Safety Monitoring

Flame, Gas, and Particle Detection Solutions


Rosemount Flame Detectors
975MR Multi-spectrum Infrared 975HR Multi-spectrum Infrared Hydrogen
Utilizes three infrared bands to detect fuel and gas fires at long Specifically designed for detection of hydrocarbon and hydrogen
distances with the highest immunity to false alarms. flames. Detects hydrocarbon and hydrogen based fuel and gas fires at
long distances with the highest immunity to false alarms.
Detect a 1 ft2 (0.1 m2) gasoline
pan fire at 215 ft (65 m) in less Detect a gasoline pan fire at 215 ft
than 5 seconds (65 m) or a hydrogen flame at 125 ft
(38 m) in less than 5 seconds
Field of view:
100 Horizontal/95 Vertical Field of view:
100 Horizontal/95 Vertical
Spectral Response:
Three IR Bands Spectral Response: Multi IR Bands
Approvals: ATEX and IECEx, FM/ Approvals: ATEX and IECEx, FM,
FMC/CSA, EN54-10 (VdS), FMC/CSA, EN54-10 (VdS), FM3260,
FM3260, IEC61508 - SIL 2 (TUV), IEC61508 - SIL 2 (TUV)
MED Wheelmark (DNV)

975UF Ultra Fast Ultraviolet Infrared 975UR Ultraviolet Infrared


Specifically designed to meet two major requirements: High-Speed Senses radiant energy in the short wave section of both the ultraviolet
Response (20 millisecond). High Reliability (immunity to false and infrared portions of the electromagnetic spectrum to detect
alarm) Detects hydrocarbon-based fuel and gas fires, hydroxyl and hydrocarbon-based fuel and gas fires. The signals from both sensors
hydrogen fires, as well as metal and are analyzed for frequency, intensity and
inorganic fires. duration. Simultaneous detection of
High-Speed Response 20 msec radiant energy in both the UV and IR
to flash fire sensors triggers an alarm signal.
Sensitivity Range: 1 ft2 (0.1 m2 )
Field of view:
n-heptane pan fire from 66 ft. (20 m)
100 Horizontal/95 Vertical
Field of view:
Spectral Response:
100 Horizontal/95 Vertical
UV: 0.1850.260 m
IR: 2.53.0 m Spectral Response: UV: 0.1850.260
m IR: 4.44.6 m
Approvals: ATEX and IECEx, FM, FMC/
Approvals: ATEX and IECEx, FM/FMC/CSA, EN54-10 (VdS), FM3260,
CSA, EN54-10 (VdS), FM3260, IEC61508 - SIL 2 (TUV)
IEC6 1508 - SIL2 (TUV)

Rosemount Open Path Gas Detectors


935 Open Path Combustible Gas 936 Open Path Toxic Gas
Open path detection system providing continuous monitoring Open path detection system providing continuous monitoring
for combustible hydrocarbon gases. for toxic gases.
Xenon Flash infrared transmitter and receiver Detects toxic hydrogen sulfide or
Detects hydrocarbon gases including ammonia gas
methane, ethylene, propane, ethane Solar blind and immune to
and butane industrial environments
High false alarm immunity
Withstands extreme vibration
Withstands extreme vibration conditions
conditions
Long Range Gas Detection up to
Detection range: 7200 m in three 200 ft (60 m)
different models (same detector
different sources) Operating Temperature: -67 F to 149 F (-55 C to 65 C)
Operating Temperature: -67 F to 149 F (-55 C to 65 C) Response time: T90 10 sec
Approvals: ATEX, IECEx, FM/FMC, GOST R, INMETRO, CU TR, Approvals: Pending
SIL 2 (TUV), FM 6325, EN60079

2
Rosemount Ultrasonic Gas Leak Detector
Incus Ultrasonic Gas Leak Detector
The Incus detects gas leaks at the speed of sound while providing Automated electronic self-test offers failsafe operation
wide area coverage. It is unaffected by inclement weather, wind, leak
direction, and gas dilution or stratification. Operating Temperature: -40 F to 185 F (-40 C to 85 C)
When used with Emersons point gas and Area coverage: 2 to 20 meters (7 to 65 feet)
optical flame detectors, a complete and
comprehensive safety system is ensured. Programmable time delays screen intermittent unwanted alarm
sources
No calibration required
Approvals: IECEx, ATEX, c FM us, EAC, KOSHA, INMETRO,
Quad sensing heads provide the widest ABS, DNV
overall detection range available on the
market
Each sensor is completely free of moving
parts and will not age, drift, or ever need
replacing under normal operating conditions

Net Safety Point Gas Detectors and Sensors

Millennium II Single Channel Millennium II Dual Channel Millennium II Basic Single Channel
Single channel universal transmitter with a Dual channel capability allows for more Designed for demanding, industrial
full character OLED display compatible with coverage area with a single transmitter - mix applications that require a local, full-featured
both the SC3 and ST3 series of combustible and match both the SC3 and ST3 series of transmitter interface but do not require a
and toxic gas sensors. combustible and toxic gas sensors. Redefines character display.
what you expect from a fixed gas detection
Long range (+2,000 ft/600 m) sensor Long range (+2,000 ft/600 m) sensor
solution.
separation separation
One transmitter for two detection points
Operating Temperature: -67 F to 185 F Operating Temperature: -67 F to 185 F
(-55C to 85C) Long range (+2,000 ft/600 m) sensor (-55 C to 85 C)
separation
Full diagnostics with event and data Bright LED indicators for Power/Alarm/
logging of over 980 sequential events Operating Temperature: -67 F to 185 F Fault conditions
(-55 C to 85 C)
Approvals: FM6320, ANSI/ISA 12.13.01, Approvals: FM6320, ANSI/ISA 12.13.01,
CSA 22.2 No. 152:2006, IECEx Full diagnostics with event and data CSA 22.2 No. 152:2006, IECEx
logging of over 980 sequential events
Approvals: FM6320, ANSI/ISA 12.13.01,
CSA 22.2 No. 152:2006, IECEx

3
Net Safety Air Particle Monitor
Millennium Air Particle Monitor (APM)
The only Infrared optical monitor that is certified for use in Not affected by high volume air velocity
hazardous areas for constant, reliable monitoring of ambient air
Operating Temperature:
for products of combustion such as smoke, oil mist, carbon, dust,
-40 F to 167 F (-40 C to 75 C)
and ash.
Approvals: CSA, ATEX, IECEx
Perform a zero in 60 seconds from start to finish
Multi-language, bright scrolling LED display allows operators to
modify at installation site

Aspirator Systems
Gas & Smoke Aspirator Systems Self Compensating Duct Probes
The aspirator system pulls a sample Self compensating duct probes allow for simple
under an adjustable vacuum representative sampling of duct environments. When used in
created by an air driven eductor. conjunction with an aspirator, they provide a complete
The sample is passed across the duct sampling system capable of operating in
sensor and exhausted, along with hazardous areas.
instrument air, via the exhaust
Delivers a representative duct sample
port.
to aspirator
Monitor for sample line
The design ensures equal
blockages
sample volumes are drawn
Suitable for sour gas applications from each sampling point
before combining them into the
Fail safe sample line clearance
aspirator
and detector testing
Operating Temperature: -40 F
Can be utilized in high and low temperature applications
to +365 F (-40 C to +185 C)
Approvals: Zone 1 & 2 hazardous areas, explosion-proof pump
Designed to fit exact duct width (maximum width: 4
version available, SIL rated low flow alarm available
meters)
Can be fully insulated from duct wall
Approvals: ATEX, GOST R, GOST K, IECEx

2016 Emerson. All rights reserved.


Global Headquarters
Emerson
The Emerson logo is a trademark and service mark of Emerson Electric Co. Rosemount and the Rosemount logotype
6021 Innovation Blvd. are registered trademarks of Rosemount Inc. All other marks are the property of their respective owners.
Shakopee, MN 55379,
USA The contents of this publication are presented for information purposes only, and while effort has been made to ensure their
T +1 866 347 3427 accuracy, they are not to be construed as warranties or guarantees, express or implied, regarding the products or services
F +1 952 949 7001 described herein or their use or applicability. All sales are governed by our terms and conditions, which are available
Safety.CSC@Emerson.com on request. We reserve the right to modify or improve the designs or specifications of our products at any time
EmersonProcess.com/FlameGasDetection without notice.