INSTRUMENT DESIGN BASIS

CLIENT: -- SHEET NO 1 OF 34

INSTRUMENT DESIGN BASIS

REVISION NO.
ISSUED FOR
PREPD. BY/DATE
CHKD. BY/DATE
APPD. BY/DATE
C930034 R3 Comp. Ref. 139635188.doc
SPECIFICATION NUMBER
REVISION RECORD SHEET XXXX/515/01
Aker Kvaerner Powergas
DESCRIPTION: INSTRUMENT DESIGN BASIS SHEET NO 2 OF 34
PROJECT: -- CLIENT: -- JOB NUMBER: --

D DETAILS OF REVISION REV NO

REVISION NO.
PREPD. BY/DATE
CHKD. BY/DATE

C930033 R3
SPECIFICATION NUMBER

INSTRUMENT DESIGN BASIS


REV : 02

CLIENT: -- SHEET NO 3 OF 34

CONTENTS PAGE NO.


1 General 5
1.1 Scope 5
1.2 Units of Measurement 5
1.3 Codes and Standards 5
1.4 Environment Data 5
1.5 P & ID Diagrams 5
2 Design Philosophy 5
2.1 Materials of Construction 5
2.2 Pressure and Temperature rating 6
2.3 Hazardous Area Requirement 6
2.4 Accessibility 6
2.5 Analogue Signals 6
2.6 Digital Signals 7
2.7 Motor Control Signals 7
2.8 Frequency Signals 8
2.9 Pneumatic Control Signals 8
3 Flow Instruments 8
3.1 Mass Flow Meters 8
3.2 Vortex Meters 8
3.3 Variable Area Meters 8
3.4 Magnetic Type Flow Meters 9
3.5 Orifice Plates 9
3.6 Positive Displacement Meters 10
3.7 Inferential Meter 10
3.8 Venture Tubes and Flow Nozzle 10
4 Temperature Instruments 10
4.1 Temperature Elements 10
4.2 Transmitters 10
4.3 Protecting Thermowells 11
4.4 Local Temperature Indicators 11
5 Pressure Instrument 11
5.1 Pressure Transmitters 11
5.2 Pressure Switches 12
5.3 Pressure Gauges 12
5.4 Chemical Seals 13
5.5 Instrument Manifolds 13
6 Level Instruments 13
6.1 Level Transmitters 13
6.2 Level Switches 13
6.3 Level Gauges 14
7 Analysis Instruments 14
7.1 Gas Detection 14
7.2 Fire Detection 14
7.3 PH and Conductivity 15
SPECIFICATION NUMBER

INSTRUMENT DESIGN BASIS


REV : 02

CLIENT: -- SHEET NO 4 OF 34
SPECIFICATION NUMBER

INSTRUMENT DESIGN BASIS


REV : 02

CLIENT: -- SHEET NO 5 OF 34

8 Weighing System 15
9 Valves 15
9.1 Control Valves 15
9.2 On Off Actuated Valves 17
9.3 Actuators 17
9.4 Solenoid Valves 17
9.5 Valve Switch Boxes 17
9.6 Self-Operated Regulating Valves 17
1 Safety and Relief Systems 18
0
10.1 General 18
10.2 Safety Relief Valves 18
10.3 Rupture Disc 18
1 Desuperheater 19
1
1 Control System 19
2
1 Emergency Shutdown System wherever 22
3 required
13.1 Hardwired Relay Logic 22
13.2 Programmable Logic Controllers for 22
ESD
1 Control Room 23
4
1 Utility Supplies 24
5
15.1 Instrument Power Supplies 24
15.2 Instrument Air Supplies 24
1 Instrument Connection 25
6
16.1 Standard Connections 25
16.2 Instrument Process Piping 25
16.3 Instrument Air Tubing 25
1 Instrument Cable and Wiring 25
7
17.1 Cable 25
17.2 Junction Boxes (Field) 26
1 Segregation and Installation 26
8
1 Earthing 27
9
2 Package Equipment 28
0
2 Documentation 28
1
2 Testing and Inspection 28
2
2 Installation 28
3
SPECIFICATION NUMBER

INSTRUMENT DESIGN BASIS


REV : 02

CLIENT: -- SHEET NO 6 OF 34

APPENDIX A 29
APPENDIX B 30
APPENDIX C 31
APPENDIX D 32
SPECIFICATION NUMBER

INSTRUMENT DESIGN BASIS


REV : 02

CLIENT: -- SHEET NO 7 OF 34

1. GENERAL
1.1. Scope
This document defines the basic requirements for the engineering and design of the
instrumentation. The purpose of this specification is to ensure a standard approach is
maintained to the engineering and design of instrumentation and equipment and that it
complies with all relevant national and international standards.
1.2. Units of Measurement
Units shall be in accordance with the list given in Appendix - A.
1.3. Code and Standards
All instrumentation shall comply with the latest version of codes and standards as given in
Appendix - D.
1.4. Environmental Data
1.4.1. Environmental Conditions - Refer Appendix - C
Instruments and equipment shall be consistent with the environmental impact
statement, with particular emphasis to the following:
Noise within 20 meters of the battery limit must not exceed 45dBA.

Fugitive process emissions must be minimized e.g.) from control valve


glands and analyser vents.
1.4.2. Field instrumentation shall have a minimum ingress protection of IP65 in
accordance with IS 2147/IEC 529. In case of instruments in hazardous area, the
intrinsically safe, explosion proof/flameproof instruments shall be certified to
specific hazardous area class by statutory body such as ATEX, PTB etc. Purging
shall not be used unless specifically called for.
1.5. Instrument Connections on Vessel Refer Appendix - B
1.6. P&I Diagrams
P&I Diagrams shall identify all instrumentation in accordance with symbols shown on the
P&I Legend Sheets.
2. DESIGN PHILOSOPHY
2.1. Materials of Construction
Materials of construction for instrument equipment shall be consistent with corrosion
resistance and the pressure and temperature conditions of the process fluids involved.
Generally the parts in contact with the process fluid shall be of a material equal to or better
than that used for the related vessel or line. Where instrument design prohibits the use of
these materials, or where a suitable material cannot be reasonably procured, the
instruments shall be isolated from the process by means of a chemical seal which shall be
identified on P&ID.
The following materials shall not be used in contact with the product:
SPECIFICATION NUMBER

INSTRUMENT DESIGN BASIS


REV : 02

CLIENT: -- SHEET NO 8 OF 34

Aluminum
Zinc
Asbestos
Brass, Bronze, Copper
Heavy metals including Mercury, Antimony and Cadmium.
Plastics containing free Phenol, formaldehyde or plasticizers.
2.2. Pressure & temperature rating
Pressure and temperature rating of instruments and components shall conform to the
design rating of the process system to which they are connected. Instruments which can
be exposed to vacuum shall have under-range protection to full vacuum.
2.3. Hazardous area requirement
2.3.1. Classification of Hazardous Areas shall be as indicated elsewhere.
2.3.2. All instrumentation located or partially located in the hazardous area shall be
suitable for classified hazardous area.
2.3.3. The preferred method of protection is by Intrinsically safe (EExia) circuits using
galvanic isolated safety barriers. Alternate methods of protection, are subject to
approval by client/consultant.
Flameproof (EExd)
Pressurised enclosures (EExp)
Increased safety (EExe)
2.3.4. ATEX/PTB approved certification shall be supplied for all electrical / electronic
equipment in the hazardous area. The use of other recognised approval authorities
shall be subject to approval by the Engineer.
2.4. Accessibility
All instruments shall be accessible from grade or platform for measurement .In case of gas
service where instruments are mounted above the taps, the installation of platform shall be
considered, if accessibility is not available. Ladder shall be provided for all such platform.
This should be properly co-ordinated with the piping group.
2.5. Analogue signals
2.5.1. Transmitters shall be two-wire conventional/smart 4-20 mA dc powered, from the
control system.
2.5.2. In case of Smart transmitters, the minimum requirement shall be as follows.
2.5.2.1. Communication Protocol shall be HART(Latest Version) and shall
be suitable for HART Maintenance System.
SPECIFICATION NUMBER

INSTRUMENT DESIGN BASIS


REV : 02

CLIENT: -- SHEET NO 9 OF 34

2.5.2.2. Accuracy of transmitters shall be +0.1% or range or better for a


rangeability of 1:15. The accuracy includes the combined effect of
linearity, hysterisis and repeatability.
2.5.2.3. Hand held configuration shall be provided for remote calibration,
remote configuration and diagnostics. It shall be possible to connect the
configurator in the main control room or junction box located in field.
2.5.2.4. Smart transmitters shall be microprocessor based and shall
incorporate non-volatile RAM, which shall store configurational data of
transmittal.
2.5.3. Retrofit type Smart Model shall not be accepted.
2.5.4. Where two wire transmitters can not be sourced transmitters shall be powered
externally by 24Vdc (preferred) or 230/100 VAC.
2.5.5. Transmitters shall be supplied with integral output meter (LCD type).
2.5.6. The range of a transmitter shall be specified such that its normal operating point is
within the middle third of the calibrated range.
2.5.7. Transmitter accuracy, repeatability and rangeability shall be suitable for their
intended use.
2.5.8. Control valve positioners shall be either with integral E/P converters or pneumatic
positioner with I/P converter powered from the control system.
2.6. Digital signals
2.6.1. Process switches shall be SPDT with noble metal contacts, wired normally closed
for the safe condition, with contacts opening in the Alarm State.
2.6.2. Digital signals shall be powered from the control system.
2.6.3. Position switches shall be inductive two-wire proximity type or mechanical
contacts as defined elsewhere.
2.6.4. Outputs to solenoid valves shall be 24Vdc or 110V AC from the control system. In
case of 24V DC Voltage level the solenoid valve shall be necessarily I.S. type.
2.7. Motor control signals
2.7.1. Remote control of motors shall typically comprise of the following:
START / STOP control output
Drive RUNNING control input
Drive REMOTE/LOCAL SELECTOR SWITCH control input
SPEED SET POINT control output to VFD (where appropriate)
The interface between Motor Control Centre located in substation and the control
system shall be indicated in Motor Control Philosophy document which shall be
separately issued to Electrical department.
SPECIFICATION NUMBER

INSTRUMENT DESIGN BASIS


REV : 02

CLIENT: -- SHEET NO 10 OF 34

2.8. Frequency signals


2.8.1. Frequency signals may be utilized for flow totalisation, or rotating equipment shaft
speed monitoring by proximity sensor.
2.9. Pneumatic control signals
2.9.1. Pneumatic control and transmission signals shall be 0.2 to 1 KG/CM2 G.
3. FLOW INSTRUMENTS
3.1. Mass flow meters
3.1.1. Coriolis flow meters shall be used for product critical flow measurement, as they
measure accurately the mass flow of fluids with varying density over a wide
rangeability and with minimum pressure loss.
3.1.2. In case of line size less than 2 and the accuracy is not main criterion straight tube
meters may be used. However in case of food / pharmaciteucal applications
straight tube may be preferred considering the contamination and cleaning
requirement.
3.1.3. In case of bent Coriolis U tubes, it shall be supported in accordance with the
manufacturers instructions to prevent piping vibration affecting the instrument. The
meter must be orientated in the pipe work to allow for self-draining. The preferred
method of installation is, vertical with flow upwards.
3.2. Vortex meters
3.2.1. Vortex shedding flow meters shall be used for general process / utility service, and
are preferred to differential pressure devices such as orifice plate.
3.2.2. This meter type may be installed either horizontally or vertically. The straight run
requirement shall be in accordance with the piping geometry.
3.3. Variable Area meters
3.3.1. Variable area meters may also be considered for clean process / utility service
and are particularly suited for Nitrogen purging applications.
3.3.2. The Meter design shall be preferably of metal tube type. The flow regulation
wherever required shall be provided by means of an integral throttle valve.
3.3.3. Installation shall be vertical with flow upwards.
3.3.4. Meters may be supplied for local indication, remote transmission of measured
variable, or a flow switch output as appropriate.
SPECIFICATION NUMBER

INSTRUMENT DESIGN BASIS


REV : 02

CLIENT: -- SHEET NO 11 OF 34

3.3.5. The use of glass VA meters shall be for non critical application
3.4. Magnetic type flow meters
3.4.1. Magnetic flow meters may be used for general process / utility service and have the
advantage of an unobtrusive crevice free installation. This meter type can only be
used on conductive liquids and is therefore not suitable for high purity water and
solvent applications. Typical applications include metering of water, caustic and
acid.
3.4.2. The meter liner material shall be suitable for the process media and design
conditions including full vacuum rating where appropriate.
3.4.3. Installation shall be at the lowest point in the pipe work to ensure the meter is
always liquid filled.
3.5. Orifice Plates
3.5.1. Orifice plates may be considered for general process and utility service where the
above methods are commercially prohibitive.
3.5.2. Orifice plates shall be sharp edged concentric type designed in accordance with
ISO5167. The orifice flanges shall be designed in accordance with ANSI B 16.36.
3.5.3. Flange taps shall be used for line sizes 50mm through to and including 200mm. For
line sizes above 250mm D and D/2 tapping will be used.
3.5.4. For line sizes less than 50mm specially calibrated orifice metering section or
Integral orifice assembly shall be used.
3.5.5. Plate material shall be stainless steel or superior material as required by process
conditions. Plate thickness shall be relative to pipe diameter and line pressure but
not less than 3 mm.
3.5.6. In general, orifice plates shall be sized using 2500mm WG differential pressure for
full scale transmitted range. Other permitted differential pressure ranges are 5000,
3750, 1250, 750 and 500 mm WG.
3.5.7. The ratio of the orifice bore to inside pipe diameter (d/D) shall be between the
limits 0.25 to 0.7.
3.5.8. Segmental orifice plates shall be used for liquids containing solids. Quarter circle
or conical entrance plates shall be used for viscous liquids.
3.5.9. Flow straightening vanes may be considered upstream of an orifice plate for flow
meter installations in large size pipes when it would be both inconvenient and
expensive to provide the "required straight run".
3.5.10. Annubar, pitot tubes may be used for flow measurement on large diameter pipe /
duct work, or where only a small pressure drop is allowed.
SPECIFICATION NUMBER

INSTRUMENT DESIGN BASIS


REV : 02

CLIENT: -- SHEET NO 12 OF 34

3.6. Positive displacement meters


3.6.1. For simple local batching application, positive displacement flow meters may be
used.
3.6.2. This meter is suitable for clean liquids free from entrained vapours and provides a
high accuracy output, including low flow and viscous applications.
3.6.3. Installation shall be arranged to ensure continuous flooding of the meter. A strainer
and drain shall be provided upstream of the meter.
3.7. Inferential Meter
3.7.1. The use of inferential meters such as turbine meters and semi-positive displacement
meters may be used as alternative to positive displacement meter.
3.8. Venturi Tubes and flow nozzle
Venturi tube and flow nozzle shall be sized as per ISO 5167. Flow nozzle material shall be
minimum SS-316. Spool piece shall be provided at the flow nozzle outlet for maintenance
purpose.
4. TEMPERATURE INSTRUMENTS
4.1. Temperature elements
4.1.1. The preferred method of temperature measurement for temperature up to 600 0C is
by Resistance Thermometer Detectors (RTDs) Resistance thermometers shall be
duplex 3-wire type, Platinum 100 ohm at 0 C complying with IEC-751.

4.1.2. Temperature measurement greater than 600 C shall be made using Nickel-Chrome
/ Nickel-Aluminum, type K thermocouples. Cryogenic temperature measurements
shall be made using Copper-Copper / Nickel / Aluminum, type T thermocouples.
4.1.3. Thermocouple shall be supplied in accordance with IEC-584. Appropriate
extension and compensating cable shall be used.
4.1.4. Thermistor elements are not permitted except for motor winding thermal
protection.
4.1.5. Temperature elements shall be supplied complete with thermowell, extension, head
and integrally mounted transmitter as a complete assembly.
4.2. Transmitters
4.2.1. Transmitters should be conventional/smart, range configurable type transmitting a
linearised 4 to 20 mA .
4.2.2. Where it is not practical to mount the transmitter within the sensor head due to
layout or environmental constraints, the transmitter shall be mounted within a local
enclosure and wired to the element with compensating cable, where appropriate.
4.2.3. In the event of temperature element failure, transmitters shall be arranged to drive
towards the alarm condition or safe control condition where one exists, or
otherwise upscale.
SPECIFICATION NUMBER

INSTRUMENT DESIGN BASIS


REV : 02

CLIENT: -- SHEET NO 13 OF 34

4.3. Protecting Thermowells


4.3.1. All temperature sensing devices shall be installed in protecting thermowells. The
thermowell material shall be minimum 316SS for temperature up to 600 0C and
Inconel above it.
4.3.2. Thermowells shall be flanged according to equipment and pipe specifications. The
flange size shall be 40 mm (1.1/2 inch) with rating and facing according to the line
classification.
4.3.3. Thermowells in high velocity service mounted on pipeline shall be assessed for
vibration resonance effect as per ASME PTC 19.3
4.3.4. For line sizes less than 80 mm (3 inch), the line size shall be increased to 80 mm for
the insertion of thermowells. For line sizes 150 and above the thermowell length
shall be selected to ensure the measurement element is within the middle third of
the pipe. Standard lengths of thermowell shall be used where possible, these are
225 mm, 275 mm, 325 mm, 350 mm, 375 mm, 400mm, 450 mm &500 mm.
4.3.5. Temperature elements on HVAC ductwork may be installed without thermowells.
Connection shall be by proprietary ductwork mounting brackets.
4.4. Local temperature indicators
4.4.1. Local temperature indicators shall be rigid stem bimetallic dial thermometer type
supplied complete with protective thermowells.
4.4.2. Dial size shall be 100 mm nominal and instruments shall be heavy duty `every
angle' head type. Temperature scales shall be direct reading and comply with
manufacturer's standard ranges. The case and stem shall be in stainless steel.
4.4.3. Scales shall be selected to cover the range requirements for both normal and design
conditions of plant operation. Filled system temperature indicators with capillary
connected bulb may be used where reading remote from measurement points is
required. Mercury filled systems must not be used.
5. PRESSURE INSTRUMENTS
5.1. Pressure transmitters
5.1.1. Pressure transmitters shall be referenced to atmospheric pressure.
5.1.2. Transmitters should be smart type, with independent adjustment of zero and span
at the instrument and from a remote location. Accuracy shall be +/-0.1% of the
calibrated span.
5.1.3. Materials of construction shall be suitable for the process media and based upon
the piping specification. In general pressure transmitters should have carbon steel
bodies and 316L stainless steel diaphragms as a minimum. For corrosive service
suitable materials and chemical seals shall be selected.
5.1.4. Scales shall be selected to cover the range requirements for both start-up, normal
and design conditions of plant operation.
5.2. Pressure switches
SPECIFICATION NUMBER

INSTRUMENT DESIGN BASIS


REV : 02

CLIENT: -- SHEET NO 14 OF 34

5.2.1. Generally analogue devices are preferred as the measurement loop is continuously
monitored for fault conditions. Where a pressure switch is selected its set point and
associated switch differential shall be clearly specified.
5.2.2. Pressure switches connected to the process shall have as a minimum, stainless steel
measuring elements.
5.2.3. Diaphragm elements are preferred for low-pressure applications but must provide
adequate containment of process media.
5.3. Pressure gauges
5.3.1. Pressure gauge accuracy shall be + 1.0% of full range.
5.3.2. Dial size shall be 100 mm and cases shall be stainless steel screw on or bayonet
bezel type. Blowout disc protection shall be provided and gauges shall be
orientated such that they vent safely.
5.3.3. Gauge windows shall be constructed from safety pattern / toughened glass.
5.3.4. Gauges shall be normally Bourdon tube type. Bellows or diaphragm-actuated
gauges shall be used for lower pressure ranges.
5.3.5. Bourdon tube material shall be type 316 stainless steel, as a minimum, with
stainless steel movement, except where process conditions require more stringent
materials.
5.3.6. Over-range protection shall be 1.3 times the maximum scale range. Where a gauge
is subject a greater pressure, a gauge protector shall be used.
5.3.7. On pulsating service a damper shall be fitted in the input connection.
5.3.8. For vibrating service gauge dials shall be glycerin filled.
5.3.9. Siphons shall be fitted to pressure gauges on steam or hot condensable gas
services.
SPECIFICATION NUMBER

INSTRUMENT DESIGN BASIS


REV : 02

CLIENT: -- SHEET NO 15 OF 34

5.3.10. A gauge valve shall be provided for isolation and calibration purposes. A primary
isolation valve shall be provided where appropriate.(To be debated)
5.3.11. To facilitate pressure gauge removal and alignment, gauges shall be connected to
the piping by means of a gauge adapter and not directly into valves.
5.3.12. Connections shall be 1/2" NPTM/BSPT (to be debated)
5.4. Chemical seals
5.4.1. Chemical seals shall be provided as required for highly viscous, corrosive, slurry,
and toxic applications. Gauges fitted with chemical seals shall be flanged in
accordance with the piping specification.
5.4.2. Fill fluids shall be suitable for the maximum process operating temperature.
5.4.3. Capillary tubes shall be armoured stainless steel and installed such that they are
continuously supported. Tube length shall be minimised to suit each installation.
5.5. Instrument Manifolds
5.5.1. 2-valve manifolds shall be used for secondary isolation, venting and calibration of
pressure instruments.
5.5.2. 3-valve manifolds shall be used for secondary isolation, venting and calibration of
differential pressure instruments.
6. LEVEL INSTRUMENTS
6.1.
Level Transmitters
6.1.1. Generally Chemical seal flush diaphragm type Differential pressure instrument
shall be used for the process Equipment.
6.1.2. Float and Tape/Board type or Ultrasonic type Instrument shall be used for large
liquid storage tanks
6.1.3. Displacer type level instruments, where used, shall be external type with side /
side connections and rotatable transmitter head. Vent and drain valves shall be
provided.
6.1.4. Nucleonic level, density or interface detection is not envisaged.
6.2.
Level Switches
6.2.1. For Liquid application, Float/Displacer type level switches shall be used, either
external cage / internal.
6.2.2. For Solids application the Level switches vibrating turning fork or capacitance
type or paddle type. Switch material shall be suitable for the fluid under use.
SPECIFICATION NUMBER

INSTRUMENT DESIGN BASIS


REV : 02

CLIENT: -- SHEET NO 16 OF 34

6.2.3. Level switch connections shall be flanged in accordance with the piping / vessel
trim specification. Nozzle connections for lined vessels and pipe work shall be
suitably sized for switch insertion
6.3. Level gauges
6.3.1. Reflex type gauge glass shall be used on all services except the following, where
transparent type shall be used
i) Interface between two liquid
ii) Liquids containing sediments or solids
iii) Liquids requiring protective shields.
6.3.2. Transparent type
Transparent type gauge glass shall be with integral illuminators.
6.3.3. The visible portion of gauge glass shall cover the range of any associated level
instrument. When two or more columns are required to cover a large range, the
visible portion of glass shall overlap atleast 50mm.
7. ANALYSIS INSTRUMENTS
These items are considered to be of specialised design and may differ widely in type depending on
the sample to be analysed. The vendors standard analysers shall be selected. Special attention
shall be given to the analyser sample conditioning systems. Detailed equipment specifications shall
be produced for all process analysers.
7.1. Gas detection
7.1.1. Flammable gas detectors shall be provided within the process plant. Sensor
calibration shall be in %LEL.
7.1.2. Toxic gas detectors shall be provided in high containment areas. Sensor calibration
shall be in ppm.
7.1.3. Sensor locations shall be determined by process, but typical locations are:
At room high / low points.
At agitator / pump seals and points of potential escape.
Within HVAC extract ductwork.
7.1.4. A local means of visual and audible alarm shall be provided.
7.2. Fire Detection
7.2.1. The plant areas should be divided into fire zone. The fire system shall be
microprocessor based addressable type.
7.2.2. The fire detection shall be carried out using fire detectors, smoke detectors,
manual call points.
7.2.3. The detector location shall be as per fire and gas system location plan.
SPECIFICATION NUMBER

INSTRUMENT DESIGN BASIS


REV : 02

CLIENT: -- SHEET NO 17 OF 34

7.2.4. The fire panel shall comprise components for the reception, indication, control and
relay signals originating from various fire detector or call points connected to it,
for activation of fire alarm sounders and Visual alarms.
7.2.5. In event of fire and gas incident with in the process area or building, the fire panel
shall initiate audible and visual alarms. Audible alarms through fire sounders and
visual alarms through beacons and all control action as per cause and effect chart.
7.3. pH and Conductivity
7.3.1. Sensors shall be insertion in line or flow through chamber type. A by-pass loop
shall be provided to allow isolation, de-pressurisation, and calibration of the
electrode system.
7.3.2. Electrodes and sealing assemblies must be designed to withstand the process
conditions, including pressure, temperature and dynamic forces as well as being
resistant to chemical attack.
7.3.3. Electrodes shall be temperature compensated and supplied complete with buffer
reference solution.
8. WEIGHING SYSTEM
8.1. Weighing systems shall be designed in conjunction with process, vessel, piping and civil
Engineers and in accordance with the manufacturer recommendations. Erroneous effects from the
following shall be minimised:
Side loads
Temperature effects
Pressure loads
Inadequate support / rigidity of civil structure.
Thermal expansion
Piping resilience
Vibration, liquid inflow / outflow effects
8.2. Load cells shall be generally shear beam type of stainless steel construction. Installation should
be of three or four load cell configuration, depending on the application.
8.3. The weigh equipment manufacturer shall supply as a minimum requirement load cells, dummy
cells, supports, tie rods, cable, summation box, zenner barriers, (if required) signal conditioning
electronics and all equipment for system calibration.
9. VALVES
9.1. Control valves
9.1.1. Control valves shall normally be pneumatic diaphragms or piston actuated
eccentric disc type with valve characteristics to suit the control application
requirements. Eccentric disc valves shall be wafer type for mounting between
process flanges.
SPECIFICATION NUMBER

INSTRUMENT DESIGN BASIS


REV : 02

CLIENT: -- SHEET NO 18 OF 34

9.1.2. Butterfly valves shall normally be used for larger line sizes, or where a small
pressure drop is available. Butterfly valves shall operate over 60 angular opening
unless the valve design provides a full 90 characteristic capability. Rotary valves
shall be wafer type suitable for mounting between pipeline flanges.
9.1.3. Control valves shall be supplied equipped and piped with air filter regulator,
electro pneumatic positioner, solenoid valve, proximity sensor, volume booster,
etc., as required.
9.1.4. Lined control valves shall generally be used for corrosive applications, however
where flashing or cavitation is likely to occur exotic materials shall be considered.
9.1.5. Plug type valves may be used in crystalline and slurry services.
9.1.6. The minimum size control valve shall be 25mm. Where the pipe size is less than
25mm the pipe size shall be increased locally to accommodate the valve.
9.1.7. Control valves glands on lethal toxic or hydrogen service shall be specified with
special consideration given to gland sealing such as providing bellow seals.
9.1.8. Trim material shall be stainless steel minimum for normal applications. Hardened
trim material or facing will be furnished on steam, high pressure, high temperature,
or erosive service as the application prescribes.
9.1.9. Leakage rate of the valves shall normally be Class IV Where tight shut-off is
required, Class VI shall be specified.
9.1.10. Control valves shall be specified to provide an acceptable noise level when
continuously operating to meet local area requirements but shall generally be less
than 80 dBA at 1 metre from control valve body and less than 45dBA 20 metres
within the site battery limit. Standard valves shall be used and solutions to noise
generation problems shall be in the following order:
Low noise trim

Inclusion of in-line diffusers and/or silencers.

Acoustic insulation.
9.1.11. Control valves operated during emergency shutdown conditions will not be
provided with either bypasses or hand wheels unless specifically shown on the P&I
Diagrams. Where bypasses are provided the CV of the bypass valve shall not
exceed the CV value of the control valve.
9.1.12. Control valves should preferably be installed in horizontal lines with the stem
vertical and the actuator uppermost. Rotary valves shall be installed with the vane-
shaft horizontal.
SPECIFICATION NUMBER

INSTRUMENT DESIGN BASIS


REV : 02

CLIENT: -- SHEET NO 19 OF 34

9.2. On off actuated valves


9.2.1. Actuated valve type, materials and connections shall be in accordance with the pipe
specification.
9.2.2. The on-off valve body size shall be same as line size.
9.3. Actuators
9.3.1. Pneumatic spring return actuators shall be generally diaphragm type for control
valves and piston actuated for on-off service. The use of motor or hydraulic
actuators shall be restricted to special applications and shall be subject to approval
by the Engineer.
9.3.2. To protect personnel and equipment actuators shall on air or control signal failure
drive the valve to the fail-safe state as indicated on the P&I diagram.
9.3.3. Double acting actuators shall be normally specified for fail last position
applications.
9.3.4. Where spring return actuation can not be provided capacity chambers may be
specified to ensure the valve fails safe on motive power failure.
9.3.5. Actuators are to be sized to drive the valve to its fail position against the maximum
line differential pressure.
9.3.6. Actuators for all valves are to be sized for the site minimum operating instrument
air pressure of 3.5 Kg/cm2g.
9.4. Solenoid valves
9.4.1. Solenoid valves and must have sufficiently sized CV so as not to impede the valve
stroking time.
9.4.2. Solenoid coils shall be mounted integral to the valve switch box
9.4.3. Where solenoid valves are fitted remote to the valve, quick exhaust valves may be
utilised to improve valve response time.
9.5. Valve switch boxes
9.5.1. A standard switch box design is preferred for all turn on off actuated valves.
The switch box shall comprise of NAMUR proximity sensors and integrally
mounted solenoid valve. Flying leads are not acceptable.
9.6. Self-Operated Regulating Valves
9.6.1. Self-operated regulating valves shall be used for pressure regulation of utility
supplies / equipment purging applications and are not recommended where precise
control is required.
SPECIFICATION NUMBER

INSTRUMENT DESIGN BASIS


REV : 02

CLIENT: -- SHEET NO 20 OF 34

9.6.2. Regulating valves shall where possible be integral type to minimise process
tapping. Pilot-operated regulation valves should be restricted to high capacity
applications.
9.6.3. Where appropriate, relief valves shall be used to protect down stream equipment
from pressure regulator failure.
9.6.4. A local means of pressure indication shall be provided to facilitate regulator
adjustment.
10. SAFETY AND RELIEF SYSTEMS
10.1. General
10.1.1. Safety and relief valves shall meet the requirements of the ASME unfired pressure
vessel code, API RP 520, and API RP 521.
10.1.2. In addition, where local codes are also applicable, the stringent requirements shall
govern.
10.2. Safety Relief valves
10.2.1. Safety relief valve orifice sizes shall be calculated on a pure area requirement
basis, capacity adjustments required by code revisions or other applicable
regulations shall be covered within valve selection procedure.
10.2.2. Safety valves for general process service shall be direct spring loaded with high lift
characteristics and be flanged with minimum carbon-steel body and stainless steel
nozzle, disc. and guides.
10.2.3. Lifting levers shall be provided as required by the applicable code for air, hot water
and steam service, to allow the disc to be lifted from the seat when the operating
pressure is 75% of the seat pressure.
10.2.4. Safety valves will be set to open at the pressure stated on the P&ID. Where
variable back pressure exceeds 10% of the set pressure balanced bellows seal type
valves shall be used.
10.3. Rupture Discs
10.3.1. Rupture discs will be scored, reverse buckling narrow face capsule type complete
with holders to fit inside the ID of the bolt circle of standard flanges. Jacking
bolts shall be supplied for disc sizes 2 and larger.
10.3.2. Where a rupture disc is installed upstream of a safety valve an excess flow valve
must be installed downstream of the disc to prevent any back pressure on the disc
in the event of disc seepage insufficient to burst the disc, and a 50mm (2) dia
pressure gauge provided to detect leakage or rupture.
SPECIFICATION NUMBER

INSTRUMENT DESIGN BASIS


REV : 02

CLIENT: -- SHEET NO 21 OF 34

11. DESUPERHEATER
The desuperheater can be either of the following types based on application.
11.1. Combined Pressure/Temperature Reducing Desuperheater.
11.1.1. This type is a combination unit, which provides steam pressure reduction and
temperature control within one unit.
11.1.2. The unit will consist of an in line or angle body type pressure reducing valve, an at
temperature section, Spray water valve and nozzle to spray cooling water and a
fixed area exit baffle (if required).
11.1.3. This unit shall be capable of providing high flow rate; tight shut off and handling
required quantity of spray water. Typical Rangeability shall be of the order of
45:1.
11.2. Variable Geometry Mechanically Atomising Desuperheater
11.2.1. This type shall be used only for steam attemperation. Typical Rangeability shall be
40:1 capable of handling fluctuating load.
11.3. Fixed Geometry Mechanically Atomising Desuperheater
11.3.1. This shall be used only for steam attemperation where load is not of fluctuating
nature. Typical Rangeability upto 3:1.
11.4. Fixed Area Annular Spray Mechanically Atomising Desuperheater
11.4.1. This shall be generally used for steam lines having diameter between 1 & 4.
Typical rangeability shall be of the order of 10 : 1
11.5. Steam Assisted Desuperheater
11.5.1. These shall be used for installation where high fluctuation of load is expected.
Typical rangeability shall be 50:1.
12. CONTROL SYSTEM
This shall consist of outstations (including plant interface), operator stations, communications and
all other equipment and software required for normal operation of the plant .The control console
in the operator control centre shall allow the operator to monitor and control the process .The
instrumentation connected to the control system shall continuously provide process and utility
data .The control system is essential for plant operation.
12.1. Rack Room Facility
12.2. It shall consist of plant I/O interface & marshalling cabinets.
12.3. To maintain the integrity of data communications between various equipment in different
locations, there shall be dual communication highways routed separately to their location
12.4. The scan time shall be 500 msec for close loops and 1 sec for open loops. Controller shall not
be loaded more than 60% of its capacity in terms of I/O and memory, whichever is lower.
SPECIFICATION NUMBER

INSTRUMENT DESIGN BASIS


REV : 02

CLIENT: -- SHEET NO 22 OF 34

12.5. In case of hazardous areas, the I/O cards shall be intrinsically safe certified. If not, external-
isolating barriers shall be provided. For I/O cards number of input/output channels shall be as per
manufacturer standard. However maximum number of channels for analogue card shall be 16 and for
digital shall be 32.
12.6. Plant Input/Output Interface
It shall comprise of the following
- Analogue input signals
- Analogue output signals
- Digital input signals
- Digital output signals
- Pulse train inputs
12.6.1. The analog input cards shall accept 4~20 mA DC two wire or four wire signals,
1~5VDC signals. Two wire transmitters shall be powered from the system.
12.6.2. The analog output cards shall drive 4~20 mADC signal to an I/P converter. Output
scaling, direct/reverse output, selectable fail safe value viz. last good value/preset
value/zero value configuration shall be provided.
12.6.3. Digital input cards shall be 24VDC .All digital inputs are potential free contacts,
card shall provide interrogation voltage to the input. These cards shall have
channel LED for status indication.
12.6.4. Digital output cards shall be 24V DC. Where required an interposing relay shall be
used. Atleast one NO contact shall be wired to the terminals. Relay contact rating
shall be 230VAC, 5A.Dc relays shall have built in free wheeling diode. All relays
shall have LED for status indication. Number of relays shall be equal to the number
of digital output channels.
12.7. Control room facilities
12.7.1. The functions required from central facility include the following
- Communication
- Plant history
- Alarm /Event Handling
- Performance monitoring
- Application programs
- Operator communications
12.8. Operator control centre(OCC)
The operator interface for the OCC shall comprise of
- Operator control console
- Event/report printers
SPECIFICATION NUMBER

INSTRUMENT DESIGN BASIS


REV : 02

CLIENT: -- SHEET NO 23 OF 34

- Emergency pushbuttons wherever required.


The equipment shall be designed to satisfy the following operational requirements.
- The movement necessary for the operator to effectively control the plant shall be
minimised.
- The layout of the individual items shall be ergonomically correct to ensure ease of
operation.
12.9. Database
The control system shall maintain a database which shall allow the operator to view the
information directly and indirectly related to the plant being monitored and controlled. The
control system shall handle data which shall reflect:
- general alarms, group status alarms and shutdown alarms and pre-alarms.
- setpoints ,measured variable and control elements status/position of all control
loops
- equipment status (e.g. running , stopped ,tripped,off-load,isolated for maintenance
or start-up etc)
12.10. System Integrity
The control system is an essential part of the plant operability and safety. Therefore it shall
maintain a high availability with high level of integrity. This shall be achieved by using high
reliability components, hardware redundancy where appropriate and good diagnostic
capability for trouble shooting.
12.11. Reliability
The control system shall have a high degree of tolerance to malfunction of hardware,
software and operator miskeying .Any fault developed shall have its effect to localized to
that part of the control system which remains operational, with a possible reduction in
level of functionality. The availability of the control system for control and process
monitoring shall be in excess of 99.95%.
12.12. The system shall be so designed such that operator will always have atleast manual access to
the control loops final element.
SPECIFICATION NUMBER

INSTRUMENT DESIGN BASIS


REV : 02

CLIENT: -- SHEET NO 24 OF 34

13. EMERGENCY SHUTDOWN SYSTEM WHEREVER REQUIRED


It shall be either of the following types
1. Hardwired relay logic
2. Programmable logic controller
The above PLCs shall meet anyone of the System Integrity Level (SIL) 1, 2, 3 as per
IEC 1508.
13.1. Hardwired relay logic
13.1.1. Logic shall be implemented with hardwired relays.
13.1.2. Only high integrity relays are to be used.
13.1.3. Relays shall be of hermetically sealed type.
13.1.4. Relay contacts shall be gold plated.
13.1.5. The relay coil shall have gravity dropout or dual springs.
13.1.6. The mechanical life expectancy of the relays shall be 100 x 106 min.
13.1.7. Relays shall be of plug-in type into a base unit.
13.1.8. Base unit shall preferably be a DIN rail mounting type and it shall be with screwed
terminals
13.2. Programmable logic controllers for ESD
13.2.1. PLCs shall be Fail-safe & microprocessor based which shall be used for plant
Emergency shutdown.
13.2.2. The system shall allow dependable and effective control of the plant and shall be
designed for maximum integrity and reliability. Integrity shall be maintained by
providing a fail-safe system. The system shall be TUV approved.
13.2.3. The system shall have facilities to replace failed equipment such as processors, I/O
cards, microprocessor, and batteries on-line without a shutdown.
13.2.4. The system shall have high integrity including automatic crosschecking, integral
self-test facility of input circuits, output circuits, and processors and provide failure
indication for operator information and action.
13.2.5. The system shutdown shall only occur in the event of an emergency situation and
not as a result of single point failure within the system. A single system fault shall
not prevent correct response to a shutdown demand.
13.2.6. The system shall be modular in construction.
SPECIFICATION NUMBER

INSTRUMENT DESIGN BASIS


REV : 02

CLIENT: -- SHEET NO 25 OF 34

13.2.7. The types of modules shall be kept to as minimum as possible in order to have
interchangeability and low spares inventory.
13.2.8. The system shall have extensive set of self-diagnostics for hardware and software
for easy maintenance.
13.2.9. The system shall be immune to noise and shall ensure safe and reliable operation
when subjected to RFI and electromagnetic disturbances.
13.2.10. The system shall be able to operate satisfactorily from 15 0C to 300C and
20% to 80% non-condensing humidity unless otherwise specified.
13.2.11. Operation of the system shall be completely unaffected if there is a
momentary powerless of the order of 20 milliseconds, unless otherwise specified.
13.3. The system shall be supplied with necessary programming tools and related accessories.
14. CONTROL ROOM
14.1. The control room and rack room shall be located in a conventional building in a non-hazardous
area. Heating, ventilation and air conditioning systems shall be included to maintain an acceptable
operating environment. Process fluids shall not be piped into the control room.
14.2. The rack room shall be located close to the control room and shall house the following
- Marshalling cabinets
- Control system I/O cabinets
- Engg. Station
- Fire and Gas cabinets
- Instrumentation Power supply distribution boards
Other Miscellaneous instrumentation.
14.3. The control room shall house all operator interfaces such as screens,keyboards, printers,ESD
push buttons and override switches etc.
14.4. The control rack room shall have false flooring and false ceiling .The false flooring depth shall
be 650 mm minimum .The false flooring shall be supported on aluminum framework and cabinets on
structural steel framework .The distance between top of false floor and bottom of false ceiling shall be
minimum 3 metres.
14.5. The lighting in the control room shall be such that there is no glare on the screens and the
minimum lux level shall be 400 lux.
14.6. The temperature inside the control room shall be minimum 21 deg C for equipment and
operator comfort.
14.7. The flooring of the control room shall be anti-static and dust-free.
14.8. The air conditioning inside the control room shall be such that supply air diffusers should not
be on the top of caibinet. The return air diffusers shall be on the top of cabinet.
14.9. Single/Multicore cables taking signals to/from the field shall enter the rack room through
sealed openings to maintain the environment within the control building.
SPECIFICATION NUMBER

INSTRUMENT DESIGN BASIS


REV : 02

CLIENT: -- SHEET NO 26 OF 34

15. UTILITY SUPPLIES


15.1. Instrument power supplies
15.1.1. The primary electrical supply for instrumentation shall be single-phase supply
supported by an uninterruptable power supply (UPS), sized to supply emergency
power on mains failure for a minimum period of 30 minutes.
15.1.2. The UPS shall be a no break change over type. A standby supply and bypass
switch shall be provided for maintenance purposes.
15.1.3. Supplies for instrumentation shall be derived from 230Vac / 24Vdc redundant
power supply units. Instrumentation power shall be wherever possible 24Vdc.
Where this can not be achieved 230Vac may be used as an alternative. Voltages
greater than 230 volts must not be used for instrument supplies.
15.2. Instrument air supplies
15.2.1. The air supply for instrumentation shall be derived from the site compressed air
system. The instrument air quality shall be in accordance with ISA S7.01 1996
The pressure dew point as measured at the dryer outlet shall be atleast10 C below
the minimum temperature to which any part of the instrument air system is
exposed .The pressure dew point shall not exceed 4 C at line pressure.
Particle size in the instrument air upto 40 micron is acceptable.
The lubricant content shall be close to zero as possible and the instrument air shall
be free of contaminant.
15.2.2. Instrument air headers and sub-headers shall be galvanised carbon steel and routed
from the main compressed air header to locations determined by the Instrument
Engineer.
15.2.3. Connections to instruments shall be via instrument air distribution manifold and
6mm / 12 mm OD tubing.
15.2.4. Local filters or filter regulators and gauges shall be supplied where appropriate.
SPECIFICATION NUMBER

INSTRUMENT DESIGN BASIS


REV : 02

CLIENT: -- SHEET NO 27 OF 34

16. INSTRUMENT CONNECTIONS


16.1. Standard connections
16.1.1. Inline instrument process connections shall be generally flanged type to ANSI
B16.5 in accordance with the piping specification. In case of food grade or pharma
applications Tri-clamp or weld in connections shall be used.
16.1.2. Standard connection sizes on piping and equipment shall be used in accordance
with the table listed in appendix C.
16.2. Instrument process piping
16.2.1. Impulse lines shall be kept as short as possible. Piping up to and including the first
process block valve and in-line instruments shall conform to the line or vessel
classifications concerned. The first block valve shall be installed as close as
possible to the line or vessel.
16.2.2. Instrument piping after the first block valve may be an alternative equal or better
material to that of the main process line or vessel. The minimum standard being
seamless 12mm OD 316 stainless steel tubing with 1.5mm wall thickness.
16.3. Instrument air tubing
16.3.1. Instrument air supply tubing shall be stainless steel or PVC covered copper tubing
as indicated in the hook-up diagram.
16.3.2. Larger diameter tubing may be used for high speed or large volume applications.
17. INSTRUMENT CABLE AND WIRING
17.1. Cable
17.1.1. Standard instrumentation cable shall be used in accordance with BS5308 part 2;
PVC insulated, with a single collective screen.
17.1.2. Analog Input / Output & Digital Inputs (Switches)
Main cable runs between control room and field junction box shall be multipair,
twisted, stranded 1.0 sq.mm, annealed bare copper conductors, PVC insulated,
overall screen and with 0.5mm2 annealed tinned copper drain wire, galvanised wire
armoured, overall PVC sheathed. Multipair cables shall be supplied in the
following standard pair 1,2,5,810,16,20& 30 pair depending on the local grouping
of field instruments.
17.1.3. Cables between Instruments and junction boxes shall be of same specification as
17.1.2. but will be of single pair instead of multipair.
17.1.4. Cables for Solenoid Valves (110VAC/230 V AC)
17.1.4.1. Main runs between control room and field junction boxes shall be
multipair, twisted, stranded 1.5 sq.mm. Annealed bare copper conductor,
PVC insulated, single layer galvanised wire armour, and overall PVC
sheathed.
SPECIFICATION NUMBER

INSTRUMENT DESIGN BASIS


REV : 02

CLIENT: -- SHEET NO 28 OF 34

17.1.4.2. The cable outer PVC sheath shall be coloured blue for intrinsically
safe cable and black for non-intrinsically safe cables.
17.1.5. Termination
17.1.5.1. Terminations shall normally be of the rail mounted, preferably Wago or
equivalent make.
17.1.5.2. Both ends of all cables and their used cores shall be identified by
individual cable marker rings as per drawing.
17.1.5.3. To achieve insulation and continuity of the screen, the drain wires shall be
accommodated using terminals with in the box.
17.1.5.4. Instrument gland entries shall be NPT.
17.1.6. Power cable colour code shall be:
230Vac: Phase Red
NeutralBlack
Earth Green
24Vdc: Positive Red
Negative Black
17.2. Junction boxes (Field)
17.2.1. All junction boxes shall be identified by permanently fixed label.
17.2.2. Junction boxes shall be certified suitable for the degree of protection, explosion
proof wherever required. Boxes shall be weatherproof to IP 55 minimum and
be provided with doors having gaskets.
17.2.3. Cables shall only enter from bottom or side inside the junction boxes. All gland
plates are to be undrilled and removable. Cable glands shall be double
compression type Cd plated brass. These shall be ex-proof wherever specified
and weather proof IP 55 to minimum.
18. SEGREGATION AND INSTALLATION
18.1. No multipair cables shall contain both intrinsically safe and non-intrinsically safe circuits.
Calculations shall be done for each intrinsically safe loop to prove that the cable capacitance and
inductance do not invalidate the certificate for intrinsic safety.
18.2. Only circuits carrying the same voltage shall be contained in the same multipair cable.
SPECIFICATION NUMBER

INSTRUMENT DESIGN BASIS


REV : 02

CLIENT: -- SHEET NO 29 OF 34

18.3. Instrument signal cables shall be run separate to power cables, the separation shall be at least
300 mm. Where crossovers of instrument and electrical signals is unavoidable, they shall be so
arranged to cross at right angles.
18.4. Intrinsically safe signal cables shall be normally routed separately to other signal types. Where
this is not practical, physical separation shall be achieved by means of a metal dividing plate.
18.5. Cables shall be routed away from access areas; high temperature equipment and areas of
potential attack by leakage of chemicals, specially solvents.
18.6. Cables shall be routed from instrument equipment rooms to field junction boxes on galvanised
steel cable ladder rack. Cables to individual instruments shall be routed in open tray
18.7. Control and Marshalling cabinets
18.7.1. Cabinets shall be freestanding enclosed type and shall be designed for bottom entry
cables. Removable gland plates for glanding cables shall be provided.
18.7.2. Cabinets shall be fabricated from CRCA sheet with a minimum thickness of 2mm
and shall be reinforced to prevent warping and buckling.
18.7.3. Cabinet doors shall be fabricated from CRCA sheet with a minimum thickness of
1.6mm. Cabinets shall be with front and rear access. Flush pull handle with keylock
shall be provided to all access doors.
18.7.4. All cabinets shall be fitted with removable eyebolts for lifting the cabinets. Also
blanking plates for eyebolts shall be provided.
19. EARTHING
19.1. The following earth systems shall be provided when applicable
- Instrument System Earth (Clean Earth) for signal earths, screens etc.
- Control Cabinet Earth (Dirty Earth) For Signal earths, screens etc.
- Barrier Device Earth for barrier system earth requirements (where intrinsically
safe zener barrier devices are included).
19.1.1. Cable screens shall be earthed at one location only and this shall generally be at the
control room terminal location area.
19.1.2. The Barrier Device earth shall be insulated from the Control Panel Earth and run
separately to the instrument system earth-electrodes.
19.1.3. For Instrument System and Barrier Device earths the total earth loop impedance
on any circuit shall be less than as specified by control system vendor.
SPECIFICATION NUMBER

INSTRUMENT DESIGN BASIS


REV : 02

CLIENT: -- SHEET NO 30 OF 34

20. PACKAGE EQUIPMENT


20.1. Instrumentation requirements for package equipment shall be in accordance with specification
INST/515/02.
21. DOCUMENTATION
Documentation for instrumentation shall generally comprise of
General specifications

Data sheets, specifications and requisitions.

Instrument schedules

Interlock and trip diagrams.

Instrument layout and routing drawings

Field wiring diagrams

Cable schedules

Hook up drawings

Loop diagrams

Instrument material take off


21.1. As built Drawings
As built drawings shall be supplied for all documents appropriate to the operation and
maintenance of the plant.
22. TESTING AND INSPECTION
Testing and inspection shall be carried out at vendors works as per inspection / test requirements
attached with each specification
Final inspection shall be performed only after the Vendor has satisfactorily completed his test.
The tests shall be a complete repeat of those tests performed by the Vendor with any additional
tests that the Purchaser shall find necessary to ensure proper operation of the equipment/system
23. INSTALLATION
23.1. Installation of all field instrumentation and equipment shall comply with the requirements of
CCI P/1 and CCI P/2 Instrument installation specification (Contractor committee on Instrumentation)
of Energy Industries Council U.K.
SPECIFICATION NUMBER

INSTRUMENT DESIGN BASIS


REV : 02

CLIENT: -- SHEET NO 31 OF 34

APPENDIX - A
UNITS OF MEASUREMENT AND SCALES

UNITS OF MEASUREMENTS
Volume : M3
Heat duty : kW
0
Temperature : C
Length : mm, m
Mass : Kg, t
Time : Sec, min, hr
Pressure : Bar a, Bar g, mm H2O, kpa.
Mass Flow : Kg/ hr , t/hr
Volume Flow : M3 / hr, Nm3 / hr
Density : Kg/ m3
Viscosity : Cp.
Voltage : V
Current : A
Power : kW, Mw
Rotation : Rpm
Noise : dBA

SCALES
Graduation of scales shall be as follows :
PARAMETER SCALE
Flow (orifice) : 0-10 sq. root
Flow ((linear) : 0-100 linear
Flow (variable area) : 1-10 linear
Level : 0-100 linear
Pressure : Direct reading (Dual Scale)
Temperature : Direct reading
SPECIFICATION NUMBER

INSTRUMENT DESIGN BASIS


REV : 02

CLIENT: -- SHEET NO 32 OF 34

APPENDIX - B
INSTRUMENT CONNECTIONS ON VESSELS

SR NO INSTRUMENT VESSEL FIRST BLOCK INSTRUMENT


CONNECTION VALVE CONNECTION
1 Displacer LT- External 2 Flanged 2 Flanged 2 Flanged
2 Displacer LT- Internal 4 Flanged ---- 4 Flanged
3 Level Gauges 1 Flanged 1 Flanged 1 Flanged
4 D.P. Instrument on Vessel 1 Flanged 1 Flanged NPT
5 Flush Diaphragm DP cell - 3 Flanged 3 Flanged 3 Flanged
HP
L 1 Flanged NPT(F) 1/2 NPT(F)
P
6 Remote Seal DP Cell - HP 3 Flanged 3 Flanged 3 Flanged
L 3 Flanged 3 Flanged 3 Flanged
P
7 Capacitance Type Inst. 2 Flanged ----- 2 Flanged
8 Level Switch- Internal Float 4 Flanged ----- 4 Flanged
9 Float & Tape Level 3 x 1.5 Flanged ------ 3 x 1.5 Flanged
Instrument
10 Ultrasonic Level Instrument 4 Flanged ----- 4 Flanged
11 Tuning Fork Type Level 1.5 NPT (F) ------- 1.5 NPT(M)
Switches
12 Pressure Transmitter 1 Flanged NPT(F) 1/2 NPT(F)
13 Pressure Gauges 1 Flanged NPT(F) 1/2 NPT (M)
14 Pressure Transmitter - Seal 2 Flanged 2 Flanged 2 Flanged
Type
15 Pressure Gauges Seal Type 2 Flanged 2 Flanged 2 Flanged
16 Thermowell 3/4 NPT ----- 3/4 NPT

NOTES:

1. For any other instrument not referred above, connection shall be as per individual requirement.
2. For serial number 14, 1 flanged connection shall be used based on availability.
3. In case of direct mounted flanged instruments, or where first block valve is specified, bolting and
gasket shall be by Piping.
All flanged connection shall be ANSI
SPECIFICATION NUMBER

INSTRUMENT DESIGN BASIS


REV : 02

CLIENT: -- SHEET NO 33 OF 34

APPENDIX - C
ENVIRONMENTAL CONDITIONS
(Project Specific Reference shall be made in this Appendix)

Local Conditions shall be as per document :


SPECIFICATION NUMBER

INSTRUMENT DESIGN BASIS


REV : 02

CLIENT: -- SHEET NO 34 OF 34

APPENDIX D
INSTRUMENT CODES / STANDARDS
SPECIFICATION NUMBER

INSTRUMENT DESIGN BASIS


REV : 02

CLIENT: -- SHEET NO 35 OF 34

SR.NO ITEM DESCRIPTION STANDARD EDITION


1 Control Valves Face to Face & End to End ANSI B 16.10
Dimensions of Valves
Control Valve Seat Leakage ANSI/FCI 70.2
Hydrostatic Testing of Control ISA S75.19
Valves
2 Safety valves Design & Installation of Pressure API RP 520 PART-I
Relieving Systems in Refineries API RP 520 PART-II
Flanged Steel Safety Relief Valves API RP 526
Seat Tightness of Pressure Valves API STD 527
Boiler & Pressure Vessel Code ASME SEC VIII with
addendum upto 1994
Bursting Discs and Bursting Disc ISO 6718
Devices
3 Orifice Plates Steel Orifice Flanges ANSI B16.36
Measurement of Fluid Flow ISO 5167
4 RTD Industrial Platinum Resistance IEC 751
Thermometer Sensors
5 Thermocouple Thermocouples-Reference Tables IEC-584 Part 1
Thermocouples-Tolerances IEC-584 Part 2
Thermocouples-Extension and IEC-584 Part 3
Compensating Cables-Tolerances
and Identification System
6 Instrument Instrumentation Cable BS 5308 Part-I & II
Cables
Specification for PVC insulated IS 1554 Part I
(Heavy Duty) Electrical Cables
Specification for PVC Insulation & IS 5831
Sheath of Electrical Cables
Specification for PVC Insulated IS 694
Cables
Specification for Conductors for IS 8130
Insulated Electric cables and
flexibles
7 Miscellaneous Instrumentation Symbols and ISA S5.1
Identification
Graphic Symbols for DCS Systems ISA S5.3

Instrument Loop Diagrams ISA S5.4


Annunciation Sequence and Spec ISA S18.1
Quality Standard for Inst. Air ISA S7.0.01
Degree of Protection provided by IEC 529
Enclosures
SPECIFICATION NUMBER

INSTRUMENT DESIGN BASIS


REV : 02

CLIENT: -- SHEET NO 36 OF 34

SR.NO ITEM DESCRIPTION STANDARD EDITION


Electromagnetic Compatibility for IEC 801
Industrial Process Measurement
and Control Equipment
Operating Conditions for Industrial IEC 654
Process Measurement and Control
Equipment
8 Hazardous Electrical Apparatus for Explosive IEC 79-1
Area Protection Gas Atmosphere-Construction and
Verification of Flameproof
Enclosure of Electrical Apparatus
Electrical Apparatus for Explosive IEC 79-2
Gas Atmosphere-Electrical
Apparatus Type of Protection p
Electrical Apparatus for Explosive IEC 79-10
Gas Atmosphere-Classification of
Hazardous Area
Electrical Apparatus for Explosive IEC 79-11
Gas Atmosphere-Intrinsic Safety
i
Electrical Apparatus for Explosive IEC 79-16
Gas Atmosphere-Artificial
Ventilation for protection of
Analyser Houses
Electrical Apparatus for use in ISA S12.0.01
Class-I, Zones -0&1
Hazardous(classified) Locations-
General Requirements
Purged and Pressurised Enclosure NFPA 496
for Electrical Equipment ISA S12.4
Wiring Practices for ISA RP 12.6
Hazardous(Classified) Locations
Instrumentation Part I-Intrinsic
safety
Intrinsically Safe System ISA TR12.2
Assessment using the Entity
Concept

9 Flanges and Screw Threads-Pipe Threads ANSI/ASME B1.20.1


Threads General Purpose(inch)
Ring Joint gaskets and groove for ANSI/ASME B16.20
Steel Pipe Flanges
Large Diameter Steel Flanges ANSI/ASME B16.47
NPS26 through 60
Steel Pipe Flanges & Flanged ANSI B 16.5
Fittings
SPECIFICATION NUMBER

INSTRUMENT DESIGN BASIS


REV : 02

CLIENT: -- SHEET NO 37 OF 34

NOTES: 1. Unless otherwise specified latest edition of the standard shall be referred