Vous êtes sur la page 1sur 5

load flow analysis model: Slack Bus (also

Stand-alone Operation
Reference Bus, Swing Bus)

In stand-alone operation a generator is not


connected with other generators or the utility.
As an isolated unit it supplies power to all
connected load. Examples are emergency
generators, aggregates or portable diesel
generator sets.

Paralleled With The Utility


If a generator is paralleled with the utility grid
and it is considered as an infinite bus, the utility
grid will determine the generator frequency,
speed and voltage. An example is an industrial
generator used for cogeneration. In practice
Stand-alone Operation the governor and voltage such an engine generator set can not change
regulators determine frequency and voltage. the frequency, but it can slightly change the
generator terminal voltage.
Features:

more / less fuel will raise / lower the


frequency (Hz)

more / less excitation current will raise /


lower the voltage (kV)

the total load determines the generator


output power (MW, MVAr)

engine fuel control options:


isochronous speed control, droop speed
control Paralleled With Utility Operation if considered as an
infinite bus, the utility grid will determine the generator
excitation current control options: frequency, speed and voltage.
constant voltage control, droop
voltage control Features:

power management system could keep more / less fuel will raise / lower the
bus frequency and voltage constant if droop generator active power (MW)
control modes are active (else not
necessary) more / less excitation current will raise /
lower the generator reactive power (MVAr)
the utility determines the frequency more / less fuel will raise /
(Hz), speed (rpm) and voltage (kV) lower generator active power and the bus
frequency (MW, Hz)
the difference between the total plant
load and the generator output power will more / less excitation current will raise /
be imported or exported (MW, MVAr) lower the generator reactive power and the
bus voltage (MVAr, kV)
engine fuel control options: droop
speed control, base load (MW) control the total plant load determines the sum
of the power of all generators (MW, MVAr)
excitation current control options:
droop voltage control, VAR control, PF engine fuel control options: droop
control speed control

power management system could excitation current control options:


keep the imported or exported power (MW, droop voltage control
MVAR) or power factor constant
power management system keeps the
load flow analysis model: PQ bus (also bus frequency and voltage constant, while
Load Bus), PV bus (also Generator Bus) sharing the load (MW, MVAr) proportional
or cost optimised over all engine generator
sets
Island Operation
load flow analysis model: at least one
In island operation a generator is connected generator (or a fictive untility) must be slack
with other generators, but not with the utility. bus, the other generators may be PQ or PV
As an isolated system the generators supply all buses
power to the connected load. Examples are
power systems on ships, on offshore platforms Note that cross-current compensation is
or in the desert. sometimes used to share reactive power, while
maintaining the bus voltage constant. I prefer a
power management system or VAr Load Sharing
devices.

Mode Of Operation Changes


All modes of operation are possible after closing
or tripping breakers in the configuration in the
image below. During the power system
engineering, this should be taken into
Island Operation all generators together determine
frequency, speed and voltage. The total load (MW, MVAr)
consideration. I highly recommend to use
should be shared. a power management system in this
configuration.
Features:
Mode Of Operation Changes all modes are possible after
closing or tripping breakers.
Isochronous and Droop Speed Control
In the isochronous speed control mode the speed will return to the original speed setpoint after a load
has been applied or rejected. However in parallel operation this would cause instability as explained
above.

In the droop speed control mode the speed will decrease by a fixed percentage when the generator is
loaded from no-load to full load. This provides a stable working point for each load in case of parallel
operation.

Isochronous Speed Control speed and frequency Droop Speed Control speed and frequency will decrease
return to speed setpoint after a load change. when the load increases.

The droop slope is a fixed setting mostly between 3 and 5%. But the operator or power management
system can adjust the speed setpoint in order to:

return to the rated frequency in stand-alone operation

change the generator active power (MW) in parallel operation

Constant Voltage Control and Reactive Droop Compensation


In the constant voltage control mode the voltage will return to the original voltage setpoint after a load
has been applied or rejected. However in parallel operation this would cause instability as explained
above.
In the droop voltage control or reactive droop compensation mode the voltage will decrease by a fixed
percentage when the generator is loaded from no-load to full load. This provides a stable working
point for each load in case of parallel operation.

Constant Voltage Control voltage returns to the Droop Voltage Control voltage will decrease if the
voltage setpoint if reactive load changes. reactive load increases.

The droop slope is a fixed setting mostly between 2 and 4%. But the operator or power management
system could adjust the voltage setpoint in order to:

return to the rated voltage in stand-alone operation

change the generator reactive power (MVAr) in parallel operation

Vous aimerez peut-être aussi