OPEN-DELTA CONNECTION
September 5, 2016 Sohalsinh Chauhan Machine, Transformer Leave a comment
Search
0

Open Delta Connection

Open delta connection also known as the V-V connection. A three phase
transformation of energy is possible using only two single phase transformers. This
connection called open-delta or V-V connection.

When one phase of the three single phase transformers connected in delta-delta
bank is unable to operate or damaged. Then supply to the load can be continued
with the remaining two phase of transformers. This connection thus obtained is
called Open Delta connection.
STAY IN TOUCH


Open delta connection is that one connection, by using two single phase
transformers we can provide a temporary three phase supply to the load. g shows
the three phase supply connected to the primaries, then on the secondary side, on
no-load three equal voltage will be available. TAG CLOUD

AC DISTRIBUTION SYSTEM

ACTIVE POWER APPARENT POWER

CABLE

CLASSIFICATION OF DISTRIBUTION
SYSTEM

CORONA DAMPER WINDING

DC DISTRIBUTION SYSTEM

DC MOTOR DEFINATION DELTA

DISTRIBUTION LINE

DISTRIBUTION SYSTEM

DISTRIBUTOR
This connection is most helpful in emergency conditions. When one of three single

http://www.electricalidea.com/2016/09/05/opendeltaconnection/ 1/4
1/16/2017 OpenDeltaConnectionElectricalidea

phase transformers connected in delta-delta bank will damage. ELECTRICAL POWER SYSTEM FEEDER

The total load carried by open delata connection is 57.7% of a detla delta connection. FERRANTI EFFECT

FUNDAMENTAL LAW
When it connected in delta detla so VA rating is given by,
GENERATING STATION
Sdd= 3 VL IL Sdd= 3 VL (3Iph)
GENERATION OF HIGH ALTERNATING
Sdd= 3 VL Ip
VOLTAGE

GROUNDING INDUCTION MOTOR

INSULATOR] LAW

MUTUAL INDUCTION OHM'S

PARALLEL OPERATION

PER UNIT VALUE POWER

POWER FACTOR PROTECTIVE DEVICE

PROTECTIVE RELAY

PROXIMITY EFFECT

REACTIVE POWER

When it connected in Open-Delta so VA raing is given by, RENEWABLE ENERGY SAG

Sod = 3 VL IL SERVICE MAINS SKIN EFFECT

Sod = 3 VL Iph STARTER SYNCHRONOUS MOTOR

Sod/Sdd = 3 VL Iph / 3 VL Iph TAP CHANGER TRANSFORMER

TRANSFORMER OIL
= 1 / 3
TRANSMISSION LINE
= 0.577
WORKING PRINCIPLE OF DC MOTOR

Therefore, load carried by the open delta is 57.7% od the original load carried bybthe
delta delta bank.
If there are three single phase transformers are connected in delta delta connection.
When one transformer become damage or removed other remaining two will
overloaded. This overloaded of each transformer is given by,

Total load of open delat / VA rating of each xmer = 3 VL Iph/ VL Iph


=3
= 1.73

This overload can be carried temporary if provision is made to reduce the load
otherwise overheating and breakdown of the other two transformer would take
place.
When three phase supply is given to the open delta connection. That both
transformer operate on dierent power factor.
One is cos (30 ) and delivered power is KVA cos (30 ).
Other is cos (30 + ) and delivered power is cos (30 + ).

It is employed :

1. When the three-phase load is too small to warrant the installation of full three-
phase transformer bank.
2. When one of the transformers in a D D bank is disabled, so that service is
continued although at reduced capacity, till the faulty transformer is repaired or a
new one is substituted.
3. It is anticipated that in future the load will increase necessitating the closing of
open delta.

Limitations :-

http://www.electricalidea.com/2016/09/05/opendeltaconnection/ 2/4
1/16/2017 OpenDeltaConnectionElectricalidea

1. Voltage become unbalanced at the secondary terminal.


2. Remaining two transformers operate on dierent power factor.
3. Power handling capacity of the transformer will be reduced. Reduction is
approximately 15.5%

If any query or suggestion about Open delta connectionplease comment below or


Email onsohal@electricalidea.com.

Related

What is Zigzag Transformer ? Scott Connection What Is Tertiary Winding


In "Power System" In "Machine" In "Machine"

DELTA DELTA CONNECTION OPEN DELTA CONNECTION

Permanent Magnet Moving Coil Instrument Star-Delta Starter

LEAVE A REPLY

Connect with:

Your email address will not be published. Required elds are marked *

Comment

Name *

Email *

Website

http://www.electricalidea.com/2016/09/05/opendeltaconnection/ 3/4
1/16/2017 OpenDeltaConnectionElectricalidea

Post Comment

Notify me of follow-up comments by email.

Notify me of new posts by email.

Powered by WordPress and Tortuga.

http://www.electricalidea.com/2016/09/05/opendeltaconnection/ 4/4

Vous aimerez peut-être aussi