DC OK Green LED Indicator PSU -
Rdy
V Adj. V Adj. O/P Voltage adjustment
input of device
+ + Output Positive
-
- Output Negative
Rdy
Rdy DC OK signal (Short)
+
-
-
PSU
Earth Rdy
N input of device
L N Input Neutral
P.S. Please adjust output voltage of each unit
L Input Line as close as possible to balance the loading.
Installation Instruction
1. Making sure wire connection of the designations and input selector are correct before turn on AC source. AC input selector is
located at left (Fig. 1) of front panel of AD1vvv-xyS models. The connector can withstand 8 lb-in torque Maximum and use
o o
copper connectors only, 60/75 C and installation in Pollution Degree 2 environment. Max. surrounding air temperature 40 C .
2. Snap power unit on TS35 DIN rail, please operate as Fig. 2. Using a "-" screw driver to pull down underside mounting bracket
to release power unit from TS35 DIN rail.
3. The left housing of power unit is design as heatsink, please keep 15mm Min. for dissipating heating. (Fig. 1)
4. For mounting power unit by mounting bracket, please loosen screws on mounting bracket
and pull both brackets outer. And then re-screw the mounting brackets to get easier operation
of mounting on wall/plate. (Fig. 3)
5. Output voltage adjustable range is +/-10% of rated voltage, over +10% might cause
over voltage protection, under - 10% might cause output flicking at lower loading.
15mm
72W 72W
DC OK DC OK
V.Adj. V.Adj.
+ +
_ _
Rdy Rdy
N N
L L
220
P.1
DIN Rail Mounting Power Supply
3.5
61
8
29
DC OK
V.Adj.
INPUT
Input voltage ..............100~240VAC/120~370VDC
+
_
Input frequency........................................47~63Hz 90
Inrush current ...................................22A/115VAC
(Cold start) 44A/230VAC N
L
OUTPUT
Hold-up time (Full load@230VAC) .....20mS Min.
Over voltage protection ...................Autorecovery
Overload protection ........................Power limited
Short circuit protection ....................Autorecovery
3
Dimensions:75(D)x96(H)x45(W)mm
AD1024F Series Single output
O/P voltage Loading (A) Ripple Line Load Redundant
Model Reg. Reg. Eff. O.V.P. MOQ CB UL TUV
Adjustment Min. Rated Max. Noise Function
AD1020-05F _10%
+5VDC + 0A 4.0A 4.0A 50mVp-p _ 1%
+ _ 1%
+ 78% 7VDC Max. None None Yes Yes Yes
_10%
AD1024-12F +12VDC + 0A 2.0A 2.0A 100mVp-p _ 1%
+ _ 1%
+ 80% 20VDC Max. None None Yes Yes Yes
AD1024-24F _10%
+24VDC + 0A 1.0A 1.0A 150mVp-p _ 1%
+ _ 1%
+ 83% 40VDC Max. None None Yes Yes Yes
_ 10%
AD1048-12FS +12VDC+ 0A 4.0A 4.0A 100mVp-p _ 1%
+ _ 1%
+ 80% 20VDC Max. None None Yes Yes Yes
_ 10%
AD1048-15FS +15VDC+ 0A 3.0A 3.0A 150mVp-p _ 1%
+ _ 1%
+ 80% 20VDC Max. None 300pcs Yes Yes Yes
_10%
AD1048-24FS +24VDC+ 0A 2.0A 2.0A 150mVp-p _ 1%
+ _ 1%
+ 83% 40VDC Max. None None Yes Yes Yes
_10%
AD1048-48FS +48VDC+ 0A 1.0A 1.0A 250mVp-p _ 1%
+ _ 1%
+ 83% 60VDC Max. None 300pcs None None None
NOTE: 1. Each output is designed to supply up to Max. current, but total loading must be limited within rated output wattage.
2. Line regulation is measured from low line to high line at rated load.
3. Load regulation is measured from 20% to 100% of rated load at 230VAC input.
4. Ripple & Noise is measured by using a 0.1uF/630V metalized capacitor & a 47uF electrolytic
capacitor parallel on the test point, at rated load and 230VAC input.
5. Efficiency is measured at rated load and 230VAC input.
P.2
DIN Rail Mounting Power Supply
111
40
48W
DC OK
V.Adj.
+
_
INPUT 110
Input voltage ..............100~240VAC/120~370VDC Rdy
Input frequency........................................47~63Hz
Inrush current ....................................22A/115VAC
(Cold start) 44A/230VAC N
L
OUTPUT
Hold-up time (Full load@230VAC) ......20mS Min.
Over voltage protection ....................Autorecovery 11 110
Overload protection .........................Power limited
Short circuit protection .....................Autorecovery
Dimensions:121(D)x110(H)x40(W)mm
AD1048F Series Single output
O/P voltage Loading (A) Ripple Line Load Redundant
Model Reg. Reg. Eff. O.V.P. MOQ CB UL TUV
Adjustment Min. Rated Max. Noise Function
AD1040-05F +5VDC +_ 10% 0A 8.0A 8.0A 50mVp-p +_ 1% +_ 1% 78% 7VDC Max. Option None Yes None None
AD1048-12F +12VDC +_ 10% 0A 4.0A 4.0A 100mVp-p +_ 1% +_ 1% 80% 17VDC Max. Option None Yes Yes None
AD1048-24F +24VDC +_ 10% 0A 2.0A 2.0A 150mVp-p +_ 1% +_ 1% 83% 30VDC Max. Option None Yes Yes None
AD1060-24F +24VDC +_ 10% 0A 2.5A 2.5A 150mVp-p +_ 1% +_ 1% 83% 30VDC Max. Option None None None None
P.3
DIN Rail Mounting Power Supply
111
56
72W
DC OK
V.Adj.
INPUT
+
Input voltage ..............100~240VAC/120~370VDC _
Input frequency........................................47~63Hz 110
Inrush current ....................................22A/115VAC Rdy
(Cold start) 44A/230VAC
OUTPUT N
L
Hold-up time (Full load@230VAC) ......20mS Min.
Over voltage protection ....................Autorecovery
Overload protection .........................Power limited
Short circuit protection .....................Autorecovery 11 110
Dimensions:121(D)x110(H)x56(W)mm
AD1072-12F _ 10%
+12VDC+ 0A 6.0A 6.0A 100mVp-p +_ 1% +_ 1% 78% 17VDC Max. Option None Yes Yes None
AD1072-24F _ 10%
+24VDC+ 0A 3.0A 3.0A 150mVp-p +_ 1% +_ 1% 81% 30VDC Max. Option None Yes Yes None
AD1072-48F _ 10%
+48VDC+ 0A 1.5A 1.5A 250mVp-p +_ 1% +_ 1% 82% 56VDC Max. Option None Yes None None
AD1100-12F _ 10%
+12VDC+ 0A 8.0A 8.0A 100mVp-p +_ 1% +_ 1% 78% 17VDC Max. Option None Yes Yes None
AD1100-24F _ 10%
+24VDC+ 0A 4.0A 4.0A 150mVp-p +_ 1% +_ 1% 81% 30VDC Max. Option None Yes Yes None
AD1100-48F _ 10%
+48VDC+ 0A 2.0A 2.0A 250mVp-p +_ 1% +_ 1% 82% 56VDC Max. Option None Yes None None
AD21001F
+12VDC 10% 0A 7.0A 7.0A 100mVp-p +_ 1% +_ 2% 77%
17VDC Max.
None 200pcs None None None
+5VDC ------ 0A 3.0A 3.0A 60mVp-p +_ 2% +_ 2% -------
+24VDC 10% 0A 3.5A 3.5A 150mVp-p +_ 1% +_ 2% 30VDC Max.
AD21002F 80% None None None None None
+5VDC ------- 0A 3.0A 3.0A 60mVp-p +_ 2% +_ 2% -------
P.4
DIN Rail Mounting Power Supply
111
75
120W
DC OK
INPUT V.Adj.
N
OUTPUT
L
Hold-up time (Full load@230VAC) ......20mS Min.
Over voltage protection ....................Autorecovery
Overload protection .........................Power limited
Short circuit protection .....................Autorecovery 11 110
Dimensions:121(D)x110(H)x75(W)mm
P.5
DIN Rail Mounting Power Supply
111
75
240W
DC OK
V.Adj.
INPUT
Input voltage ....................115/230VAC selectable +
_
Input frequency........................................47~63Hz 110
Inrush current ...................................22A/115VAC Rdy
AD1240-12S +12VDC10% 0A 20A 20A 100mVp-p 1% 1% 80% 17VDC Max. Option None Yes Yes None
AD1240-24S +24VDC10% 0A 10A 10A 150mVp-p 1% 1% 82% 30VDC Max. Option None Yes Yes None
AD1240-48S +48VDC10% 0A 5A 5A 250mVp-p 1% 1% 82% 56VDC Max. Option None Yes Yes None
AD1360-24S +24VDC10% 0A 15A 15A 150mVp-p 1% 1% 82% 30VDC Max. Option None None Yes None
AD1360-48S +48VDC10% 0A 7.5A 7.5A 250mVp-p 1% 1% 82% 56VDC Max. Option None None None None
P.6
DIN Rail Mounting Power Supply
111
100
240W
INPUT L DC OK
Input frequency........................................47~63Hz
Inrush current ....................................22A/115VAC Rdy
AD1240-12C +12VDC10% 0A 20A 20A 100mVp-p 1% 1% 80% 17VDC Max. Option None Yes Yes None
AD1240-24C +24VDC10% 0A 10A 10A 150mVp-p 1% 1% 81% 30VDC Max. Option None Yes Yes None
AD1240-48C +48VDC10% 0A 5A 5A 250mVp-p 1% 1% 83% 56VDC Max. Option None Yes Yes None
NOTE: 1. Each output is designed to supply up to Max. current, but total loading must be limited within rated output wattage.
2. Line regulation is measured from low line to high line at rated load.
3. Load regulation is measured from 20% to 100% of rated load at 230VAC input.
4. Ripple & Noise is measured by using a 0.1uF/630V metalized capacitor & a 47uF electrolytic
capacitor parallel on the test point, at rated load and 230VAC input.
5. Efficiency is measured at rated load and 230VAC input.
P.7
DIN Rail Mounting Power Supply
111
100
240W
INPUT L DC OK
Input frequency........................................47~63Hz
Inrush current ....................................22A/115VAC Rdy
AD1360-12C +12VDC10% 0A 30A 30A 100mVp-p 1% 1% 80% 17VDC Max. Option None Yes Yes None
AD1360-24C +24VDC10% 0A 15A 15A 150mVp-p 1% 1% 81% 30VDC Max. Option None Yes Yes None
AD1360-48C +48VDC10% 0A 7.5A 7.5A 250mVp-p 1% 1% 83% 56VDC Max. Option None Yes Yes None
NOTE: 1. Each output is designed to supply up to Max. current, but total loading must be limited within rated output wattage.
2. Line regulation is measured from low line to high line at rated load.
3. Load regulation is measured from 20% to 100% of rated load at 230VAC input.
4. Ripple & Noise is measured by using a 0.1uF/630V metalized capacitor & a 47uF electrolytic
capacitor parallel on the test point, at rated load and 230VAC input.
5. Efficiency is measured at rated load and 230VAC input.
P.8
DIN Rail Mounting Power Supply
111
100
500W
L DC OK
INPUT N V Adj.
AD1500-24S +24VDC10% 0A 21A 21A 150mVp-p 1% 2% 86% 30VDC Max. Option None Yes Yes None
AD1500-48S +48VDC10% 0A 10.5A 10.5A 250mVp-p 1% 2% 86% 56VDC Max. Option None Yes Yes None
NOTE: 1. Each output is designed to supply up to Max. current, but total loading must be limited within rated output wattage.
2. Line regulation is measured from low line to high line at rated load.
3. Load regulation is measured from 20% to 100% of rated load at 230VAC input.
4. Ripple & Noise is measured by using a 0.1uF/630V metalized capacitor & a 47uF electrolytic
capacitor parallel on the test point, at rated load and 230VAC input.
5. Efficiency is measured at rated load and 230VAC input.
P.9
DC Motor Power Supply
111
56
100W
DC OK
V.Adj.
+
INPUT _
_ 110
Input voltage ..............100~240VAC/120~370VDC
Input frequency........................................47~63Hz +
Inrush current ....................................22A/115VAC
(Cold start) 44A/230VAC N
L
OUTPUT
Hold-up time (Full load@230VAC) ......20mS Min.
11 110
Over voltage protection ....................Autorecovery
Overload protection .........................Power limited
Short circuit protection .....................Autorecovery
Dimensions:121(D)x110(H)x56(W)mm
AD1100M-24F +24VDC10% 0A 4A 8A 150mVp-p 1% 2% 80% 30VDC Max. Yes 300pcs None None None
AD1100M-48F +48VDC10% 0A 2A 4A 250mVp-p 1% 2% 81% 56VDC Max. Yes 300pcs None None None
AD1100M-72F +72VDC10% 0A 1.4A 2.8A 500mVp-p 1% 2% 81% 95VDC Max. Yes 300pcs None None None
NOTE: 1. Each output is designed to supply up to peak current within 3 minutes but total loading must be limited within
rated output wattage.
2. Line regulation is measured from low line to high line at rated load.
3. Load regulation is measured from 20% to 100% of rated load at 230VAC input.
4. Ripple & Noise is measured by using a 0.1uF/630V metalized capacitor & a 47uF electrolytic
capacitor parallel on the test point, at rated load and 230VAC input.
5. Efficiency is measured at rated load and 230VAC input.
P.10
DC Motor Power Supply
111
75
150W
DC OK
V.Adj.
+
INPUT _
_ 110
Input voltage ..............100~240VAC/120~370VDC
Input frequency........................................47~63Hz +
Inrush current ....................................22A/115VAC
N
(Cold start) 44A/230VAC
L
OUTPUT
Hold-up time (Full load@230VAC) ......20mS Min.
Over voltage protection ....................Autorecovery
11 110
Overload protection .........................Power limited
Short circuit protection .....................Autorecovery Dimensions:121(D)x110(H)x75(W)mm
AD1150M-24F +24VDC10% 0A 6.3A 10A 150mVp-p 1% 2% 80% 30VDC Max. Yes 300pcs None None None
AD1150M-48F +48VDC10% 0A 3.2A 5A 250mVp-p 1% 2% 81% 56VDC Max. Yes 300pcs None None None
AD1150M-72F +72VDC10% 0A 2A 3.5A 500mVp-p 1% 2% 81% 95VDC Max. Yes 300pcs None None None
NOTE: 1. Each output is designed to supply up to peak current within 3 minutes but total loading must be limited within
rated output wattage.
2. Line regulation is measured from low line to high line at rated load.
3. Load regulation is measured from 20% to 100% of rated load at 230VAC input.
4. Ripple & Noise is measured by using a 0.1uF/630V metalized capacitor & a 47uF electrolytic
capacitor parallel on the test point, at rated load and 230VAC input.
5. Efficiency is measured at rated load and 230VAC input.
P.11
DC Motor Power Supply
111
75
240W
DC OK
V.Adj.
INPUT +
_
Input voltage ....................115/230VAC selectable _ 110
Input frequency.......................................47~63Hz +
Inrush current ...................................22A/115VAC
(Cold start) 44A/230VAC N
230
L
OUTPUT
Hold-up time (Full load@230VAC) .....20mS Min.
Over voltage protection ...................Autorecovery 11 110
Overload protection ........................Power limited
Short circuit protection ....................Autorecovery
Dimensions:121(D)x110(H)x75(W)mm
AD1240M-24S +24VDC10% 0A 10A 15A 150mVp-p 1% 2% 80% 30VDC Max. Yes 300pcs None None None
AD1240M-48S +48VDC10% 0A 5A 7.5A 250mVp-p 1% 2% 81% 56VDC Max. Yes 300pcs None None None
AD1240M-72S +72VDC10% 0A 3.5A 5.5A 500mVp-p 1% 2% 81% 95VDC Max. Yes 300pcs None None None
NOTE: 1. Each output is designed to supply up to peak current within 3 minutes but total loading must be limited within
rated output wattage.
2. Line regulation is measured from low line to high line at rated load.
3. Load regulation is measured from 20% to 100% of rated load at 230VAC input.
4. Ripple & Noise is measured by using a 0.1uF/630V metalized capacitor & a 47uF electrolytic
capacitor parallel on the test point, at rated load and 230VAC input.
5. Efficiency is measured at rated load and 230VAC input.
P.12
DC Motor Power Supply
111
100
500W
L DC OK
INPUT N V Adj.
AD1500M-24S +24VDC10% 0A 21A 30A 150mVp-p 1% 2% 80% 30VDC Max. Yes 300pcs None None None
AD1500M-48S +48VDC10% 0A 10.5A 15A 250mVp-p 1% 2% 81% 56VDC Max. Yes 300pcs None None None
AD1500M-72S +72VDC10% 0A 7A 10.5A 500mVp-p 1% 2% 81% 95VDC Max. Yes 300pcs None None None
NOTE: 1. Each output is designed to supply up to peak current within 3 minutes but total loading must be limited within
rated output wattage.
2. Line regulation is measured from low line to high line at rated load.
3. Load regulation is measured from 20% to 100% of rated load at 230VAC input.
4. Ripple & Noise is measured by using a 0.1uF/630V metalized capacitor & a 47uF electrolytic
capacitor parallel on the test point, at rated load and 230VAC input.
5. Efficiency is measured at rated load and 230VAC input.
P.13
Lead-Acid Battery Charger
111
56
72W
Floating
Boosting
INPUT
Bat+
Input voltage ..............100~240VAC/120~370VDC Bat+
Input frequency........................................47~63Hz Bat - 110
Inrush current ....................................22A/115VAC Bat -
(Cold start) 44A/230VAC
N
OUTPUT L
Hold-up time (Full load@230VAC) .. ....20mS Min.
Over voltage protection ................ ....Autorecovery
Overload protection .................. .......Power limited
11
Short circuit protection ............... ......Autorecovery
Reverse polarity protection ...... ........Autorecovery
Dimensions:121(D)x110(H)x56(W)mm
AD1072C-12F +14.7VDC +13.8VDC 6A Max. 1% 1% 80% 22VDC Max. 200pcs None None None
AD1072C-24F +29.4VDC +27.6VDC 3A Max. 1% 1% 82% 37VDC Max. 200pcs None None None
Charging curve
VDC A
Type 12V 24V
Code 1
2
a (A) 6.0 3.0 a
b (A) 0.6 0.6
P.14
Lead-Acid Battery Charger
111
56
72W
Charging
Indication
V.Adj.
INPUT
Bat.+
Input voltage ..............100~240VAC/120~370VDC Bat.- 110
Input frequency........................................47~63Hz
Rdy
Inrush current ....................................22A/115VAC
(Cold start) 44A/230VAC
N
OUTPUT
L
Hold-up time (Full load@230VAC) .. ....20mS Min.
Over voltage protection .....................Autorecovery
Overload protection ..........................Power limited
11 110
Short circuit protection ......................Autorecovery
Reverse polarity protection ...............Autorecovery
Dry contact alarm signal ...........................1A relay
Dimensions:121(D)x110(H)x56(W)mm
AD1072C-12FR +14.7VDC +13.8VDC 6A Max. 1% 1% 80% 22VDC Max. 200pcs None None None
AD1072C-24FR +29.4VDC +27.6VDC 3A Max. 1% 1% 82% 37VDC Max. 200pcs None None None
Charging curve
VDC A
Type 12V 24V
Code 1
2
a (A) 6.0 3.0 a
b (A) 0.6 0.6
P.15
Lead-Acid Battery Charger
111
75
120W
INPUT Floating
Boosting
Input voltage ..............100~240VAC/120~370VDC
Input frequency........................................47~63Hz Bat+
Inrush current ....................................22A/115VAC Bat+
(Cold start) 44A/230VAC Bat - 110
Bat -
OUTPUT
N
Hold-up time (Full load@230VAC) .. ....20mS Min.
Over voltage protection ................ ....Autorecovery L
Overload protection .................. .......Power limited
Short circuit protection ............... ......Autorecovery
Reverse polarity protection ...... ........Autorecovery 11 110
Dimensions:121(L)x110(W)x75(H)mm
AD1120C-12F +14.7VDC +13.8VDC 10A Max. 1% 1% 81% 22VDC Max. 200pcs None None None
AD1120C-24F +29.4VDC +27.6VDC 5A Max. 1% 1% 82% 37VDC Max. 200pcs None None None
AD1120C-48F +58.8VDC +55.2VDC 2.5A Max. 1% 1% 84% 51VDC Max. 200pcs None None None
Charging curve
VDC A
Type 1
Code 12V 24V 48V
2 a
a (A) 10 5 2.5
b (B) 0.6 0.6 0.6
2 (VDC) 14.7 29.4 58.8
b
3 (VDC) 13.8 27.6 55.2
P.16
Lead-Acid Battery Charger
111
75
No.:AD120
Dimensions:121x110x75mm
120W
INPUT Charging
Indication
Input frequency........................................47~63Hz
Bat+
Inrush current ....................................22A/115VAC
Bat -
(Cold start) 44A/230VAC 110
Rdy
OUTPUT
Hold-up time (Full load@230VAC) .......20mS Min. N
Over voltage protection .....................Autorecovery L
Overload protection ..........................Power limited
Short circuit protection ......................Autorecovery
Reverse polarity protection ...............Autorecovery 11 110
Dray contact alarm signal .........................1A relay
Dimensions:121(L)x110(W)x75(H)mm
AD1120C-12FR +14.7VDC +13.8VDC 10A Max. 1% 1% 81% 22VDC Max. 200pcs None None None
AD1120C-24FR +29.4VDC +27.6VDC 5A Max . 1% 1% 82% 37VDC Max. 200pcs None None None
AD1120C-48FR +58.8VDC +55.2VDC 2.5A Max. 1% 1% 84% 51VDC Max. 200pcs None None None
Charging curve
VDC A
Type 1
Code 12V 24V 48V
2 a
a (A) 10 5 2.5
b (B) 0.6 0.6 0.6
2 (VDC) 14.7 29.4 58.8
b
3 (VDC) 13.8 27.6 55.2
P.17
Enclosed Power Supply
73
147
INPUT
Input voltage ..............100~240VAC/120~370VDC
Input frequency........................................47~63Hz
Inrush current ....................................22A/115VAC
(Cold start) 44A/230VAC
OUTPUT
Hold-up time (Full load@230VAC) .. ....20mS Min. 45
Over voltage protection .............. ......Autorecovery
Overload protection ................ .........Power limited
Short circuit protection ............ .........Autorecovery
Reverse polarity protection ...... ........Autorecovery
Dimensions:147(L)x73(W)x45(H)mm
AE1060C-12F +14.7VDC +13.8VDC 5A Max. 1% 1% 80% 17VDC Max. 200pcs None None None
AE1060C-24F +29.4VDC +27.6VDC 2.5A Max. 1% 1% 83% 35VDC Max. 200pcs None None None
Charging curve
VDC A
Type 12V 24V
Code 1
2
a (A) 5 2.5 a
b (A) 0.6 0.6
P.18
Lead-Acid Battery Charger
175
INPUT
Input voltage ..............100~240VAC/120~370VDC
Input frequency........................................47~63Hz
Inrush current ....................................22A/115VAC
(Cold start) 44A/230VAC
OUTPUT 88
50.5
5
Hold-up time (Full load@230VAC) .. ....20mS Min.
Over voltage protection ................ ....Autorecovery
Overload protection .................. .......Power limited
Short circuit protection ............... ......Autorecovery
Reverse polarity protection ...... ........Autorecovery
Over temperature protection ............Power limited
Dimensions:175(L)x88(W)x55.5(H)mm
AE1090C-24F +29.4VDC +27.6VDC 3.5A Max. 1% 1% 84% 37VDC Max. 200pcs None None None
AE1090C-36F +44.1VDC +41.4VDC 2.5A Max. 1% 1% 84% 51VDC Max. 200pcs None None None
AE1090C-48F +58.8VDC +55.2VDC 1.8A Max. 1% 1% 85% 67VDC Max. 200pcs None None None
Charging curve
VDC Rescue Floating
Charge
Constant
Current
Constant Voltage
Charge
A
1
Type 2 a
Code 24V 36V 48V
P.19
Lead-acid Battery Charger
INPUT
Input voltage ..............100~240VAC/120~370VDC
Input frequency........................................47~63Hz
Inrush current ....................................22A/115VAC
(Cold start) 44A/230VAC
OUTPUT
Hold-up time (Full load@230VAC) .. ....20mS Min.
Over voltage protection ................ ....Autorecovery
Overload protection .................. .......Power limited
Short circuit protection ............... ......Autorecovery
Reverse polarity protection ...... ........Autorecovery
Over temperature protection ............Power limited
Dimensions:188(L)x97(W)x52(H)mm
AE1150C-12FA +14.7VDC +13.8VDC 12.5A Max. 1% 1% 82% 17VDC Max. 200pcs None None None
AE1150C-24FA +29.4VDC +27.6VDC 6.5A Max. 1% 1% 83% 35VDC Max. 200pcs None None None
AE1150C-48FA +58.8VDC +55.2VDC 4A Max. 1% 1% 84% 52VDC Max. 200pcs None None None
Charging curve
VDC A
Type 48V
Code 12V 24V
1
a (A) 12.5 6.5 4 2 a
b (A) 0.6 0.6 0.6
P.20
Lead-acid Battery Charger
175
INPUT
Input voltage ..............100~240VAC/120~370VDC
Input frequency........................................47~63Hz
Inrush current ....................................22A/115VAC
(Cold start) 44A/230VAC
OUTPUT 88
50.5 5
Hold-up time (Full load@230VAC) .. ....20mS Min.
Over voltage protection ................ ....Autorecovery
Overload protection .................. .......Power limited
Short circuit protection ............... ......Autorecovery
Reverse polarity protection ...... ........Autorecovery
Over temperature protection ............Power limited
Dimensions:175(L)x88(W)x55.5(H)mm
AE1150CFC Series Built-in MCU
Charging voltage Charging current Efficiency
Model Boost Float Line Reg. Load Reg. O.V.P. MOQ CB UL TUV
(A)
AE1150C-12FC +14.7VDC +13.6VDC 12.5A Max. 1% 2% 83% 17VDC Max. 200pcs None None None
AE1150C-24FC +29.4VDC +27.2VDC 6.5A Max. 1% 2% 84% 35VDC Max. 200pcs None None None
AE1150C-36FC +44.1VDC +40.8VDC 4.1A Max. 1% 2% 84% 50VDC Max. 200pcs None None None
AE1150C-48FC +58.8VDC +54.4VDC 3.2A Max. 1% 2% 84% 67VDC Max. 200pcs None None None
Charging curve
VDC Rescue Floatin g
Charge
Constant
Current
Constant Volta ge
Charge
A
Type
Code 12V 24V 36V 48V 1
2 a
a (A) 12.5 6.5 4.1 3.2
1 (VDC) 14.7 29.4 44.1 58.8
2 (VDC) 13.6 3
27.2 40.8 54.4
3 (VDC) 8 16 24 32
P.21
Lead-acid Battery Charger
1.5
20
99
INPUT
4
Input voltage ..............100~240VAC/120~370VDC
Input frequency........................................47~63Hz
Inrush current ....................................22A/115VAC 20
(Cold start) 44A/230VAC
1.5
OUTPUT
Hold-up time (Full load@230VAC) .. ....20mS Min.
Over voltage protection ................ ....Autorecovery
Overload protection .................. .......Power limited 59
Short circuit protection ............... ......Autorecovery
Reverse polarity protection ...... ........Autorecovery
Over temperature protection ............Power limited
153
Dimensions:150(L)x153(W)x59(H)mm
EPS 1210 +14.7VDC +13.8VDC 10.0A Max. 1% 2% 83% 17VDC Max. 200pcs None None None
EPS 2405 +29.4VDC +27.6VDC 5.0A Max. 1% 2% 84% 35VDC Max. 200pcs None None None
Charging curve
2 (VDC) 3
13.8 27.6
30Mins.
Cha rging time
Input connection: IEC320 C14 socket
DC output: 1.2m, 16AWG x2 + alligator clip
P.22
Lead-acid Battery Charger
1.5
25
4
139
INPUT
Input voltage .....................115/230VAC selectable
Input frequency........................................47~63Hz
4
Inrush current ....................................22A/115VAC
(Cold start) 44A/230VAC 25
OUTPUT 1.5
Hold-up time (Full load@230VAC) .. ....20mS Min.
Over voltage protection ................ ....Autorecovery I
Overload protection .................. .......Power limited 115V
59 230V O
Short circuit protection ............... ......Autorecovery
Reverse polarity protection ...... ........Autorecovery
Over temperature protection ............Power limited
153
Dimensions:200(L)x153(W)x59(H)mm
EPS 240W Series Built-in MCU
Charging voltage Charging current Efficiency
Model Boost Float Line Reg. Load Reg. O.V.P. MOQ CB UL TUV
(A)
EPS 1220 +14.7VDC +13.8VDC 20A Max. 1% 2% 84% 17VDC Max. 200pcs None None None
EPS 2410 +29.4VDC +27.6VDC 10A Max. 1% 2% 86% 35VDC Max. 200pcs None None None
Charging curve
VDC Rescue Floating
Charge
Constant
Current
Constant Voltage
Charge
A
Type 12V 24V
1
Code 2 a
a (A) 20.0 10.0
30Mins.
Cha rging time
Input connection: IEC320 C14 socket
DC output: 1.2m, 14AWG x2 + alligator clip
P.23
Lead-acid Battery Charger
102
115V
60
O
I
60
INPUT
Input voltage .....................115/230VAC selectable
Input frequency........................................47~63Hz 230
Inrush current ....................................22A/115VAC
(Cold start) 44A/230VAC
OUTPUT
Hold-up time (Full load@230VAC) .. ....20mS Min.
Over voltage protection ................ ....Autorecovery
Overload protection .................. .......Power limited
Short circuit protection ............... ......Autorecovery
Reverse polarity protection ...... ........Autorecovery
Over temperature protection ............Power limited
Dimensions:200(L)x153(W)x59(H)mm
AE1360CS Series Built-in MCU
Charging voltage Charging current Efficiency
Model Boost Float Line Reg. Load Reg. O.V.P. MOQ CB UL TUV
(A)
AE1360C-24S +29.4VDC +27.6VDC 15A Max. 1% 1% 84% 35VDC Max. 200pcs None None None
AE1360C-48S +58.8VDC +55.2VDC 7.5A Max. 1% 1% 84% 70VDC Max. 200pcs None None None
AE1500C-24S +29.4VDC +27.6VDC 20A Max. 1% 1% 84% 35VDC Max. 200pcs None None None
AE1500C-48S +58.8VDC +55.2VDC 10A Max. 1% 1% 84% 70VDC Max. 200pcs None None None
Charging curve
VDC Rescue Floating
Series AE1360CS AE1500CS Charge
Constant
Current
Constant Voltage
Charge
A
Type 24V 48V 24V 48V 1
Code 2 a
a (A) 15 7.5 20 10
1 (VDC) 14.7 29.4 14.7 29.4
3
2 (VDC) 13.8 27.6 13.8 27.6
3 (VDC) 16 32 16 32
P.24
Custom - Made Products
LED Application
LCD Application
Battery Charger