merL o PVC /I/SULATED CABLES o

CONSTRUCTION
CONDUCTOR PLAIN ANNEALED COPPER CONDUCTOR
INSULATION PVC
COLOUR OF INSULATION RED, YELLOW BLUE, GREEN, BLACKAND WHITE
SHEATH PVC
COLOUR OF CORES SINGLE-CORE RED OR BLACK, OTHER COLOURS
UPON REQUEST
TWIN-CORE REDAND BLACK
THREE-CORE RED, YELLOWAND BLUE
FOUR.CORE RED, YELLOW BLUEAND BLACK
COLOUR OF SHEATH BLACIVWHITE/R ED
PVG-I NSU LATED, NON-SHEATHED GABLES.
450 /,750 VOLTS
MAXIMUM CONDUCTOR TEMPERATURE: 70 OC
Max. Conductor
Resistance at 20"C
Cross Approx.
Sectional Insulation Overall Plain Minimum Approx.
Area Thickness Diameter Annealed Insulation Weight
of Conductor (Upper Limit) Copper Resistance at 70 "C Per 100 Meter

mmt mm mm Q/Km MQ/Km Kg

1.5 0.1 3.3 12.r0 0.0110 2.r


ii
I .5 'i ,
"^'11,1
r.tl..fll . 0.7 3.5 t2.10 0.0100 2.r
2.5 0.8 3.9 7 .4r 0.0100 3.3
;J
2.5 " "r 'trJ. 0.8 4.2 7 .4r 0.0090 3.2
4 0.8 4.8 4.6r 0.0077 4.9
6 0.8 5.4 3.08 0.0065 6.9
10 1.0 6.8 I .83 0.0065 11.6
T6 1.0 8.0 1.15 0.0050 n.9
25 t.2 9.8 0.727 0.0050 28.0
35 t.2 11.0 0.524 0.0040 37 .5

50 r.4 13.0 0.3 87 0.0045 s0.5


70 1,4 15.0 0.268 0.0035 7 1.5

95 r.6 r7 .0 0.193 0.003s 98.5


r20 1.6 r 9.0 0.153 0.0032 t22.0
150 1.8 2r.0 0.r24 0.0032 150.5
r85 2.0 23.5 0.0991 0.0032 188.5

240 2.2 26.5 0.07 54 0.0032 246.0


300 2.4 29.s 0.060 r 0.0030 307 .5

400 2.6 33.5 0.0470 0.0028 39 r.5


500 2.8 37.0 0.0366 0.0028 499.2

630 2.8 4r.0 0.0283 0.0025 634.3


* r.25 0.7 3.5 14.6 0.0r 10 2.0
* Product produce according to Mega Kabel specification.
Notes : Current rating and voltage drop refer to Page A- 1
.J'h Page 2

MEcA
5*F.trL O PVC /I/SULATED CABLES o

PVG-I NSULATED, PVG-SH EATH ED GABLES.


300 / 500 vours
MAXIMUM CONDUCTOR TEMPERATURE: 70 OC
Approx. Overall Max. Conductor
Diameter Resistance at 20 "C
Cross Minimum Approx.
Sectional Insulation Lower
Sheath Upper Plain Insulation Weight
Area Thickness Thickness Limit Limit Annealed Resistance Per
of Conductor
Copper at70 "C 100 Meter
mmt mm mm mm mm Q/Km MQ/Km Kg

1.5 0.7 0.8 4.2 4.9 12.r0 0.0110 3.6


1.5 0.7 0.8 4.3 5.0 t2.10 0.0100 3.5

2.5 0.8 0.8 4.8 5.8 1 .4r 0.0 100 4.8


2.5 0.8 0.8 5.0 6.0 7 .4r 0.0090 4.1
4 0.8 0.9 5.4 6.8 4.61 0.0071 7.1

6 0.8 0.9 6.0 1.4 3.08 0.0065 9.4


10 1.0 0.9 7.2 8.8 I .83 0.0065 t4.5
r6 1.0 1.0 8.4 r 0.5 1.15 0.00s2 22.0

25 r.2 l.l r 0.0 12.5 0.127 0.0050 32.1

35 r.2 l.l I 1.0 r 3.5 0.524 0.0044 43.4


* 1.25 0.7 0.8 4.3 5.1 14.6 0.01 10 3.3
* Product produce according to Mega Kabel specification.

600/1000 vours

Nominal Insulation Sheath Approx. Approx.


Area Thickness Thickness Overall Cable
of Conductor Diameter Weight

mm' mm mm mm Kg/km

50 r.4 r.4 15. l 592


70 t.4 r.4 16.9 808
95 1.6 1.5 t9.4 I 100

120 1.6 1.5 2r.0 I 353


150 1.8 r.6 23.2 1658

r85 2.0 1.7 25.8 2065


240 2.2 1.8 29.0 268r
300 2.4 r.9 32.1 333s
400 2.6 2.0 35.8 42t9
500 2.8 2.r 39.6 5268
630 2.8 2.2 43.8 668 I

Notes Current rating and voltage drop refer to Page A- I


Page 3

^a"h
5/t+,
ME,CA
,sB*rF . PVC /I/SULATED CABLES O

PVG-I NSU LATED, PVG-SH EATH ED GABLES.


300/500 voriTs
oC
MAXIMUM CONDUCTOR TEMPERATURE z 70
Approx. Overall Max. Conductor
Diameter Resistance at 20'C
Cross Minimum Approx.
Sectional Insulation Sheath Lower Upper Plain Tinned Insulation Weight
Area Thickness Thickness Limit Limit Annealed Annealed Resistance Per
of Conductor Copper Copper at 70 "C 100 Meter
mm' mm mm mm mm Q/Km Q/I(m MQ/Km Kg
1.5 0.7' r.2 7.6 10.0 12.r0 12.20 0.0110 10.3

1.5 0,7 r.2 7.8 r0.2 12.IO 12.20 0.0100 t0.4


2.5 0.8 1,2 8.8 11.5 I .41 7 .56 0.0100 14.4

2.5 0.8 1,2 9.2 t2.0 7 .4r 7 .56 0.0090 14.l


4 0.8 1,2 9.7 12.5 4.6r 4.70 0.0085 19.6

6 0.8 1,2 r0.l 14.0 3.08 3.1r 0.0065 25.4


10 1.0 t.4 13.8 t7 .5 1.83 1.84 0.0065 4r.3
2.5 x 2C (Flat Twin) 0.8 1.0 5.4 x 8.9 6.4 x I 1.5 7 .4r 0.0100 l 1.0

600nooo vot,Ts

Nominal Thickness Thickness Approx. Approx.


Area Shape of of Overall Cable
of Conductor of Conductor Insulation Sheath Diameter Weight

mmt mm mm mm Kg/km

T6 C.C. 1.0 1.8 18.6 601

25 S.S. 1.2 1.8 18.4 880

25 C.C. 1.2 1.8 22.1 923


35 S.S. 1.2 1.8 20.r 920
50 S.S. r.4 1.8 22.8 t220
70 S.S. 1,4 1.9 25.5 1670

95 S.S. r.6 2.0 29.3 2270

t20 S.S. 1.6 2.r 31.8 2800

150 S.S. 1.8 2.2 35. I 34r0


185 S.S. 2.0 2.4 39.1 4210
240 S.S. 2.2 2.5 43.9 5560

300 S.S. 2.4 2.7 48.7 6930


400 S.S. 2.6 2.9 54.2 8770
Colours for core identification: red and black.
Black sheath.
Shape : C.C. : Circular Compacted Stranded Conductor (Class 2).
C.S. : Circular Stranded Conductor (Class 2).
S.S. : Shaped Stranded Conductor (Class 2).
Notes : Current rating and voltage drop refer to Page A- 3
Page 4

^JA
5/t,
MtrGA
5*u_T?1, O PVC /I/SULATED CABLES O

PVG-I NSULATED, PVG-SHEATHED GABLES.


300 1500 vours
MAXIMUM CONDUCTOR TEMPERATURE: 70 OC
Approx. Overall Max. Conductor
Diameter Resistance at 20 oC
Cross Minimum Approx.
Sectional Insulation Sheath Lower Upper Plain Tinned Insulation Weight
Area Thickness Thickness Limit Limit Annealed Annealed Resistance Per
of Conductor Copper Copper at 70 "C 100 Meter
mmt mm mm mm mm Q/Km O/Km MC)/Km Kg

1.5 0.1 r.2 8.0 10.5 12.l t2.2 0.01 10 12.3


1.5 0.1 1.2 8.3 r 0.8 L2.l 12.2 0.0100 I 3.0

2.5 0.8 t.2 9.2 t2.0 7 .41 L56 0.0100 17 .4

2.5 0.8 t.2 9.8 t2.6 7 .4r 7 .56 0.0090 t7 .2

4 0.8 t.2 r0.2 13.0 4.61 4.70 0.008s 24.0

6 0.8 1.4 II.7 r 5.5 3.08 3.11 0.006s 32.0

t0 1.0 1.4 t4.3 19.0 r .83 I .84 0.0065 52.4

60011000 vol;Ts

Nominal Thickness Thickness Approx. Approx.


Area Shape of of Overall Cable
of Conductor of Conductor Insulation Sheath Diameter Weight

mmt mm mm mm Kg/km

t6 C.C. 1.0 r.8 19.1 750


25 S.S. t.2 1.8 20.4 l 069

25 C.C. 1.2 r.8 23.5 l 090

35 S.S. t.2 1.8 22.4 l 360

50 S.S. t.4 1.8 25.5 l8 10


70 S.S. t.4 1.9 28.7 2480
95 S.S. T,6 2.1 3 3.3 3390
r20 S.S. t.6 2.2 36.3 4180
150 S.S. 1.8 2.3 40.0 5r l0
185 S.S. 2.0 2.5 44.6 64r0
240 S.S. 2.2 2.6 50. r 8 150

300 S.S. 2.4 2.8 55.6 10 140

400 S.S. 2.6 3.1 62.2 t2860

Colours for core identification: red. yellow and blue.


Black sheath.
Shape : C.C. : Circular Compacted Stranded Conductor (Class 2).
C.S. : Circular Stranded Conductor (Class 2).
S.S. : Shaped Stranded Conductor (Class 2).
Notes : Cunent rating and voltage drop refer to Page A-3
.Jh
55/t,
ME,CA
_ry*u_Ft- O PVC /I/SLILATED CABLES o

PVG-INSULATED, PVG.SHEATHED GABLES.


300 / 500 vouTs
MAXIMUM CONDUCTOR TEMPERATURE: 70 OC
Approx. Overall Max. Conductor
Diameter Resistance at 20'C
Cross Minimum Approx.
Sectional Insulation Lower
Sheath Upper Plain Tinned Insulation Weight
Area Thickness Thickness Limit Limit Annealed Annealed Resistance Per
of Conductor Meter
Copper Copper at70 "C 100

mmt mm mm mm mm f)/Km Q/Km MC'/Krn Kg

1.5 0.7 1.2 8.8 I1.5 t2.l 12.20 0.0110 I 5.0


1.5 0.7 t.2 9.r 11.8 t2.l 12.20 0.0100 15.3

2.5 0.8 1.2 t0.2 r 3.0 7 .41 t .56 0.0 r 00 2r.4


2.5 0.8 t.2 10.8 l 3.6 7 .41 7 .56 0.0090 2r.5
4 0.8 t.4 n.2 r4.5 4.6r 4.10 0.0085 3 1.0

6 0.8 1.4 12.8 n.0 3.08 3.1l 0.0065 4t.0


l0 1.0 1.4 I 5.8 20.5 r .83 1.84 0.006s 66.0

600/1000 voLTs

Nominal Thickness Thickness Approx. Approx.


Area Shape of of Overall Cable
of Conductor of Conductor Insulation Sheath Diameter Weight

mmt mm mm mm Kg/km

l6 C.C. 1.0 r.8 2t.6 960


25 S.S. 1.2 1.8 22.9 1381
25 C.C. 1.2 1.8 25.9 r 400

35 S.S. t.2 1.8 25.4 I 808

50 S.S. 1.4 r.9 29.2 2450


70 S.S. T,4 2.0 33.0 3 350
95 S.S. 1.6 2.2 3 8.3 45 80

120 S.S. 1.6 2.3 41.8 5630


150 S.S. 1.8 2.5 46.3 6920
r85 S.S. 2.0 2.6 5 1.3 8640
240 S.S. 2.2 2.8 5 8.0 t1290
300 S.S. 2.4 3.1 64.6 r4095
400 S.S. 2.6 3.3 72.0 r 7860

Colours for core identification: red. vellow. blue and black.


Black sheath.
Shape : C.C. : Circular Compacted Stranded Conductor (Class 2).
C.S. : Circular Stranded Conductor (Class 2).
S.S. : Shaped Stranded Conductor (Class 2).
Notes : Current rating and voltage drop refer to Page A- 3
.a"h Page 6

5/,+,
MEGA
-5*F,trI-, o PVC INSULATED, PVC SHEATHED ARMOURED CABLES o

CONSTRUCTION
CONDUCTOR PLAIN ANNEALED COPPER CONDUCTOR
INSULATION PVC
BEDDING PVC
ARMOUR GALVANISED STEELWIRES
SHEATH PVC
COLOUR OF CORES TWIN-CORE RED AND BLACK
THREE.CORE RED, YELLOW AND BLUE
FOUR-CORE RED. YELLOW. BLUEAND BLACK
COLOUR OF SHEATH : BLACK
PVG-I NSU LATED, PVC-SH EATH E D ARM OU RED GABLES.
600 / {ooo voLTs
Extruded
Bedding

Thickness Thickness Nominal Thickness Approx. Approx.


Nominal of of armour of Overall Cable
Area Shape Insulation Extruded wire Oversheath Diameter wt.
of Conductor of Conductor Bedding diameter
mmt mm mm mm mm mm Kg/km

1.5 C.S. 0.6 0.8 0.9 r.3 tI.7 279


1.5 C.C. 0.6 0.8 0.9 r.4 12.3 300
2.5 C.S. 0.1 0.8 0.9 r.4 l3.l 347
2.5 C.C. 0.7 0.8 0.9 t.4 r 3.6 349
4 C.C. 0.8 0.8 0.9 1.4 15. I 434
6 C.C. 0.8 0.8 0.9 1.5 16.5 520
10 C.C. 1.0 0.8 r.25 1.6 20.r 800
r6 C.C. 1.0 0.8 r.25 1.6 21.9 960
25 S.S. r.2 1.0 1.6 r.l 23 1435
25 C.C. 1.2 1.0 1.6 t.7 26.1 r435
35 S.S. r.2 1.0 1.6 1.8 24.9 r 680
50 S.S. t.4 1.0 1.6 t.9 27.8 2100
70 S.S. 1.4 1.0 1.6 r.9 30.4 2640
95 S.S. 1.6 1.2 2.0 2.1 35.5 3680
t20 S.S. t.6 1.2 2.0 2.2 3 8.0 43r0
150 S.S. 1.8 r.2 2.0 2.3 4r.3 5060
r85 S.S. 2.0 r.4 2.s 2.4 46.4 6570
240 S.S. 2.2 t.4 2.5 2.5 5r.2 8110
300 S.S. 2.4 r.6 2.5 2.7 56.4 9190
400 S.S. 2.6 1.6 2.5 2.9 6r.9 1r850
Colours for core identification: red and black.
Black sheath.
Shape : C.C. : Circular Compacted Stranded Conductor (Class 2).
C.S. : Circular Stranded Conductor (Class 2).
S.S. : Shaped Stranded Conductor (Class 2).
Notes : Current rating and voltage drop refer to Page A-5
.J"k
5/1,
Mtrc,A..
-_5,+u_FL o PVC INSUIATED, PVC SHEATHED ARMOARED CABLES O

PVG-I NSU LATE D, PVG-SH EATH ED AMOURED CABLES.


600 t{ooo volTs
Extruded
Bedding

Thickness Thickness Nominal Thickness Approx. Approx.


Nominal of of armour of Overall Cable
Area Shape Insulation Extruded wire Oversheath Diameter wt.
of Conductor of Conductor Bedding diameter
mmt mm mm mm mm mm Kg/km

1.5 C.S. 0.6 0.8 0.9 1.4 12.3 32r


1.5 C.C. 0.6 0.8 0.9 r.4 12.8 3t9
2.5 C.S. 0.1 0.8 0.9 t.4 13.6 402
2.5 C.C. 0.7 0.8 0.9 T,4 t4.l 392
4 C.C. 0.8 0.8 0.9 r.4 l 5.8 485

6 C.C. 0.8 0.8 r.25 1.5 18.0 690


l0 C.C. 1.0 0.8 t.25 r.6 2r.2 920
r6 C.C. 1.0 0.8 r.25 T,6 23.r r200
25 S.S. 1.2 1.0 t.6 t.7 25.0 177 0

25 C.C. t.2 1.0 1,6 t.7 28.2 1843

35 S.S. 1.2 1.0 r.6 1.8 27.3 2230

50 S.S. 1.4 1.0 1.6 r.9 30.5 28r8


l0 S.S. t.4 t.2 2.0 2.0 35.0 3900

95 S.S. t.6 t.2 2.0 2,7 39.3 4990

t20 S.S. t.6 T,2 2.0 2.2 42.2 59 10

r50 S.S. 1.8 t.4 2.5 2.4 47 .5 7 530

185 S.S. 2.0 r.4 2.5 2.5 5 r.9 9060

240 S.S. 2.2 r.6 2.5 2.6 57.8 11410

300 S.S. 2.4 1.6 2.5 2.8 63.2 r 3780

S.S. 2.6 1.6 2.5 3.0 69.6 r6232

Colours for core identification: red, vellow and blue.


Black sheath.
Shape : C.C. : Circular Compacted Stranded Conductor (Class2).
C.S. : Circular Stranded Conductor (Class 2).
S.S. : Shaped Stranded Conductor (Class 2).
Notes : Current rating and voltage drop refer to Page A-5
^a^h
5/t,
MEcA
-*P.flr o PVC INSUIATED, PVC SHEATHED ARMOURED CABLES O

pvG-tNsuLATED, PVG-SHEATHED ARMOURED CABLES.


600 / {ooo volTs
Extruded
Bedding

Thickness Thickness Nominal Thickness Approx. Approx.


Nominal of of armour of Overall Cable
Area Shape
Insulation Extruded wire Oversheath Diameter wt.
of Conductor
Bedding diameter
of Conductor

mmt mm mm mm mm mm Kg/km

1.5 C.S. 0.6 0.8 0.90 r.4 l 3.0 357

1.5 C.C. 0.6 0.8 0.90 r.4 l 3.5 357

2.5 C.S. 0.1 0.8 0.90 t.4 t4.5 447

2.5 C.C. 0.1 0.8 0.90 1.4 r 5.0 450

4 C.C. 0.8 0.8 l .25 1.5 17.8 670

6 C.C. 0.8 0.8 r.25 1.5 t9.2 170

t0 C.C. 1.0 0.8 1.25 1.6 22.8 I 083

I6 C.C. 1.0 1.0 r.60 r.7 26.3 1587

25 S.S. t.2 1.0 r.60 1.8 21 .8 2r88


25 C.C. t.2 1.0 1.60 1.8 30.7 2t54
3s S.S. t.2 1.0 1.60 1,9 30.5 2139

50 S.S. t.4 t.2 2.00 2.0 35.4 31 46

l0 S.S. 1,4 1.2 2.00 2.1 39.2 4198

95 S.S. r.6 t.2 2.00 2.2 44.3 6n4


r20 S.S. 1.6 r.4 2.50 2.4 49.3 197 6

150 S.S. r.8 r.4 2.50 2.5 5 3.6 9630

185 S.S. 2.0 r.6 2.50 2.6 59.0 n392


240 S.S. 2.2 r.6 2.50 2.8 65.7 t44r4
300 S.S. 2.4 r.6 2.50 3.0 72.0 ll 502
400 S.S. 2.6 1.8 3.15 3.3 81.3 21467

Colours for core identification: red, yellow, blue and black.


Black sheath.
Shape : C.C. : Circular Compacted Stranded Conductor (Class 2).
C.S. : Circular Stranded Conductor (Class 2).
S.S. : Shaped Stranded Conductor (Class 2).
Notes : Current rating and voltage drop refer to Page A-5
Page 9

^J'h
55/t+,
ME,CA
.-5*B_FL O PVC INSULATED. PVC SHEATHED ARMOURED AUXILIARY CABLES o

CONSTRUCTION
CONDUCTOR PLAIN ANNEALED COPPER CONDUCTOR
INSTJLATION PVC
BEDDING PVC
ARMOTJR GALVANISED STEEL WIRES
SHEATH PVC
COLOUR OF CORES WHITE WITH BLACK NUMBERING
COLOUR OF SHEATH BLACK

PVC-|NSULATED, PVG-SHEATHED ARMOURED AUXTLIARY CABLES.


600 t{ooo volTs
Extruded Bedding

Number Nominal Thickness Thickness Nominal Thickness Approx. Approx.


of Area of of Extruded armour of Overall Cable
cores of Conductor Insulation Bedding wire diameter Oversheath Diameter wt.
n mmt mm mm mm mm mm kg/km

5 0.8 0.90 | 4.3 453

0.8 0.rx) 15.2 525


r0 0.8 r .25 19.0 815

t2 1.5 0.6 0.8 125 t9.4 819


l9 0.8 l .25 22.2 I I4l
27 1.0 I .6t) 26.7 168 I

37 1.0 1.60 29.2 2042


-18 1.0 1.60 32.9 247 6

5 0.8 0.90 16.3 603


l 0.8 1.25 l 8.0 854
l0 0.8 1.25 2r.9 I 043
ll 2.5 0.7 0.8 t.25 22.4 TT4I

l9 1.0 1.60 26.6 l7l0


27 r.0 1.60 30.7 2t99
3l 1.0 1.60 34.0 27 tl
.+8 t.2 2.00 39.5 3689
Page 10

^a.h
5/+,
ME,GA
mBr;,Ek o XLPE INSAI-ATED, PVC SHEATHED CABLES o

CONSTRUCTION
CONDUCTOR PLAIN ANNEALED COPPER CONDTJCTOR
INSULATION XLPE (CROSS-LTNKED POLYETHYLENE) RATED 900C
SHEATH PVC
COLOUR OF CORES SINGLE-CORE : NATTJRAL. RED OR BLACK. OTHER
COLOURS UPON REQUEST
TWIN-CORE : RED AND BLACK
THREE-CORE : RED. YELLOWAND BLUE
FOUR-CORE : RED. YELLOW BLUEAND BLACK
COLOUR OF SHEATH : BLACK

XLPE TNSULATED, PVC-SHEATHED GABLES.


600 / {ooo voLTs
Cross
Sectional Insulation Sheath Approx. Approx.
Area Shape Thickness Thickness Overall Cable
of Conductor of Conductor Diameter Weight

mmt mm mm mm Kg/km

I6 C.C. 0.7 l.-t 9.1 2r0


25 C.C. 0.9 I.-t I 1.0 310
35 C.C. 0.9 I .-l t2.3 410
50 C.C. 1.0 l .-1 13.1 540
l0 C.C. l.l r.1 15.1 750
95 C.C. 1.1 1.5 l 7.8 l 020

t20 C.C. t.2 1.5 19.1 1260


150 C.C. t.4 1.6 21.9 l 560

185 C.C. 1.6 1.6 24.1 r920


240 C.C. t.7 1.7 27 .l 2470
300 C.C. 1.8 1.8 30.5 3090
400 C.C. 2.0 1.9 3 3.5 40r0
500 C.C. 2.2 2.0 37 .4 5035
630 C.C. 2.4 ')) 42.0 6500

Shape C.C. : Circular Compacted Stranded Conductor (Class 2).


Notes Current rating and voltage drop refer to Page A-2
Page 1 1

^a'h
5/4t
MEGA
.,5*8..trL . XLPE INSAI-ATED, PVC SHEATHED CABLES o

xLpE INSULATED, PVG SHEATHED GABLES.


1[ffi,'l
I

GOO

Cross
Sectional Insulation Sheath Approx. Approx.
Area Shape Thickness Thickness Overall Cable
of Conductor of Conductor Diameter Weight

mmt mm mm mm Kg/km

r.5 C.S. 0.7 1.8 10.5 r20


2.5 C.S. 0.7 1.8 11.5 150

4 C.S. 0.7 1.8 12.5 195

6 C.C. o.7 1.8 13.5 250


10 C.C. 0.7 1.8 1 5.5 355

l6 C.C. 0.7 1.8 17 .4 475

25 S.S. 0.9 r.8 r7 .6 635

35 S.S. 0.9 1.8 18.5 835

50 S.S. 1.0 1.8 2r.0 tI20


70 S.S. 1.1 1.8 23.5 r545
95 S.S. 1.1 r.9 26.5 2070
r20 S.S. t.2 2.0 29.0 2580

150 S.S. r.4 2.2 32.5 3200


185 S.S. r.6 2.3 35.5 3955

240 S.S. r.7 2.5 39.s 5 150

300 S.S. r.8 2.6 44.0 6470


400 S.S. 2.0 2.9 50.0 8 150

Colours for core identification: red and black.

Black sheath.
Shape : C.S. : Circular Stranded Conductor (Class 2).
C.C. : Circular Compacted Stranded Conductor (Class 2).
S.S. : Shaped Stranded Conductor (Class 2).
Notes : Current rating and voltage drop refer to Page A-4
.a"k Page 12

5/,+,
ME,GA
MPIFI. o XLPE INSULATED, PVC SHEATHED CABLES.

XLPE TNSULATED, pVG SHEATHED GABLES.


600 / {ooo volTs
Cross
Sectional Insulation Sheath Approx. Approx.
Area Shape Thickness Thickness Overall Cable
of Conductor of Conductor Diameter Weight

mmt mm mm mm Kg/km

1.5 C.S. 0.7 1.8 I 1.5 r49


2.5 C.S. 0.1 1.8 12.0 185

4 C.S. 0.7 1.8 I 3.0 240


6 C.C. 0.7 1.8 r4.5 315

10 C.C. 0.7 1.8 16.5 465

I6 C.C. 0.7 r.8 18.0 645

25 C.C. 0.9 1.8 20.6 905

35 S.S. 0.9 1.8 21.3 12r0


50 S.S. 1.0 r.8 24.0 r 600

70 S.S. l.l 1.9 27 .5 2260


95 S.S. l.l 2.0 31.0 3030

r20 S.S. 1.2 2.1 34.0 3875

150 S.S. t.4 2.3 39.r 4700

r85 S.S. 1.6 2.4 41.5 58 10

240 S.S. r.7 2.6 47 .0 7 570

300 S.S. 1.8 2.8 5 1.0 93s0


400 S.S. 2.0 3.0 57 .5 I 2000

Colours for core identification: red, yellow and blue.


Black sheath.

Shape C.S. : Circular Stranded Conductor (Class 2).


C.C. : Circular Compacted Stranded Conductor (Class 2).
S.S. : Shaped Stranded Conductor (Class 2).
Notes Current rating and voltage drop refer to Page A-4
Page 13

^a"h
5/*,
MEGA
,*B,.PI. o XLPE INSULATED, PVC SHEATHED CABLES o

XLPE INSULATED, PVG SHEATHED GABLES.


600 / {ooo vouTs
Cross
Sectional Insulation Sheath Approx. Approx.
Area Shape Thickness Thickness Overall Cable
of Conductor of Conductor Diameter Weight

mm' mm mm mm Kg/km

1.5 C.S. 0.7 1.8 12.5 175


2.5 C.S. 0.7 r.8 13.5 220
4 C.S. 0.7 1.8 14.5 300
6 C.C. 0,7 1.8 16.0 395
10 C.C. 0.7 1.8 r7 .5 580
I6 C.C. 0.7 1.8 19.5 840
25 C.C. 0.9 1.8 22.9 r200
35 S.S. 0.9 1.8 24.r r592
50 S.S. 1.0 1.9 27.0 2r00
70 S.S. 1.1 2.0 3r.2 3012
95 S.S. 1.1 2.r 35.0 4050
t20 S.S. t.2 2.3 3 8.0 5020
r50 S.S. r.4 2.4 42.5 6020
r85 S.S. 1.6 2.6 48.0 17 I0
240 S.S. 1.7 2.8 54.r 10050

300 S.S. 1.8 3.0 6r.6 r2400


400 S.S. 2.0 3.3 67.0 16100

Colours for core identification: red, yellow, blue and black


Black sheath.
Shape : C.S. Circular Stranded Conductor (Class 2).
C.C. Circular Compacted Stranded Conductor (Class2).
S.S. : Shaped Stranded Conductor (Class 2).
Notes : Current rating and voltage drop refer to Page A-4
.J'h Page 14

5/+,
MEGA
HF,.rI. o XLPE INSALATED, PVC SHEATHED ARMOARED CABLES o

CONSTRUCTION
CONDUCTOR PLAIN ANNEALED COPPER CONDUCTOR
INSULATION xLpE (cRoss-LTNKED poLyETHyLENE) RATE 900C
BEDDING PVC
ARMOUR GALVANISED STEELWIRES
SHEATH PVC
COLOUR OF CORES TWIN-CORE : RED AND BLACK
THREE-CORE : RED, YELLOWAND BLUE
FOUR-CORE : RED, YELLOW BLUE AND BLACK
COLOUR OF SHEATH BLACK

XLPE TNSULATED, PVG SHEATHED ARMOURED GABLES.


600 / {ooo vol.Ts
Cross
Sectional Insulation Nominal Approx.
Sheath Approx.
Area Shape Thickness diameter of Thickness Overall Cable
of Conductor of Conductor steel wire Diameter Weight

mmt mm mm mm mm Kg/km

1.5 C.S. 0.7 0.9 1.8 t4.5 345


2.5 C.S. 0.7 0.9 1.8 r 5.5 390
4 C.S. 0.1 0.9 1.8 16.5 450
6 C.C. 0.7 0.9 1.8 18.0 530
10 C.C. 0.7 0.9 1.8 19.5 675
I6 C.C. 0.7 0.9 1.8 2r.5 800
25 S.S. 0.9 T,6 1.8 22.5 r230
35 S.S. 0.9 r.6 1.8 24.0 1480

50 S.S. 1.0 r.6 1.8 26.5 l 840

70 S.S. l.l t.6 2.0 29.5 2450


95 S.S. 1.1 2.0 2.1 3 3.0 32r0
r20 S.S. 1,2 2.0 2.2 36.0 3 850
150 S.S. r.4 2.0 2.3 39.5 4650
185 S.S. r.6 2.5 2.5 44.0 5880
240 S.S. t.7 2.5 2.7 48.0 1260
300 S.S. 1.8 2.5 2.8 52.5 8t 40
400 S.S. 2.0 2.5 3.1 5 8.5 I 1405
Colours for core identification: red and black.
Black sheath.
Shape : C.S. : Circular Stranded Conductor (Class 2).
C.C. : Circular Compacted Stranded Conductor (Class 2).
S.S : Shaped Stranded Conductor (Class 2).
Notes : Current rating and voltage drop refer to Page ,{-6
Page 15

^a^k
5/t+
MEGA
$t",Et o XLPE INSULATED, PVC SHEATHED ARMOURED CABLES o

XLPE TNSULATED, PVG SHEATHED ARMOURED GABLES.


600 / {ooo volTs
Cross
Sectional Insulation Nominal Sheath Approx. Approx.
Area Shape Thickness diameter of Thickness Overall Cable
of Conductor of Conductor steel wire Diameter Weight

mmt mm mm mm mm Kg/km

1.5 C.S. 0.7 0.9 r.8 15.5 380

2.5 C.S. 0.7 0.9 1.8 16.0 430

4 C.S. 0.7 0.9 1.8 r7 .5 515

6 C.C. 0.7 0.9 1.8 18.5 610

10 C.C. 0.7 0.9 1.8 20.0 190


I6 C.C. 0.7 0.9 1.8 22.0 1030

25 C.C. 0.9 r.6 1.8 26.0 t670


35 S.S. 0.9 1.6 1.8 26.5 I 930

50 S.S. 1.0 1.6 1.8 29.5 2450


70 S.S. 1.1 2.0 2.0 34.0 3440
95 S.S. t.l 2.0 2.2 37 .5 4380
r20 S.S. 1.2 2.0 2.3 40.0 5450

150 S.S. r.4 2.5 2.5 45.0 6680

185 S.S. 1.6 2.5 2.6 49.5 8050

240 S.S. r.7 2.5 2.8 55.0 l0l 80

300 S.S. 1.8 2.5 3.0 59.5 r2t50


400 S.S. 2.0 2.5 3.2 66.s 1 5540

Colours for core identification: red, yellow and blue.


Black sheath.

Shape C.S. : Circular Stranded Conductor (Class 2).


C.C. : Circular Compacted Stranded Conductor (Class 2).
S.S. : Shaped Stranded Conductor (Class 2).
Notes Current rating and voltage drop refer to Page 4.-6
.a'h Page 16

5/#,
MEGA
5fT',-:L o XLPE INSULATED, PVC SHEATHED ARMOURED CABLES o

xLPE-l NSU LATED, PVG-SH EATH E D ARMOURED GABLES.


600 t{ooo vours
Cross
Sectional Insulation Nominal Sheath Approx. Approx.
Area Shape Thickness diameter of Thickness Overall Cable
of Conductor of Conductor steel wire Diameter Weight

mm' mm mm mm mm Kg/km

1.5 C.S. 0.7 0.9 1.8 16.0 420


2.5 C.S. 0.7 0.9 1.8 t7 .0 485
4 C.S. 0.7 0.9 1.8 r 8.5 590
6 C.C. 0.7 0.9 1.8 19.5 715
10 C.C. 0.7 0.9 1.8 2t.5 940
T6 C.C. 0.7 1.6 1.8 24.5 I 480
25 C.C. 0.9 1.6 1.8 28.0 t957
35 S.S. 0.9 1,6 t.9 29.5 2400
50 S.S. 1.0 r.6 2.0 32.5 3 160

70 S.S. 1.1 2.0 2.2 38.0 4320


95 S.S. 1.1 2.0 2.3 4t.0 5500
r20 S.S. 1.2 2.5 2.5 46.0 7120
150 S.S. r.4 2.5 2.6 5 1.0 8550
185 S.S. r.6 2.5 2.8 s 8.0 l 0400

240 S.S. L.l 2.5 3.0 64.0 13 100

300 S.S. 1.8 2.5 3.2 68.0 15800


400 S.S. 2.0 3.2 3.5 t7 .0 2IT2O

Colours for core identification: red. vellow blue and black.


Black sheath.

Shape C.S. : Circular Stranded Conductor (Class 2).


C.C. : Circular Compacted Stranded Conductor (Class 2).
S.S. : Shaped Stranded Conductor (Class 2).
Notes Current rating and voltage drop refer to Page A-6
.a'h Page 17

55/t,
ME,CA
5,'+P.rI' . SINGLE CORE, XLPE INSULATED. PVC SHEATHED ARMO(IRED CABLES .

CONSTRUCTION
CONDUCTOR PLAIN ANNEALED COPPER CONDUCTOR
INSULATION XLPE (CROSS-LINKED POLYETHYLENE) RATED 900C
BEDDNG PVC

ARMOUR HARD-DRAWN ALUMINIUM WIRE


SHEATH PVC

COLOIJR OE SHEATH : BLACK

XLPE INSULATED, PVG-SHEATHED ARMOURED GABLES.


600 l{ooo volTs
Extruded
Bedding

Nominal Thickness Thickness Nominal Thickness Approx. Approx.


Area Shape
of of armour of Overall Cable
Insulation Extruded wire Oversheath Diameter wt.
of Conductor of Conductor diameter
Bedding
mmt mm mm mm mm mm Kg/km

50 C.C. 1.0 1.0 t.25 1.8 19.0 750


70 C.C. l.l r.0 t.25 1.8 20.5 980

95 C.C. l.l 1.0 t.6 1.8 22.s r270


t20 C.C. t.2 1.0 t.6 1.8 24.0 I 570

150 C.C. 1.4 1.0 t.6 1.8 26.5 l 890

185 C.C. 1.6 1.0 1.6 1.8 28.5 2300


240 C.C. 1.7 1.0 1.6 1.9 32.5 2900
300 C.C. r.8 1.0 r.6 1.9 34.s 3 6s0
400 C.C. 2.0 t.2 2.0 2.r 39.s 4600

500 C.C. 2.2 t.2 2.0 2.2 43.0 5700

630 C.C. 2.4 t.2 2.0 2.3 49.s 7 400

800 C.C. 2.6 1.4 2.5 2.5 55.0 9360


l 000 C.C. 2.8 1.4 2.5 2.7 6l .0 11600

Shape C.C. : Circular Compacted Stranded Conductor (Class 2).


Notes Current rating and voltage drop refer to Page A-l
SINGLE CORE PVC INSULATED CABLE
SINGLE CORE PVC INSULATED PVC VoLTAGE 300/500 V, 4501750V OR 600/1000V
SHEATHED CABLE AMBIENT TEMPERATURE 3O"C
CONDUCTOR OPERATING TEMPERATURE 7O"C

Enclosed In Gonduit or In Trunking On Perforated Cable Tray


Size of 2 cables 1- phase 3 or 4 cables 3- phase
Gonductor 2 cables 1- phase ac, touching
ac or dc
ac or dc
flat and touching Trefoil
( mm') (amp) (amp) (amp) (amp) (amp)

1.0 13.5 12
1.5 17.5 15.5
2.5 24 21
4 32 28
6 41 36
10 57 50
16 76 68
25 101 89 131 114 110
35 125 110 162 143 137
50 151 134 196 174 167
70 192 171 251 225 216
95 232 207 304 275 264
120 269 239 352 321 308
150 30q 262 406 372 356
185 341 296 463 427 409
240 400 346 546 507 485
300 458 394 629 587 561
400 546 467 754 689 656
500 626 533 868 789 749
630 720 611 1 005 905 855
800 1 086 1020 971
1 000 '1216 1149 1079

VOLTAGE DROP

2 cables 1- phase ac 3 or 4 cables 3 - phase ac


Size of
Conductor Enclosed in on cable tray, Enclosed in on cable tray, on cable tray,
conduit touching conduit flat and touching trefoil
( mm') (Mv/A/m) (Mv/A/m) (Mv/A/m) (Mv/A/m) (Mv/A/m) (Mv/A/m)

1.0 44 44 44 38 38 38
1.5 29 29 29 25 25 25
2.5 18 18 18 15 15 15
4 11 11 11 9.5 9.5 9.5
6 7.3 7.3 7.3 6.4 6.4 6.4
10 4.4 4.4 4.4 3.8 3.8 3.8
16 2.8 2.8 2.8 2.4 2.4 2.4
25 1.75 1.80 1.75 1.5s 1.55 1.50
35 1.25 1.30 1.25 1.10 1.10 1.10
50 0.93 1.00 0.95 0.85 0.84 0.82
70 0.63 0.72 0.66 0.61 0.60 0.57
95 0.46 0.56 0.50 0.48 0.47 0.43
120 0.36 0.47 0.41 0.41 0.40 0.36
150 0.29 0.41 0.34 0.36 0.34 0.30
185 0.23 0.37 0.29 0.32 0.31 o.26
240 0.180 0.33 0.25 0.29 0.27 0.22
300 0.145 0.31 0.22 0.27 0.25 0.190
400 0.105 0.29 0.20 0.25 0.24 0.17 5
500 0.086 0.28 0.185 0.2s 0.23 0.160
630 0.068 0.27 0.17 5 0.24 0.22 0.150
800 0.053 0.1 65 0.22 0.1 45
1 000 0.042 0.1 60 0.21 0.1 40
Note : Gorrection factors for ambient temperature and group installation, please refer Page B-1
.a I-
M I'C;A SINGLE CORE XLPE INSULATED PVC
11 l\IiIrl SHEATHED CABLE VOLTAGE 600/1OOO V
AMBIENT TEMPERATURE 3O"C
CONDUCTOR OPERATING TEMPERATURE gO"C

Enclosed In Gonduit or ln Trunking On Perforated Cable Tray


Size of 3 or 4 cables 3-phase
2 cables 1-phase ac
Gonductor 2 cables 1-phase 3 or 4 cables 3-phase
ac or dc
ac or dc ac touching
flat and touching
trefoil
( mm') (amp) (amp) (amp) (amp) (amp)
1.0 17 15
1.5 23 20
2.5 31 28
4 42 37
6 54 48
10 75 66
16 100 88
25 133 117 161 141 135
35 164 144 200 176 169
s0 198 175 242 216 207
70 253 222 310 279 268
95 306 269 377 342 328
120 354 312 437 400 383
150 393 342 504 464 444
185 449 384 575 533 510
240 528 4s0 679 634 607
300 603 514 783 736 703
400 683 584 940 868 823
500 783 666 1 083 998 946
630 900 764 1254 1151 1088
800 1 358 1275 1214
1 000 1520 1436 1349

VOLTAGE DROP

2 cables 1-phase ac 3 or 4 cables 3-phase ac


Size of
Conductor Enclosed in on cable tray, Enclosed in on cable tray, on cable tray
conduit touching conduit flat and touching trefoil
( mm') ( mv/A/m ) ( mv/A/m ) ( mv/A/m ) ( mv/A/m ) ( mv/A/m ) ( mv/A/m )

1.0 46 46 46 40 40 40
1.5 31 31 31 27 27 27
2.5 19 19 19 16 16 16
4 12 12 12 10 10 10
6 7.9 7.9 7.9 6.8 6.8 6.8
10 4.7 4.7 4.7 4.0 4.0 4.0
16 2.9 2.9 2.9 2.5 2.5 2.5
25 1.85 1.90 1.85 1.65 1.60 1.60
35 1.35 1.35 1.35 1.15 1.15 1.15
50 0.99 1.05 1.00 0.90 0.87 0.87
70 0.68 0.75 0.71 0.65 0.62 0.61
95 0.49 0.58 0,52 0.s0 0.46 0.45
120 0.39 0.48 0.43 o.42 0.38 0.37
1s0 0.32 0.43 0.36 0.37 0.32 0.31
185 0.25 0.37 0.30 0.32 0.28 0.26
240 0.190 0.33 0.25 0.29 0.24 o.22
300 0.155 0.31 0.22 0.27 0,21 0.195
400 0.120 0.29 0.20 0.25 0.195 0.175
500 0.093 0.28 0.185 0.24 0.180 0.160
630 0.072 0.27 0.17 5 0.23 0.170 0.150
800 0.056 0.170 0.165 0.145
1 000 0.04s 0.165 0.165 0.140
Note : Gorrection factors for ambient temperature and group installation, please refer Page B-l
.JL
55/{,
MEcA PVC INSULATED PVC SHEATHED
Kn BtlI -
MULTI-CORE CABLE
VoLTAGE 300/500V OR 600/1000 v
AMBIENT TEMPERATURE 3O"C
CONDUCTOR OPERATING TEMPERATURE 7O"C

Enclosed ln Conduit or ln Trunking On Perforated Gable Tray


Size of
two-core cable three or four-core two core cable three or four-core
Gonductor 1 phase ac or dc cable 3 phase ac
1 phase ac or dc cable 3 phase ac
( mm') (amp) (amp) (amp) (amp)
1.0 13 11.5 17 14.5
1.5 16.5 15 22 18.5
2.5 23 20 30 25
4 30 27 40 34
6 38 34 51 43
10 52 46 70 60
16 69 62 94 80
25 90 80 119 101
35 111 99 148 126
50 133 118 180 153
70 168 149 232 196
95 179 282 238
?o1
120 232 206 328 276
150 258 225 379 319
185 294 255 434 364
240 344 297 514 430
300 394 339 593 497
400 470 402 715 597

VOLTAGE DROP

Gonductor
Gross- Two-core Two-core cablen Thr- or four-Gore,
section cable,dG single-phase a.c three-phase a.c
area
( mm') ( mv/A/m ) ( mv/A/m ) ( mv/A/m )

1.0 44 44 38
1.5 29 29 25
2.5 18 18 15
4 11 11 9.5
6 7.3 7.3 6.4
10 4.4 4.4 3.8
16 2.8 2.9 2.4
25 1.75 1.75 1 .50
35 1.25 1.25 1.10
50 0.93 0.94 0.81
70 0.63 0.65 0.57
95 0.46 0.50 0.43
120 0.36 o,41 0.35
150 0.29 0.34 0.29
18s 0.23 o.29 0.25
240 0.180 0.24 o.21
300 0.1 45 o.21 0.185
400 0.105 0.185 0.160
Note : Correction factors for ambient temperature and group installation, please refer Page B-1
.JL
55fl{,
M11 CA XLPE INSULATED PVC SHEATHED
K./\tlliI -
MULTI-CORE CABLE
VOLTAGE 600/1000 V
AMBIENT TEMPERATURE 3O"C
CONDUCTOR OPERATING TEMPERATURE gO"C

Enclosed In Gonduit or ln Trunking On Perforated Gable Tray


Size of
Conductor two-core cable three or four-core two core cable three or four-core
1 phase ac or dc cable 3 phase ac 1 phase ac or dc cable 3 phase ac
( mm') (amp) (amp) (amp) (amp)
1 17 15 21 18
1.5 22 19.5 26 23
2.5 30 26 36 32
4 40 35 49 42
6 51 44 63 54
10 69 60 86 75
16 91 80 115 100
25 119 105 149 127
35 146 128 185 158
50 175 154 225 192
70 221 194 289 246
95 265 233 352 298
120 305 268 410 346
150 334 300 473 399
185 384 340 542 456
240 459 398 641 538
300 532 455 741 621
400 625 536 865 741

VOLTAGE DROP

Gonductor
cross- Two-core Two-core cable, Thr- or four-Gore,
section cable,dG single-phase a.c three-phase a.c
area
( mm') ( mv/A/m ) ( mv/A/m ) ( mv/A/m )

1.0 46 46 40
1.5 31 31 27
2.5 19 19 16
4 12 12 10
6 7.9 7.9 6.8
10 4.7 4.7 4.O
16 2.9 2.9 2.5
25 1 .85 1.90 1.65
35 1 .35 1.35 1 .15

50 0.98 1 .00 0.87


70 0.67 0.69 0.60
95 0.49 0.52 0.45
120 0.39 o.42 0.37
150 0.31 0.35 0.30
185 0.25 o.29 o.26
240 0.195 0.24 0.21
300 0.1 55 o.21 0.185
400 o.120 0.190 0.165
Note : Gorrection factors for ambient temperature and group installation, please refer Page B-1
.-L
5tt
Mtr(jA PVC INSULATED PVC SHEATHED
I\,,rI:T:I -
MULTI-CORE ARMOURED CABLE
VOLTAGE 600/1 OOO V
AMBIENT TEMPERATURE 3O'C
GROUND TEMPERATURE 2O'C
CONDUCTOR OPERATING TEMPERATURE 7O"C

On Perforated Gable Tray Direct In Ground or ln Duct ln Ground


Size of
Conductor l two- core cable 1 three or four-core two core cable 1 three or four-core
1 phase ac or dc cable 3 phase ac phase ac or dc cable 3 phase ac
( mm') (amp) (amp) (amp) (amp)
1.5 22 19 22 18
2.5 31 26 29 24
4 41 35 37 30
6 53 45 46 38
10 72 62 60 50
16 97 83 78 64
25 128 110 99 82
35 157 135 119 98
50 190 163 140 116
70 241 207 173 143
95 291 251 204 169
120 336 290 231 192
150 386 332 261 217
185 439 378 292 243
240 516 445 336 280
300 592 510 379 316
400 683 590

VOLTAGE DROP

Gonductor
cross- Two-Gore Two-core cable, Three- of four-GOren
section cable,dc single-phase a.c three-phase a.c
area

( mm') ( mv/A/m ) ( mv/A/m ) ( mv/A/m )


1.5 29 29 25
2.5 18 18 15
4 11 11 9.5
6 7.3 7.3 6.4
10 4.4 4.4 3.8
16 2.9 2.9 2.4
25 1.75 1.75 1.50
35 1.25 1.25 1.10
s0 0.93 0.94 0.81
70 0.63 0.65 0.57
95 0.46 0.50 0.43
120 0.36 0.41 0.35
150 0.29 0.34 0.29
185 0.23 0.29 0.25
240 0.1 80 0.24 0.21
300 0.145 0.21 0.1 85
400 0.1 05 0.185 0.160
Note : Correction factors for ambient temperature and group installation, please refer Page B-'l
.aA
5/n,
MEcA XLPE INSULATED PVC SHEATHED
5'+nTtl,- MULTI-CORE ARMOURED CABLE
VOLTAGE 600/1 OOO V
AMBIENT TEMPERATURE 3O"C
GROUND TEMPERATURE 20 "C
CONDUCTOR OPERATING TEMPERATURE gO"C

On Perforated Gable Tray Direct In Ground or ln Duct ln Ground


Size of
Conductor l two-core cable 1 three or four-core 1 two core cable 1 three or four-core
1 phase ac or dc cable 3 phase ac 1 phase ac or dc cable 3 phase ac
( mm') (amp) (amp) (amp) (amp)
1.5 29 25 25 21
2.5 39 33 33 28
4 52 44 43 36
6 66 56 53 44
10 90 78 71 58
16 115 99 91 75
25 152 131 116 96
35 188 162 139 115
50 228 197 164 135
70 291 251 203 167
95 354 304 239 197
120 410 353 271 223
150 472 406 306 251
185 539 463 343 281
240 636 546 395 324
300 732 628 446 365
400 847 728

VOLTAGE DROP

Conductor
Gross- Two-core Two-core cablen Three- or fouf-Gor,
section cable,dG single-phase a.c three-phase a.c
area

( mm') ( mv/A/m ) ( mv/A/m ) ( mv/A/m )


1.5 31 31 27
2.5 19 19 16
4 12 12 10
6 7.9 7.9 6.8
10 4.7 4.7 4
16 2.9 2.9 2.5
25 1.95 1.90 1.65
35 1.35 1.35 1.15
50 0.gg 1.00 0.87
70 0.67 0.69 0.60
95 0.49 0.52 0.45
120 0.39 0.42 0.37
150 0.31 0.35 0.30
185 0.25 0.29 0.26
240 0.1 95 0.24 0.21
300 0.1 55 0.21 0.1 85
400 0.120 0.1 90 0.1 65
Note : Correction factors for ambient temperature and group installation, please refer Page B-l
.a
1$
I.
,:,p

-r'tlr
\{t.,(;,4
K.z\ltl"-l
XLPE INSULATED PVC SHEATHED
SINGLE.CORE ARMOURED CABLE
VOLTAGE 600/1 OOO V
AMBIENT TEMPERATURE 3O"C
CONDUCTOR OPERATING TEMPERATURE gO'C

On Perforated
On Perforated Cable Tray
Cable Tray
Size of
Conductor two cables 1-phase Three or four cables three phase ac
ac or dc touching
flat and touching
trefoil
( mm') (amp) (amp) (amp)
50 253 232 222
70 322 293 28s
9s 389 352 346
120 449 405 402
150 516 462 463
185 587 524 529
240 689 612 625
300 792 700 720
400 899 767 815
500 1016 851 918
630 1146 935 1027
800 1246 987 1119
1 000 1345 1 055 1214

VOLTAGE DROP

On Perforated Cable Tray On Perforated Gable Tray


Size of three or four cables, three-phase,
Conductor two cables, 1 phase ac, touching
two cables ,dc
ac, touching
trefoil
( mm') ( mv/A/m ) ( mv/A/m ) ( mv/A/m ) ( mv/A/m )

50 0.98 1.00 0.88 0.87


70 0.67 0.71 0.65 0.62
95 0.49 0.55 0.52 0.47
120 0.39 0.45 0.44 0.39
150 0.31 0.38 0.39 0.33
185 0.25 0.33 0.34 0.28
240 0.1 95 0.28 0.30 0.24
300 0.1 55 0.25 0.28 0.21
400 0.115 0.22 0.27 0.1 95
500 0.093 0.21 0.25 0.1 80
630 0.073 0.1 95 0.24 0.170
800 0.056 0.190 0.23 0.1 65
1 000 0.045 0.1 80 0.21 0.1 55

Note : Correction factors for ambient temperature and group installation, please refer Page B-l
.aL
5tt
MtrGA
t<,+nT:1,-

AMBIENT TEMPERATURE 25 30 35 40 45
IN AIR PVC 70 "G 1.03 1 0.94 0.87 0.79
XLPE 90 "C 1.02 1 0.96 0.91 0.87

AMBIENT TEMPERATURE 50 55 60
IN AIR PVC 70 "C 0.71 0.61 0.5
XLPE 90 "C 0.82 0.76 0.71 0.65 0.58 0.5 0.41

AMBIENT TEMPERATURE 10 15 20 25 30 35
IN PVC 70'C 1.10 1.05 1.00 0.95 0.89 0.84
GROUND XLPE 90 "C 1.07 1.04 1 .00 0.96 0.93 0.89 0.85 0.80

2 3 4 5 6 7 8
Enclosed in Conduit 0.80 0.70 0.65 0.60 0.57 0.54 0.52
or
in Trunking I 10 12 14 16 18 20
0.5 0.48 0.45 0.43 0.41 0.39 0.38

1 2 3
Touching
(Flat) Horizontal 0.98 0.91 0.87
On a Perforated Cable Vertical 0.96 0.86
Tray, Single core
Single Layer Touching
Spaced* Horizontal 1.0 0.98 0.96
(Trefoil) Vertical 1.0 0.91 0.89

2 3 4 5 6 7 I
Touching 0.88 0.82 0.77 0.75 0.73 0.73 0.72

Spaced* Horizontal 1.0 0.98 0.95 0.91


On a Perforated Gable
Tray, Multi-core Layer Vertical 0.91 0.89 0.88 0.87
Vertical or 9 10 12
Horizontal
Touching 0.72 0.72 0.72

Spaced* Horizontal

Vertical

" Spaced " means a clearance between adjacent surface of at least one cable diameter (De). Where the horizontal
clearences between adjacent cable exceeds 2 x De, no correction factor need to be applied.
.Jh
MEGA
5+HT?Ii

2 3 5 6
Laid Directly In
Touching 0.75 0.65 0.55 0.5
The Ground
Spaced* 0.8 0.7 0.55 0.55

2 3 4 5 6
Laid In Duct
Touching 0.85 0.75 0.7 0.65 0.6
In The Ground
Spaced* 0.90 0.85 0.80 0.80 0.80

Value given apply to an installation depth of 0.7 m and a soilthermal resistivity of 2.5 K.m/W
Spaced *
Laid direct , one cable diameter clearance
Laid in duct , 0.25m duct-to-duct clearance
.JA
\1 f rt;.4
*.-.\Ill:l

VOLTAGE 450/750V AND 600/1 OOOV

SIZE XLPE CABLE PVG CABLE


( mm') ohm/km 1(A 1(A
1.5 12.1 0.215 0.173
2.5 7.41 0.358 0.288
4 4.61 o.572 0.46
6 3.08 0.858 0.69
10 1.83 1.43 1.15
16 1 .15 2.298 1.84
25 0.727 3.575 2.875
35 0.524 5.005 4.025
50 0.387 7.15 5.75
70 0.268 10.01 8.05
95 0.1 93 13.585 10.925
120 0.1 53 17.16 13.8
1s0 0.124 21 .45 17.25
185 0.0991 26.455 21 .275
240 0.0754 34.32 27.6
300 0.0601 42.9 34.5
400 0.o47 57.2 41 .2
500 0.0366 71.5 51 .5
630 0.0283 90.09 64.89
800 0.0221 114.4 82.4
1 000 0.0176 143 103

NOTE:

XLPE Cable 0.143 A


l=
,tf
PVC Cable 0.115 A
l= For A equal and less than 300 mm'
,tf
0.103 A
l=
,r For A greater than 400 mm'

t: SHORT CICUIT CURRENT in KA


A: CONDUCTOR CROSS-SECTION AREA in mm2
t: TIME OF SHORT CIRCUIT in second