Vous êtes sur la page 1sur 4

Characterize interconnects with S-

parameters, Part 2
David Maliniak, Teledyne LeCroy - March 10, 2015

This is a continuation of Characterize interconnects with S-Parameters, which focuses on


fundamentals. This article digs a little deeper into what S-parameters can show us about an
interconnect; say, for example, a two-port microstrip line on a PC board. Unlike the one-port DUT in
our earlier post, this configuration gives us the opportunity to look at not only S11 (return loss or
reflected signal), but also S21 (insertion loss or transmitted signal).

Figure 1: Measuring S-parameters of a two-port interconnect.

As Figure 1 depicts, the second (or output) port in this device under test (DUT) would be connected
to a second port on our network analyzer, again using a precision 50- cable. The first network-
analyzer port, shown at left in Figure 1, provides an input signal from which we can now measure
both S11 and S21 for this DUT.S11 tells us about any impedance variations and lossiness in the
DUT. If there's a significant amount of loss, that will show up in a lessened amplitude in the
reflected waveform. As shown in Figure 1, VSWR is easily calculated from S11.With the output
port of our interconnect connected to our network analyzer, we can now measure S21. Insertion loss
is the magnitude of S21 in decibels and is the transmitted signal coming out of the far end of the
interconnect. Primarily, S21 tells us about the amount of loss in the interconnect, but it also tells us
something about impedance and reflections. Any energy that is reflected back out of the input port 1
is obviously not going to appear at the output port 2, which speaks to impedance.
Figure 2: The connection between insertion loss and return loss

Here is a useful sanity check: For a good, transparent interconnect, S11 will be a large negative
value in decibels, so we should not see much reflected energy. Meanwhile, S21 should be near or at
zero.Now that we've discussed both insertion and return loss, let's take a look at the connection
between them (see Figure 2). Generally, we're interested in the waveform that is transmitted
through to port 2 of the interconnect, but it's interesting to see how the reflected waveform affects
what is transmitted.It would seem logical to assume that the incident waveform would be equal to
the reflected waveform plus the transmitted waveform, or S11 + S21 = 1. That would hold true if
there were conservation of voltage, but there isn't. There is, however, conservation of energy, and
the energy in a wave is roughly equal to the square of the voltage. So a better approximation would
be 1 = S112 + S212 + any losses in the system. Those losses might be conductor loss, dielectric loss,
crosstalk, coupling, or radiation. If we were to assume a lossless interconnect, we would have quite a
solid relationship between the reflected and transmitted signals. Insertion loss would be S21 = 1 -
S112.
Figure 3: Insertion loss plotted against return loss in dB.

But how do you measure the amplitude of the incident wave and the reflected wave if they are on the
same port? There are a few ways. With a frequency-domain instrument, a directional coupler will
pick off the signal in only one direction. With a time-domain instrument, use a fast edge for the
incident waveform. The sampler also can discern the reflected waveform because it happens later in
time.

An important consideration: What level of reflected signal will significantly impact the transmitted
signal? The plot in Figure 3, which uses the equation at center, shows S21 in the vertical axis and
S11 in the horizontal axis. At -20 dB of return loss, the reflection is 10% of the incident
waveform's amplitude (see note below). But even with that 10% reflection, there is nearly no impact
on insertion loss. At -10 dB, some 30% of the signal energy is being reflected but with only -0.5 dB of
impact on insertion loss. So we can have a good amount of reflected energy without noticing much of
a difference in transmitted signal.

The bottom line? If you want to ensure that return loss doesn't have much effect on insertion loss,
you want to hold return loss to a maximum of -13 dB. What would -13 dB of return loss mean in
terms of an impedance discontinuity in our interconnect? If it's a 50- transmission line, we're
talking about a 12- impedance variation. So if impedance doesn't vary more than that, you won't
see much impact on insertion loss. It's a decent rule of thumb for understanding how much return
loss is too much in your interconnect.
Note: There is a healthy amount of confusion in the industry about how to interpret the dB value of
S-parameters, and we may have caused confusion by using the word "energy." S-parameters are a
ratio of amplitudes, such that in dB, you follow the formula Sxy_db = -20log (Vout/Vin), where Vout
and Vin are the voltages at ports x and y, with other ports terminated (typically at 50 ohms). So at -
20 dB, the amplitude is down by a factor of 10: Vout/Vin = 0.1. For an S11 of -10dB, the amplitude of
the reflection is down to 31.6% of the input. When determining the energy (or power) that is not
reflected, we need to do the appropriate squaring, as mentioned in the article. (S21 = sqrt(1-
S11^2). This evaluates to an S21 = 0.949, or ~0.5 dB. For more information, we recommend this
informative article by Eric Bogatin.

Originally published in the Test Happens blog.

About the Author


David Maliniak joined Teledyne LeCroy in 2012 as Technical Marketing Communications Specialist.
He worked for over 30 years in the electronics OEM B2B press, most recently as Test and
Measurement and EDA Technology Editor at Electronic Design magazine. Maliniak holds a BA in
Journalism from New York University.

Also See:

Slash SoC power consumption in the interconnect


Rule of Thumb #3 Signal speed on an interconnect
Measure Q-Factor With a VNA
How to think in dB

Vous aimerez peut-être aussi