WARNING NO WIRING
Show window: 7m
According to Section 2.20.2.5(g) (2):
Total Load = 7/0.3 x 200 = 4666.66667VA
= 4666.66667/230=20.28986A - Ohms Law was use and since we are talking
about single phase load 230 V is the voltage to be use.
According to Section 2.10.2.5(a) and Table 2.10.2.3(b) (2):
Number of branch circuit for 20 A is
20.28986/16 2 branch circuits.
Each branch circuit has:
20.28986/2 = 10.14493 A
WARNING NO WIRING
Sign Lighting: Assume 12 20A branch circuits
According to Table 2.10.2.3(b) (a):
Each branch circuit is 16 A
WARNING NO WIRING
INCOMPLETE
WARNING NO WIRING
Chiller Fridge - 13 units 1/6 hp
Each branch circuit has a full load current of 2.2 A.
According to Section 4.30.2.4: =2.2(1.25)=2.75
According to Section 4.30.4.2, Table 4.30.4.2 and Section 2.40.1.6 (a):
Using an Inverse time breaker =2.2(2.5)=5.5
WARNING NO WIRING
Note: The diameter and cross-sectional area of wire are not yet calculated.
Level 2-5
GL: Assume 75% continuous loading
64.7200839/16 = 4.04500524 = 4
Each Branch circuit has :
64.7200839/4 = 16.180021
Using Section 2.40.1.6 (a):
Each branch circuit will be using 20 AT CB.
Level 6-22
SA:
Total load = 120*180 = 21600 VA
Max Load = 10000+(11600)(.5) = 15800
Iload = 15800/230 = 68.6957 A
No of branch circuit for 20 A
68.6957/16 = 5 branch circuit
Each branch circuit
68.6957 / 5 = 13.73914
Branch circuit wires
3(2.0 2 ) in 15 mm diameter RMC
3 5.5 2 in 15 mm diameter
b) 12 A each branch circuit
Iw = 12(1.25) = 15 A
Icb = 12(2.5) = 30 A
2 - 2.0 2 & 1 5.5 2
- 3 5.5 2 in 15 mm diameter
3 5.5 2 in 15 mm diameter