Vous êtes sur la page 1sur 14

SUBMITTAL COVER

AND TRANSMITTAL
PRIME PROJECT # 15002 SUBMITTAL # 26 24 16.02
Proj. Title GCCISD 2015 MEP Renovations Bid Pkg 2 Date in April 28, 2015
Own/CM Goose Creek CISD Subject Panelboards for Distribution Switchgear - MCC (BJH)
Project # 15-013
A/E Proj # 03 001 0561 003 LEED

FROM SUBCONTRACTOR/SUPPLIER TO PROJECT SUBMITTAL REVIEWER 4/28/2015


Company VA Electrical Contractors, LLC. Company Estes McClure & Associates, Inc.
Contact * James Bowers Contact Will Hill
Address 3546 Loop 337 Bldg 1A Address 3608 West Way
New Braunfels TX 78130 Tyler TX 75703
Phone 281-416-5060 Mobile 281-303-6622 Phone 1-903-581-2677 Mobile 903-530-2582
Fax 1-830-302-7136 Other Fax 1-903.581.2721 Other
Email james@vaelectric.net Email whill@estesmcclure.com
Area affected: Baytown Junior High

* Please coordinate all correspondence through Prime's Project Manager, Ike Spiker:
Phone 281-999-0875 Fax 281-999-0885 Email ispiker@primecontractorsinc.com
COMMENTS
Please note this submittal is for MCC - Motor Control Centers associated with the Panelboards for Distribution Switchgear at
Baytown Junior High
ITEM DESCRIPTION QTY UNIT MANUFACTURER/SUPPLIER DUE BY APPROVAL
Bill of Materials 1 ea Siemens 05/12/15 APP
MCC - Details Drawings 1 ea Siemens 05/12/15 APP
MCC - Circuit Schedule 1 ea Siemens 05/12/15 APP
MCC - Nameplate Schedule 1 ea Siemens 05/12/15 APP
Motor Control Center Product Data 1 ea Siemens 05/12/15 APP
REVIEWER PLEASE CODE EACH ITEM: APP=Approved AAN=Approved As Noted REJ=Rejected R&R=Revise & Resubmit

DISTRIBUTED TO
Ike Spiker, Prime Contractors, Inc. Copy for record
Robert Lawson, Prime Contractors, Inc. Copy for record
GENERAL CONTRACTOR STAMP REVIEWER STAMP
REVIEWED CORRECT & RESUBMIT Received Monday, June 01, 2015
REVIEWED AS NOTED NOT APPROVED Stamped as APPROVED on date 6/1/2015
REVIEWING IS ONLY FOR GENERAL COMPLIANCE WITH THE CONTRACT Comments
DOCUMENTS. THIS DOES NOT RELIEVE THE SUBCONTRACTOR OF THE
RESPONSIBILITY FOR VERIFYING ALL DIMENSIONS, COMPLYING WITH Reviewed by Matt Hensley at EMA on 6/1/15
THE CONTRACT DOCUMENTS, OR FOR ERRORS ON AND/OR OMISSIONS REVIEWED
FROM THIS SUBMITTAL. QUANTITIES HAVE NOT BEEN CHECKED. Comment Code: A - No Exceptions

Reviewed Item - Note / Comment


26 24 16 - Panelboards - MCC5 - No Exceptions
Digitally signed by Kimberly Vopat
DN: cn=Kimberly Vopat, o=Prime Contractors Inc, ou=Project,
email=kvopat@primecontractorsinc.com, c=US
Date: 2015.06.01 11:56:59 -05'00'
By:

Monday, June 01, 2015 Page 1 of 1


SUBMITTAL COVER
AND TRANSMITTAL
PRIME PROJECT # 15002 SUBMITTAL # 26 24 16.02
Proj. Title GCCISD 2015 MEP Renovations Bid Pkg 2 Date in April 28, 2015
Own/CM Goose Creek CISD Subject Panelboards for Distribution Switchgear - MCC (BJH)
Project # 15-013
A/E Proj # 03 001 0561 003 LEED

FROM SUBCONTRACTOR/SUPPLIER TO PROJECT SUBMITTAL REVIEWER 4/28/2015


Company VA Electrical Contractors, LLC. Company Estes McClure & Associates, Inc.
Contact * James Bowers Contact Will Hill
Address 3546 Loop 337 Bldg 1A Address 3608 West Way
New Braunfels TX 78130 Tyler TX 75703
Phone 281-416-5060 Mobile 281-303-6622 Phone 1-903-581-2677 Mobile 903-530-2582
Fax 1-830-302-7136 Other Fax 1-903.581.2721 Other
Email james@vaelectric.net Email whill@estesmcclure.com
Area affected: Baytown Junior High

* Please coordinate all correspondence through Prime's Project Manager, Ike Spiker:
Phone 281-999-0875 Fax 281-999-0885 Email ispiker@primecontractorsinc.com
COMMENTS
Please note this submittal is for MCC - Motor Control Centers associated with the Panelboards for Distribution Switchgear at
Baytown Junior High
ITEM DESCRIPTION QTY UNIT MANUFACTURER/SUPPLIER DUE BY APPROVAL
Bill of Materials 1 ea Siemens 05/12/15 PND
MCC - Details Drawings 1 ea Siemens 05/12/15 PND
MCC - Circuit Schedule 1 ea Siemens 05/12/15 PND
MCC - Nameplate Schedule 1 ea Siemens 05/12/15 PND
Motor Control Center Product Data 1 ea Siemens 05/12/15 PND
REVIEWER PLEASE CODE EACH ITEM: APP=Approved AAN=Approved As Noted REJ=Rejected R&R=Revise & Resubmit

DISTRIBUTED TO
Ike Spiker, Prime Contractors, Inc. Copy for record
Robert Lawson, Prime Contractors, Inc. Copy for record
GENERAL CONTRACTOR STAMP REVIEWER STAMP
REVIEWED CORRECT & RESUBMIT
REVIEWED AS NOTED NOT APPROVED
REVIEWING IS ONLY FOR GENERAL COMPLIANCE WITH THE CONTRACT
DOCUMENTS. THIS DOES NOT RELIEVE THE SUBCONTRACTOR OF THE
RESPONSIBILITY FOR VERIFYING ALL DIMENSIONS, COMPLYING WITH
THE CONTRACT DOCUMENTS, OR FOR ERRORS ON AND/OR OMISSIONS
FROM THIS SUBMITTAL. QUANTITIES HAVE NOT BEEN CHECKED.

Digitally signed by Kimberly Vopat


DN: cn=Kimberly Vopat, o=Prime Contractors Inc, ou=Project,
email=kvopat@primecontractorsinc.com, c=US
Date: 2015.06.01 11:57:05 -05'00'
By:

Tuesday, April 28, 2015 Page 1 of 1


ELECTRICAL SUBMITTAL

SPECIFICIATION SECTION 26 24 16

PANELBOARDS FOR DISTRIBUTION SWITCHGEAR

MCC - MOTOR CONTROL CENTERS

GOOSE CREEK CONSOLIDATED


INDEPENDENT SCHOOL DISTRICT
ELECTRICAL CONTRACTOR:
VA ELECTRIC
12221 FUQUA, SUITE C
HOUSTON, TX 77034

SUPPLIER:
THE REYNOLDS COMPANY
6775 BINGLE RD
HOUSTON, TX 77092
Bill of Materials
Group: Package 2 - Baytown Junior High

1 MCC--MCC

MCC, TIASTAR, 20 (Front Only), Circuit Breaker, 480 33W Delta AC, 60 Hz, 35,000,
1 - Indoor (Std), 600, Tin, Copper, I (Std. Unit Diagrams Only), Bd (Unit control tb).

1 - SECTION
1 - Encl. 20IN D Front Only 20IN W
1 - 600A Main Lug Only.
1 - MLO 600A, Top
3 - FVNR, CB, SZ 1, 10HP.
1 - FVNR Size 1, CB 10 HP
1 - ESP200 Overload
1 - CPT 50VA 1 Sec. 2 Pri. Fuses Std. Cap.
1 - Pull-Apart Control Terminals
2 12 x 16 SPACE
1 - Prepared Space Height 12
1 - 125AF 125AT HE FCB.
1 - FCB, 125A Max, HE G Trip Amperage 125
1 - SECTION
1 - Encl. 20IN D Front Only 20IN W
1 - 250AF 175AT FD6 FCB.
1 - FCB, 225A Max, FD6 Trip Amperage 175
1 - 125AF 100AT HE FCB.
1 - FCB, 100A Max, HE G Trip Amperage 100
1 - 42 x 16 SPACE
1 - Prepared Space Height 42

whitmd000_03261501_01_00_O00 6 4/16/2015
Motor Control Centers
GENERAL BUS UNITS
1.50" ANCHOR ANCHOR
38mm DETAIL DETAIL
19.69" SERVICE 480 33W AC BRACING 42K AIC SYM MIN WITHSTAND RATINGS
500mm SYSTEM GROUNDING SOLIDLY GROUNDED CB COMBINATION 35K AIC SYM
2.75" 2.75" FREQUENCY 60 HZ BUS RATING _ CB FEEDER 35K AIC SYM
70mm 70mm AVAIL FAULT CURR 35K AIC SYM FUSIBLE COMBINATION _
1.50" 14.50" 14.50" SERVICE ENTRANCE NOT APPLICABLE HORIZONTAL BUS _ FUSIBLE FEEDER _
38mm 369mm 369mm RATING 600A (1/8 X 2)
.69" DIA. 20" 20" MCC TYPE TIASTAR MATERIAL COPPER WIRING CLASS I
18mm 508mm 508mm TEMP RATING 65 DEGREES C TYPE BD (CTRL TERM BLKS)
LABELS PLATING TIN CTRL TERM BLOCKS PULL-APART
UL WHERE APPLICABLE BARRIERS STANDARD LEXAN EXTRA UNUSED PTS _
CSA WAIVED INSULATION _ POWER TERM BLOCKS NOT APPLICABLE
3"
76mm CONTROL WIRE 16 AWG MTW
BOTTOM BOTTOM
13.69"/348mm CONDUIT CONDUIT REGIONAL CODES - VERTICAL BUS POWER WIRE STANDARD
RATING SEE SECTION DETAILS CONTROL TERMINALS _
ALTITUDE RATINGS UP TO 3000FT / 915M MATERIAL COPPER POWER TERMINALS _
PLATING TIN WIRE MARKERS _
3" 17" 17"
76mm 432mm 432mm CUST INSPECT REQD NONE STAB PLATING TIN TYPE _
1.5" 1.5"
38mm 38mm CERTIFIED TEST RPTS _ NEUTRAL BUS GENERAL OPTIONS NONE
RATING _ UNIT DIAG ON DOOR _
GENERAL NOTES _ MATERIAL _ HEATER TBLS ON DOOR _
.5" TOP TOP _ PLATING _ UNIT SIDE BARRIER _
6.25"/159mm CONDUIT CONDUIT
13mm _ LOCATION _
P6 LUGS _
_
TOP TOP
6.88"/175mm HORIZONTAL GROUND BUS NAMEPLATES
CONDUIT CONDUIT
SHOP NOTES _ RATING 300A (1/4 X 1)
.63" 17" 17" _ MATERIAL COPPER UNIT STANDARD
16mm 432mm 432mm _ PLATING UNPLATED COLOR (FACE/TEXT) BLACK/WHITE
1.5" 1.5"
_ LOCATION FRONT BOTTOM TEXT SIZE 3/16
38mm 38mm
_ LUGS (1) 6-300 KCMIL TEXT SEE NAMEPLATE INFO
LUG PAD _
ATTACHMENT STANDARD
VERTICAL GROUND BUS
RATING _ COMPONENT _
MATERIAL _
PLATING _ MASTER 2X6
MOTOR GND TERMINALS _ COLOR (FACE/TEXT) WHITE/BLACK
SEC. 01 SEC. 02 TEXT SIZE 1/2

01F C E C E
O N O N
SECTION 2X4
12"/305mm MLO 9"/229mm N T N T 9"/229mm
STRUCTURE COLOR (FACE/TEXT) WHITE/BLACK
600A D R D R
A TEXT SIZE 1/2
Y Y
01FA 02FA 4.5" 4.5" NEMA TYPE 1 TEXT SEE NAMEPLATE INFO
FVNR-1 FCB 115mm 115mm EXTERNAL _
B
10HP 175AT
C HEIGHT 91.125" / 2315MM
01FC
D FVNR-1
DEPTH 20" / 508MM FRT ONLY
10HP 02FD
E FCB
01FE 100AT PAINT GRAY ANSI 61 INCOMING

REAR

FRONT
F FVNR-1
90" 90"
10HP 02FF GENERAL OPTIONS NONE MAIN ENTRY TYPE CABLE ENTRY UNIT
2286mm 72" 2286mm
G SPACE FISH-TAPE BARRIERS _ LOCATION TOP
1829mm
01FG REMOV BOT PLATES _ SECTION 01
H SPACE BASE CHANNELS _ UNIT 01F
SEISMIC _ INCOMING CABLES (2)350 KCMIL
I TWO-PC BACKPLATE _ _ _
01FI
FUNGUS PROOFING _ - -
J SPACE
4"
K 102mm SPACE HEATERS - -
01FK 7.5" SIZE _ - -
L FCB 191mm POWER SOURCE _ - -
125AT BARRIER _ - -
COND. CO
THERMOSTAT _ - -
6"/153mm ENTRY EN - -
4" SPECIAL DIAGRAMS _ - -
1.125" SS 01 102mm 1.125"
INTERCONNECTION _
28.6mm 40" 20" 28.6mm
COMMUNICATION _ - -
1016mm 508mm
SPACE HEATER _ - -
CUSTOMER SECT. ID LIGHT/SWITCH/RECEP _ - -
DEPTH (In/mm) 20/508 20/508 VENTILATION _ - -
WIDTH (In/mm) 20/508 20/508 MISC 1 _ - -
HORIZONTAL BUS YES YES MISC 2 _ - -
VERTICAL BUS TYPE 300A FRONT 300A FRONT MISC 3 _ - -
VB BARRIERS ISOLATED ISOLATED
VB SHUTTERS - -
VB W/W ACCESS HOLES NO NO
DOUBLE DEEP BUS-THRU - -
THERMOSTAT - -
FLUORESCENT LIGHT - -
LIGHT SWITCH - -
DUPLEX RECEPTACLE - -
NEMA 3R DOOR FAN - - JOB

OPTIONS - -
OPTIONS - - Goose Creek ISD '15 MEP Renovations
OPTIONS - - P.O. CUST.
GENERAL NOTES - THE REYNOLDS COMPANY
GENERAL NOTES CONTR CONSLT
GENERAL NOTES VA ELECTRICAL CONTRACTORS NOT KNOWN
SHOP NOTES MN MN TIE BY ENG. LOC. DESIGNATION
SHOP NOTES - whitmd
SHOP NOTES S.O. DATE - MCC
SHOP NOTES - 2-12-2015
N1 APP. MFG. LOC. DWG. NO.

N2
-
N3 1 0 carddx 2-12-2015 whitmd000_03261501_01_00_O00-22000-1
APP. DWG. FILE
N4 Siemens Industry, Inc. REV.

NO. REVISIONS DRAWN DATE SHEET OF


BY: Alpharetta, Georgia 1 3 1
UNIT SCHEDULE
UNIT NO UNIT DESCRIPTION MOTOR DATA CIRCUIT BREAKER/DISCONNECT SWITCH OVERLOAD WIRING CONTROL CIRCUIT TOT AUX PILOT FACTORY USE ONLY
CUST SII L/R TYPE SUB HT SZ HP/ KW FLA SF RPM FRAME or DS TRIP or CLIP RNG or FUSE TYPE RNG/HTR DIAGRAM TY FU VOLT CPT NO NC DEVICES UNIT OPTIONS N UNIT NOTES NOTES PUCX
_ 01F - MLO - 12 600 - _ - - - - - - - - - - - _ - - - - _ _ _ _ _ _ _ FMNR
_ 01FA - FVNR - 12 1 10 HP 14.0 - - ETI 125 40 - 115-375 - ES200 5.5-22 D68601009 UT 2/1 120 50 1 0 _ _ _ _ _ UMNM
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - E2 - -
_ 01FC - FVNR - 12 1 10 HP 14.0 - - ETI 125 40 - 115-375 - ES200 5.5-22 D68601009 UT 2/1 120 50 1 0 _ _ _ _ _ UMNM
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - E2 - -
_ 01FE - FVNR - 12 1 10 HP 14.0 - - ETI 125 40 - 115-375 - ES200 5.5-22 D68601009 UT 2/1 120 50 1 0 _ _ _ _ _ UMNM
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - E2 - -
_ 01FG - SPACE - 12 - - - - - - - - - - - - - - _ - - - - _ _ _ _ _ _ _ FMNL
_ 01FI - SPACE - 12 - - - - - - - - - - - - - - _ - - - - _ _ _ _ _ _ _ FMNL
_ 01FK - FCB - 12 - - - - - - HEG 125 125 - - - - - D68500FDR - - - - _ _ _ _ _ _ _ UMNM
_ 02FA - FCB - 18 - - - - - - FD6 250 175 - - - - - D68500FDR - - - - _ _ _ _ _ _ _ UMNM
_ 02FD - FCB - 12 - - - - - - HEG 125 100 - - - - - D68500FDR - - - - _ _ _ _ _ _ _ UMNM
_ 02FF - SPACE - 42 - - - - - - - - - - - - - - _ - - _ - _ _ _ _ _ _ _ FMNL

JOB

Goose Creek ISD '15 MEP Renovations


P.O. CUST.
- THE REYNOLDS COMPANY
CONTR CONSLT
VA ELECTRICAL CONTRACTORS NOT KNOWN
TIE BY ENG. LOC. DESIGNATION

- whitmd
S.O. DATE - MCC
- 2-12-2015
APP. MFG. LOC. DWG. NO.

-
whitmd000_03261501_01_00_O00-22000-2
APP. DWG. FILE
Siemens Industry, Inc. REV.

SHEET 2 OF 3 1
Alpharetta, Georgia
ABBREVIATIONS NOTES

UT - UNIT TRANSFORMER PROVIDES CONTROL POWER; X/Y SHOWS PRIMARY/SECONDARY P6 - THIS MCC IS PROVIDED WITH A BOTTOM MOUNTED GROUND BUS. BOTTOM CONDUIT
FUSES. SPACE IS RESTRICTED; SEE DRAWING D79641 FIGURE 1.
E2 - HIGH EFFICIENCY MOTOR APPLICATION.
ES200 - ESP200 SOLID STATE OVERLOAD RELAY.

JOB

Goose Creek ISD '15 MEP Renovations


P.O. CUST.
- THE REYNOLDS COMPANY
CONTR CONSLT
VA ELECTRICAL CONTRACTORS NOT KNOWN
TIE BY ENG. LOC. DESIGNATION

- whitmd
S.O. DATE - MCC
- 2-12-2015
APP. MFG. LOC. DWG. NO.

-
whitmd000_03261501_01_00_O00-22000-3
APP. DWG. FILE
Siemens Industry, Inc. REV.

SHEET 3 OF 3 1
Alpharetta, Georgia
Introduction

Technical Specifications Summary tiastar MCC


Bus and Electrical Ratings
Horizontal Bus Ratings 600A, 800A, 1200A, 1600A, 2000A,
2500A1

Horizontal Bus Material Copper with tin or silver plating,


or Aluminum2 with tin plating

Vertical Bus Ratings 300A, 600A, 800A

Vertical Bus Options Isolated (standard)


Insulated and isolated (optional)
Auto Shutters (optional)

Bus Bracing 42K AIC, 65K AIC, 100K AIC

Max MCC Voltage Rating 600 V

Enclosure
Enclosure Type NEMA 1 (standard), NEMA 1A,
NEMA 2, NEMA 12,
NEMA 3R (non walk-in)

High Density 6 Units Option Available

VFD, RVSS Units Available

Back-to-Back Option Available

Dimensions
Section Depth 15, 20 , 21 (back-to-back),
31 (double deep), 41 (double deep)

Section Width 20, 24, 30, 40, 50, 60

1
NEMA 1 only
2
for 600-1200A, 65KA, 65C

5
Introduction Standard MCC

Product Features & Benefits


Siemens tiastar Motor Control Centers (MCC) are composed of a number of vertical
sections bolted together which allows for future addition of MCC vertical sections in case
the customer requires expansion.

Benefits Feature

Entire horizontal bus


Easy accessibility assembly is in top
for faster 12 of the vertical section
maintenance

Easy visual
Clear Lexan horizontal
inspection of wireway barrier
horizontal bus

Ease of installation Plug-in units with


and movement of integrated
plug-in units racking handles

6
Introduction

Benefits Feature

Prevents arcing
Isolated and insulated
faults from bus assembly (Optional)
propagating

Improved service Dual location pilot


access to save time device panel

Clearly indicates
Industrys best unit
equipment status operating handle
(ON, TRIP, OFF)

Vous aimerez peut-être aussi