. 62
(High Static)

Ducted pg. 64
(Low Static,
Convertible)

Ducted pg. 66
(Low Static,
Bottom Return)

Vertical (Upflow)/ pg. 68


Horizontal (Left) Air
Handling Unit

Ceiling Suspended pg. 70

Convertible Surface pg. 72


Mounted

Floor Standing pg. 74


(With Case)

Floor Standing pg. 76


(Without Case)

43
Indoor Units

Multi V, Mini, Plus II and Sync II do not use water piping or long distribution ducts,
EFFICIE
E NT reducing installed costs, while increasing system efficiency. In any air conditioning
system, pumps and fans work against the static pressure introduced by pipes and
ductwork. The longer the pipe or duct, the greater the static pressure the pump or
fan must work against. The LG Multi V, Mini, Plus II and Sync II systems completely
remove water piping from the system, and most, if not all of the ductwork. In
addition, the modularity of Multi V allows indoor units to be turned off when they
are not being used. The result is fewer system losses and lower utility bills.

LG indoor units offer a wide range of styles and features to meet all of your cooling
AESTHE
ETIC
CS and heating needs and match universally with all Multi V systems. With indoor unit
choices including cassettes that mount flush to the ceiling, ducted units that hide
completely concealed in the ceiling, and mirror finished wall mounted units that fit
into any dcor, the LG Multi V system offers unparalleled aesthetic design with a
complete array of indoor units to fit into any application.

44
Indoor Units

Quiet
COMFORT Multi V indoor units are among the quietest in the industry with rated sound levels
as low as 23dB(A). In addition to temperature, airflow, and dehumidification,
extremely low sound levels contribute to a relaxing environment.

Dehumidification
Multi V offers the best in dehumidification. Most DX systems cycle to maintain setpoint
affecting efficiency and reducing their runtime hindering proper dehumidification.
Load matching with Multi V not only occurs with the variable and constant speed
compressor combination, but also with the electronic expansion valves and variable
speed fans in each individual indoor unit. This allows the system to run longer
at lower loads providing ultimate dehumidification adding comfort to reduced
energy consumption. In addition, Multi V indoor units can be set to operate in a
dehumidification mode helping to remove moisture from the air even when there is
no call for cooling.

Individualized zone control


Multi V systems allow the user to control the space to the exact temperature desired.
Each evaporator is equipped with its own variable speed fan and electronic expansion
valve, giving completely unfettered temperature control, airflow direction, and fan
speed control to occupants in every zone. If cooling or heating is not wanted, the
user can simply turn off their indoor unit, or turn it to fan mode for air movement
further enhancing comfort while promoting reduced power consumption.

Indoor air quality


All Multi V indoor units incorporate a reusable washable filter. Long distribution and
return ducts are not required for this system, so dust and duct mold accumulation are
reduced. With independent indoor units, odors from one zone will not be carried to
other zones. ArtCool Mirror and wall mounted indoor units can be set to go through
a fan cycle at the end of cooling operation for 30 minutes to warm up and dry the
coil helping minimize mold growth. Ceiling cassette units come standard with
plasma filters to aid in removing mites, pollen, and allergens. ArtCool Mirror and wall
mounted units come standard with plasma and carbon filters which help to remove
odor.

45
Indoor Units

01 02 03

NEO PL ASMA
AIR PURIFYING
SY
YSTEM

01 Pre
Filter
Indoor units come factory supplied with a washable pre-filter.

02 Carbon Filter

ArtCool mirror and wall mounted units come factory supplied with a carbon filter.

03 PlasmaFilter
The plasma filter developed uniquely by LG comes factory installed and powered
as standard on 1, 2, and 4-way ceiling cassettes as well as ArtCool mirror and wall
mounted indoor units.

* Plasma filter type found in 4-way ceiling cassettes.

* Pre filter standard on all units


* Plasma filter available only on ArtCool Mirror, Wall Mounted, and Ceiling Cassette indoor units (models SE, S5, S8, TJ, TL, TM, TN, TP, TQ, and TR)
* Carbon filters available only on ArtCool Mirror and Wall Mounted indoor units (models SE, S5, and S8)

46
Indoor Units

Multi V offers flexible control options to accommodate any requirement. With


FLEXIBLE various thermostat options the individual user in the space can control temperature,
CONTROL airflow, and even turn their unit off when it is not needed. System controllers like AC
Smart can allow a building operator to control individual indoor units from a central
location as well as monitor their operation. LG also offers BACnet and LonWorks
gateways as well as building network units (ACP) with workstation software (AC
Manager) that allow control and monitoring from a remote location.

Lightweight
ENGINEERED Multi V indoor units are lightweight making them easy to move without the need
FOR EASY for lifts. Their light weight also allows indoor units to be easily hung, in most cases
without additional support requirements.
INSSTALL ATION
Small size
The small size of the Multi V indoor units makes them easy to install anywhere.
In fact, they are among the smallest in the industry. Indoor units fit in locations
traditional air handlers cannot. Whether you are installing a ceiling cassette or
ducted unit, it will be an easy fit into even the tightest spaces.

Reduced cost
Fewer materials and less installation time and labor make the LG Multi V system more
cost effective than conventional ducted systems. Indoor units can be piped up using
copper refrigerant lines instead of larger, more labor intensive water piping. Long
distribution ducts take up plenum space. Multi V requires no distribution ducts. In fact,
in most cases Multi V indoor units require no ductwork at all.

47
Indoor Units
MBh 7 9 12 15 18

Series
Mirror
pg. 52

Standard Wall Mounted


pg. 54

1-Way
pg. 56

2-Way
Ceiling pg. 58

Cassette 4-way
(21 X 21 ) Inch
(570 X 570) mm pg. 60

4-way
(33 X 33 ) Inch
(840 X 840) mm pg. 60

Ducted
(High Static) pg. 62
Ceiling
Concealed Ducted
Duct (Low Static,
Convertible) pg. 64

Ducted
(Low Static,
Bottom Return) pg. 66

Vertical / Horizontal
Air Handler pg. 68

Ceiling
Suspended pg. 70

Convertible Surface
Mounted pg. 72

With Case
pg. 74
Floor
Standing
Without Case
pg. 76

48
Indoor Units

24 28 30 36 42 48 54 76 96

49
50
Indoor Units

Indoor Units ARN U 07 3 TN C 2


Family
ARN/URN = Multi V Indoor Unit
(Refrigerant R410A)

Type
U = DC Inverter Heat Pump

Nominal Capacity
07= 7,000 Btu/h 24= 24,000 Btu/h 48= 48,000 Btu/h
09= 9,000 Btu/h 28= 28,000 Btu/h 54= 54,000 Btu/h
12= 12,000 Btu/h 30= 30,000 Btu/h 76= 76,000 Btu/h
15= 15,000 Btu/h 36= 36,000 Btu/h 96= 96,000 Btu/h
18= 18,000 Btu/h 42= 42,000 Btu/h
Electrical Connection
3 = 208-230/60/1

Model
B1 = Ducted (low static, convertible) S5 = Wall Mounted
B2 = Ducted (low static, convertible) S8 = Mirror
B3 = Ducted (low static, bottom return) SE = Wall Mounted/Mirror
B4 = Ducted (low static, bottom return) TJ = 1-Way Ceiling Cassette
B8 = Ducted (high static) TL = 2-Way Ceiling Cassette
BG = Ducted (high static) TM = 4-Way Ceiling Cassette
BH = Ducted (high static TN = 4-Way Ceiling Cassette
BR = Ducted (high static) TP = 4-Way Ceiling Cassette
CE = Floor Standing TQ = 4-Way Ceiling Cassette
CF = Floor Standing TR = 4-Way Ceiling Cassette
NJ = V/H Air Handler Unit VE = Convertible Surface Mounted
NK = V/H Air Handler Unit VJ = Ceiling Suspended

Feature

Generation
2 = Second

51
Indoor Units


Mirrror

The ArtCool Mirror wall mounted units have style to fit any dcor. Similar to the
standard wall mounted unit, the ArtCool Mirror hangs on an easily installed factory
supplied wall bracket making installation simple. ArtCool Mirror units can be installed
in fine homes and residences, upscale hotel guest rooms and lobbies, or any space
with a fashionable interior design.

Operation Fan speed control


Auto changeover (Sync II only) Chaos swing (random louver swing)
Auto operation Chaos wind (random fan speed)
Auto clean (coil dry)1 Jet cool (fast cooling)
Auto restart
Child lock Filter
Dual thermistor control Washable pre-filter
Forced operation Plasma
Group control Carbon
Hot start
Self diagnostics Controllers
Sleep mode 7-day programmable controller
Timer (on/off) Simple controller with mode
Weekly schedule Simple controller without mode
Soft dry (dehumidification) Wireless handheld controller

Airflow Other
Auto direction/swing (up/down) Choice of panel color2
Auto direction/swing (left/right)

1: Requires wireless handheld controller


2: Mirror panel comes standard, silver and blue panels are optional (See page 91)

Model ARNUR2 073 SE 093 SE 123 SE 153 SE 183 S8 243 S8


Btu/h 7,500 9,600 12,300 15,400 19,100 24,200
Cooling
kW 2.2 2.8 3.6 4.5 5.6 7.1
Capacity
Btu/h 8,500 10,900 13,600 17,100 21,500 27,300
Heating
kW 2.5 3.2 4 5 6.3 8
Cooling kW 0.040 0.040 0.040 0.040 0.040 0.040
Power Input
Heating kW 0.040 0.040 0.040 0.040 0.040 0.040
Power Supply V / Hz / 208-230 / 60 / 1 208-230 / 60 / 1 208-230 / 60 / 1 208-230 / 60 / 1 208-230 / 60 / 1 208-230 / 60 / 1
inch 36.0 x 6.5 x 11.1 36.0 x 6.5 x 11.1 36.0 x 6.5 x 11.1 36.0 x 6.5 x 11.1 43.9 x 7.9 x 11.8 43.9 x 7.9 x 11.8
Dimensions(WDH) Body
mm 915 x 169 x 282 915 x 169 x 282 915 x 169 x 282 915 x 169 x 282 1107 x 200 x 299 1107 x 200 x 299
Weight Ibs(kg) 24.7(11.2) 24.7(11.2) 24.7(11.2) 24.7(11.2)) 28.7(13) 28.7(13)
Sound Pressure (H/M/L)4 dBA 37/33/23 39/35/25 41/36/27 42/36/27 39/37/35 41/39/37
Air Flow Rate (H/M/L) cfm 247/212/141 282/247/177 353/283/212 371/283/212 445/406/353 530/494/459

Note :
1. Capacities are based on the following conditions
Cooling-Indoor temp. 80F DB / 67F WB Heating-Indoor temp. 70F DB
Outdoor temp. 95F DB Outdoor temp. 47F DB / 43F WB
Interconnecting Piping Length 25ft (7.5m) Interconnecting Piping Length 25ft (7.5m)
Level Difference of 0ft (0m) Level Difference of 0ft (0m)
2. Capacities are net capacities
3. Due to our policy of innovation some specifications may be changed without notification
4. Sound pressure levels as tested in an anechoic chamber under Korea Standard KSA0701

52
53
Indoor Units

WALLL
MOUNTTED

Extending just 7 inches or less off the wall, the Multi V wall mounted units are among
the lowest profile in the industry. The wall mounted unit hangs on an easily installed
factory supplied wall bracket making installation simple. Multi V wall mounted
units can be installed in homes and residences, hotel guest rooms and lobbies, or
anywhere with free wall space.

Operation Manual direction (left/right)3


Auto changeover (Sync II only) Fan speed control
Auto operation Chaos swing (random louver swing)
Auto clean (coil dry)1 Chaos wind (random fan speed)
Child lock Jet cool (fast cooling)
Dual thermistor control
Forced operation Filter
Group control Washable pre-filter
Hot start Plasma
Self diagnostics Carbon
Sleep mode
Timer (on/off) Controllers
Weekly schedule 7-day programmable controller
Soft dry (dehumidification) Simple controller with mode
Simple controller without mode
Airflow Wireless handheld controller
Auto direction/swing (up/down)
Auto direction/swing (left/right)2

1: Requires wireless handheld controller


2: S5 models only
3: SE models only

Model ARNU L2 073 SE 093 SE 123 SE 153 SE 183 S5 243 S5


Btu/h 7,500 9,600 12,300 15,400 19,100 24,200
Cooling
kW 2.2 2.8 3.6 4.5 5.6 7.1
Capacity
Btu/h 8,500 10,900 13,600 17,100 21,500 27,300
Heating
kW 2.5 3.2 4 5 6.3 8
Cooling kW 0.040 0.040 0.040 0.040 0.040 0.040
Power Input
Heating kW 0.040 0.040 0.040 0.040 0.040 0.040
Power Supply V / Hz / 208-230 / 60 / 1 208-230 / 60 / 1 208-230 / 60 / 1 208-230 / 60 / 1 208-230 / 60 / 1 208-230 / 60 / 1
inch 35.2 x 6.5 x 11.1 35.2 x 6.5 x 11.1 35.2 x 6.5 x 11.1 35.2 x 6.5 x 11.1 42.9 x 7 x 11.8 42.9 x 7 x 11.8
Dimensions(WDH) Body
mm 895 x 165 x 282 895 x 165 x 282 895 x 165 x 282 895 x 165 x 282 1090 x 178 x 300 1090 x 178 x 300
Weight Ibs(kg) 19.8(9) 19.8(9) 19.8(9) 19.8(9) 26.5(12) 26.5(12)
Sound Pressure (H/M/L)4 dBA 37/33/23 39/35/25 41/36/27 42/36/27 37/34/31 43/37/32
Air Flow Rate (H/M/L) cfm 198/177/162.5 247/230/212 336/318/300 371/318/300 424/371/318 494/459/353

Note :
1. Capacities are based on the following conditions
Cooling-Indoor temp. 80F DB / 67F WB Heating-Indoor temp. 70F DB
Outdoor temp. 95F DB Outdoor temp. 47F DB / 43F WB
Interconnecting Piping Length 25ft (7.5m) Interconnecting Piping Length 25ft (7.5m)
Level Difference of 0ft (0m) Level Difference of 0ft (0m)
2. Capacities are net capacities
3. Due to our policy of innovation some specifications may be changed without notification
4. Sound pressure levels as tested in an anechoic chamber under Korea Standard KSA0701

54
55
Indoor Units

The 1-way ceiling cassette models


1-W
WAY mount flush with the ceiling. Ceiling
CEILIN
NG cassettes can be installed in offices,

CASSSETT TE hallways, homes and residences,


hotel guest rooms and lobbies, or
anywhere wall space is not available.

Operation Filter
Auto changeover (Sync II only) Washable pre-filter
Auto operation Plasma
Auto restart
Child lock Controllers
Dual thermistor control 7-day programmable controller
Forced operation Simple controller with mode
Group control Simple controller without mode
Hot start Wireless handheld controller
Self diagnostics
Sleep mode Other
Timer (on/off) Condensate lift1
Weekly schedule Ventilation (outside air)2
Soft dry (dehumidification) Standard grill3

Airflow
Auto direction/swing (up/down)
Fan speed control
Chaos wind (random fan speed)
Jet cool (fast cooling)

1: 27 inches from bottom of unit


2: Temperature, humidity, and volume limitations apply
See Engineering Manual for static pressure requirements and condition limits
3: Standard grill is a required option (PT-HJC1)

Model ARNUC2 073 TJ 093 TJ 123 TJ


Btu/h 7,500 9,600 12,300
Cooling
kW 2.2 2.8 3.6
Capacity
Btu/h 8,500 10,900 13,600
Heating
kW 2.5 3.2 4
Cooling kW 0.040 0.040 0.040
Power Input
Heating kW 0.040 0.040 0.040
Power Supply V / Hz / 208-230 / 60 / 1 208-230 / 60 / 1 208-230 / 60 / 1
inch 33.8 x 16.1 x 5.4 33.8 x 16.1 x 5.4 33.8 x 16.1 x 5.4
Body
mm 860 x 410 x 138 860 x 410 x 138 860 x 410 x 138
Dimensions(WDH)
inch 42.1 x 18.9 x 0.8 42.1 x 18.9 x 0.8 42.1 x 18.9 x 0.8
Front Panel
mm 1070 x 480 x 20 1070 x 480 x 20 1070 x 480 x 20
lbs 25.4 25.4 25.4
Body
kg 11.5 11.5 11.5
Weight
lbs 8 8 8
Front Panel
kg 4 4 4
Sound Pressure (H/M/L)4 dBA 40/38/37 40/38/37 41/39/37
Air Flow Rate (H/M/L) cfm 265/229/212 265/229/212 283/247/212

Note :
1. Capacities are based on the following conditions
Cooling-Indoor temp. 80F DB / 67F WB Heating-Indoor temp. 70F DB
Outdoor temp. 95F DB Outdoor temp. 47F DB / 43F WB
Interconnecting Piping Length 25ft (7.5m) Interconnecting Piping Length 25ft (7.5m)
Level Difference of 0ft (0m) Level Difference of 0ft (0m)
2. Capacities are net capacities
3. Due to our policy of innovation some specifications may be changed without notification
4. Sound pressure levels as tested in an anechoic chamber under Korea Standard KSA0701

56
57
Indoor Units

The LG 2-way ceiling cassette models


2-W
WAY mount flush with the ceiling. Ceiling
CEILIN
NG cassettes can be installed in offices,

CASSSETT TE conference rooms, hallways, homes


and residences, break rooms and
lobbies, or anywhere wall space is not
available.

Operation Filter
Auto changeover (Sync II only) Washable pre-filter
Auto operation Plasma
Auto restart
Child lock Controllers
Dual thermistor control 7-day programmable controller
Group control Simple controller with mode
Forced operation Simple controller without mode
High ceiling Wireless handheld controller
Hot start
Self diagnostics Other
Sleep mode Condensate lift1
Timer (on/off) Standard grill2
Weekly schedule
Soft dry (dehumidification)

Airflow
Auto direction/swing (up/down)
Fan speed control
Chaos wind (random fan speed)
Jet cool (fast cooling)

1: 27 inches from bottom of unit


2: Standard grill is a required option (PT-HLC1)

Model ARNUC2 183 TL 243 TL


Btu/h 19,100 24,200
Cooling
kW 5.6 7.1
Capacity
Btu/h 21,500 27,300
Heating
kW 6.3 8.0
Cooling kW 0.070 0.070
Power Input
Heating kW 0.070 0.070
Power Supply V / Hz / 208-230 / 60 / 1 208-230 / 60 / 1
inch 32.6 x 21.6 x 8.9 32.6 x 21.6 x 8.9
Body
mm 830 x 550 x 225 830 x 550 x 225
Dimensions(WDH)
inch 41.3 x 25.2 x 1.1 41.3 x 25.2 x 1.1
Front Panel
mm 1050 x 640 x 28.5 1050 x 640 x 28.5
lbs 48.5 48.5
Body
kg 22 22
Weight
lbs 10 10
Front Panel
kg 5 5
Sound Pressure (H/M/L)4 dBA 40/35/30 42/37/32
Air Flow Rate (H/M/L) cfm 459/424/353 601/530/459
Note :
1. Capacities are based on the following conditions
Cooling-Indoor temp. 80F DB / 67F WB Heating-Indoor temp. 70F DB
Outdoor temp. 95F DB Outdoor temp. 47F DB / 43F WB
Interconnecting Piping Length 25ft (7.5m) Interconnecting Piping Length 25ft (7.5m)
Level Difference of 0ft (0m) Level Difference of 0ft (0m)
2. Capacities are net capacities
3. Due to our policy of innovation some specifications may be changed without notification
4. Sound pressure levels as tested in an anechoic chamber under Korea Standard KSA0701

58
59
Indoor Units

4 -W
WAY
CEILIN
NG
CASSSETT TE

The LG 4-way ceiling cassette models offer capacities up to 4 tons. With maintenance
friendly features like the optional auto elevation grill (fig.1) it becomes easy to access
filters for cleaning even on the highest ceilings. Independently controlled vanes (fig.2)
allow individualized control in all directions around the 4-way ceiling cassette. The unit
also has specially designed vanes (fig.3) that direct air where it is wanted and covers
the corners of the room. Removable corner access panels (fig.4) allow easy access
for height adjustment and maintenance checks. Ceiling cassettes can be installed in
schools, offices, conference rooms, homes and residences, hotel guest rooms and
lobbies, or anywhere wall space is not available.

Model ARNUC2 073 TR 093 TR 123 TR 153 TQ 183 TQ


Btu/h 7,500 9,600 12,300 15,400 19,100
Cooling
kW 2.2 2.8 3.6 4.5 5.6
Capacity
Btu/h 8,500 10,900 13,600 17,100 21,500
Heating
kW 2.5 3.2 4.0 5.0 6.3
Cooling kW 0.043 0.043 0.043 0.043 0.043
Power Input
Heating kW 0.043 0.043 0.043 0.043 0.043
Power Supply V / Hz / 208-230 / 60 / 1 208-230 / 60 / 1 208-230 / 60 / 1 208-230 / 60 / 1 208-230 / 60 / 1
inch 22.4 x 22.4 x 8.4 22.4 x 22.4 x 8.4 22.4 x 22.4 x 8.4 22.4 x 22.4 x 10.1 22.4 x 22.4 x 10.1
Body
mm 570 x 570 x 214 570 x 570 x 214 570 x 570 x 214 570 x 570 x 256 570 x 570 x 256
Dimensions(WDH)
inch 27.5 x 27.5 x 1.2 27.5 x 27.5 x 1.2 27.5 x 27.5 x 1.2 27.5 x 27.5 x 1.2 27.5 x 27.5 x 1.2
Front Panel
mm 700 x 700 x 30 700 x 700 x 30 700 x 700 x 30 700 x 700 x 30 700 x 700 x 30
lbs 28.9 31.3 31.3 34.2 34.2
Body
kg 13.1 14.2 14.2 15.5 15.5
Weight
lbs 7.5 7.5 7.5 7.5 7.5
Front Panel
kg 3 3 3 3 3
Sound Pressure (H/M/L)4 dBA 29/27/26 30/29/27 32/30/27 36/34/32 37/35/34
Air Flow Rate (H/M/L) cfm 265/247/212 283/265/251 307/283/247 388/353/328 396/388/353

Note :
1. Capacities are based on the following conditions
Cooling-Indoor temp. 80F DB / 67F WB Heating-Indoor temp. 70F DB
Outdoor temp. 95F DB Outdoor temp. 47F DB / 43F WB
Interconnecting Piping Length 25ft (7.5m) Interconnecting Piping Length 25ft (7.5m)
Level Difference of 0ft (0m) Level Difference of 0ft (0m)
2. Capacities are net capacities
3. Due to our policy of innovation some specifications may be changed without notification
4. Sound pressure levels as tested in an anechoic chamber under Korea Standard KSA0701

60
Indoor Units

Operation Filter
Auto changeover (Sync II only) Washable pre-filter
Auto operation Plasma
Auto restart
Child lock Controllers
Dual thermistor control 7-day programmable controller
Forced operation Simple controller with mode
Group control Simple controller without mode
High ceiling Wireless handheld controller
Hot start
Self diagnostics Other
Sleep mode Condensate lift1
Timer (on/off) Ventilation (outside air)
Weekly schedule Side branch ducting
Soft dry (dehumidification) Standard grill4
Auto elevation grill kit5
Airflow Corner access panels
Auto direction/swing (up/down)
Fan speed control
Chaos wind (random fan speed)
Swirl wind (alternating vanes)
Jet cool (fast cooling)

1: 27 inches from bottom of unit


2: Ventilation kit required for 24-48 MBh PTVK410 and PTVK420
Temperature, humidity, and volume limitations apply
See Engineering Manual for static pressure requirements and condition limits
3: See Engineering Manual for airflow and static pressure requirements
4: Standard grill is a required option (PT-UQC for 7-18MBh/ PT-UMC for 24-48MBh)
5: Available only with 24-48 MBh (PTEGM0)

(fig.1) Auto Elevation Grill5

Even air distribution Temp.


80.6F
(27C)

59F
(15C)

(fig.2) Independent Vanes (fig.3) Vane Design (fig.4) Corner Access Panels

Model ARNUC2 243 TP 283 TP 363 TN 423 TM 483 TM


Btu/h 24,200 28,000 36,200 42,000 48,100
Cooling
kW 7.1 8.2 10.6 12.3 14.1
Capacity
Btu/h 27,300 31,500 40,600 43,800 51,200
Heating
kW 8.0 9.2 11.9 13.8 15.9
Cooling kW 0.033 0.033 0.144 0.144 0.144
Power Input
Heating kW 0.033 0.033 0.144 0.144 0.144
Power Supply V / Hz / 208-230 / 60 / 1 208-230 / 60 / 1 208-230 / 60 / 1 208-230 / 60 / 1 208-230 / 60 / 1
inch 33.0 x 33.0 x 8.0 33.0 x 33.0 x 8.0 33.0 x 33.0 x 9.7 33.0 x 33.0 x 11.7 33.0 x 33.0 x 11.7
Body
mm 840 x 840 x 204 840 x 840 x 204 840 x 840 x 246 840 x 840 x 298 840 x 840 x 298
Dimensions(WDH)
inch 37.4 x 37.4 x 1.2 37.4 x 37.4 x 1.2 37.4 x 37.4 x 1.2 37.4 x 37.4 x 1.2 37.4 x 37.4 x 1.2
Front Panel
mm 950 x 950 x 30 950 x 950 x 30 950 x 950 x 30 950 x 950 x 30 950 x 950 x 30
lbs 45.8 45.8 51.8 56.4 56.4
Body
kg 20.8 20.8 23.5 25.6 25.6
Weight
lbs 12.5 12.5 12.5 12.5 12.5
Front Panel
kg 6 6 6 6 6
Sound Pressure (H/M/L)4 dBA 36/34/31 39/35/33 43/40/37 44/41/38 46/43/41
Air Flow Rate (H/M/L) cfm 600/529/459 671/565/494 883/742/671 1059/954/848 1095/1024/954

Note :
1. Capacities are based on the following conditions
Cooling-Indoor temp. 80F DB / 67F WB Heating-Indoor temp. 70F DB
Outdoor temp. 95F DB Outdoor temp. 47F DB / 43F WB
Interconnecting Piping Length 25ft (7.5m) Interconnecting Piping Length 25ft (7.5m)
Level Difference of 0ft (0m) Level Difference of 0ft (0m)
2. Capacities are net capacities
3. Due to our policy of innovation some specifications may be changed without notification
4. Sound pressure levels as tested in an anechoic chamber under Korea Standard KSA0701

61
Indoor Units

DUCTED
D
[ H ig
gh Sta
atic
c]

High static ducted models offer a full range of capacities from to 8 tons. With
short supply and return ducts, static pressure losses are minimized when compared
to conventional ducted systems. Ducted units can be installed in schools, offices,
conference rooms, homes and residence retrofits, hallways and lobbies, or anywhere
a unit must be concealed.

Operation Airflow
Auto changeover (Sync II only) Fan speed control
Auto operation
Auto restart Filter
Child lock Washable pre-filter
Dual thermistor control
Group control
Controllers
E.S.P. control
7-day programmable controller
Hot start
Simple controller with mode
Self diagnostics
Simple controller without mode
Sleep mode
Wireless handheld controller
Timer (on/off)
Weekly schedule
Soft dry (dehumidification) Other
Condensate lift2
Ventilation (Outside Air)3

1: Requires 7-day programmable controller


2: 27 inches from bottom of unit
3: Temperature, humidity, and volume limitations apply
See Engineering Manual for condition limits

Model ARNUA2 073 BH 093 BH 123 BH 153 BH 183 BH 243 BH


Btu/h 7,500 9,600 12,300 15,400 19,100 24,200
Cooling
kW 2.2 2.8 3.6 4.5 5.6 7.1
Capacity
Btu/h 8,500 10,900 13,600 17,100 21,500 27,300
Heating
kW 2.5 3.2 4.0 5.0 6.3 8.0
Cooling kW 0.150 0.150 0.150 0.150 0.150 0.150
Power Input
Heating kW 0.150 0.150 0.150 0.150 0.150 0.150
Power Supply V / Hz / 208-230 / 60 / 1 208-230 / 60 / 1 208-230 / 60 / 1 208-230 / 60 / 1 208-230 / 60 / 1 208-230 / 60 / 1
inch 34.7 x 17.7 x 10.2 34.7 x 17.7 x 10.2 34.7 x 17.7 x 10.2 34.7 x 17.7 x 10.2 34.7 x 17.7 x 10.2 34.7 x 17.7 x 10.2
Dimensions(WDH) Body
mm 882 x 450 x 260 882 x 450 x 260 882 x 450 x 260 882 x 450 x 260 882 x 450 x 260 882 x 450 x 260
Weight lbs(kg) 57.4(26) 57.4(26) 57.4(26) 57.4(26)) 58.5(26.5) 58.5(26.5)
Sound Pressure (H/M/L)4 dBA 34/33/32 35/34/33 37/35/34 39/38/37 42.5/41/37 45/43/41
Air Flow Rate (H/M/L) cfm 247/230/212 318/282/247 424/353/318 494/424/353 547/477/438 646/597/547
(High Mode-factory set)
in wg 0.31 0.31 0.31 0.31 0.31 0.31
External Static Pressure4
Air Flow Rate (H/M/L) cfm 247/230/212 318/282/247 424/353/318 494/424/353 540/480/364 671/579/512
(Standard Mode)
in wg 0.24 0.24 0.24 0.24 0.24 0.24
External Static Pressure4

Note :
1. Capacities are based on the following conditions
Cooling-Indoor temp. 80F DB / 67F WB Heating-Indoor temp. 70F DB
Outdoor temp. 95F DB Outdoor temp. 47F DB / 43F WB
Interconnecting Piping Length 25ft (7.5m) Interconnecting Piping Length 25ft (7.5m)
Level Difference of 0ft (0m) Level Difference of 0ft (0m)
2. Capacities are net capacities
3. Due to our policy of innovation some specifications may be changed without notification
4. External Static Pressure, as shipped from the factory, does not include air filter or connected ductwork, but applies to any fan speed

62
Indoor Units

Model ARNU A2 283 BG 363 BG 423 BG 483 BR URNU 763 B8 A2 URNU 963 B8 A2
Btu/h 28,000 36,200 42,000 48,100 76,400 95,500
Cooling
kW 8.2 10.6 12.3 14.1 22.4 28
Capacity
Btu/h 31,500 40,600 43,800 51,200 86,000 107,500
Heating
kW 9.2 11.9 13.8 15.9 25.2 31.5
Cooling kW 0.450 0.450 0.450 0.450 0.8 0.8
Power Input
Heating kW 0.450 0.450 0.450 0.450 0.8 0.8
Power Supply V / Hz / 208-230 / 60 / 1 208-230 / 60 / 1 208-230 / 60 / 1 208-230 / 60 / 1 208-230 / 60 / 1 208-230 / 60 / 1
inch 46.5 x 17.7 x 11.7 46.5 x 17.7 x 11.7 46.5 x 17.7 x 11.7 48.4 x 23.2 x 15 61.5 x 18.1 x 27.1 61.5 x 18.1 x 27.1
Dimensions(WDH) Body
mm 1182 x 450 x 297 1182 x 450 x 297 1182 x 450 x 297 1230 x 590 x 380 1562 x 460 x 688 1562 x 460 x 688
Weight lbs(kg) 83.8(38) 83.8(38) 83.8(38) 117(53) 192(87) 192(87)
Sound Pressure (H/M/L)4 dBA 44/42/40 46/44/42 48/46/45 45/43/41 50/48/48 52/50/50
Air Flow Rate (H/M/L) cfm 915/851/770 1141/1024/893 1218/1141/1084 1582/1434/1176 2260/1765/1765 2542/2260/2260
(High Mode-factory set)
in wg 0.40 0.40 0.40 0.55 0.87 0.87
External Static Pressure
Air Flow Rate (H/M/L) cfm 893/770/622 1003/893/770 1130/1003/961 1568/1395/1183 2118/1765/1765 2683/2260/2260
(Standard Mode)
in wg 0.31 0.31 0.31 0.40 0.60 0.60
External Static Pressure

Note :
1. Capacities are based on the following conditions
Cooling-Indoor temp. 80F DB / 67F WB Heating-Indoor temp. 70F DB
Outdoor temp. 95F DB Outdoor temp. 47F DB / 43F WB
Interconnecting Piping Length 25ft (7.5m) Interconnecting Piping Length 25ft (7.5m)
Level Difference of 0ft (0m) Level Difference of 0ft (0m)
2. Capacities are net capacities
3. Due to our policy of innovation some specifications may be changed without notification
4. Sound pressure levels as tested in an anechoic chamber under Korea Standard KSA0701

63
Indoor Units

DUCTE
ED
[ Low
w Statiic,
Conve rtib
ble ]

With a vertical depth of just 7 1/2 in., the convertible low static ducted models
allow installation in ceilings. This ducted unit can be converted between rear and
bottom return for maximum ducting flexiblity. With minimal supply and return
ducts, static pressure losses are almost non-existent. Ducted units can be installed
in hotel guest rooms, lobbies, residencies or anywhere a unit must be concealed.

Operation Filter
Auto changeover (Sync II only) Washable pre-filter
Auto operation
Auto restart Controllers
Child lock 7-day programmable controller
Dual thermistor control Simple controller with mode
Group control Simple controller without mode
E.S.P. control Wireless handheld controller
Hot start
Self diagnostics Other
Sleep mode Condensate lift2
Timer (on/off)
Ventilation (Outside Air)3
Weekly schedule
Soft dry (dehumidification)

Airflow
Fan speed control

1: Requires 7-day programmable controller


2: 27 inches from bottom of unit
3: Temperature, humidity, and volume limitations apply
See Engineering Manual for condition limits

Model ARNU G2 073 B1 093 B1 123 B1 153 B1 183 B2 243 B2


Btu/h 7,500 9,600 12,300 15,400 19,100 24,200
Cooling
kW 2.2 2.8 3.6 4.5 5.6 7.1
Capacity
Btu/h 8,500 10,900 13,600 17,100 21,500 27,300
Heating
kW 2.5 3.2 4.0 5.0 6.3 8.0
Cooling kW 0.030 0.030 0.030 0.030 0.080 0.80
Power Input
Heating kW 0.030 0.030 0.030 0.030 0.080 0.80
Power Supply V/ Hz / 208-230 / 60 / 1 208-230 / 60 / 1 208-230 / 60 / 1 208-230 / 60 / 1 208-230 / 60 / 1 208-230 / 60 / 1
inch 32.3 x 21.7 x 7.5 32.3 x 21.7 x 7.5 32.3 x 21.7 x 7.5 32.3 x 21.7 x 7.5 43.3 x 21.7 x 7.5 43.3 x 21.7 x 7.5
Dimensions(WDH) Body
mm 820 x 575 x 190 820 x 575 x 190 820 x 575 x 190 820 x 575 x 190 1100 x 575 x 190 1100 x 575 x 190
Weight lbs(kg) 46.3(21) 46.3(21) 46.3(21) 46.3(21) 57.3(26) 57.3(26)
Sound Pressure (H/M/L)4 dBA 35/33/31 36/35/33 37/36/35 38/37/36 40/37/34 43/40/37
Air Flow Rate (H/M/L) cfm 300/265/229 335/300/265 371/335/300 406/371/335 565/494/424 671/600/530
(High Mode-factory set)
in wg 0.08 0.08 0.08 0.08 0.08 0.08
External Static Pressure4
Air Flow Rate (H/M/L) cfm 300/265/229 335/300/265 371/335/300 406/371/335 565/494/424 671/600/530
(Standard Mode)
in wg 0 0 0 0 0 0
External Static Pressure4
Note :
1. Capacities are based on the following conditions
Cooling-Indoor temp. 80F DB / 67F WB Heating-Indoor temp. 70F DB
Outdoor temp. 95F DB Outdoor temp. 47F DB / 43F WB
Interconnecting Piping Length 25ft (7.5m) Interconnecting Piping Length 25ft (7.5m)
Level Difference of 0ft (0m) Level Difference of 0ft (0m)
2. Capacities are net capacities
3. Due to our policy of innovation some specifications may be changed without notification
4. External Static Pressure, as shipped from the factory, does not include air filter or connected ductwork, but applies to any fan speed

64
65
Indoor Units

The low static bottom return ducted indoor unit


DUCTED
D has a vertical depth of just 7 inches allowing
[ Low Sta
atic
c, installation in ceilings or soffits with minimal
Botttom Retuu rn
n]
vertical clearance. This unit is easily tailored
to installation in an entry soffit with optional
suction canvas and/or grill (shown installed).
With minimal supply and return ducts, static
pressure losses are almost non-existent. Ducted
units can be installed in hotel guest rooms,
lobbies, residences, entries, or anywhere a unit
must be concealed.

Operation Filter
Auto changeover (Sync II only) Washable pre-filter
Auto operation
Auto restart Controllers
Child lock 7-day programmable controller
Dual thermistor control Simple controller with mode
Group control Simple controller without mode
E.S.P. control Wireless handheld controller
Hot start
Self diagnostics
Other
Sleep mode
Condensate lift2
Timer (on/off)
Ventilation (outside air)3
Weekly schedule
Suction grill4
Soft dry (dehumidification)
Suction canvas 4

Airflow
Fan speed control

1: Requires 7-day programmable controller


2: 27 inches from bottom of unit
3: Temperature, humidity, and volume limitations apply
See Engineering Manual for condition limits
4: Suction grill and suction canvas are optional (See page 90)

Model ARNU G2 073 B3 093 B3 123 B3 153 B3 183 B4 243 B4


Btu/h 7,500 9,600 12,300 15,400 19,100 24,200
Cooling
kW 2.2 2.8 3.6 4.5 5.6 7.1
Capacity
Btu/h 8,500 10,900 13,600 17,100 21,500 27,300
Heating
kW 2.5 3.2 4.0 5.0 6.3 8.0
Cooling kW 0.030 0.030 0.030 0.030 0.080 0.80
Power Input
Heating kW 0.030 0.030 0.030 0.030 0.080 0.80
Power Supply V / Hz / 208-230 / 60 / 1 208-230 / 60 / 1 208-230 / 60 / 1 208-230 / 60 / 1 208-230 / 60 / 1 208-230 / 60 / 1
inch 32.3 x 22.6 x 7.5 32.3 x 22.6 x 7.5 32.3 x 22.6 x 7.5 32.3 x 22.6 x 7.5 43.3 x 22.6 x 7.5 43.3 x 22.6 x 7.5
Dimensions(WDH) Body
mm 820 x 575 x 190 820 x 575 x 190 820 x 575 x 190 820 x 575 x 190 1100 x 575 x 190 1100 x 575 x 190
Weight lbs(kg) 46.3(21) 46.3(21) 46.3(21) 46.3(21) 57.3(26) 57.3(26)
Sound Pressure (H/M/L)4 dBA 37/34/33 39/35/34 40/37/34 41/40/37 43/40/37 46/43/37
Air Flow Rate (H/M/L) cfm 282/229/194 318/247/212 353/282/229 388/353/282 494/424/353 600/530/353
(High Mode-factory set)
wg in
w 0.08 0.08 0.08 0.08 0.08 0.08
External Static Pressure4
Air Flow Rate (H/M/L) cfm 282/229/194 318/247/212 353/282/229 388/353/282 494/424/353 600/530/353
(Standard Mode)
wg in 0 0 0 0 0 0
External Static Pressure4

Note :
1. Capacities are based on the following conditions
Cooling-Indoor temp. 80F DB / 67F WB Heating-Indoor temp. 70F DB
Outdoor temp. 95F DB Outdoor temp. 47F DB / 43F WB
Interconnecting Piping Length 25ft (7.5m) Interconnecting Piping Length 25ft (7.5m)
Level Difference of 0ft (0m) Level Difference of 0ft (0m)
2. Capacities are net capacities
3. Due to our policy of innovation some specifications may be changed without notification
4. External Static Pressure, as shipped from the factory, does not include air filter or connected ductwork, but applies to any fan speed

66
67
Indoor Units

Vertical (Upflow)/Horizontal (Left) air handler units offer


VERTIICAL/ capacities from 1.5 to 4.5 tons. With external static pressure
HORIZZONTAL capabilities up to one inch water gauge, this unit can be
applied in conventional or retrofit applications that previously
AIR
R HANDLER used vertical upflow or horizontal left air handling units.

Operation Airflow
Auto operation Fan speed control
Auto restart Vertical up
Child lock Horizontal left
Dual thermistor control
E.S.P. control Controllers
Group control 7-day programmable controller
Hot start Simple controller with mode
Self diagnostics Simple controller without mode
Sleep mode Wireless handheld controller
Soft dry (dehumidification)
Timer (on/off)
Other
Ventilation (Outside Air)2
Electric heater (optional)3

1: Requires 7-day programmable controller


2: Temperature, humidity, and volume limitations apply
See Engineering Manual for condition limits
3: Refer to the installation manual for important electrical safety and functional information

Model ARNUA2 183NJ 243NJ 303NJ 363NJ


Btu/h 18,000 24,000 30,000 36,000
Cooling
kW 5.3 7.0 8.8 10.6
Capacity
Btu/h 20,000 27,000 34,000 40,000
Heating
kW 5.9 7.9 10.0 11.7
Cooling kW 0.080 0.120 0.178 0.193
Power Input
Heating kW 0.080 0.120 0.178 0.193
Power Supply V / Hz / 208-230/60/1 208-230/60/1 208-230/60/1 208-230/60/1
inch 18 x 21-3/8 x 48-5/8 18 x 21-3/8 x 48-5/8 18 x 21-3/8 x 48-5/8 18 x 21-3/8 x 48-5/8
Dimensions(WDH) Body
mm 457 x 543 x 1,236 457 x 543 x 1,236 457 x 543 x 1,236 635 x 543 x 1,401
Net Weight lbs(kg) 130 130 130 165
Sound Pressure (H/M/L)4 dBA 42/41/39 43/42/41 44/43/42 44/40/38
High Air Flow Rate- cfm 530/480/380 710/640/480 880/800/630 990/880/800
Mode (H/M/L)5
in wg 0.5 0.5 0.5 0.5
External Static Pressure6
Standard Air Flow cfm 530/480/380 710/640/480 880/800/630 990/880/800
Rate Mode (H/M/L)5
in wg 0.3 0.3 0.3 0.3
External Static Pressure6

Note :
1. Capacities are based on the following conditions
Cooling-Indoor temp. 80F DB / 67F WB Heating-Indoor temp. 70F DB
Outdoor temp. 95F DB Outdoor temp. 47F DB / 43F WB
Interconnecting Piping Length 25ft (7.5m) Interconnecting Piping Length 25ft (7.5m)
Level Difference of 0ft (0m) Level Difference of 0ft (0m)
2. Capacities are net capacities
3. Due to our policy of innovation some specifications may be changed without notification
4. Sound pressure levels as tested in an anechoic chamber under Korea Standard KSA0701
5. The factory standard is High Mode
6. External Static Pressure, as shipped from the factory, does not include air filter or connected ductwork, but applies to any fan speed

68
Indoor Units

Model ARNU A2 423NK 483NK 543NK


Btu/h 42,000 48,000 54,000
Cooling
kW 12.3 14.1 15.8
Capacity
Btu/h 46,000 54,000 60,000
Heating
kW 13.5 15.8 17.6
Cooling kW 0.260 0.330 0.366
Power Input
Heating kW 0.260 0.330 0.366
Power Supply V / Hz / 208-230/60/1 208-230/60/1 208-230/60/1
inch 25 x 21-3/8 x 55-1/8 25 x 21-3/8 x 55-1/8 25 x 21-3/8 x 55-1/8
Dimensions(WDH) Body
mm 635 x 543 x 1,401 635 x 543 x 1,401 635 x 543 x 1,401
Weight lbs(kg) 165 165 165
Sound Pressure (H/M/L)4 dBA 46/44/41 49/46/41 50/49/47
High Air Flow Rate cfm 1,250/1,100/1,000 1,400/1,260/1,000 1,475/1,400/1,260
Mode (H/M/L)5
in wg 0.5 0.5 0.5
External Static Pressure
Standard Air Flow Rate cfm 1,250/1,100/1,000 1,400/1,260/1,000 1,475/1,400/1,260
Mode (H/M/L)5
in wg 0.3 0.3 0.3
External Static Pressure6

Note :
1. Capacities are based on the following conditions
Cooling-Indoor temp. 80F DB / 67F WB Heating-Indoor temp. 70F DB
Outdoor temp. 95F DB Outdoor temp. 47F DB / 43F WB
Interconnecting Piping Length 25ft (7.5m) Interconnecting Piping Length 25ft (7.5m)
Level Difference of 0ft (0m) Level Difference of 0ft (0m)
2. Capacities are net capacities
3. Due to our policy of innovation some specifications may be changed without notification
4. Sound pressure levels as tested in an anechoic chamber under Korea Standard KSA0701
5. The factory standard is High Mode
6. External Static Pressure, as shipped from the factory, does not include air filter or connected ductwork, but applies to any fan speed

69
Indoor Units

CEILIN
NG
SUSPEE NDE D

The ceiling suspended indoor unit is hung from the ceiling unobtrusively. These
units are ideal for retrofit applications where plenum space is not available. Ceiling
suspended units can be installed in dormitories, entries, storerooms, offices, or
anywhere ceiling suspended units are desired.

Operation Airflow
Auto changeover (Sync II only) Auto direction/swing (up/down)
Auto operation Auto direction/swing (left/right)
Auto restart Fan speed control
Child lock Chaos wind (random fan speed)
Dual thermistor control Jet cool (fast cooling)
Forced operation
Group control Filter
High ceiling Washable pre-filter
Hot start
Self diagnostics Controllers
Sleep mode 7-day programmable controller
Timer (on/off) Simple controller with mode
Weekly schedule Simple controller without mode
Soft dry (dehumidification)
Wireless handheld controller

Model ARNUA2 183 VJ 243 VJ


Btu/h 19,100 24,200
Cooling
kW 5.6 7.1
Capacity
Btu/h 21,500 27,300
Heating
kW 6.3 8
Cooling kW 0.063 0.063
Power Input
Heating kW 0.063 0.063
Power Supply V / Hz / 208-230 / 60 / 1 208-230 / 60 / 1
inch 37.4 x 8.7 x 25.6 37.4 x 8.7 x 25.6
Dimensions(WDH) Body
mm 950 x 220 x 650 950 x 220 x 650
Weight Ibs(kg) 54.2(24.6) 54.2(24.6)
Sound Pressure (H/M/L)4 dBA 42/40/37 43/41/39
Air Flow Rate (H/M/L) cfm 565/495/424 636/566/495

Note :
1. Capacities are based on the following conditions
Cooling-Indoor temp. 80F DB / 67F WB Heating-Indoor temp. 70F DB
Outdoor temp. 95F DB Outdoor temp. 47F DB / 43F WB
Interconnecting Piping Length 25ft (7.5m) Interconnecting Piping Length25ft (7.5m)
Level Difference of 0ft (0m) Level Difference of 0ft (0m)
2. Capacities are net capacities
3. Due to our policy of innovation some specifications may be changed without notification
4. Sound pressure levels as tested in an anechoic chamber under Korea Standard KSA0701

70
71
Indoor Units

Installed near the floor or suspended


CONVE ERTIB
BLE from the ceiling, the convertible surface
SURFA
ACE mounted indoor unit offers installation

MOUNTTED flexibility. These units are great for retrofit


applications where plenum space is not
available. Convertible surface mounted
units can be installed in dormitories,
entries, storerooms, hotel guest rooms,
schools, offices, or anywhere floor and
ceiling suspended units are desired.

Operation Airflow
Auto changeover (Sync II only) Auto direction/swing (up/down)
Auto operation Auto direction/swing (left/right)
Auto restart Fan speed control
Child lock Chaos swing (random louver swing)
Dual thermistor control Chaos wind (random fan speed)
Forced operation Jet cool (fast cooling)
Group control
High ceiling Filter
Hot start Washable pre-filter
Self diagnostics
Sleep mode
Controllers
Timer (on/off)
7-day programmable controller
Weekly schedule
Simple controller with mode
Soft dry (dehumidification)
Simple controller without mode
Wireless handheld controller

Model ARNUA2 093 VE 123 VE


Btu/h 9,600 12,300
Cooling
kW 2.8 3.6
Capacity
Btu/h 10,900 13,600
Heating
kW 3.2 4
Cooling kW 0.03 0.03
Power Input
Heating kW 0.03 0.03
Power Supply V / Hz / 208-230 / 60 / 1 208-230 / 60 / 1
inch 35.4 x 7.9 x 19.3 35.4 x 7.9 x 19.3
Dimensions(WDH) Body
mm 900 x 200 x 490 900 x 200 x 490
Weight Ibs(kg) 30.2(13.7) 30.2(13.7)
Sound Pressure (H/M/L)4 dBA 36/32/28 38/36/30
Air Flow Rate (H/M/L) cfm 268/243/219 325/268/244

Note :
1. Capacities are based on the following conditions
Cooling-Indoor temp. 80F DB / 67F WB Heating-Indoor temp. 70F DB
Outdoor temp. 95F DB Outdoor temp. 47F DB / 43FWB
Interconnecting Piping Length 25ft (7.5m) Interconnecting Piping Length 25ft (7.5m)
Level Difference of 0ft (0m) Level Difference of 0ft (0m)
2. Capacities are net capacities
3. Due to our policy of innovation some specifications may be changed without notification
4. Sound pressure levels as tested in an anechoic chamber under Korea Standard KSA0701

72
73
Indoor Units

Floor standing indoor units with the


FLO
OOR architectural case offer quiet operation.
STANDIING A 7 day programmable controller can
[ With
h Ca
ase
e] be mounted on the unit. Filters at the
bottom of the unit are easy to access for
cleaning and replacement. These units are
ideal for retrofit applications where radiators
are being replaced. Floor standing units can
be installed in hotel guest rooms, schools,
offices, dormitories, entries, storerooms,
churches or anywhere floor standing units
are desired.

Operation Airflow
Auto changeover (Sync II only) Fan speed control
Auto operation
Auto restart Filter
Child lock Washable pre-filter
Dual thermistor control
E.S.P. control
Controllers
Hot start
7-day programmable controller
Self diagnostics
Simple controller with mode
Sleep mode
Simple controller without mode
Timer (on/off)
Wireless handheld controller
Weekly schedule
Soft dry (dehumidification)

1: Requires 7-day programmable controller

Model ARNU A2 073 CE 093 CE 123 CE 153 CE 183 CF 243 CF


Btu/h 7,500 9,600 12,300 15,400 19,100 24,200
Cooling
kW 2.2 2.8 3.6 4.5 5.6 7.1
Capacity
Btu/h 8,500 10,900 13,600 17,100 21,500 27,300
Heating
kW 2.5 3.2 4 5 6.3 8
Cooling kW 0.030 0.030 0.030 0.030 0.080 0.080
Power Input
Heating kW 0.030 0.030 0.030 0.030 0.080 0.080
Power Supply V / Hz / 208-230 / 60 / 1 208-230 / 60 / 1 208-230 / 60 / 1 208-230 / 60 / 1 208-230 / 60 / 1 208-230 / 60 / 1
inch 42.2 x 8.0 x 25.0 42.2 x 8.0 x 25.0 42.2 x 8.0 x 25.0 42.2 x 8.0 x 25.0 52.9 x 8.0 x 25.0 52.9 x 8.0 x 25.0
Dimensions(WDH) Body
mm 1067 x 203 x 635 1067 x 203 x 635 1067 x 203 x 635 1067 x 203 x 635 1345 x 203 x 635 1345 x 203 x 635
Weight Ibs(kg) 59.5(27) 59.5(27) 59.5(27) 59.5(27) 75.0(34) 75.0(34)
Sound Pressure (H/M/L)4 dBA 35/33/31 36/34/32 37/35/33 38/37/35 40/37/34 43/40/37
Air Flow Rate (H/M/L) cfm 300/265/229 335/300/265 371/335/300 406/353/335 565/494/424 635/565/494

Note :
1. Capacities are based on the following conditions
Cooling-Indoor temp. 80F DB / 67F WB Heating-Indoor temp. 70F DB
Outdoor temp. 95F DB Outdoor temp. 47F DB / 43F WB
Interconnecting Piping Length 25ft (7.5m) Interconnecting Piping Length 25ft (7.5m)
Level Difference of 0ft (0m) Level Difference of 0ft (0m)
2. Capacities are net capacities
3. Due to our policy of innovation some specifications may be changed without notification
4. Sound pressure levels as tested in an anechoic chamber under Korea Standard KSA0701

74
75
Indoor Units

Floor standing indoor units operate quietly.


FLO
OOR Floor standing indoor units without the
STANDIING architectural case can be installed with
[ With
houtt Case ] aftermarket cabinets or built into a
perimeter wall. These units are ideal for
retrofit applications where vertical fan
coils or radiators are being replaced. Floor
standing units can be installed in hotel guest
rooms, schools, offices, dormitories, entries,
storerooms, churches or anywhere floor
standing units are desired.

Operation Airflow
Auto changeover (Sync II only) Fan speed control
Auto operation
Auto restart Filter
Child lock Washable pre-filter
Dual thermistor control
E.S.P. control Controllers
Hot start 7-day programmable controller
Self diagnostics Simple controller with mode
Sleep mode Simple controller without mode
Timer (on/off)
Wireless handheld controller
Weekly schedule
Soft dry (dehumidification)

1: Requires 7-day programmable controller

Model ARNU U2 073 CE 093 CE 123 CE 153 CE 183 CF 243 CF


Btu/h 7,500 9,600 12,300 15,400 19,100 24,200
Cooling
kW 2.2 2.8 3.6 4.5 5.6 7.1
Capacity
Btu/h 8,500 10,900 13,600 17,100 21,500 27,300
Heating
kW 2.5 3.2 4 5 6.3 8
Cooling kW 0.030 0.030 0.030 0.030 0.080 0.080
Power Input
Heating kW 0.030 0.030 0.030 0.030 0.080 0.080
Power Supply V / Hz / 208-230 / 60 / 1 208-230 / 60 / 1 208-230 / 60 / 1 208-230 / 60 / 1 208-230 / 60 / 1 208-230 / 60 / 1
inch 38.5 x 7.5 x 25.2 38.5 x 7.5 x 25.2 38.5 x 7.5 x 25.2 38.5 x 7.5 x 25.2 49.5 x 7.5 x 25.2 49.5 x 7.5 x 25.2
Dimensions(WDH) Body
mm 978 x 190 x 639 978 x 190 x 639 978 x 190 x 639 978 x 190 x 639 1,256 x 190 x 639 1,256 x 190 x 639
Weight Ibs(kg) 44.1(20) 44.1(20) 44.1(20) 44.1(20) 59.5(27) 59.5(27)
Sound Pressure (H/M/L)4 dBA 35/33/31 36/34/32 37/35/33 38/37/35 40/37/34 43/40/37
Air Flow Rate (H/M/L) cfm 300/265/229 335/300/265 371/335/300 406/353/335 565/494/424 635/565/494

Note :
1. Capacities are based on the following conditions
Cooling-Indoor temp. 80F DB / 67F WB Heating-Indoor temp. 70F DB
Outdoor temp. 95F DB Outdoor temp. 47F DB / 43F WB
Interconnecting Piping Length 25ft (7.5m) Interconnecting Piping Length 25ft (7.5m)
Level Difference of 0ft (0m) Level Difference of 0ft (0m)
2. Capacities are net capacities
3. Due to our policy of innovation some specifications may be changed without notification
4. Sound pressure levels as tested in an anechoic chamber under Korea Standard KSA0701

76
77
CONTROLS & ACCESSORIES
Unit controllers are engineered with the building occupant in mind providing a wide range of capabilities
ranging from simple on/off and mode control to full function unit controllers that will meet the level of
control and system sustainability required by even the most demanding applications.

78
Remote Controller

Simple pg. 80

Wired Remote
Controller

7-day pg. 81
Programmable

Wireless Remote
Handheld Controller pg. 81

Central Controller

Keypad pg. 84
[Simple Central Controller]

Function Controller pg. 84

Function Scheduler pg. 85

AC Smart pg. 86

Building Interoperability

Gateway pg. 88

BACnet Gateway pg. 88

ACP pg. 89

AC Manager pg. 89

79
Controls and Accessories

Use in Multi V Sync II applications, or in Multi V Mini1 or Plus II1


Sim
mplle applications where no central mode control exists. This controller
Controolle
er provides the occupant control of operating mode, fan speed, and
With
h Mod
de Seelec
ec
ctio
on temperature setpoint. The Simple Controller ships from the factory
(PQ
QRCCUC
C S0
0 C) with 30 ft. of #22 AWG, three conductor, stranded, shielded cable.

Unit operation On/Off Discharge vanes - Auto Swing/ Fixed


Temperature Control (F or C) Child lock
Cooling range (F) 64-86 Auto (or manual) addressing
Heating range (F) 60-86 Up to 2 controllers per indoor unit
Mode selection Fan only/Heat/Cool/ Control a group of up to 16 units from 1 controller
Auto/Dehumidification1 Temperature sensor location Unit/Controller/Remote Sensor
Fan speed
External static pressure control

1: First indoor unit on will determine mode (cooling/heating) for Multi V Mini and Plus II

Use in Multi V Mini1 or Plus II1 applications where mode is


Sim
mplle controlled centrally or Multi V Sync II applications where only
Controolle
er temperature setting is desired. This controller provides the
With
hout Mode e Se
ele
e ct i o n occupant control of fan, and temperature setpoint. The Simple
(PQ
QRCCFC
C S0
0 C)) controller ships from the factory with 30 ft. of #22 AWG, three
conductor, stranded, shielded cable.

Unit operation On/Off Discharge vanes - Auto Swing/ Fixed


Temperature Control (F or C) Child lock
Cooling range (F) 64-86 Auto (or manual) addressing
Heating range (F) 60-86 Up to 2 controllers per indoor unit
Fan speed Control a group of up to 16 units from 1 controller
External static pressure control Temperature sensor location Unit/Controller/Remote Sensor

1: First indoor unit on will determine mode (cooling/heating) for Multi V Mini and Plus II

80
Controls and Accessories

Use in applications where the occupant will have control of


7- Day
y indoor unit operation options or when a weekly schedule is
Pro
ogra
ammable desired. The 7-day programmable controller ships from the
Contrrolle
er factory with 30 ft. of #22 AWG, three conductor, stranded,
[Wirred Re
emo
ote
e Control
ro
ol le
e r] shielded cable.
(PQR RCUSA
A1)

Unit operation On/Off Temperature sensor location Unit/Controller/Remote Sensor


Mode selection Fan only/Heat/Cool/ Plasma electronic filter On/Off
Auto/Dehumidification1 Clean filter indicator
Fan auto control Temperature Control (F or C)
Fan speed Adjustable dead band (C) 1-7
External static pressure control2 Cooling range (F) 64-86
High ceiling control2 Heating range (F) 60-86
Discharge air direction control2 7-day programmable schedule.
Discharge vanes - Auto Swing/ Fixed2 Up to 2 non-overlapping event periods per day
Select direction(s) of air flow2 Holiday scheduling
Child lock 2-hour battery backup
Auto unit addressing Exit setting after 25 seconds (1 minute for scheduling)
Up to 2 controllers per indoor unit. Infrared receiver eye for use with
Control a group of up to 16 units from 1 controller LG wireless hand-held controllers3

1: First indoor unit on will determine mode (cooling/heating) for Multi V Mini and Plus II
2: Availability depends on indoor unit model (See indoor unit functions)
3: Required for Ducted and Floor Standing indoor unit models

The handheld controller can control any LG indoor unit equipped with
Wire
ele
esss a unit mounted infrared eye or connected to a 7-day programmable
Handhe eldd controller. Use in applications where the occupant wishes to have
Contrrolle
er complete control of the indoor unit.
(PQW
WRHD
DF0))

Adjustable dead band (C) 1-7


Unit operation On/Off
Cooling range (F) 64-86
Mode selection Fan only/Heat/Cool/
Heating range (F) 60-86
Auto/Dehumidification
Adjustable sleep timer - 1 to 7 hours
Fan speed
Timer operation ON/Off
Discharge air throw distance control1
Exit reservation mode after 30 seconds
Discharge air direction control1
Wall mounted controller cradle
Discharge vanes - Auto Swing/ Fixed1
Auto Clean (indoor unit coil dry)2
Auto unit addressing
Infrared signal operating range 15 ft., 45 off center 2
Plasma electronic filter ON/Off1
2 AAA Batteries (included)
Temperature Control (F or C)

1: Availability depends on indoor unit model (See indoor unit functions)


2: Only with ArtCool Mirror and Wall Mounted indoor units
3: Requires 7-day programmable controller for ducted and floor standing indoor unit models

81
Controls and Accessories

The remote sensor allows the designer to select the


Wall Mounted location for the space temperature sensor. Included
Temperaature wiring and connector plugs directly into the indoor unit
Senso
or printed circuit board. The remote temperature sensor is
(PQ
QRSSTA0
0) for use with ducted and ceiling cassette indoor units and
comes with 50 ft. of #22 AWG, two conductor, stranded,
shielded cable.
* Not for use with ArtCool Mirror or Wall Mounted indoor units

82
Controls and Accessories

The Dry Contact Unit provides interface flexibility to the


Dr y Con
ntact controls engineer for indoor unit operation. The Dry
Unitt Contact Unit is designed to enable or disable normal
(PQD
DSB1, PQ
QDSSBC
C) indoor unit operations or determine occupancy for
setback temperature setting through a binary input. A
binary output indicates if a system malfunction occurred.
A field supplied binary signal could be taken from a
building automation system, timer, keycard switch, door
switch, motion detector or any occupancy, or condition
sensor. The Dry Contact Unit can also be used to start/
stop other occupancy related devices such as exhaust
fans, fresh air dampers and fans, or lighting.

Model PQDSB1 PQDSBC

Input Power Source 24 VAC 5 -12V D/C

Wire Entry Side or Rear Side or Rear

Unit Operation Field Selectable - Enable/Disable Field Selectable - Enable/Disable

Auto Restart Upon Unit Enable Signal Field Selectable - Yes/No Field Selectable - Yes/No

Locked Operation At Preset Temperature Setpoint N/A Field Selectable - Enable/Disable

Fan Operation Locked at Low Speed N/A Field Selectable - Enable/Disable

Temperature Setpoint Lock N/A Field Selectable - Normal / Setback

Reset Temperature Setpoint Range (f) N/A Field Selectable - 64 - 86

Dimensions 3-1/16 x 4-1/8 x 1-3/8 3-1/16 x 4-1/8 x 1-3/8

Mounting Surface Surface

Minimum 18 AWG Minimum 18 AWG


Field Provided Interface Wiring
3 Conductor Stranded 3 Conductor Stranded

Maximum Wiring Length 984 ft. 984 ft.

* Under certain conditions or configurations, some combinations of settings may not be available

83
Controls and Accessories

The Central Controller Keypad provides centralized enable,


Centra
al disable and simple monitoring for up to 16 indoor units.
Contro
olller Up to 16 Central Controller Keypads can be linked together
Keypa
ad on a single communication bus providing control and
[Sim
mple Ce
entrral Co
ontroll
ollle r] monitoring for up to 256 indoor units. Indoor units can be
(PQ
QC SB101S0) either enabled or disabled with the push of a single button.
Multiple color LED lights indicate the current run condition
of the indoor units.

16 indoor unit push button switches - (Enable/Disable) All indoor units - (Enable/Disable)
Controller power switch/indicator - (On/Off/Error) Lockout local controllers - (Enable/Disable)

Packaged with one Central Controller Keypad, a Central


Functtio
on Function Controller provides the building owner with
Contrrolle
er the capability of modifying the operating mode, fan
(PQC
C SC10
01S0
0) speed and temperature setpoints of all indoor units,
either individually or all at the same time. The Central
Function Controller can be used with one to eight Central
Controller Keypads controlling up to 128 indoor units.

For use with up to 8 Central Controller Keypads Cooling range (F) 64-86
Control groups of up to 16 indoor units Heating range (F) 60-86
Unit operation On/Off Mode control
Temperature Control (F or C) Fan speed

84
Controls and Accessories

Packaged with one Central Controller Keypad, the


Functtio
on Central Scheduler is used in applications where
Schedduleer the building owner prefers to have the capability
(PQC
C SD13
3 0A
A0) to modify adjustable operating parameters, as
well as configure weekly operating schedules
for indoor units individually or in groups of up
to 16 indoor units at the same time. The Central
Scheduler is designed to work in conjunction
with one to eight Central Controller Keypads
controlling up to 128 indoor units.

For use with up to 8 Central Controller Keypads Fan speed


Control groups of up to 16 indoor units 7-day programmable schedule
Temperature Control (F or C) Holiday scheduling
Cooling range (F) 64-86 Up to 2 non-overlapping event periods per day
Heating range (F) 60-86 2 hour battery backup
Mode control

The wall mounted fan and operating mode selector switch


Mode e interfaces with all Multi V Mini and Plus II outdoor units. The
Sele
ectoor fan selector switch allows the user to lock the fan on or allow

Switch the fan to cycle as dictated by the system software. By default,


[Cooll / Hea
at Sele
ector
o r]]
the operating mode of the first on indoor unit determines the
(PRD
DSBM M) outdoor unit operating mode. When a mode selector switch is
installed, the switch forces the operating mode of the outdoor
unit to heating or cooling.

2 toggle switches Cover plate and switch included


Fan Operating Mode Switch Auto/On Field provided handy box required for wall mounting.
Operating Mode Switch Cooling/Heating

85
Controls and Accessories

AC Sm
ma r t
(PQC
C SW3
320A
A1E
E)

LGs most advanced central controller, the AC Smart was designed for the LG Multi
V system and can be used to enable or disable devices including traditional split
systems, rooftop air conditioners, ventilation units, fans, lights, or any other electrical
device through the optional Digital Output kit (PQNFP00T0). AC Smart controls
up to 64 devices as standard or up to 128 devices with the optional Expansion Kit
(PQCSE440U0). The AC Smart can be accessed from a remote location via ethernet.

7 in. touchscreen LCD Grouped local unit controllers Lock/Unlock


Stylus pen with storage slot Adjustable temperature range restriction
Binary system shut down input contacts Fan speed Auto/Low/Med/High/Power1
Operation On/Off Controls up to
Display - On/Off -64 devices
Display backlight - On/Off -128 devices with expansion kit (PQCSE440U0)
Customize names - zone/group/unit -16 units per group
Mode select - Auto/Cool/Dehumidification/Heat/Fan Only -64 devices per group
Setpoint control All/Group/Unit/Device -64 devices per zone
Local controller lock function - All/Mode/Temp/Fan -16 outdoor units

1: Availability depends on indoor unit model being controlled

Group Control
Group up to 64 devices by refrigerant circuit, floor, tenant, department, area, or any
desired breakdown. AC Smart controls and monitors device operating schedules, room
temperatures and other operating parameters.

Conserve Energy
AC Smart may be programmed to start and stop each device based on a customizable
365 day schedule. Local unit controller functions may be limited or locked out using
AC Smart and temperature reset schedules for unoccupied periods can be set for each
device. Energy saving control algorithms may also be set up and operated.

System Backup
The AC Smart is equipped with an onboard battery that enables continued operation
during brief power outages. A USB port is also provided to backup the AC Smart setup
and to update software.

Malfunction Notification via E-mail


When the AC Smart detects a unit malfunction, the controller has the ability to notify
the response party via email.

86
Controls and Accessories

Tabbed Navigation
- Basic Control
- Schedule
- History
- Auto Control
- System Setup

Temperature Control (F or C)
- Cooling range (F) 64-86
- Heating range (F) 60-86
- Adjustable dead band (C) 1-7

Operating Schedule Setup


- Multiple display modes
- Set by Device/Group/All
- Set Mode/Temp/Temp Range/Fan Speed/Local Controller Lock
- Set by Hour/Period/Day/Month/Year/Holiday

Indoor unit operational status - display quantity


of indoor units
- Display All/Group/Unit
- Local controller Locked/Unlocked/Other
- Operating mode - Auto/Cool/Heat
- Unit operation - On/Off/Malfunction
- Auto swing - On/Fixed Position

Device setpoint data display status


- Display device type - All/Air Conditioners/Ventilators/Other Devices
- Display device by All/Group/Unit
- Air Conditioner average temperature setpoint - All/Group/Unit
- Air Conditioner average actual temperature - All/Group/Unit

The 128 Expansion Kit doubles the control and


128 monitoring capacity of the AC Smart central
E xpan
nsiion Kit controller from 64 to 128 devices.
(PQC
C SE44
4 0U
U 0)

The Digital Output (DO) kit provides additional


Diggital binary outputs to control ancillary devices such
Outpu ut (D
DO) as lighting, exhaust fans, or ventilation dampers.
It is designed to add digital outputs used with
E xpannsio
on Kitt the ACP or AC Smart.
(PQ
QNFP00T0)

87
Controls and Accessories

Interoperability with leading brands of building automation systems is accomplished using the LonWorks or BACnet
open protocol gateways. LonWorks and BACnet gateways will allow control and monitoring of key points promoting
sustainable, energy efficient operation.

The LonWorks Gateway provides open protocol


LonWo
orkss communication between Multi V air conditioning
Gatew
way products and various building automation systems to
(PQN
NFB16
6A1)) control and monitor up to 64 connected devices. A pair of
shut down contacts is provided. The LonWorks Gateway is
certified to LonMark version 3.3.

The BACnet Gateway provides open protocol


BACnett communication between Multi V air conditioning
Gatew
way products and various brands of building automation
(PQN
NFB17
7B0)) systems to control and monitor up to 256 connected
devices. Binary inputs can be read through any of 20
digital inputs with feedback through any of 4 digital
outputs. The BACnet Gateway conforms to ANSI/
ASHRAE 135, version 1.0.

LonWorks BACnet

Indoor Unit On/Off Indoor Unit On/Off

Control Monitor Control Monitor

Indoor Unit On/Off O O O O

Operating Mode O O O O

Fan Speed O O O O

Temperature Setpoint O O O O

Locking Function O O O O

Auto Swing O O O O

Indoor Temperature O O

Error Monitoring and Code O O

88
Controls and Accessories

LG offers a less complicated yet sophisticated building management system designed for your Multi V system. The
Advanced Control Platform (ACP) controls up to 256 devices on multiple outdoor units, while the AC Manager workstation
software brings together up to 16 ACP units to control and monitor up to 4,096 devices from a central location. The ACP
is ideal for campus applications where there is no existing building management system.

The Advanced Control Platform (ACP) is available in


ACP two models capable of controlling and monitoring up
Witthoutt Diigiita
al I//O to 256 devices. Both provide building management
(PQC
CPA11
1A0
0 E) control of your Multi V system while the model with
digital inputs and outputs (I/O) allows binary control
Witth Dig
gita
al I/O
O
(PQC
CPB11A0E)
of ancillary equipment such as lighting, exhaust fans
and ventilation dampers and monitoring of lighting
or other occupancy sensors. When used with the
Power Distribution Integrator (PDI), ACP can limit air
PQCPB11A0E
conditioning unit peak electrical demand and report
outdoor unit energy consumption by indoor unit.

AC Manager is a PC workstation software suite


AC Man
na g e r designed to provide a user friendly window into up
(PQC
C S S52
2 0A
A0E
E) to 16 ACP building control unit. From the central
workstation the user can control and monitor up to
4,096 devices and utilize a number of energy saving
algorithms for sustainable building efficiency.

Remote Internet Access


The ACP panel can be set up to allow the building operator access using a web browser
from any computer on the network to perform basic control and monitoring functions.

Energy Saving Capabilities


AC Manager is designed to provide operational control of Multi V air conditioning
equipment making it easy for the building operator to design and implement custom
energy saving strategies. Combining the built in energy consumption algorithms of
Multi V with the intuitive graphical user interface of AC Manager provides the engineer
with a picture of the systems operating parameters. When used in conjunction with
the Power Distribution Integrator (PDI), the AC Manager can be set up to perform load
shedding algorithms to reduce building electrical demand.

89
Controls and Accessories

Operating History
AC Man
na g e r AC Manager provides operating event history including the date, time, air conditioner
address, operating mode, operation status, and past and current malfunction codes
(PQC
C S S52
2 0A
A0E
E)
for the connected devices. Custom reports are available for a chosen period of time,
a group of connected devices and type of data. Equipment malfunctions can be
immediately reported to the building operator providing an opportunity to respond
and repair the equipment.

Access Security
Access to AC Manager requires a USB dongle for authentication on the workstation.

Features Include

Operation On/Off Grouped local unit controllers Lock/Unlock


Display - On/Off Adjustable temperature range restriction
Customized names - zone/group/unit Fan speed Auto/Low/Med/High/Power1
Mode select - Auto/Cool/Dehumidification/Heat/ Auto Swing1
Fan Only Up to 256 indoor units per ACP
Setpoint control All/Group/Unit/Device Control of up to 16 ACP panels
Local controller lock function-All/Mode Only/ Control and monitor of up to 4,096 devices
Temp/Fan control

1: Availability depends on indoor unit model being controlled

Graphical User Interface


LG software engineers concentrated on minimizing the number of mouse clicks per
task in the development of AC Manager. Color graphic, object driven, drag-n-drop,
easy to read and understand button icons make AC Manager one of the easiest
workstation software packages to use.
Main Menu Temperature Control (F or C)
- Home - Cooling range (F) 64-86
- Basic Control - Heating range (F) 60-86
- Peak Control - Adjustable deadband (C) 1-7
- Schedule
- Manage History Device setpoint data display status
- Accumulated Power - Display device type by All/Air Conditioners/Ventilators/Other Devices
- Device Interface Control - Display device by All/Group/Unit
- Monitor - Air Conditioner average temperature setpoint All/Group/Unit
- System Setting - Air Conditioner average actual temperature All/Group/Unit

Indoor unit operational status Operating Schedule Setup


- Display quantity of indoor units - Multiple display modes
- Displayed by All/Group/Unit - Set by Device/Group/All
- Local controller - Locked/Unlocked/Other - Set Mode/Temp/Temp Range/Fan Speed/Local
- Operating mode - Auto/Cool/Heat Controller Lock
- Unit operation - On/Off/Malfunction - Set by Hour/Period/Day/Month/Year/Holiday
- Auto Swing On/Fixed Position

* AC Manager peak demand control display * AC Manager schedule display

90
Controls and Accessories

Power
Disstrib
butio
on
Integrrattor (P
PDI)
(PQN
NUD1SS01))

The Power Distribution Integrator (PDI) tracks outdoor unit energy consumption
broken down by indoor unit operation ratio. The PDI requires a field supplied
wattmeter per outdoor unit and can track the outdoor units power consumption for
up to one outdoor unit and 48 indoor units. Power consumption is displayed by indoor
unit on the two line LCD display. If the user desires to download the data to a PC or
a printed report the Power Distribution Integrator can be used with the Advanced
Control Platform (ACP) and AC Manager.

1 monitor per Multi V outdoor unit Current power usage


Up to 48 indoor units per monitor Standby (unit off) usage
Energy consumption displayed in watt-hours Custom period usage
Power consumption display modes (kWh)

91
Controls and Accessories

Capable of lowering the filter to 14 ft. below the unit, the auto elevation grill
Auto provides easy access to the filter for cleaning on high ceilings. The auto elevation grill
Ele
evatio
on Grill kit is available on 24-48 MBh 4-Way Ceiling Cassettes.

Kitt
(PTE
EGM0
0)

Note: Requires standard grill kit

Ventilation kits are available for use with 4-way ceiling cassettes to allow fresh air
Ventilattio
on Kit to be brought directly into the unit.
(PTT VK4
410 and
d PTV
VK42 0
and PTVK K430
0)

PTVK410 + PTVK4202 PTVK4303


Notes
1. It is imperative to carefully consider volume and conditions of fresh air for proper indoor unit operation.
2. The PTVK410 + PTVK420 is for use with 4-way ceiling cassettes 2448 MBh.
3. The PTVK430 is for use with 4-way ceiling casettes 718MBh.
4. TE frames do not allow ventilation collection.

Applied together or alone, the suction grill and canvas can be used with the low
Suctio
on G r i l l static bottom return ducted indoor unit. The suction grill and suction canvas match
and Canvas up to the low static bottom return ducted indoor unit without special field design.

7-15MBh 18 - 24MBh
Suction Grill PBSGB30 PBSGB40
Suction Canvas PBSC30 PBSC40

Suction Canvas

Suction Grill

92
Controls and Accessories

The optional group control cable kit is required when grouping multiple indoor units
Group
p Control with a single zone controller. Each indoor unit beyond the first will require this cable
Cable
e Kit kit for group control.
(PZZCWRCG3)

Note: Cable may be field supplied for 24-48 MBh 4-Way Ceiling Cassettes (TM, TN, TP frames)

Optional ARTCOOLTM Mirror panels are available in silver and blue.

Mirro
or Panel
Frame Silver Blue

SE 7-15MBh PSAPECV10 PSAPECB10

S8 18-24MBh PSAP8CV10 PSAP8CB10

An optional air guide is available for Multi V Plus II and Sync II outdoor units to change
Airr Guiide the discharge direction from vertical to horizontal.
(PQ
QAGA)

Headers and Y-Branches are specially designed and manufactured under tight
Headerrs and quality control for low pressure drop to ensure the Multi V system operates at peak
Y- Bran
nches performance with the longest piping runs in the industry.

93
LG Electronics Inc.
For continual product development, LG reserves the right to change specifications without notice.

Distributed by:

Supersedes: PG-MULTIV-2010-VER3; VRF-PC-BA-001-US 011JAN 21


LG Electronics, HVAC Division
11405 Old Roswell Road
Alpharetta, Georgia 30009
www.lghvac.com
www.lgusa.com

VRF-PC-BA-001-US 011B14C

Vous aimerez peut-être aussi