Vous êtes sur la page 1sur 70

Product Guide 2013

Low Voltage Switchboards


and Switchgear

LV Switchboards/Switchgear
Low Voltage Switchboards and Switchgear

Tab 1 CMP Switchboards. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . T1-3


1
Tab 2 Pow-R-Line C Switchboards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . T2-7 2
Tab 3 Commercial Metering Switchboards . . . . . . . . . . . . . . . . . . . . . . T3-17 3
Tab 4 Integrated Facility Switchboards . . . . . . . . . . . . . . . . . . . . . . . . . T4-19
4
5
Tab 5 Pow-R-Line C Switchboards with
Drawout Moulded-Case Circuit Breaker. . . . . . . . . . . . . . . . . . . . T5-31 6
Tab 6 Generator Connection Assemblies 7
Generator Quick Connect Switchboards . . . . . . . . . . . . . . . . . . T6-35 8
Customer Service Termination Enclosure. . . . . . . . . . . . . . . . . . T6-37 9
Roll-Up Generator Quick Connect Assembly. . . . . . . . . . . . . . . T6-39 1
Tab 7 Pow-R-Line C Switchgear . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . T7-41 1
1
Tab 8 Components. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . T8-47
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Low Voltage Switchboards and SwitchgearCA015002ENAugust 2013www.eatoncanada.ca T1-1
Low Voltage Switchboards and Switchgear
CMP Switchboards
1
Contents
CMP-A1 Switchboard
1
Description Page
Standards and Certifications.................................... T1-4 2
Product Selection.................................................... T1-4
Technical Data and Specifications............................ T1-5 3
Dimensions.............................................................. T1-6
4
5
6
7
8
9
1
CMP Switchboards 1
Product Description Features, Benefits Main breaker maximum Busbar System 1
Eatons CMP switchboard and Functions 800A (CMP-A1) and Silver-flashed copper or
combines all three The service entrance 1200A (CMP-A2) tin-plated aluminum 1
components of a service panel is CSAT approved Breakers are padlockable
entrance application into a and completely factory to ensure maximum Main Breaker 1
single cell, including a main assembled. Barriers are security Eaton type main breaker,
service compartment, a
utility metering section and
provided to isolate the
main disconnect, the utility
Standard enclosure
ratings of CSA Type 1;
maximum 800A (CMP-A1) 1
or 1200A (CMP-A2) with
the distribution feeders, metering compartment sprinklerproof optional
providing the most flexible and the distribution Sealing screws, knurled
standard thermal-magnetic or
solid-state trip units available.
1
and compact footprint for section into three separate thumb screws and The trip unit on the standard
the entire service entrance compartments. The design padlock hasp thermal-magnetic breaker 1
switchboard. allows for the assembly may be changed; however,
Utility ground stud
to be reversed in the field
Wireways and hydro
all power to the switchboard 1
Application Description without modification and must be disconnected prior to
stubs are available
Commercial facilities
to accommodate either top
or bottom entry of service
removal of the breaker cover. 1
Institutions and entrance cables. Enclosure The main breaker section
school boards
The service entrance
comes complete with 1
Retail buildings Compact and space- provisions for padlocking
switchboard is standard
efficient
CSA Type 1; sprinklerproof
the main breaker and the 1
Top or bottom entry sealing screws on the front
optional. It is fabricated
Meets the provincial from code gauge formed
cover. Grounding is supplied
with a removable disconnect
1
and municipal metering galvanized steel, complete link to ground the neutral,
requirements
Accommodates Eaton
with flat covers to form a the service conduit and the 1
rigid deadfront totally system ground.
Pow-R-Line 4 distribution
panel (40X space;
enclosed structure. 1
1X = 1-3/8 inch) All compartments are
Optional wireway designed to make 1
components totally front
Accommodates a variety
of utility CTs and PTs
accessible to enable the
panel to be installed against
1
CSA approved up to the wall.
800A (CMP-A1) and 1
1200A (CMP-A2) at All covers are painted
600 Vac ANSI 61 grey. 1
1
1
Low Voltage Switchboards and SwitchgearCA015002ENAugust 2013www.eatoncanada.ca T1-3
1 Low Voltage Switchboards and Switchgear
CMP Switchboards

Utility Metering Compartment Distribution Section Standards and Certifications Product Selection
1 The utility metering The distribution section CSA C22.2 No. 31 Description Type
compartment is designed accepts the installation CSA C22.2 No. 244
2 to meet the provincial of circuit breakers on a

800A maximum at 600 Vac CMP-A1
and municipal utility Pow-R-Line 4 type interior. 1200A maximum at 600 Vac CMP-A2
3 requirements. It is bussed A flat cover is supplied and
and pre-drilled to accept any space not occupied by Breaker Accessories
4 standard bus type current
transformers. Utility CTs
a feeder breaker has a filler
plate, allowing no access to
Padlock hasp
Visible windows
and PTs can be easily parts when energized.
5 factory or field installed. The Electronic trip units
compartment has provisions The distribution section Shunt trip
6 for sealing the front cover, accommodates a minimum
Auxiliary switch
and the cover has a hinged of 14 three-pole breakers
Bell alarm
7 door for easy access. (21X of circuit breaker
distribution space;
Metering options include: 1X = 1-3/8 inch).
8
CTswindow type and The panel section has
9 bar type provisions to accept breakers
to a maximum of 1200A.
External clamp-on CTs to
1
verify meter
Up to four PTs in utility
compartment
1 Neutral and ground
studs available
1
Utility specific options:
1 Standard
BC Hydro
1 Brampton Hydro
Hydro Quebec
1
Mississauga
1
1
1
1
1 CMP with Wireway and 40X Pow-R-Line 4 Distribution Panel

1
1
1
1
1
1
1
1
1
1
T1-4 Low Voltage Switchboards and SwitchgearCA015002ENAugust 2013www.eatoncanada.ca
Low Voltage Switchboards and Switchgear
CMP Switchboards
1
Technical Data and Specifications
1
Rating Breaker Options CMP-A2
The service entrance panel bus is rated to 800A (CMP-A1), kA Value
2
Device Ampere Mounting
1200A (CMP-A2), 600V, three-phase, four-wire, 60 Hz. Type
Main Breakers
Rating 240V 600V Height a
3
Interrupting Rating
Maximum 100 kA at 600V
KD Frame 70400 b 65200 2565 4X 4
LD Frame 300600 65200 2550 6X
Maximum 200 kA at 240V LG Frame 250600 65200 1865 4X 5
MDL Frame 300800 c 65100 2535 6X

Breaker Options CMP-A1 ND Frame 6001200 65200 2565 6X 6


NG Frame 5001200 65200 2565 6X
Device
Type
Ampere
Rating
kA Value
240V 600V
Mounting
Height a
Branch Breakers 7
FD Frame 15225 18200 1435 3X
Main Breakers
JD Frame 70250 65200 1835 3X 8
KD Frame 70400 b 65200 2565 4X
KD Frame 70400 b 65200 2565 4X
LD Frame 300600 65200 2550 6X
LD Frame 300600 65200 2550 6X 9
LG Frame 250600 65200 1865 4X
LG Frame 250600 65200 1865 4X
MDL Frame 300800 c 65100 2535 6X
MDL Frame 300800 c 65100 2535 6X 1
ND Frame 400800 65200 2565 6X
ND Frame 6001200 65200 2565 6X
NG Frame 320800 65200 2565 6X
NG Frame 5001200 65200 2565 6X 1
Branch Breakers
FD Frame 15225 18200 1435 3X Branch Fusible SwitchesOptional 40X Distribution 1
JD Frame 70250 65200 1835 3X
Cell Width
KD Frame 70400 b 65200 2565 4X
Device
Type 38-Inch 44-Inch
Mounting
Height a 1
LD Frame 300600 65200 2550 6X
LG Frame 250600 65200 1865 4X
30/30A twin
30/60A twin
Y
Y
Y
Y
4X
4X
1
60/60A twin
100/100A twin
Y
Y
Y
Y
4X
5X
1
200A (single or twin)
400A
Y
Y
Y
Y
6X
9X
1
600A
800A
Y
N
Y
Y
11X
11X
1
1200A d N Y 15X
1
NNote
a 1X = 1-3/8 inch.
1
b Ampere ratings below 100A available with electronic trip unit only.
c Ampere ratings below 400A available with thermal-magnetic only.
1
d Only available with CMP-A2.

1
1
1
1
1
1
1
1
1
1
Low Voltage Switchboards and SwitchgearCA015002ENAugust 2013www.eatoncanada.ca T1-5
1 Low Voltage Switchboards and Switchgear
CMP Switchboards

Dimensions
1 Approximate Dimensions in Inches (mm)

2 Layout A: Top-Fed CMP-A1 Layout B: Bottom-Fed CMP-A2


(800A Maximum at 600 Vac) (1200A Maximum at 600 Vac)
3
4
5 24.00
(609.6)
Main Breaker
36.00 a
6 (914.4)
21X Chassis

7
30.00 Utility CT/PT

8 (762.0) Compartment
30.00 Utility CT/PT
(762.0) Compartment
9
1 36.00 a
21X Chassis
(914.4) 24.00
1 (609.6)
Main Breaker

1 30.00 12.00 44.00


12.00
(304.8) (304.8)
(762.0) (1117.6)
1
1
Layout C: Top-Fed CMP with Layout D: Bottom-Fed CMP with Wireway
1 40X Pow-R-Line 4 Distribution and 40X Pow-R-Line 4 Distribution

1
1
Main Breaker Main Breaker
1
1
1 Utility CT/PT
Compartment a
Utility CT/PT
Compartment a
40X Pow-R-Line 4 Wireway 40X Pow-R-Line 4

1
1
1 21X Chassis
a
15X Chassis
a

1
12.00 12.00
1
b 18.00/24.00 30.00/44.00 24.00/38.00/44.00 b
30.00/44.00 24.00/38.00/44.00 (304.8) (304.8)
(762.0/1117.6) (609.6/965.2/1117.6) (457.2/609.6) (762.0/1117.6) (609.6/965.2/1117.6)

1 NNote

1
a 1X = 1-3/8 inch.
b Width of cell is determined by breaker size and trip unit type. For fusible switches 800A and above, 44-inch-wide (1117.6 mm) cell is required. Contact Eaton for more information.

1
1
1
T1-6 Low Voltage Switchboards and SwitchgearCA015002ENAugust 2013www.eatoncanada.ca
Low Voltage Switchboards and Switchgear
Pow-R-Line C Switchboards
2
Contents
Pow-R-Line C Switchboard
1
Description Page
Standards and Certifications.................................... T2-9 2
Product Selection.................................................... T2-10
Technical Data and Specifications............................ T2-14 3
4
5
6
7
8
9
1
Pow-R-Line C Switchboards 1
Product Description Application Description Features, Benefits A main moulded-case 1
Eaton Pow-R-Line CE The Pow-R-Line C and Functions circuit breaker or a main
switchboards combine a switchboard is ideally suited fusible switch, within the 1
space-saving design with to commercial and industrial Main Devices sizes listed for panelboard
a modular construction and applications such as: Magnum DS power circuit
design, can be included
in the panel-mounted
1
increased system ratings breakers, fixed-mounted
Institutions and assembly in lieu of a
to provide economical and
dependable electrical system school boards or drawout, 800A to separate, individually 1
6000A at 600 Vac mounted unit
distribution and protection. Office towers
Health care facilities
maximum100% rated
Eaton fixed-mounted
Ground fault protection on 1
Retail facilities feeders if required
Utility
moulded-case circuit
breakers up to 2500A,
Optional 10X 1
600 Vac maximum (1X = 1-3/8 inch) box
Solar applications

Residential Eaton fusible switches
available for meters, 1
protection and control
up to 1200A, 600 Vac
Commercial
maximum
devices 1
Industrial Pow-R-Line C designates
Bolted pressure switches
up to 4000A a family of distribution 1
Ground fault protection on switchboards, incorporating
main device if required design concepts that fit
the ever-increasing need
1
for applications on high
Distribution Devices short-circuit systems, while 1
Moulded-case circuit retaining maximum safety
breakers fixed-mounted and convenience throughout 1
up to 2000A, 600 Vac the line.
maximum
Feeder circuit protective 1
Moulded-case circuit
devices are an assembly
breakers drawout up to of units mounted on a 1
600A, 600 Vac maximum panelboard-type base
Fusible switches up to (panelboard construction). 1
1200A, 600 Vac maximum Circuit protective devices
Fusible switched meter are front accessible. 1
sockets (FSMC) up to
200A (48.00-inch-wide
cell only)
1
1
1
Low Voltage Switchboards and SwitchgearCA015002ENAugust 2013www.eatoncanada.ca T2-7
2 Low Voltage Switchboards and Switchgear
Pow-R-Line C Switchboards

Enclosure Standard Switchboard Height Provision for Busway Surge Protection Device (SPD)
1 Standard enclosure is CSAT The standard Pow-R-Line C Entrance and Exit Standard integrated surge
Type 1; sprinklerproof, Type2, switchboard height is Busway connections to protection device with
2 3R are optional. Structures 90.00 inches (2286.0 mm). switchboard sections include integral disconnect is
and formed doors are made Custom height is cutout and drilling in the available if required. Please
3 of code gauge steel. available at 78.00 inches top of the switchboard with refer to Tab 8Components
(1981.0 mm) high. riser connections from the or contact Eaton for more
4 Standard Finish Optional base channels
switchboard device or the
bus, up to the point where
information.
Grey paint finish (ANSI 61) 1.00 inch (25.4 mm), the bus duct enters the
5 using a modern, completely 1.50 inches (38.1 mm) switchboard. No connections Transition Cells
automated and continuously (standard option) or are furnished external to Transition structures are
6 monitored electrostatic 2.00 inches (50.8 mm) high the switchboard. required for connecting
powder coating. This available. Consult Eaton for switchboards to the
In all transactions involving
7 continually monitored system
includes spray de-grease
other options.
busway attached to switch-
secondary of power centre
transformer (dry or fluid
and clean, spray rinse, iron boards, it is essential that filled), motor control
8 phosphate spray coating
Provision for Future Devices
Chassis/Group Mounted
information regarding centres, and for other special
rinse, nonchemical seal, orientation of the busway switchboard configurations
9 oven drying, electrostatic
Where a provision for future
circuit protective devices
with respect to the front such as L or U shaped
powder spray paint coating of the switchboard be lineups. In some applications,
is required, the space and
1 and oven curing.
a blank filler plate will be
supplied to the coordinating
assembly plant.
an extra structure complete
with connections is required;
supplied. Connections and
1 Integral Base mounting hardware are NNote: Additional depth to the
switchboard may be required.
in others, where switchboard
depth and space permit, only
The ruggedly formed base not included. Optional
the connection conductors
1 greatly increases the rigidity insulated main bus is
On Pow-R-Line C are required. Refer to factory
of the structure, reduces available if required.
switchboards, a bus system for these applications.
1 the possibility of damage is used to connect the bus
during the installation of the Busbar System duct to the individually PLC Transfer Schemes
1 equipment, and is suitable for
rolling, jacking and handling.
Standard tin-plated aluminum mounted device, the main or
Advanced PLC-based transfer
or copper up to 3000A. sub-main switchboard bus,
A lifting angle is bolted and load shedding schemes
1 onto the top of the bus
Standard silver-plated copper or the vertical main bus of
the panel-mounted circuit can be designed for various
for 4000A to 6000A. Tin-
compartment structure for protective device panels. applications such as data
plated copper also available.
1 increased strength.
Optional insulated main bus
centres, health care facilities
Side or rear hydro stub, and wastewater treatment
is available.
1 Front Accessible
collector bus, utility wireway
and transformer coordination
plants. HMI is optional for
touch screen monitoring
Standard bus and connectors
Front accessible switchboards to Eaton standard cross bus and control of incoming,
1 align at the rear, enabling
on all switchboards are
rated for use on systems are available; consult Eaton tie and feeder power
them to be placed against capable of producing up to factory for more information. circuit breakers. Contact
1 a wall (Pow-R-Line C front 50,000A rms symmetrical an Eaton sales engineer
accessible). If the main short-circuit current at the for more information.
Utility Metering Provisions
1 section is deeper than others,
due to physical size of the
incoming terminals.
Meets all provincial and
main device, the necessary Increased bus short-circuit municipal utility metering Bus Duct Integration
1 off-set in lineup will occur in ratings equal to that of requirements Custom bus duct can be
front, and the main section connected switchboard Utility ground studs integrated into switchboard
1 will be accessible from the devices, up to 200,000A rms available assemblies. Eaton can design
side as well as from the front. symmetrical, are available Utility CTs and PTs and manufacture custom bus
1 Standard front accessible in most Pow-R-Line C can be easily factory or duct flanges to coordinate
switchboards will align at switchboards when approved field installed with the bus duct risers of
1 the front and the rear. main devices are installed.
Contact Eaton for more
a wide range of amperage.

information. CSA labeled Customer Metering


1 Rear Accessible
switchboard sections are Full line of Eaton
Eaton offers rear accessible marked with their applicable microprocessor-based
1 switchboards that align at the
front and the rear.
short-circuit rating. customer metering and
NNote: The short-circuit rating monitoring devices. Please
1 of the switchboard assembly refer to Tab 8Components,
is limited to the interrupting or contact Eaton for more
1 capacity of the lowest rated
branch device.
information.

1
1
T2-8 Low Voltage Switchboards and SwitchgearCA015002ENAugust 2013www.eatoncanada.ca
Low Voltage Switchboards and Switchgear
Pow-R-Line C Switchboards
2
Transformer and MCC Advanced Metering Standards and Certifications
Close-Coupling and Communications CSA C22.2 No. 31
1
Close-couple dry-type, Eaton has an extensive line of CSA C22.2 No. 244
liquid-filled transformers powerful metering products,

Seismic qualified to
2
and motor control centres trip units, controllers and
Zone 4 per IBC/CBC
(MCC) with standard gateways, that can be wired 3
switchboard configurations together in switchboards to
can be supplied. Transformer
unit substations and MCC
create an intelligent system
and interface with building
4
bus coordination would management and SCADA
create a compact lineup and systems. 5
minimization of installation
time by eliminating cable
Special Dimensions
6
installations. and Configurations
Eaton has the ability to offer
7
Integrated Transfer Switches custom dimensions to suit
Eaton automatic transfer limited space requirements. 8
switches (contactor, Special heights, special
moulded-case circuit breaker depths and widths, corner 9
or power circuit breaker sections, back-to-back, front
type, including optional access only (on deeper
switchboards that normally
1
bypass-isolation type)
can be integrated into a require rear access), rear
switchboard lineup. Electrical access and side access 1
and mechanical coordination configurations are available.
is ensured when transfer 1
switches are integrated into Arc Flash Considerations
the switchboard.
Arc flash is an ongoing
1
concern in the electrical
industry. Eaton offers a 1
variety of solutions to reduce
the risk of arc flash such 1
as the Arcflash Reduction
Maintenance SystemE in 1
moulded-case or power
circuit breakers, safety
shutters in Magnum drawout
1
power circuit breakers, infra-
red viewing windows and 1
remote racking accessories.
1
1
1
1
1
1
1
1
1
1
1
1
Low Voltage Switchboards and SwitchgearCA015002ENAugust 2013www.eatoncanada.ca T2-9
2 Low Voltage Switchboards and Switchgear
Pow-R-Line C Switchboards

Product Selection
1 For complete application and pricing information, contact your local Eaton sales office.

2 Wireway Cell Layouts


3 Approximate Dimensions in Inches (mm)
Wireways are front access with rear and side access option, top or bottom incoming,
4 three- or four-wire, aluminum or copper, with bolted cover standard and front door optional.

5 Pow-R-Line C Switchboards Wireway Section Layout a

6
7
8
9 90.00 Wireway
(2286.0)
1
1
1
1 W
D

1 Wireway

1
Pow-R-Line C Wireway Cells
1 Cell Depth Cell Width (W)

1 Ampere
Rating
18.00
(457.2)
24.00
(609.6)
30.00
(762.0)
36.00
(914.4)
60.00 to 90.00
(1524.0 to 2286.0)
18.00
(457.2)
24.00
(609.6)

1 800
1200
n
n
n
n
n
n
n
n
n
n
n
n
n
n

1 2000
2500
n
n
n
n
n
n
n
n
n
n
n n
n

1 3000
3200
n
n
n
n
n
n
n
n
n
n

1 4000 n n n

NNote
1 a 91.50 inches (2324.1 mm) high with 1.50 inch (38.1 mm) optional base channel.
Specific municipality code designs available. Consult Eaton for more information.

1 Consult Eaton for CSA enclosure rating.


Custom 78.00 inches (1981.2 mm) high wireways available. Consult Eaton for custom height information.
Custom lug sizing and spacing available. Consult Eaton for more information.
1
1
1
1
1
1
1
T2-10 Low Voltage Switchboards and SwitchgearCA015002ENAugust 2013www.eatoncanada.ca
Low Voltage Switchboards and Switchgear
Pow-R-Line C Switchboards
2
Main and Utility Cell Layouts
Approximate Dimensions in Inches (mm) 1
With copper or aluminum main bus; system incoming by cable or bus duct; 2
available for indoor or outdoor structures.

Pow-R-Line C Switchboards Main and Utility Section Layouts a


3
4
5
GFR Metering
Compartment
6
Main/
Sub-Main
Main/
Sub-Main
Main/
Sub-Main
7
Breaker Device Device

90.00
8
90.00 90.00 90.00
(2286.0) (2286.0) (2286.0) (2286.0)
9
Utility CT/PT
Compartment
Utility CT/PT
Compartment
Utility CT/PT
Compartment
Utility CT/PT
Compartment 1
1
38.00/48.00 b 38.00/48.00 b 38.00/48.00 b 38.00/48.00 b
1
(965.2/1219.2) (965.2/1219.2) (965.2/1219.2) (965.2/1219.2)
18.00/24.00 18.00/24.00 18.00/24.00 18.00/24.00 1
(457.2/609.6) (457.2/609.6) (457.2/609.6) (457.2/609.6)

Layout A Layout B Layout C Layout D


1
Top-mounted main/sub-main Top-mounted main/sub-main Top-mounted main/sub-main Top-mounted main/sub-main
bolted pressure switch with breaker with utility metering device with utility device with horizontal 1
utility metering compartment compartment and vertical metering compartment. metering compartment and
and ground fault relay. metering compartment. utility metering compartment.
1

Standard Pow-R-Line C Main and Utility CellsMain Devices


1
Ampere Rating Main Device Frame Layout A Layout B Layout C Layout D 1
1002500 Moulded-case circuit breaker F, J, K, L, M, N, R n n n
4001200 Fusible switch FDP n n 1
12002000 Fusible switch Pringle switch n n
25003000 c Fusible switch Pringle switch n n 1
3000 c Fusible switch Pringle switch n n
8001200 c Power circuit breaker Fixed mounted n n n 1
12003200 c Power circuit breaker Fixed mounted n n n
4000 c 6000 d Power circuit breaker Fixed mounted n n 1
8001200 d Power circuit breaker Drawout n n
12003200 d Power circuit breaker Drawout n n 1
40006000 d Power circuit breaker Drawout
1
n n

NNote
a 91.50 inches (2324.1 mm) high with 1.50 inch (38.1 mm) optional base channel.
b Main devices up to and including 3200A require 38.00-inch-wide (965.2 mm) cells; main devices 40006000A require 48.00-inch-wide (1219.2 mm) cells. 1
c 24.00 inch (609.6 mm) depth required.
d Additional depth required. Consult Eaton for more information. 1
All layouts shown are top fed. Consult Eaton for top and bottom incoming.
Custom 78.00 inches (1981.2 mm) high main utility available. Consult Eaton for custom heights.
Consult Eaton for copper or aluminum bussing, CSA enclosure rating, and horizontal and vertical metering.
1
Power XpertT Metering is not compatible with vertical metering layout (Layout B).
1
1
1
Low Voltage Switchboards and SwitchgearCA015002ENAugust 2013www.eatoncanada.ca T2-11
2 Low Voltage Switchboards and Switchgear
Pow-R-Line C Switchboards

Main and Half-High Distribution Cell Layouts


1 Approximate Dimensions in Inches (mm)
2 With copper or aluminum main bus; system incoming by cable or bus duct;
available for indoor or outdoor structures.
3
Pow-R-Line C Switchboards Main and Half-High Distribution Section Layout a

4
5
6
b Main/
18X/22X
7 Chassis
Sub-Main
Device

8
90.00 90.00

9 (2286.0) (2286.0)

1 Main/ b
18X/22X
Sub-Main Chassis
Device
1
1 38.00 38.00
(965.2) (965.2)
1 24.00 24.00
(609.6) (609.6)
1 Bottom-mounted main/ Top-mounted main/
sub-main breaker with sub-main breaker with
1 distribution chassis. distribution chassis.

1
Pow-R-Line C Main and Half-High Cells
1 Main Devices
Ampere Main Main/ Distribution
1 Rating Device Frame Utility Chassis
4002500 Moulded-case K, L, M, N, R Main 18X
1 circuit breakers
4002500 Moulded-case K, L, M, N, R Main 22X
1 4001200
circuit breakers
Fusible switch FDP Main 18X

1 4001200 Fusible switch FDP Main 22X


NNote
1 a 91.50 inches (2324.1 mm) high with 1.50 inch (38.1 mm) optional base channel.
b 1X = 1-3/8 inch.

1 Consult Eaton for CSA enclosure rating.


Consult Eaton for horizontal and vertical metering.
Consult Eaton for top or bottom incoming and additional layouts.
1
1
1
1
1
1
1
T2-12 Low Voltage Switchboards and SwitchgearCA015002ENAugust 2013www.eatoncanada.ca
Low Voltage Switchboards and Switchgear
Pow-R-Line C Switchboards
2
Distribution Cell Layouts
Approximate Dimensions in Inches (mm)
1
Distribution boards are offered in copper or aluminum, three- or four-wire, 2
with cable in option available.
Pow-R-Line C Switchboards Distribution Section Layout a 3
4
5
6
50X
b 7
Vertical
90.00
(2286.0)
Panel
Space
8
for
Devices 9
1
1
38.00/48.00 c
(965.2/1219.2)
1
18.00/24.00
(457.2/609.6)
1
50X Distribution Chassis
1
Standard Pow-R-Line C Distribution CellsBranch Devices 1
Ampere Rating Frame Feeder Device Distribution Size
1
1001600 F, J, K, L, M, N d, R e Moulded-case circuit breaker 18X / 22X / 50X
20600 JG, LG Drawout MCCB f 18X / 22X / 50X 1
30/60 Single Fusible switch 18X / 22X / 50X
100 Single/twin Fusible switch 18X / 22X / 50X 1
200 Single/twin Fusible switch 18X / 22X / 50X
400 Single Fusible switch 18X / 22X / 50X 1
600 Single Fusible switch 18X / 22X / 50X
800 Single Fusible switch 18X / 22X / 50X 1
1200 Single Fusible switch 18X / 22X / 50X
1
Commercial Metering Switchboard 1
Eaton offers Fusible Switch Metering Centres (FSMC) for commercial metering applications.
Please refer to Tab 3Commercial Metering for more information. 1
NNote 1
a 91.50 inches (2324.1 mm) high with optional base channel.
b 1X = 1-3/8 inch. 1
c Width of cell may require 48.00 inches (1219.2 mm) due to cable sizing or other features; consult Eaton for more information.
d For cable sizing 750 kcmil and greater, 48.00-inch-wide (1219.2 mm) cell required. 1
e Copper bussing and 50 kAIC only.
f Refer to Tab 5Pow-R-Line C Switchboards with Drawout Moulded-Case Circuit Breaker, for more information. 1
Consult Eaton for CSA enclosure rating.
1
1
1
Low Voltage Switchboards and SwitchgearCA015002ENAugust 2013www.eatoncanada.ca T2-13
2 Low Voltage Switchboards and Switchgear
Pow-R-Line C Switchboards

Technical Data and Specifications


1
X Spacing of Circuit Protection Devices a
2 Approximate Dimensions in Inches (mm)

3 Layout for Branch and Horizontally Mounted Main Devices

4 Max. Amperage Device

5 Filler
Sub Panel
1X Breaker to Fusible Transition, All Widths

BAB, QBHW, GHB, GBH


6 12X 18 poles

100A
7 20X 42 poles
Note: BAB/QBHW with shunt
trips require an additional pole
(i.e., single-pole is two-pole size)
8 1P 1P 1X
2P 2P 2X EHD, FDB, FD, HFD,
225
9 3P 3P 3X
FDC,FDE, HFDE (three-pole)

2P 2P 2X
1
225 ED, EDH, EDC
3P 3P 3X
2 or 3P 2 or 3P 3X 100 FB-P

1 2 or 3P
2 or 3P
2 or 3P 3X
3X
250 JD, HJD, JDC

1 2 or 3P 2 or 3P 4X
38.00 (965.2) Wide Box

400 DK, KD, HKD, KDC, CKD, CHKD 


2 or 3P 4X

1 2 or 3P

2 or 3P
4X

6X
600

400
LGE, LGH, LGU

LCL, LA-P

1 2 or 3P 6X 600 LD, HLD, CLD, CHLD, LDC

2 or 3P 6X 800 MDL, HMDL, CMDL, CHMDL


1 2 or 3P 6X 800 ND , HND , NDC , NG 

1 2 or 3P 6X 1200 ND , HND , NDC , NG 

1 3P 7X 250A JG Single Drawout MCCB

3P 9X 600A LG Single Drawout MCCB


1 30A 30A 4X 30A Fusible Switch

1 60A

100A
60A

100A
4X

5X
60A

100A
Fusible Switch

Fusible Switch

1 200A 200A 6X 200A Fusible Switch

200A 6X 200A Fusible Switch


1
400A 9X 400A Fusible Switch

1 600A 11x 600A Fusible Switch

1 2 or 3P 6X 800 NB-P

2 or 3P 6X 1200 CND, CHND, CNDC, NG


1
48.00 (965.2) Wide Box

3P 3P 7X 250A JG Twin Drawout MCCB

1 3P 3P 9X 600A LG Twin Drawout MCCB

1 800A 11X 800A Fusible Switch

1 1200A 15X 1200A Fusible Switch

1 NNote

1
a 1X = 1-3/8 inch.
b No twin-mounted 100% rated K Frame breaker.

1 c For cable sizing greater than 500 kcmil, 48.00-inch-wide (1219.2 mm) cell required.
d For 100% rated 1200A frame, 48.00-inch-wide (1219.2 mm) cell required.

T2-14 Low Voltage Switchboards and SwitchgearCA015002ENAugust 2013www.eatoncanada.ca


Low Voltage Switchboards and Switchgear
Pow-R-Line C Switchboards
2
Moulded-Case Circuit Breakers Load Lug Options a

Ampere Mechanical Mechanical


1
Frame Rating Lugs Copper Only
F 20 #14#10
2
50
100
#14#4
#141/0
3
150
200
#44/0
#44/0
4
225 #44/0
#6300 kcmil
#44/0
5
J
K
250
225
#4350 kcmil
(1) #3350 kcmil
#4350 kcmil
(1) #3350 kcmil
6
400 (1) 250500 kcmil (1) 250500 kcmil
7
(2) 3/0350 kcmil (2) 3/0250 kcmil
(2) 2/0350 kcmil (1) 500750 kcmil 8
(1) 2/0500 kcmil
(1) 500750 kcmil 9
LD 400 (1) 4/0600 kcmil
450 (2) #44/0 kcmil 1
500 (2) 3/0350 kcmil
600 (2) 400500 kcmil (2) 250350 kcmil 1
LG 400 (1) 500750 kcmil (1) 500750 kcmil
(1) #3500 kcmil (1) #3500 kcmil 1
600 (1) #2500 kcmil (2) #2500 kcmil
M 600 (2) 2/0500 kcmil 1
700 (2) #1500 kcmil
800 (3) 3/0400 kcmil (3) 3/0300 kcmil 1
(2) 500750 kcmil
N 700 (2) 1500 kcmil (2) 2/0500 kcmil 1
1000 (3) 3/0400 kcmil (3) 3/0500 kcmil
1200 (4) 4/0500 kcmil (4) 3/0400 kcmil 1
(3) 500750 kcmil
R 1600 (4) 5001000 kcmil (4) #1600 kcmil 1
2000 (6) #2600 kcmil
1
Fusible Switch Load Lug Options b
1
Ampere Rating Mechanical Lugs (Cu/Al)
30/60/100 #141/0 1
200 #4300 kcmil
400 250750 kcmil or (2) 3/0250 kcmil 1
600 (2) #4600 kcmil or (4) 3/0250 kcmil
800 (3) 250750 kcmil or (6) 3/0250 kcmil 1
1200 (4) 250750 kcmil or (8) 3/0250 kcmil
1
Bolted Pressure Switch Lug Options
1
Please consult Eaton for bolted pressure switch lug options.

NNote
1
1
a For MLO options, please refer to Eatons Panelboard catalogue.
b The load lugs are not field replaceable.

1
1
1
1
Low Voltage Switchboards and SwitchgearCA015002ENAugust 2013www.eatoncanada.ca T2-15
2 Low Voltage Switchboards and Switchgear
Pow-R-Line C Switchboards

This page intentionally left blank.


1
2
3
4
5
6
7
8
9
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
T2-16 Low Voltage Switchboards and SwitchgearCA015002ENAugust 2013www.eatoncanada.ca
Low Voltage Switchboards and Switchgear
Commercial Metering Switchboards
3
Contents
Commercial Metering Switchboard
1
Description Page
Standards and Certifications.................................... T3-18 2
Product Selection.................................................... T3-18
Dimensions.............................................................. T3-18 3
4
5
6
7
8
9
1
Commercial Metering Switchboards 1
Product Description Features, Benefits Main Bus Enclosure 1
Eaton commercial metering and Functions Single-bolt bus joints Freestanding, front
switchboards use space- The commercial metering up to 3000A for ease accessible design (rear 1
saving design with modular switchboard has a free- of installation at accessible where required)
construction, incorporating standing switchboard shipping splits Structures are ANSI 61 1
metering sections with construction; it is factory 50 kA bracing standard; light grey baked enamel,
tenant feeder circuits using
meter sockets to meet
assembled and fully
integrated.
65, 85, 100 kA optional code gauge steel with
formed doors / removable
1
Tin-plated aluminum bus
local utility or customer back sheets; other colours
requirements. All meter
is standard with optional
silver-plated copper optional 1
sockets and associated Metering Unit / Metering Cell
available Standard enclosures
feeder devices are Twin-mounted 30A,
Provision for future are CSAT Type 1; 1
completely factory prewired 60A and 100A metering sprinklerproof optional
extension is provided
and shipped ready for the
installation of the meters.
switches available
as standard Split back sheets for 1
Single-mounted 200A
Available with a bus ease of handling
Eaton offers a number of
metering switches available
Metering switches are
connected, incoming Single-cell shipping splits 1
options for commercial Pow-R-Line CE main cell available as standard for
metering switchboards. type FSMC (fusible switch
meter sockets), suitable to
or a separate, standalone ease of handling 1
These include assemblies main lugs only structure
accept revenue grade, self-
that meet utility requirements
for globe type watthour contained meters
Channel sills optional 1
meters and electronic tenant Various meter base jaw
metering switchboards. options available to meet 1
all requirementsmost
Application Description common is Star (Y) type, 1
seven jaw, suitable for
Commercial multi-metering
applications such as:
four-wire systems up to
347/600V
1
Shopping centres Switch jaws are spring
reinforced to firmly
1
Office buildings
grip blades
Condominium complexes
Maximum quantity of
1
Apartment buildings
six FSMC twin or single
units can be installed 1
in each 90.00inch
(2286.0mm) high 1
x 48.00-inch-wide
(1219.2mm) enclosure 1
1
Low Voltage Switchboards and SwitchgearCA015002ENAugust 2013www.eatoncanada.ca T3-17
3 Low Voltage Switchboards and Switchgear
Commercial Metering Switchboards

Standards and Certifications Product Selection Dimensions


1 CSA C22.2 No. 229 Approximate Dimensions in Inches (mm)
CSA C22.2 No. 31 FSMC Device Options
2
CSA C22.2 No. 244 FSMC Layout
Ampere Single
3 Rating or Twin X Space a
30/30 Twin 7X

4 30/60 Twin 7X
60/30 Twin 7X
5 60/60 Twin 7X
100/100 Twin 7X
6 200 Single 7X
NNot
7 a 1X = 1-3/8 inch.

8 90.00
(2286.0)

9
1
1
1 18.00/24.00
48.00
(457.2/609.6)
1 (1219.2)

1
1
1 FSMC Units Installed in
Pow-R-Line C Switchboard

1 Twin 30A, 60A or 100A FSMC Switch

1
1
1
1
Single 200A FSMC Switch
1
1
1
1
1
1
1
1
1
T3-18 Low Voltage Switchboards and SwitchgearCA015002ENAugust 2013www.eatoncanada.ca
Low Voltage Switchboards and Switchgear
Integrated Facility Switchboards
4
Contents
Integrated Facility Switchboards
1
Description Page
Features, Benefits 2
and Functions...................................................... T4-20
Options.................................................................... T4-20 3
Standards and Certifications.................................... T4-20
Product Selection.................................................... T4-21 4
Technical Data and Specifications............................ T4-29
5
6
7
8
9
1
Integrated Facility Switchboards 1
Product Description The service entrance Other associated equipment Application Description 1
Eaton Integrated Facility equipment can be integrated can also be integrated into Eaton Integrated Facility
SwitchboardsE (IFSE) utilizes with multiple lighting the assembly, including Switchboards are designed 1
the modular Pow-R-Line CE and appliance branch dry-type distribution to meet specific needs for:
switchboard design to panelboards into a compact
front accessible group-
transformers, time clock
space, lighting control, Retail stores
1
integrate traditionally
mounted switchboard. electronic controls, surge Commercial offices
separate electrical distribution
and control equipment Where multiple switchboards protection devices, metering,

High rise buildings
1
into a single space-saving or panelboards are used automatic transfer switches
factory assembled and in the same electrical and energy monitoring
Correctional facilities
1
room as a conventional devices. Depending upon Agricultural facilities
connected package.
distribution system, the
integrated design significantly
the application, other user-
defined equipment such as a
Industrial facilities 1
Hospitals / health
reduces equipment space subsystem control package
requirements, as well as may also be incorporated.
care facilities 1
Educational facilities
minimizes installation time
and costs. Whether the application is 1
a multi-site prototype or a
single application, integrated 1
switchboards offer time and
space-saving features. 1
1
1
1
1
1
1
1
1
1
Low Voltage Switchboards and SwitchgearCA015002ENAugust 2013www.eatoncanada.ca T4-19
4 Low Voltage Switchboards and Switchgear
Integrated Facility Switchboards

Features, Benefits Space Savings Options


1 and Functions The space-saving
Busbar System
Standard bus in the Automatic transfer
switchboard installation
2 Front Accessible provides additional usable
switchboards is tin-plated
aluminum or silver-plated
switches
Breakers
Integrated facility floor space. For example: copper; optional tin-plated
3 switchboards are front Retail storesfloor space copper available.
Metering
accessible and align at the Dry-type transformers
for sales
4 rear, enabling them to be
Officesadditional Short-Circuit Rating
Enclosed control
placed against a wall. Most Seismic construction
storage, cubicle
5 switchboards align at the
front and the rear. If the main Health careadditional
Standard bus and connectors
on all switchboards are rated
Surge protection devices
work area for use on systems capable UPS
section is deeper than others
6 due to physical size of the Retrofitsability to fit of producing up to 65 kA HVAC control
main device, the necessary existing rooms rms symmetrical short-circuit Harmonic blocking filter
7 off-set in line-up will occur current at the incoming Power factor correction
in the front, and the main Site Construction Savings terminals. Generator Quick Connect
8 section will be accessible Timely installation of the Short-circuit ratings up to
from both the front and electrical system typically is 200 kA symmetrical are Standards and Certifications
9 the side. a key element on the critical available when used with CSAT C22.2 No. 31
path for any project. approved devices. Contact
CSA C22.2 No. 244
1 Standard Switchboard Height
Along with the time to
Eaton for more information.
Factory wired panelboards
Switchboard height is install the equipment, other and dry-type distribution
1 90.00 inches (2286.0 mm). expenses include the time to Bus Duct Integration transformers meet CSA
handle all of the loose pieces Applications such as condo, C22.2 No. 31 and the
1 Switchboard Shipping Splits of equipment arriving on a job
site and ensuring it reaches
commercial office towers Canadian Electrical Code
The sections can be and health care facilities may Zone 4 Construction (IBC/
the proper trades person.
1 shipped as specified by
With Eaton Integrated Facility
require bus duct. Custom
bus duct flanges can be
CBC Seismic Qualified)
the customer to meet
Switchboards, one piece designed and manufactured
1 specific requirements.
of equipment is typically to coordinate with bus duct
For retrofit applications, shipped to a job site virtually risers of a wide range of
1 single-piece switchboard eliminating these issues. amperages. The bus duct can
structures can be shipped to even be directly integrated
The equipment may also
1 facilitate movement through
be used for temporary into the switchboard,
limited access doorways, etc. eliminating the need for bus
power on job sites, further
1 reducing construction plugs and therefore creating
a more compact footprint.
Factory Interconnections expenses and times.
1 Where interconnections
are required within the IFS, Lighting Control
1 power cabling is factory
Eaton lighting control
installed and sized per the
panelboards with remote
Canadian Electrical Code.
1 control breakers can be
installed in IFS assemblies.
1
1
1
1
1
1
1
1
1 Traditionally Mounted Equipment

1 Integrated Facility Switchboard

T4-20 Low Voltage Switchboards and SwitchgearCA015002ENAugust 2013www.eatoncanada.ca


Low Voltage Switchboards and Switchgear
Integrated Facility Switchboards
4
Product Selection
1
Integrated Facility Switchboard Applications
2
Electrical Room With and Without IFSPlan View
3
Panel L1 Panel L2 4
Main
IFS
Switchboard
5
Transformer
Integrated Facility
Switchboard Solution
6
7

Telephone
8
Telephone Panel P3 Panel P2 Panel P1

9
Traditional Electrical Room IFS Electrical Room
1
Optimized IFS LayoutFront View 1
Main RD 1
Breaker
Customer P1 P3 L1
1
Metering Feeder
Breaker
Section 1
Utility SPD Dry-Type
Metering
Section
P2
Distribution
L2
1
Transformer
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Low Voltage Switchboards and SwitchgearCA015002ENAugust 2013www.eatoncanada.ca T4-21
4 Low Voltage Switchboards and Switchgear
Integrated Facility Switchboards

Approximate Dimensions in Inches (mm)


1
Integrated Facility Switchboards Distribution Section Layout
2 Eaton Pow-R-Line panelboard integrationfactory wired from feeder device in adjacent section(s) to panelboards.
Standard features include lockable trim doors and factory-mounted overcurrent devices.
3
Style 1 and 2 Integrated Facility Switchboards Distribution Section Layout
4
W
5 3.00
(76.2)
3.00
(76.2)

6
3.00
7 D (76.2)
Conduit Area
12.00
(304.8)
8 Cell A

9 90.00 90.00
Floor Plan
Cell C Style 1 and 2 Sections
(2286.0) (2286.0)
1 W
3.00 3.00
1 Cell B (76.2) (76.2)

1 3.00
D (76.2) Conduit Area 3.00
1 D D
(76.2)
W W
1
IFS Style 1 Section IFS Style 2 Section Floor Plan
1 Style 2 Section with Blank Steel Backpan Only

1 IFS Style 1 Allowable Configurations (Select One Panelboard Type per Panelboard Cell)
Main Maximum Branch Allowable Width (W) Depth (D)
1 Panel
Cell
Panelboard
Type
Maximum
Vac Rating
Device
Type
Main Rating
Amperes
Circuit Panelboard
Ampere Range Modifications Standard Optional Standard Optional
Section
Height

1 IFS Style 1 Section


A Pow-R-Line 1a 240 MLO 600 15100 ab 26.00 (660.4) 30.00 (762.0) 18.00 (457.2) 24.00 (609.6) 90.00 (2286.0)

1 Breaker 225 20.00 (508.0) 26.00 (660.4)


30.00 (762.0)
Pow-R-Line 2a 600Y/347 MLO 600 15100 ab 26.00 (660.4) 30.00 (762.0) 18.00 (457.2) 24.00 (609.6) 90.00 (2286.0)
1 Breaker 225 20.00 (508.0) 26.00 (660.4)
30.00 (762.0)
1 Pow-R-CommandE 240 MLO 225 15100 ab 20.00 (508.0) 26.00 (660.4) 18.00 (457.2) 24.00 (609.6) 90.00 (2286.0)
480Y/277 30.00 (762.0)
1 Blank steel
backpan c
None d 20.00 (508.0) 26.00 (660.4)
30.00 (762.0)
18.00 (457.2) 24.00 (609.6) 90.00 (2286.0)

1 B Pow-R-Line 1a 240 MLO


Breaker
600
225
15100 ab 26.00 (660.4)
20.00 (508.0)
30.00 (762.0)
26.00 (660.4)
18.00 (457.2) 24.00 (609.6) 90.00 (2286.0)

30.00 (762.0)
1 Pow-R-Line 2a 600Y/347 MLO 600 15100 ab 26.00 (660.4) 30.00 (762.0) 18.00 (457.2) 24.00 (609.6) 90.00 (2286.0)

1 Breaker 225 20.00 (508.0) 26.00 (660.4)


30.00 (762.0)
Pow-R-Command 240 MLO 225 15100 ab 20.00 (508.0) 26.00 (660.4) 18.00 (457.2) 24.00 (609.6) 90.00 (2286.0)
1 480Y/277 30.00 (762.0)
Blank steel None d 20.00 (508.0) 26.00 (660.4) 18.00 (457.2) 24.00 (609.6) 90.00 (2286.0)
1 backpan c 30.00 (762.0)
NNote
1 a Copper main lugs, ground bar circuit breaker handle lockoff devices, nameplates, 200% rated neutral through 400A, permanent circuit numbers, directory frames, shunt trip breakers, through-feed
lugs to panel immediately above or below.

1 b If panel sizing with non-interchange main is 48.00 inches (1219.2 mm) high or less, the panel will fit in a half section. If it is 72.00 inches (1828.8 mm) high, you must use a full section.
If it is 60.00 inches (1524.0 mm) high, contact Eaton for structure dimensions. (One exception is PRL 1a/2a with 400A MLO and 42 circuits, which will fit in half section.)
c Possible uses: HVAC, dimming, contactors, A/V equipment and data rack equipment. Contact Eaton for details.
1 d Galvanized steel backpan provided for customer specified equipment. Contact Eaton for details.

T4-22 Low Voltage Switchboards and SwitchgearCA015002ENAugust 2013www.eatoncanada.ca


Low Voltage Switchboards and Switchgear
Integrated Facility Switchboards
4
Approximate Dimensions in Inches (mm)
1
Style 1 and 2 Integrated Facility Switchboards Distribution Section Layout

W
2
3.00
(76.2)
3.00
(76.2) 3
4
3.00
D (76.2)
Conduit Area
12.00
(304.8)
5
Cell A
6
90.00 90.00
Cell C
Floor Plan
Style 1 and 2 Sections
7
(2286.0) (2286.0)

W 8
3.00 3.00
Cell B (76.2) (76.2) 9
3.00 1
D (76.2) Conduit Area 3.00
D D
(76.2)
1
W W
1
IFS Style 1 Section IFS Style 2 Section Floor Plan
Style 2 Section with Blank Steel Backpan Only
1
IFS Style 2 Allowable Configurations (Select One Panelboard Type per Panelboard Cell)
1
Main Maximum Branch Allowable Width (W) Depth (D)
Panel
Cell
Panelboard
Type
Maximum
Vac Rating
Device
Type
Main Rating
Amperes
Circuit Panelboard
Ampere Range Modifications Standard Optional Standard Optional
Section
Height 1
IFS Style 2 Section
C Pow-R-Line 1a 240 MLO 600 15100 ab 26.00 (660.4) 30.00 (762.0) 18.00 (457.2) 24.00 (609.6) 90.00 (2286.0)
1
Pow-R-Line 2a 600Y/347
Breaker
MLO
400
600 15100 ab 26.00 (660.4) 30.00 (762.0) 18.00 (457.2) 24.00 (609.6) 90.00 (2286.0)
1

Pow-R-Line 3a 600
Breaker
MLO
400
600 15125 ab 26.00 (660.4) 30.00 (762.0) 18.00 (457.2) 24.00 (609.6) 90.00 (2286.0)
1
Breaker 400
1
Pow-R-Command 480Y/277 MLO 400 15100 ab 26.00 (660.4) 30.00 (762.0) 18.00 (457.2) 24.00 (609.6) 90.00 (2286.0)
Breaker 225 1
Blank steel None d 20.00 (508.0) 26.00 (660.4) 18.00 (457.2) 24.00 (609.6) 90.00 (2286.0)

NNote
backpan c 30.00 (762.0)
1
a Copper main lugs, ground bar circuit breaker handle lockoff devices, nameplates, 200% rated neutral through 400A, permanent circuit numbers, directory frames, shunt trip breakers, through-feed
lugs to panel immediately above or below.
1
b If panel sizing with non-interchange main is 48.00 inches (1219.2 mm) high or less, the panel will fit in a half section. If it is 72.00 inches (1828.8 mm) high, you must use a full section.
If it is 60.00 inches (1524.0 mm) high, contact Eaton for structure dimensions. (One exception is PRL 1a/2a with 400A MLO and 42 circuits, which will fit in half section.) 1
c Possible uses: HVAC, dimming, contactors, A/V equipment and data rack equipment. Contact Eaton for details.
d Galvanized steel backpan provided for customer specified equipment. Contact Eaton for details. 1
1
1
1
1
1
1
Low Voltage Switchboards and SwitchgearCA015002ENAugust 2013www.eatoncanada.ca T4-23
4 Low Voltage Switchboards and Switchgear
Integrated Facility Switchboards

Approximate Dimensions in Inches (mm)


1
Style 3 and 4 Integrated Facility Switchboards Distribution Section Layout
2
3
4 Cell F
W
5 Cell D 3.00
(76.2)
3.00
(76.2)

6
90.00 90.00 3.00
7 (2286.0) (2286.0) D (76.2) Conduit Area 3.00
(76.2)

8
Cell E
9 Floor Plan Style 3 Section
with Blank Space in Cell E

1 Bottom Entry Conduit Space not


Recommended with Transformer
D D in Cell E or F (Style 3 or 4)
1 W W

1 IFS Style 3 Section IFS Style 4 Section

1 IFS Style 3 Allowable Configurations (Select One Panelboard Type per Panelboard Cell)
Main Maximum Branch Allowable Width (W) Depth (D)
1 Panel Panelboard Maximum Device Main Rating Circuit Panelboard Section
Cell Type Vac Rating Type Amperes Ampere Range Modifications Standard Optional Standard Optional Height

1 IFS Style 3 Section


D Pow-R-Line 1a 240 MLO 600 15100 a 26.00 (660.4) 30.00 (762.0) 24.00 (609.6) 90.00 (2286.0)
1 Breaker 225
Pow-R-Line 2a 600Y/347 MLO 600 15100 a 26.00 (660.4) 30.00 (762.0) 24.00 (609.6) 90.00 (2286.0)
1 Breaker 225
Pow-R-Line 3a 600 MLO 600 15125 ab 26.00 (660.4) 30.00 (762.0) 24.00 (609.6) 90.00 (2286.0)
1 Breaker 400
Pow-R-Line C 600 MLO 800 15600 a 26.00 (660.4) 36.00 (914.4) 24.00 (609.6) 90.00 (2286.0)
1 switchboard
chassis
Breaker 600 30.00 (762.0)
MLO or 800 15600 a 36.00 (914.4) 24.00 (609.6) 90.00 (2286.0)
1 Breaker
Pow-R-Command 240 MLO 225 15100 a 26.00 (660.4) 30.00 (762.0) 24.00 (609.6) 90.00 (2286.0)
1 Blank steel
480Y/277
None c 26.00 (660.4) 30.00 (762.0) 24.00 (609.6) 90.00 (2286.0)
backpan
1 NNote

1 a Copper main lugs, ground bar circuit breaker handle lockoff devices, nameplates, 200% rated neutral through 400A, permanent circuit numbers, directory frames, shunt trip breakers, through-feed
lugs to panel immediately above or below.
b If panel sizing with non-interchange main is 48.00 inches (1219.2 mm) high or less, the panel will fit in a half section. If it is 72.00 inches (1828.8 mm) high, you must use a full section.
1 If it is 60.00 inches (1524.0 mm) high, contact Eaton for structure dimensions. (One exception is PRL 1a/2a with 400A MLO and 42 circuits, which will fit in half section.)
c Galvanized steel backpan provided for customer specified equipment. Contact Eaton for details.
1 Select one Panelboard Type or one Blank Steel Backpan and either one Transformer or one Blank Space per Cell.

1
1
1
1
1
T4-24 Low Voltage Switchboards and SwitchgearCA015002ENAugust 2013www.eatoncanada.ca
Low Voltage Switchboards and Switchgear
Integrated Facility Switchboards
4
Approximate Dimensions in Inches (mm)
1
Style 3 and 4 Integrated Facility Switchboards Distribution Section Layout
2
3
Cell F
4
W
Cell D 3.00
(76.2)
3.00
(76.2)
5
6
90.00 90.00 3.00
(2286.0) (2286.0) D (76.2) Conduit Area 3.00
(76.2)
7
8
Cell E
Floor Plan Style 3 Section 9
with Blank Space in Cell E
Bottom Entry Conduit Space not
Recommended with Transformer 1
D D in Cell E or F (Style 3 or 4)
W W
1
IFS Style 3 Section IFS Style 4 Section
1
IFS Style 3 and 4 General Purpose Dry-Type Distribution Transformers 1
Panel Panelboard Temperature kVA Full Cap Taps Allowable Width (W) Depth (D) Section
Cell Type Rise Windings Range FCAN FCBN Modifications Standard Optional Standard Optional Height 1
IFS Style 3 Section
E ab Transformer c 150C only d Aluminum 1545 42.5% 22.5% a 26.00 (660.4) 24.00 (609.6) 90.00 (2286.0)
1
150C only d Aluminum 75 42.5% 22.5% 30.00 (762.0) 24.00 (609.6) 90.00 (2286.0)
1
a

115C Aluminum 112.5 42.5% 22.5% a 36.00 (914.4) 24.00 (609.6) 90.00 (2286.0)
IFS Style 4 Section
Fa Transformer c 150C Aluminum 150 42.5% 22.5% a 36.00 (914.4) 30.00 (762.0) 90.00 (2286.0)
1
225 42.5% 22.5% 44.00 (1117.6) 36.00 (914.4) 90.00 (2286.0)
1
a

NNote
a Copper windings, 115C, 80C, K-Factor, low sound are available options but may change dimensions.
b Either one F Frame or K Frame circuit breaker can be included in any transformer section to be used as a disconnect.
1
c General purpose CSA C802.2 Energy Efficient.
d Contact Eaton for other temperature rise transformers and special requirements.
1
1
1
1
1
1
1
1
1
1
1
Low Voltage Switchboards and SwitchgearCA015002ENAugust 2013www.eatoncanada.ca T4-25
4 Low Voltage Switchboards and Switchgear
Integrated Facility Switchboards

Approximate Dimensions in Inches (mm)


1
Style 5 and 6 Integrated Facility Switchboards Distribution Section Layout
2
W
3 3.00
(76.2)
3.00
(76.2)

4 a
22X 3.00

5 Cell G
Distribution
Chassis
D (76.2)
Conduit Area
12.00
(304.8)
Cell H
6
90.00 90.00
7 (2286.0) (2286.0) Floor Plan
Style 5 and 6 Sections

8 22X
a

Distribution Cell G
9 Chassis
Cell H

1
D D
1 W W

IFS Style 5 Section IFS Style 6 Section


1
1 IFS Style 5 and 6 Allowable Configurations (Select One Panelboard Type per Panelboard Cell)
Main Maximum Branch Allowable Width (W) Depth (D)
1 Panel
Cell
Panelboard
Type
Maximum
Vac Rating
Device
Type
Main Rating
Amperes
Circuit Panelboard
Ampere Range Modifications Standard Optional Standard Optional
Section
Height

1 IFS Style 5 and 6 Sections


G Pow-R-Line 1a 240 MLO 600 15100 bc 26.00 (660.4) 30.00 (762.0) 18.00 (457.2) 24.00 (609.6) 90.00 (2286.0)

1 Breaker 225
Pow-R-Line 2a 600Y/347 MLO 600 15100 bc 26.00 (660.4) 30.00 (762.0) 18.00 (457.2) 24.00 (609.6) 90.00 (2286.0)

1 Breaker 225
Pow-R-Line 3a 600 MLO 600 15125 bc 26.00 (660.4) 30.00 (762.0) 18.00 (457.2) 24.00 (609.6) 90.00 (2286.0)
1 Breaker 400
Pow-R-Command b 240 MLO 225 15100 b 26.00 (660.4) 30.00 (762.0) 18.00 (457.2) 24.00 (609.6) 90.00 (2286.0)
1 H Pow-R-Line C
480Y/277
600 MLO 800 15600 b 26.00 (660.4) 30.00 (762.0) 18.00 (457.2) 24.00 (609.6) 90.00 (2286.0)
switchboard 36.00 (914.4)
1 chassis
Breaker
Breaker
600
800 15600 b 36.00 (914.4) 24.00 (609.6) 90.00 (2286.0)

1 NNote
a 1X = 1-3/8 inch.

1 b Copper main lugs, ground bar circuit breaker handle lockoff devices, nameplates, 200% rated neutral through 400A, permanent circuit numbers, directory frames, shunt trip breakers,
through-feed lugs to panel immediately above or below.

1 c If panel sizing with non-interchange main is 48.00 inches (1219.2 mm) high or less, the panel will fit in a half section. If it is 72.00 inches (1828.8 mm) high, you must use a full section.
If it is 60.00 inches (1524.0 mm) high, contact Eaton for structure dimensions. (One exception is PRL 1a/2a with 400A MLO and 42 circuits, which will fit in half section.)

1
1
1
1
1
1
1
T4-26 Low Voltage Switchboards and SwitchgearCA015002ENAugust 2013www.eatoncanada.ca
Low Voltage Switchboards and Switchgear
Integrated Facility Switchboards
4
Approximate Dimensions in Inches (mm)
1
Style 7 Integrated Facility Switchboards Distribution Section Layout
2
W
3
Cell Cell 4
I J D
5
Floor Plan Style 7 Section
6
There is no Bottom Entry
Conduit Space with
Transformer in Cell J
7
Cell K
8
9
IFS Style 7 Section 1
IFS Style 7 Panelboard Over Dry-Type Transformer (Select One Panelboard Type per Panelboard Cell)
1
Panel Panelboard Maximum
Main
Device
Maximum
Main Rating
Branch
Circuit
Allowable
Panelboard
Width (W) Depth (D)
Section
1
Cell Type Vac Rating Type Amperes Ampere Range Modifications Standard Optional Standard Optional Height
IFS Style 7 Section
1
I Pow-R-Line 1a 240 MLO
Breaker
400 15100 a 36.00 (914.4) 24.00 (609.6) 90.00 (2286.0)
1
Pow-R-Line 2a 600Y/347 MLO
Breaker
400 15100 a 36.00 (914.4) 24.00 (609.6) 90.00 (2286.0)
1
J Pow-R-Line 1a 240 MLO 400 15100 a 36.00 (914.4) 24.00 (609.6) 90.00 (2286.0)
1
Breaker
Pow-R-Line 2a 600Y/347 MLO 400 15100 a 36.00 (914.4) 24.00 (609.6) 90.00 (2286.0) 1
Breaker
Pow-R-Line 3a 600 MLO 400 15225 ab 36.00 (914.4) 24.00 (609.6) 90.00 (2286.0) 1
Breaker

IFS Style 7 General Purpose Dry-Type Distribution Transformers


1
Panel Panelboard Temperature kVA
Full Cap Taps
Allowable
Width (W) Depth (D)
Section 1
Cell Type Rise Windings Range FCAN FCBN Modifications Standard Optional Standard Optional Height
IFS Style 7 Section 1
K Transformer cd 150C only e Aluminum 1575 42.5% 22.5% f 36.00 (914.4) 24.00 (609.6) 90.00 (2286.0)
115C Aluminum 112.5 42.5% 22.5% f 36.00 (914.4) 24.00 (609.6) 90.00 (2286.0) 1
NNote
a Copper main lugs, ground bar circuit breaker handle lockoff devices, nameplates, 200% rated neutral through 400A, permanent circuit numbers, directory frames, shunt trip breakers,
1
through-feed lugs to panel immediately above or below.
b If panel sizing with non-interchange main is 48.00 inches (1219.2 mm) high or less, the panel will fit in a half section. If it is 72.00 inches (1828.8 mm) high, you must use a full section. 1
If it is 60.00 inches (1524.0 mm) high, contact Eaton for structure dimensions. (One exception is PRL 1a/2a with 400A MLO and 42 circuits, which will fit in half section.)
c Either one F Frame or K Frame circuit breaker can be included in any transformer section to be used as a disconnect. 1
d General purpose CSA C802.2 Energy Efficient.
e Contact Eaton for other temperature rise transformers and special requirements. 1
f Copper windings, 115C, 80C, K-Factor, and harmonic mitigating transformers are available options but may change dimensions.

1
1
1
1
Low Voltage Switchboards and SwitchgearCA015002ENAugust 2013www.eatoncanada.ca T4-27
4 Low Voltage Switchboards and Switchgear
Integrated Facility Switchboards

Approximate Dimensions in Inches (mm)


1
Integrated Facility Switchboards ATS Section Layout
2 Eaton Pow-R-Line panelboard and integrated wall-mounted ATS (non-bypass)factory wired from feeder devices in adjacent sections.
Standard features include lockable trim doors and factory-mounted overcurrent devices.
3
Style 8, 9, 10 and 11 Integrated Facility Switchboards Ats Section Layout
4
5
6
a
22X
7 Cell L Cell O
Distribution
Chassis

8
90.00 90.00 90.00 90.00
9 (2286.0) (2286.0) Cell N (2286.0) (2286.0)

1
22X a
Cell M Cell P
1 Distribution
Chassis

1
D D D D
1 W W W W

1 IFS Style 8 Section IFS Style 9 Section IFS Style 10 Section IFS Style 11 Section

1 IFS Style 8, 9, 10 and 11 Contactor-Based, Non-Bypass Transfer Switches (Select One ATS Type per ATS Cell)
1 Maximum Main Rating
Width
20.00 26.00 30.00 36.00
Depth
18.00 24.00
Standard Terminals
Load Side, Normal Neutral
ATS Cell Vac Rating Amperes (508.0) (660.4) (762.0) (914.4) (457.2) (609.6) and Standby Source Connection
1 IFS Style 8, 9, 10 and 11 Sections

1 L/M/O/P 480 40100 n n n n n n (1) #142/0 (3) #141/0


600 40100 n n n n n n (1) #6250 kcmil (3) #141/0
1 480 150200 n n n n n n (1) #6250 kcmil (3) 1/0250 kcmil
600 150200 n n n n n n (1) #6250 kcmil (3) 1/0250 kcmil
1 480 225400 n n n n n n (2) 3/0250 kcmil (6) 250500 kcmil
(1) 3/0600 kcmil
1 N 480 40100 n n n n n n (1) #142/0 (3) #141/0
600 40100 n n n n n n (1) #6250 kcmil (3) #141/0
1 480 150200 n n n n n n (1) #6250 kcmil (3) 1/0250 kcmil
600 150200 n n n n n n (1) #6250 kcmil (3) 1/0250 kcmil
1 480 225400 n n n n n n (2) 3/0250 kcmil (6) 250500 kcmil
(1) 3/0600 kcmil
1 600 225400 n n n (2) 3/0250 kcmil (6) 250500 kcmil
(1) 3/0600 kcmil
1 6001200 n n n (4) 1/0750 kcmil (12) 1/0750 kcmil
480 6001200 n n n (4) 1/0750 kcmil (12) 1/0750 kcmil
1 NNote
a 1X = 1-3/8 inch.
1 All amperages available in three- and four-pole.

1
1
1
T4-28 Low Voltage Switchboards and SwitchgearCA015002ENAugust 2013www.eatoncanada.ca
Low Voltage Switchboards and Switchgear
Integrated Facility Switchboards
4
Approximate Dimensions in Inches (mm)
1
IFS Style 8, 9, 10 and 11 Breaker-Based, Non-Bypass Transfer Switches
(Select One ATS Type per ATS Cell) 2
Width Depth
Frame Maximum Main Rating 26.00 30.00 36.00 18.00 24.00 3
ATS Cell Size Vac Rating Amperes (660.4) (762.0) (914.4) (457.2) (609.6)
IFS Style 8, 9, 10 and 11 Sections 4
L/M/O/P F 600 30150 n n n n n
240 30200 5
N F 600 30150 n n n n n
240 30200 6
K, L, M 600/240 225600 n n n
Na 600/240 8001200 n n n 7
NNote
a Please consult Eaton for N size breaker frame. 8
All amperages available in two-, three- and four-pole.
9
Technical Data and Specifications 1
Contactors / Motor Control
1
Consult Eaton for complete application.
1
Seismic Construction
Zone 4 seismic is optional. 1
Metering 1
Metering can be installed in the following standard cells:
1
Blank steel backpan (20, 26, 30, 36 inches wide)
Pow-R-Line 4 chassis (minimum 36 inches wide, 1
22X spacing)
Metering products: 1


IQ 100 (130, 140, 150)
IQ 200 (250, 260)
1
PXM (2250, 2260, 2270, 4000, 6000, 8000) 1
PXG (400e, 600e, 800e)
IQ 35M 1
Non-Eaton products
Consult Eaton for more information. 1
1
1
1
1
1
1
1
1
1
Low Voltage Switchboards and SwitchgearCA015002ENAugust 2013www.eatoncanada.ca T4-29
4 Low Voltage Switchboards and Switchgear
Integrated Facility Switchboards

This page intentionally left blank.


1
2
3
4
5
6
7
8
9
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
T4-30 Low Voltage Switchboards and SwitchgearCA015002ENAugust 2013www.eatoncanada.ca
Low Voltage Switchboards and Switchgear
Pow-R-Line C Switchboards with Drawout Moulded-Case Circuit Breaker
5
Contents
Pow-R-Line C Switchboard with Drawout Moulded-Case Circuit Breakers
1
Description Page
Standards and Certifications.................................... T5-32 2
Product Selection.................................................... T5-33
Technical Data and Specifications............................ T5-33 3
Dimensions.............................................................. T5-33
4
5
6
7
8
9
1
Pow-R-Line CE Switchboards with Drawout Moulded-Case Circuit Breaker 1
Product Description Application Description The base cassette is Drawout Cassette 1
Eaton drawout moulded- Drawout moulded-case circuit designed to accept the The drawout cassette
case circuit breakers are breaker switchboards are drawout cassette that contains the breaker and is 1
installed in switchboards in ideal for applications such as: contains the breaker. The group-mounted. The cassette
a group-mounted manner.
Data centres
loadside feeder conductors
are also part of the base
incorporates a viewing 1
Breakers use drawout window and an external
Health care facilities cassette, allowing the
cassettes and are three-
pole with ratings from 20A

Process industry loadside feeder conductors
racking port. The viewing
window allows personnel to
1
to 600A. The breakers are to remain with the base visually inspect the breaker
inserted and removed via a
Institutions cassette when the breaker is status and to see whether 1
Laboratories removed without removing the breaker is connected to
mechanical system similar
to other drawout designs Critical load applications the loadside conductors. or disconnected from the 1
associated with switchgear; The base cassette contains a bus. The window exposes
however, these breakers Features, Benefits drawout racking mechanism, the Connected/Disconnected
position indicator on the base
1
are horizontally mounted in and Functions a Connected/Disconnected
cassette. The external racking
a traditional switchboard.
Feeder devices are also Enclosures
position indicator and a pull-
port allows access to the 1
apart terminal block base
front accessible and front racking mechanism to draw
connected.
CSAT Type 1, sprinklerproof (used for connections to the
breaker accessories). out the breaker. 1
optional. Please consult Eaton
for other enclosure types.
Group-mounted drawout
moulded-case circuit breakers
NNote: Per industry practice,
all power to the board section
The drawout cassette
contains handles attached
1
include Eaton JG and LG must be disconnected at its to the deadfront to help
breaker families and include
Base Cassette
source before working on any easily remove the breaker. 1
standard thermal-magnetic The base cassette is electrical equipment. The cassette also contains
trip units or optional Eaton permanently factory mounted
to the switchboards chassis.
a pigtail wiring harness, 1
310+ electronic trip units. Safety features include which is factory-wired from
The lineside connections finger-safe connections to
use bus connectors and are the moulded-case circuit
the breaker accessory ports
and contains a pull-apart
1
factory connected to the breaker drawout cassette and terminal block that attaches
switchboards vertical bus. a mechanism system that the permanently mounted 1
will not allow the breaker to female terminal block located
be connected or removed on the base cassette. 1
while the breaker is in the External connections on
energized, ON, position. the secondary side of the 1
terminal block are provided
by the installer.
1
1
1
Low Voltage Switchboards and SwitchgearCA015002ENAugust 2013www.eatoncanada.ca T5-31
5 Low Voltage Switchboards and Switchgear
Pow-R-Line C Switchboards with Drawout Moulded-Case Circuit Breaker

The drawout cassette Surge Protection Devices (SPDs) When the Eaton Arcflash Zone selective interlocking
1 employs two breaker Eaton SPDs are available. Reduction Maintenance provides increased system
familiesthe JG and the A moulded-case circuit System is enabled, the protection and can reduce
2 LG with standard thermal- breaker is provided as a resulting reduced arc-flash arc-flash risk by allowing the
magnetic trip unit. Optional lineside disconnect for energy allows for reduced breaker closest to the fault
3 310+ electronic trip units
offer ampere ratings from
the SPD. Refer to Tab 8 PPE, which improves worker
comfort and mobility. With
to trip without any preset
time delays. This is achieved
Componentsor contact
20A to 250A on the JG and the Arcflash Reduction by selecting and setting the
4 100A to 600A on the LG.
Eaton for more information.
Maintenance System set trip unit equipped with the
at 2.5X or 4.0X, it reduces zone selective interlocking
5 Breaker Options
Optional Infrared (IR) incident energy levels to allow option. The hardwired
Viewing Windows PPE Category 0 for currents connection between the
6 Electronic trip units
Infrared viewing windows
Infrared windows are an of 2.5X or 4.0X the breaker trip units sends a restraining
available option on both ampere rating or greater. The signal upstream, allowing the
7 for the lineside and
loadside connections
the JG and LG families of
single-mounted drawout
initial setting of each Arcflash
Reduction Maintenance
breaker closest to the fault
to act instantaneously. Zone
Shunt trips moulded-case circuit breaker System trip unit is determined selective interlocking reduces
8 Auxiliary contacts
cassettes. Infrared windows by completing a power stress on the distribution
can be located to view the system analysis to assess system and can reduce arc-
9 Bell alarm
Zone selective interlocking
lineside and/or loadside available fault current at the flash risk by isolating faults
connections. circuit breaker. Based on that without time delays.
1 Arcflash Reduction analysis, the Maintenance
mode protection settings are
Maintenance SystemE Arcflash Reduction Standards and Certifications
defined, achieving a reduced
1 The JG and LG families Maintenance System
level of arc-flash energy. The
CSA C22.2 No. 31
of drawout breakers are The Eaton Arcflash Reduction Maintenance mode is then CSA C22.2 No. 244
1 available in either a single Maintenance System provides activated by adjusting the trip
group-mounted design or reduced levels of incident units instantaneous setting to
1 a high-density, twin group-
mounted design where two
arc-flash energy when put
in the Maintenance mode.
desired Maintenance mode
levels that are determined by
breakers occupy the same The Arcflash Reduction
1 vertical space. Maintenance System is
the power analysis.
available on the LG family of
1 Short-Circuit Rating
drawout MCCBs, combining Electronic Trip Units With Zone
Selective Interlocking (ZSI)
the Arcflash Reduction
1 The short-circuit current
rating of the switchboard is
Maintenance System with
the Digitrip 310+ electronic
Unlike power air circuit
breakers, moulded-case
determined by the short- trip unit and allowing for the circuit breakers do not offer
1 circuit current rating of the ability to place the trip unit in the ability to turn off the
lowest rated overcurrent Maintenance mode to reduce instantaneous trip settings.
1 device in the switchboard. potential arc-flash energy. As a result, the coordination
This is done by a dedicated between one breaker and
1 Busbar System instantaneous sensing circuit another could compromise
with settings of 2.5 and 4.0 selectivity (breaker closest
Standard tin-plated copper
1 bus and silver-plated copper.
times the current rating of
the trip unit. This dedicated
to the fault opening first).
Zone selective interlocking
analog sensing circuit delivers is designed to mitigate
1 Metering breaker clearing times that are selectivity issues with
A full line of Eaton customer faster than instantaneous by moulded-case circuit breakers.
1 metering is available. All eliminating microprocessor
Both the JG and LG families
options offered in Eatons processing latencies. This
of moulded-case circuit
1 standard bolt-on switchboard provides superior arc flash
breakers offer zone selective
product are also available reduction to competing
interlocking as an option.
1 with the Pow-R-Line drawout systems that simply lower
the standard instantaneous
moulded-case circuit breaker
pickup set point.
1 switchboard. Refer to Tab8
Componentsor contact
Eaton for more information.
1
1
1
1
1
T5-32 Low Voltage Switchboards and SwitchgearCA015002ENAugust 2013www.eatoncanada.ca
Low Voltage Switchboards and Switchgear
Pow-R-Line C Switchboards with Drawout Moulded-Case Circuit Breaker
5
Product Selection Technical Data and Specifications
Eaton Pow-R-Line C switchboard: 1
Standard Adjustable Thermal-Magnetic
Single Group-Mounted
Feeder Trip Units
Maximum 4000A rating 2
Rated at 240, 480 and 600 Vac
250A JG Frame 600A LG Frame
Maximum interrupting ratings: 3
70A 250A 200 kAIC at 240 Vac
90A 300A 100 kAIC at 480 Vac 4
100A 350A 65 kAIC at 600 Vac
125A 400A 5
150A 500A
175A 600A Short-Circuit Current Ratings
6
200A Short-Circuit Rating kA
225A Maximum Breaker
Ampere Rating
Breaker
Frame
Symmetrical by Vac
240V 480V 600V
7
250A
250 JGS 85 35 18 8
JGH 100 65 25
Optional 310+ Electronic Trip Units
Twin Group-Mounted
Feeder
250A JG Frame 600A LG Frame
JGC 200 100 35 9
JGU 200 150 50
20A 100A 600 LGS 85 35 25 1
25A 125A LGH 100 65 35
30A 150A LGC 200 100 50 1
40A 175A LGU 200 150 65
45A 200A 1
50A 225A
Optional Accessories
70A 250A
Position a
1
80A 300A
90A 350A
Accessory Left Right
1
100A 400A Alarm contact (Make/Break) n

110A 450A Auxiliary switch (1A/1B) n


1
125A 500A Auxiliary switch (2A/2B) n

150A 600A Auxiliary switch and alarm contact n 1


175A Shunt trip (specify voltage) n

200A Undervoltage release mechanism n 1


225A
250A 1
Dimensions
Approximate Dimensions in Inches (mm) 1
Drawout Group-Mounted X Space Factors b
1
Breaker Family Type
Group-Mounted
Chassis X Space
Width 1
and Configuration Required 38.00 (965.2) 48.00 (1219.2)
JG family, single mount 7X n n
1
JG family, dual/twin mount
LG family, single mount
7X
9X

n
n
n
1
LG family, dual/twin mount
NNote
9X n
1
a Only one accessory per position.
b 1X = 1-3/8 inch.
1
1
1
1
1
1
Low Voltage Switchboards and SwitchgearCA015002ENAugust 2013www.eatoncanada.ca T5-33
5 Low Voltage Switchboards and Switchgear
Pow-R-Line C Switchboards with Drawout Moulded-Case Circuit Breaker

This page intentionally left blank.


1
2
3
4
5
6
7
8
9
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
T5-34 Low Voltage Switchboards and SwitchgearCA015002ENAugust 2013www.eatoncanada.ca
Low Voltage Switchboards and Switchgear
Generator Connection Assemblies
6
Contents
Typical Generator Quick Connect Assembly
1
Description Page
Generator Quick Connect Switchboards.................. 2
Standards and Certifications............................... T6-36
Product Selection............................................... T6-36 3
Technical Data and Specifications....................... T6-36
Dimensions........................................................ T6-36
4
Customer Service Termination Enclosure................ T6-37
Roll-Up Generator Quick Connect Assembly........... T6-39
5
6
7
8
External View Internal View
9
1
Generator Quick Connect Switchboards 1
Product Description Application Description Features, Benefits Safer and More Reliable 1
The Eaton Generator Quick The Generator Quick Connect and Functions Reduces the potential
Connect Switchboard is Switchboard can be applied safety hazards associated 1
an engineered assembly in both new and retrofit Reduced Downtime with connecting the
designed to allow safe applications. (Speed of Connection) mobile generator to 1
and reliable connection of The Generator Quick Connect the facilitys electrical
The switchboard supports system under lost power
a mobile generator to the
facilitys electrical system. all market segments and
Switchboard is ready for
immediate connection. conditions
1
applications, such as: Eliminates the safety
Once the Quick Connect
The Eaton Quick Connect
Commercial facilities Switchboard is installed: hazards of generator 1
includes Cam-type
cables lying in the path of
receptacles, standard
mechanical lugs, a dedicated
Institutions and
school boards
A permanent connection customers or employees 1
point for temporary mobile
generator-service disconnect, Retail buildings
and a manual key-interlock

Industrial facilities
power is established
No additional field Reduced Emergency Costs 1
transfer scheme. The modifications to the The costs associated with
switchboard provides a
Residential facilities
internal switchboard are temporarily connecting 1
quick and safe supply of Health care facilities
required to connect the mobile generators, such as
emergency power to parts of Wastewater treatment
facilities
generator cables modifying switchboards, 1
the electrical power system making physical modifications
Modifications to the
that are not covered by the
emergency power system;
Data centres
facilitys physical structure to buildings, and routing 1
to accommodate generator cables to connect the mobile
it can also back up existing
generators. cables (e.g., drilling holes generator, are eliminated or
greatly reduced.
1
in walls) is not required
Loads connected to the
Generator Quick Connect
No routing of cables 1
through doorways,
Switchboard can be safely
transferred to an alternative
windows, hallways or
staircases is required
1
power source.
1
1
1
1
1
1
Low Voltage Switchboards and SwitchgearCA015002ENAugust 2013www.eatoncanada.ca T6-35
6 Low Voltage Switchboards and Switchgear
Generator Connection Assemblies

Decreased Utility Dependency Standards and Certifications Technical Data and Specifications
1 The Quick Connect CSAT C22.2 No. 31
Switchboard allows the Generator Quick Connect kW Ratings (Rated up to 600V)
2
a
facility to switch between
kW (Maximum) Rating c
utility feed and generator
3 feed, without relying on utility
Ampere
80% Rated Generator
Disconnect Breaker
100% Rated Generator
Disconnect Breaker
for disconnect service. Rating b 600V 208V 600V 208V
4 Product Selection 400 266 92 332 115

5 Standard Generator Quick


600
800
399
531
138
184
498
664
173
230
Connect Assembly
6 Standard ratings available
1200
1600
797
1063
276
368
996
1329
345
461
up to 2000A (80% rated)
7 or 1600A (100% rated)
Generator Quick Connect Main Breaker Ratings
Detailed operating

8 instructions mounted
on front cover
Breaker Maximum Interrupting Rating (kA)
Cam Lock Receptacles with Frame Ampere Rating 240V 600V

9 Colour-Coded Generator Connections The Generator Service


Disconnect is a CSA
N-Frame 1200 65, 100 25, 35, 65
R-Frame 1600 125, 200 50, 65
approved circuit breaker
1 key interlocked with the R-Frame 2000 (80% rated) 125, 200 50, 65
service disconnect
1 Accessories include Generator Quick Connect Schematic
ground fault, shunt trip,
1 auxiliary contacts and
alarms
1 Colour-coded Cam-type Inside
Switchboard
Building Wall Generator Quick Connnect

Bottom Flip-Up Cover for plug receptacles for easy


1 Easy Access to Incoming Lugs
or Cam Lock Receptacles
connection to generator
Mechanical lugs are Generator
Portable

1
Cable
provided for alternate Generator Power

method of connecting
generator cables
1 Standard enclosure is
Underground Conduit

CSA Type 1; sprinklerproof,


1 Type 2, 3R are optional
Pow-R-Line CE Dimensions
1 construction similar Approximate Dimensions in Inches (mm)
to Eatons standard
1 switchboard Standard structures are 24.00 inches (762.0 mm) deep, by
30.00 inches (762.0 mm) wide by 90.00 inches (2286.0 mm) high.
1 Custom Generator Quick
Connect Assembly CSA Type 3R enclosures are equipped with a 13.00-inch
(330.0 mm) front structure extension.
1 Accommodates ratings
greater than 1600A NNote
(100% rated) or 2000A
1 (80% rated); consult Eaton
a 50 kAIC standard bus bracing.
b Standard ratings up to 1600A; for higher amperages, consult Eaton.
for more information
1 Custom integration into
c Calculated using the following: kW (max.) = [(V*A*1.73*PF)/1000]*(breaker rating)
with PF (power factor) equaling 0.8.
switchboard lineups are
1 available; consult Eaton
for more information
1
1
1
1
1
1
T6-36 Low Voltage Switchboards and SwitchgearCA015002ENAugust 2013www.eatoncanada.ca
Low Voltage Switchboards and Switchgear
Generator Connection Assemblies
6
Contents
Customer Service Termination Enclosure
1
Description Page
Generator Quick Connect Switchboards.................. T6-35 2
Customer Service Termination Enclosure................
Catalogue Number Selection.............................. T6-38 3
Product Selection............................................... T6-38
Technical Data and Specifications....................... T6-38
4
Roll-Up Generator Quick Connect Assembly........... T6-39
5
6
7
8
9
1
Customer Service Termination Enclosure 1
Product Description Features, Benefits Busbar System Standards and Certifications 1
Eaton Customer Service and Functions Standard aluminum
Termination Enclosures bussing
CSA C22.2 No. 31
1
(CSTEs) are the splitter Enclosure Optional copper bussing;
connection assemblies Eaton CSTEs are made please consult Eaton for 1
between utility transformers with code gauge steel more information
and the customers main
distribution for specific
construction. Standard 1
enclosures are CSA Type 3R, Utility Metering
utility applications. complete with ventilation
and a padlocking handle. Utility CTs and PTs are 1
installed by others. Optional
Both pad-mounted and remote meter assemblies 1
wall-mounted designs availableEATON #M501.
are available. 1
Terminations
Load mechanical lugs 1
to suit #2500 kcmil
Provisions for utility two- 1
hole compression lugs
on line side 1
1
1
1
1
1
1
1
1
1
Low Voltage Switchboards and SwitchgearCA015002ENAugust 2013www.eatoncanada.ca T6-37
6 Low Voltage Switchboards and Switchgear
Generator Connection Assemblies

Catalogue Number Selection


1
2 CSTE 4 1 M W
3 Ampere Rating Design
Volts Connection
4 4 = 400A
6 = 600A 1 = 120/240 M = Utility
P = Pad-mount
W = Wall-mount
8 = 800A 2 = 120/208 metering
5 10 = 1000A
12 = 1200A
6 = 347/600 S = Splitter

16 = 1600A
6 20 = 2000A
25 = 2500A
7 30 = 3000A

NNot
8 Please use catalogue number selection for purchasing.

9
Product Selection
1 Approximate Dimensions in Inches (mm)

1 Wall-Mounted Cste Available as Splitter Only

1 Ampere Rating Width Depth Height


400 30.00 (762.0) 10.00 (254.0) 30.00 (762.0)
1 6001000 36.00 (914.4) 16.00 (406.4) 46.00 (1168.4)
12002000 46.00 (1168.4) 23.00 (584.2) 48.00 (1219.2)
1 25004000 60.00 (1524.0) 30.00 (762.0) 60.00 (1524.0)

1 Wall-Mounted Cste Available as Splitter with Utility Metering Provisions


Ampere Rating Width Depth Height
1 400 30.00 (762.0) 10.00 (254.0) 30.00 (762.0)
6001000 36.00 (914.4) 16.00 (406.4) 46.00 (1168.4)
1 12001600 46.00 (1168.4) 23.00 (584.2) 48.00 (1219.2)
20004000 60.00 (1524.0) 30.00 (762.0) 60.00 (1524.0)
1
Pad-Mounted Cste Available as Splitter Only or Splitter with
1 Utility Metering Provisions
Ampere Rating Width Depth Height
1 4001000 36.00 (914.4) 16.00 (406.4) 52.00 (1320.8)

1 12001600 46.00 (1168.4) 23.00 (584.2) 48.00 (1219.2)


20004000 60.00 (1524.0) 30.00 (762.0) 60.00 (1524.0)

1
Technical Data and Specifications
1
Ratings
1 120/240 Vac
208Y/120V
1 600Y/347V
Ampere ratings of 400, 600, 800, 1000, 1200, 1600, 2000,
1 2500, 3000A (for ratings above 3000A, consult Eaton)
Assembly short-circuit rating: 50,000A rms symmetrical
1
1
1
1
T6-38 Low Voltage Switchboards and SwitchgearCA015002ENAugust 2013www.eatoncanada.ca
Low Voltage Switchboards and Switchgear
Generator Connection Assemblies
6
Contents
Roll-Up Generator Quick Connect Assembly
1
Description Page
Generator Quick Connect Switchboards.................. T6-35 2
Customer Service Termination Enclosure................ T6-37
Roll-Up Generator Quick Connect Assembly........... 3
Catalogue Number Selection.............................. T6-40
Product Selection............................................... T6-40
4
Technical Data and Specifications....................... T6-40
5
6
7
8
9
1
Roll-Up Generator Quick Connect Assembly 1
Product Description Features, Benefits Busbar System Standards and Certifications 1
Eatons Roll-Up Generator and Functions Standard aluminum
Quick Connect Assembly bussing
CSA C22.2 No. 31
1
is the connection assembly Enclosure Optional copper bussing,
between the temporary Eaton Roll-Up Generator please consult Eaton for 1
generator and the customers Quick Connect Assemblies more information
main distribution or transfer
switch.
are made with code gauge 1
steel construction. Standard Terminations
Roll-Up Generator Quick enclosure is CSA Type 3R
with a padlocking handle;
Accommodates 1
Connect Assemblies are mechanical and
Type 4X is optional.
splitter connection points
housing generator connection
compression lugs 1
Both pad-mounted and Provisions for two-hole
points and load connection
points.
wall-mounted designs
are available.
compression lugs or 1
cam lock receptacles
1
1
1
1
1
1
1
1
1
1
1
1
Low Voltage Switchboards and SwitchgearCA015002ENAugust 2013www.eatoncanada.ca T6-39
6 Low Voltage Switchboards and Switchgear
Generator Connection Assemblies

Catalogue Number Selection


1
2 RUG 4 1 PC
3 Ampere Rating Design
Volts
4 4 = 400A
6 = 600A 1 = 120/240
P = Pad-mount
W = Wall-mount
8 = 800A 2 = 120/208 PC = Pad-mount (cam lock)
5 10 = 1000A
12 = 1200A
6 = 347/600 WC = Wall-mount (cam lock)

16 = 1600A
6 20 = 2000A
25 = 2500A
7 30 = 3000A

NNot
8 Please use catalogue number selection for purchasing. Catalogue number selection is for
standard CSA Type 3R enclosure. Consult Eaton for CSA Type 4X enclosures.

9
Product Selection
1 Approximate Dimensions in Inches (mm)

1
Wall-Mounted Roll-Up Generator Quick Connect Assembly Available as
1 Splitter Connection with or without Cam Locks
Ampere Rating Width Depth Height
1 6001000 36.00 (914.4) 16.00 (406.4) 46.00 (1168.4)
12001600 46.00 (1168.4) 23.00 (584.2) 48.00 (1219.2)
1 20004000 60.00 (1524.0) 30.00 (762.0) 60.00 (1524.0)

1 Pad-Mounted Roll-Up Generator Quick Connect Assembly Available as


Splitter Connection without Cam Locks
1 Ampere Rating Width Depth Height

1 6001000
12001600
36.00 (914.4)
46.00 (1168.4)
16.00 (406.4)
23.00 (584.2)
58.00 (1473.2)
60.00 (1524.0)

1 20004000 60.00 (1524.0) 30.00 (762.0) 72.00 (1828.8)

Pad-Mounted Roll-Up Generator Quick Connect Assembly Available as


1 Splitter Connection with Cam Locks

1 Ampere Rating Width Depth Height


6001600 46.00 (1168.4) 23.00 (584.2) 72.00 (1828.8)
1 20004000 60.00 (1524.0) 30.00 (762.0) 72.00 (1828.8)

1 Technical Data and Specifications


1 Ratings
120/240 Vac
1 208Y/120V
600Y/347V
1 Ampere ratings of 600, 800, 1000, 1200, 1600, 2000, 2500,
3000A (for ratings above 3000A, consult Eaton)
1 Assembly short-circuit rating: 50,000A rms symmetrical

1
1
1
1
T6-40 Low Voltage Switchboards and SwitchgearCA015002ENAugust 2013www.eatoncanada.ca
Low Voltage Switchboards and Switchgear
Pow-R-Line C Switchgear
7
Contents
Pow-R-Line C Switchgear
1
Description Page
Standards and Certifications.................................... T7-44 2
Optional Breaker Accessories.................................. T7-44
Dimensions.............................................................. T7-46 3
4
5
6
7
8
9
1
Pow-R-Line C Switchgear 1
Product Description Features, Benefits Standard 100 kA short- Structure Features 1
Eatons Pow-R-Line CE and Functions circuit bus bracing Standard finish: Grey
switchgear is an assembly Lower installation and Optional 150 and 200 kA paint finish (ANSI 61) using 1
of metal enclosures, each maintenance costs short-circuit bus bracing a modern, completely
housing drawout or fixed Higher interrupting ratings Optional insulating barriers automated and continuously 1
mounted low voltage power and withstand ratings to isolate the cable monitored electrostatic
powder coating. This
circuit breakers. Better coordination compartment from the
bus compartment continually monitored
1
The Canadian switchgear is capability system includes spray
particularly designed for the Increased tripping
Both indoor and outdoor
walk-in and non-walk-in de-grease and clean, spray 1
construction market such sensitivity rinse, iron phosphate spray
enclosures; standard
as data centres, hospitals,
retail, office buildings and
Enhanced safety measures enclosure is CSA Type coating spray rinse, non- 1
Higher quality, reliability 1; optional enclosures chemical seal, oven drying,
commercial applications. In
addition to power breakers,
and maintainability are CSA Type 2, 3R; electrostatic powder spray
paint coating and oven curing.
1
the switchgear includes Communications and sprinklerproof optional
control and measuring power quality monitoring Full range of safety Integral base: The ruggedly 1
devices such as relays, and measuring capabilities solutions dealing with formed base greatly increases
instruments, meters, Pow-R-Line C switchgear
arc flash hazards by using
Eaton Arcflash Reduction
the rigidity of the structure,
reduces the possibility of
1
instrument transformers and provides:
Maintenance System damage during the installation
control power transformers.
100% rated, fully features of the equipment, and is 1
selective protection suitable for rolling, jacking
Application Description
Integral microprocessor-
Maximum ratings for and handling. A lifting angle 1
Switchgear is used to Pow-R-Line C switchgear are is bolted onto the top of the
based breaker tripping
protect, control and monitor
low voltage distribution systems
600 Vac, 12,000A continuous
cross bus and 200,000A
bus compartment structure 1
for increased strength.
systems. Primarily used as Two-step stored-energy short-circuit capacity.
standalone distribution breaker closing Heavy-duty door hinges: 1
assemblies, they can Each breaker door is
also be incorporated into mounted with hinge pins. 1
secondary unit substations: Removal of the door is easily
UPS systems and generator
systems. Switchgear is ideally
accomplished by just lifting
the hinge pin. This allows
1
suited to applications such easy access to the breaker
as construction, commercial internal compartment for 1
and utility with distribution inspection and maintenance.
systems rated 600V or 1
below, 200 kAIC or below
bus bracing, and 12,000A 1
or below continuous loads
(cross bus). 1
Low Voltage Switchboards and SwitchgearCA015002ENAugust 2013www.eatoncanada.ca T7-41
7 Low Voltage Switchboards and Switchgear
Pow-R-Line C Switchgear

Rear cover/doors: In Closing spring automatic Single-cylinder key interlock Ground: A ground bus is
1 Pow-R-Line C switchgear, discharge: Mechanical can be installed on the furnished the full length of
standard rear bolted covers interlocking automatically breaker. Accessible on the the switchgear assembly and
2 are provided. 48.00-inch-wide discharges the closing faceplate of the breaker, the is fitted with terminals for
(1219.2 mm) cells are split springs when the breaker device can be ordered to lock purchasers connections.
3 into two sections to facilitate
handling during removal and
is removed from its
compartment.
the breaker in the open or
closed position. Glass reinforced polyester
installation. Optional rear and bus bracing and
4 doors are also available. Optional safety shutters: support insulation system:
Positive acting safety Bus Features Glass reinforced polyester
5 Through-the-door design:
The following functions may
shutters that isolate the
breaker connections to the
Buses and connections: is a total system providing
exceptional mechanical
Vertical and cross bus
be performed without the main bus when the breaker and dielectric withstand
6 need to open the circuit is withdrawn from the cell
ratings in Pow-R-Line C
switchgear are based on a strength, as well as high
breaker doorlever the is an option offered for CSAT and ANSI standard resistance to heat, flame and
7 breaker between positions additional safety beyond our temperature rise of 65C moisture. Substantial testing
(drawout), operate manual standard design. They reduce above a maximum ambient to demonstrate accelerated
8 charging system and view the potential of accidental air temperature of 40C. effects of heating and cooling
the spring charge status flag, contact with live bus. on the mechanical and
Bus ampacities: Vertical
9 close and open breaker, view
and adjust trip unit and read
Optional insulating covers
(boots) are furnished and cross bus ratings in
dielectric properties of this
system prove it to provide
the breaker rating nameplate. on live main stationary Pow-R-Line C switchgear are superior performance for
1 disconnecting contacts in 2000, 3000, 4000, 5000 and decades of trouble-free
Cassette design: The breaker compartments equipped for 6000A. In addition, an 8000, operation.
1 cassette supports the
breaker in the cell, as well
future breakers. 10,000 and 12,000A cross
Optional bus insulation:
bus rating is available.
as on the movable extension Breaker inspection: Insulated bus systems with
1 rails when the breaker is When withdrawn on the Bus bracing: Vertical bus removable PVC boots for
placed into or removed rails, breaker is completely configuration provides an inspection and maintenance.
1 from the cell. The extension accessible for visual optional industry-leading
rails allow the breaker to be inspection; tilting is not short-circuit withstand rating Barriers: Optional vented
1 drawn out without having necessary. The rails are of 200,000A. Standard
bracing is 100,000A. It has
polypropylene barriers
isolate the main bus and
to de-energize the entire permanent parts of every
been verified through testing connections from the cable
1 switchgear lineup. breaker cassette.
to maximum withstand compartment providing
Accessibility: When the rear Interference interlocks: 200,000A short-circuit for added safety to the workers
1 door is open or removed, Supplied on breakers and a full 30 cycles. while reducing the potential
each breaker compartment in compartments where of objects falling into the bus
NNote: Short-circuit rating of
1 provides front access to
isolated, vertical wireways,
the compartments are of
the same physical size.
switchgear assembly is limited to
compartment. In addition,
vertical barriers between
the interrupting capacity of the
primary disconnects and Interference interlocks ensure cable sections can be added
1 other breaker compartment an incorrect breaker cannot
lowest rated branch device.
to reduce potential hazards.
accessories for ease of field be inserted. Plating: Bolted, silver-plated Barriers are removable
1 wiring and troubleshooting copper main buses are to give access to the bus
field connections. Optional key interlock compartment for inspection
(cassette mounted): This standard. The plating is
1 Four-position drawout: mechanism holds the breaker over the entire length of the and maintenance.
Breakers can be in connected, cell mechanically trip-free to bar, not just at the joints.
1 test, disconnected or prevent electrical or manual Optional tin-plated copper
removed position. The closing. Breaker can be buses are available.
1 breaker can be moved stored in compartment, and Full neutral: For four-wire
between the connected, test completely removed for applications, the neutral
1 and disconnected positions
while the compartment door
maintenance or for use as
a spare without disturbing
bus is rated 100% of main
bus rating as standard.
is closed. the interlock. Modification of
1 the breaker is not required.
Neutral cross bus ratings up
to a maximum of 12,000A
Single- or double-cylinder are available as an option.
1 cassette-mounted key Additionally, four-pole
interlock is available as breakers can be used in
1 an option. conjunction with four-wire
systems.
1
1
1
1
T7-42 Low Voltage Switchboards and SwitchgearCA015002ENAugust 2013www.eatoncanada.ca
Low Voltage Switchboards and Switchgear
Pow-R-Line C Switchgear
7
Wiring Features Control wire: Standard wire Surge Protection Device (SPD) Integrated Transfer Switches
Cable compartment: is Type SIS insulated stranded Standard integrated surge Eaton automatic transfer
1
The cable compartment gives copper, extra flexible No. 14 protection device with switches (using power
ample room for terminating AWG minimum. integral disconnect is circuit breakers, including 2
the power cables. Removable Control wire marking: available if required. The SPD optional bypass-isolation
top roof sheets allow for Control wire marking is is mounted on the back pan, type) can be integrated 3
easy conduit hub installation. provided as a standard at and the removable display into a switchgear lineup.
The floor of the cable
compartment is open to allow
each end of the wire. As an is mounted on the door; the
SPD is protected by a small
Electrical and mechanical
coordination is ensured when
4
option, wire marking can be
cable entry from underground 30A fusible rotary switch. power circuit breaker transfer
duct banks. Optional bottom
added to the control wiring
by using heat shrink sleeve Please refer to Tab8 switches are integrated into 5
plates are available. type marking. This marking is Components or contact the switchgear. Maximum
designed to be a permanent, Eaton for more information. selectivity is achieved due 6
In addition to cable, custom to the high withstand rating
busway and nonsegregated one-piece, heat-shrink sleeve
bus duct can be terminated designed to provide clear, PLC Transfer Schemes
of the power circuit breaker 7
durable identification of wires transfer switch.
in the compartment.
and cables. Advanced PLC-based transfer
and load shedding schemes
8
Lug pad: The lugs are Advanced Metering
Secondary terminal can be designed for various
located on the breaker run-
backs to accommodate lug compartment: There are applications such as data
and Communications 9
72 finger-safe secondary centres, health care facilities Eaton has an extensive line of
orientations at an optional
45-degree angle. This reduces connections for a standard and waste water treatment powerful metering products, 1
frame Pow-R-Line C breaker. plants. HMI is optional for trip units, controllers and
the bending radius of the
gateways that can be wired
cable needed for making the The customers secondary
terminal connections are
touch screen monitoring and
control of incoming, tie together in switchgears to
1
connections, thus reducing
located at the front of the and feeder power circuit create an intelligent system
installation and maintenance
time. Mechanical setscrew structure behind an optional breakers. Contact Eaton for and interface with Building 1
separate door, providing more information. Management and SCADA
type lugs are standard.
Optional NEMA two-hole access to these connections Systems. 1
compression lugs are without the need to open the Bus Duct Integration
available. breaker compartment door.
Custom bus duct can be
Special Dimensions 1
and Configurations
Short-circuiting terminal integrated into switchgear
Control raceway: A vertical
wireway is provided for blocks: Based on customer assemblies. Eaton can design Eaton has the ability to offer 1
specific requirement. Consult and manufacture custom bus custom dimensions to suit
routing of factory wiring in
each switchgear section. Eaton for more information. duct flanges to coordinate limited space requirements. 1
with the bus duct risers of a Special heights, special
Breaker secondary terminal Shipping split connection:
blocks are mounted as As an option, at each
wide range of amperage. depths and widths, corner
sections, back-to-back
1
standard above each circuit shipping split, the control and front-access-only
breaker. The terminal blocks
are rated 30A, and will
connections are made with Transformer and configurations are available. 1
plug-in terminal blocks rated MCC Close-Coupling
accept bare wire, ring or
spade terminals for wire size
300V, 10A. The terminal Close-couple dry type,
Arc Flash Considerations 1
blocks mechanically interlock liquid-filled transformers or
maximum of No. 10. without removing the Arc flash is an ongoing
line or load connections.
motor control centres (MCC)
with standard switchgear concern in the electrical 1
Control circuits may be wired
This method of making configurations can be industry. Eaton can offer
in all cells without removing
the circuit breaker. In the shipping split control supplied. Transformer unit- a variety of solutions to 1
addition, power circuits may connections increases the substations and MCC bus- reduce the risk of arc flash
be connected in the rear of speed of installation and coordination would create such as Arcflash Reduction 1
the switchgear at the same reduces the potential of a most compact lineup and Maintenance System in
time control circuits are being incorrect connections. minimization of installation power circuit breakers, safety
shutters in Magnum drawout
1
wired in the front of the time by eliminating cable
power circuit breakers, infra-
switchgear. installations.
red viewing windows and 1
For applications involving remote racking accessories.
excessive wiring, or 1
nonstandard terminal blocks,
terminal blocks are optionally
mounted on the rear frame
1
with the power cables where
they are readily accessible 1
for customers connections
and inspection. 1
1
1
Low Voltage Switchboards and SwitchgearCA015002ENAugust 2013www.eatoncanada.ca T7-43
7 Low Voltage Switchboards and Switchgear
Pow-R-Line C Switchgear

Standards and Certifications Optional Breaker Lifting Device Options Padlockable Pushbutton Cover
1 CSAT C22.2 No. 31 Accessories Eaton provides a variety of A padlockable cover is
ANSI C37.20.1 lifting options such as breaker available to limit access to the
2
Built in an ISOT
Shunt Trip Device lifting yokes and portable lift ON and OFF pushbuttons.
certified facility The shunt trip opens trucks. Please refer to Eaton
3 the circuit breaker catalogue PG01301002E
Mechanical Operations Counter
instantaneously when its (Miscellaneous Accessories)
The operations counter is
4 coil is energized by a voltage for more information.
a mechanical device used
input. A total of two shunt
to provide a record of the
5 trips can be mounted on an
Eaton power circuit breaker.
Auxiliary Switch number of circuit operations.
Eatons Magnum DS Power An auxiliary switch provides It is mounted in the lower
6 Circuit Breakers comply with: remote electrical indication if right portion of the circuit
Electrical Motor Operator the circuit breaker is open or breaker and can be viewed
ANSI C37.13
7 ANSI C37.16
A motor operator is an closed. Up to three auxiliary
switches can be mounted
through the front cover.
electric motor assembly
ANSI C37.17 in the circuit breaker. Each
8
ANSI C37.50
internally mounted in the
circuit breaker. It charges the switch has two normally open
Key Off Lock Provisions
closing springs electrically for (a) and two normally closed The key off lock secures
9 NNote: Consult Eaton for
Seismically Qualified designs
remote or local operation. The (b) contacts for a total of the circuit breaker in the
motor operator can be factory 12 available contacts. OFF position. It is mounted
and for ANSI certified designs.
1 or site installed. in the lower right portion of
the circuit breaker and can
Mechanical Trip Indicator Flag be viewed through the front
1 Spring Release Device A red, pop-out mechanical cover. The customer supplies
The spring release remotely trip flag is located just above the key lock. The provisions
1 closes the circuit breaker the trip unit in the circuit available are for Kirk.
when the coil is energized by breakers front cover. It
1 a voltage input. The closing operates by popping out
to indicate that the circuit
Latch Check Switch
spring must already be
breaker opened in response A latch check switch (LCS)
1 charged for the device
to work. to an overcurrent condition. indicates when the circuit
The flag is manually reset by breaker is ready to close.
1 pushing it back into position. The internal version of the
Bubble Cover The circuit breaker can be re- LCS is wired to the spring
1 Plexiglass breaker covers closed, even if the flag is not release. It will not permit
activation of the spring
for security and dust ingress reset. An optional overcurrent
release until the circuit
1 protection. trip switch, however, can be
used as an electrical lockout. breaker is fully charged and
the trip latch is reset.
1 Undervoltage Release
The undervoltage release Bell Alarm / Overcurrent
Trip Switch Cassettes
1 opens the circuit breaker
An overcurrent trip switch For information on breaker
when its supply voltage falls
(bell alarm) provides an cassettes, refer to Eaton
1 below 70%. If the release is
not energized to 85% of its electrical indication when catalogue RP01301001E.
supply voltage, the circuit a circuit breaker trips as
1 breaker cannot be reclosed a result of an overcurrent
electrically or manually. condition. Opening as a result
1 of a circuit breakers manual
open button, shunt trip or
1 undervoltage release does
not cause the overcurrent trip
switch to operate.
1
1
1
1
1
1
1
T7-44 Low Voltage Switchboards and SwitchgearCA015002ENAugust 2013www.eatoncanada.ca
Low Voltage Switchboards and Switchgear
Pow-R-Line C Switchgear
7
Pow-R-Line C SwitchgearTypical Cell Configurations
1
Maximum 3000A Cross Bus a

2
3
Instrument Inst. Inst. Inst.
Compartment Comp.
or SPD
Comp.
or SPD
Comp.
or SPD 4
Main
800120001600
Main
8001200
Tie c
8001200
Feeder
8001200
5
200025003000 16002000 16002000 16002000
90.00 90.00 3000 90.00 3000 90.00 6
(2286.0) (2286.0) (2286.0) c (2286.0) Feeder
b b Blank or
Feeder
b Blank or
Tie or
b
8001200
16002000
7
Utility Feeder
CT/PT
Compartment Feeder
8
Blank or Blank or
8001200
Feeder Feeder
16002000 9
1
d d d
38.00 24.00 24.00 24.00
(965.2) (609.6) (609.6) (609.6)

72.00/78.00/84.00/90.00
(1828.8/1981.2/2133.6/2286.0)
72.00/78.00/84.00/90.00
(1828.8/1981.2/2133.6/2286.0)
72.00/78.00/84.00/90.00
(1828.8/1981.2/2133.6/2286.0)
72.00/78.00/84.00/90.00
(1828.8/1981.2/2133.6/2286.0)
1
1
1
3000A Maximum, 3200A, 4000A, 5000A, 6000A, 8000A Cross Bus a 4000A, 5000A, 6000A Cross Bus a
1
1
Feeder Inst. Inst. Instrument
8001200
16002000
Comp.
or SPD
Comp.
or SPD
Compartment or SPD
1
Feeder Feeder
8001200
Feeder Main 1
8001200 8001200 400050006000
16002000
90.00 Transition 90.00
16002000
90.00 2500 90.00
16002000
90.00 1
(2286.0) Cell (2286.0) (2286.0) (2286.0) Feeder f (2286.0)
Feeder
e e
8001200
e Blank or
Feeder
c 8001200
16002000
e
1
16002000 Utility
e 25003000

Feeder Feeder Feeder f


CT/PT
Compartment 1
8001200 8001200 8001200
16002000 16002000
2500
16002000
25003000
1
24.00
(609.6)
d
24.00
(609.6)
d
24.00
(609.6)
d
24.00
(609.6)
d
48.00
(1219.2)
1
78.00/84.00/90.00 78.00/84.00/90.00 78.00/84.00/90.00 78.00/84.00/90.00 78.00/84.00/90.00 1
(1981.2/2133.6/2286.0) (1981.2/2133.6/2286.0) (1981.2/2133.6/2286.0) (1981.2/2133.6/2286.0) (1981.2/2133.6/2286.0)

1
NNote
a Higher bus ampacities available; please contact Eaton for more information.
1
1
b 90.00-inch (2286.0 mm) height does not include optional base channel. Standard height is 1.50 inches (38.1 mm), custom height of 2.00 inches (50.8 mm) or 4.00 inches (101.6 mm) available.
c Maximum one tie breaker per cell.
d 30.00-inch-wide (762.0 mm) cells are available for certain applications. Contact Eaton for more information.
e Feeder can be 800, 1200, 1600, 2000A; blank if there are two 2500A feeders in the same distribution section.
1
f Maximum one 3000A feeder per cell.
Consult Eaton for custom layouts.
1
1
1
Low Voltage Switchboards and SwitchgearCA015002ENAugust 2013www.eatoncanada.ca T7-45
7 Low Voltage Switchboards and Switchgear
Pow-R-Line C Switchgear

4000A, 5000A, 6000A Cross Bus a


1
2
Instrument Instrument Instrument
3 Compartment or SPD Compartment or SPD Compartment or SPD
Instrument
Compartment or SPD

4 Main Main Main


40005000 40005000 4000
5 90.00 90.00 90.00 90.00
Feeder
40005000
(2286.0) (2286.0) (2286.0) (2286.0)
6 b b b b

7 Blank Blank
Tie
4000

8 Blank

9 48.00
(1219.2)
48.00
(1219.2)
48.00
(1219.2)
48.00
(1219.2)

1 78.00/84.00/90.00
(1981.2/2133.6/2286.0)
78.00/84.00/90.00
(1981.2/2133.6/2286.0)
78.00/84.00/90.00
(1981.2/2133.6/2286.0)
78.00/84.00/90.00
(1981.2/2133.6/2286.0)

1
1 NNote
a Higher bus ampacities available; please contact Eaton for more information.

1 b 90.00 inch (2286.0 mm) height does not include optional base channel. Standard height is 1.50 inches (38.1 mm), custom height of 2.00 inches (50.8 mm) or 4.00 inches (101.6 ) available.
Main breaker can be in cell B, C or D.
Consult Eaton for custom layouts.
1
1 Dimensions
Approximate Dimensions in Inches (mm)
1
1 Switchgear Dimensions
Pow-R-Line C Interrupting Short-Time
1 Cell Width Breaker Frame Rating Rating
24.00 (609.6) or 800A, 1600A, 2000A, Maximum 100 kA 85 kA for 60 cycles
1 30.00 (762.0) 3000A, 3200A
48.00 (1219.2) 4000A, 5000A, 6000A Maximum 100 kA 100 kA for 60 cycles
1
Breaker Frame Size
1 Ampere
Rating Height Depth Width
1 8003200 16.40 (416.6) 15.40 (391.2) 16.30 (414.0)

1 40006000 16.40 (416.6) 15.40 (391.2) 34.20 (868.7)

1
1
1
1
1
1
1
T7-46 Low Voltage Switchboards and SwitchgearCA015002ENAugust 2013www.eatoncanada.ca
Low Voltage Switchboards and Switchgear
Components
8
Contents
Components
1
Description Page
Moulded-Case Circuit Breakers 2
Magnum Power Circuit Breakers............................. T8-50
Trip Units.................................................................. T8-51 3
Fusible Switches...................................................... T8-57
Surge Protection Devices........................................ T8-61
4
Metering.................................................................. T8-62
5
6
7
8
Series C Moulded-Case Circuit Breaker Product Family
9
1
Moulded-Case Circuit Breakers 1
Quick ReferenceSeries CT Circuit Breakers a
1
Circuit Cont. Amp.
CSAT Listed Interrupting Ratings rms Symmetrical Amperes (kA) 1
Breaker Rating No. of Volts Trip Vac Ratings Vdc Ratings c
Type @ 40C Poles AC DC Type b 120 120/240 240 277 347 480Y/277 480 600Y/347 600 125 250 125/250 1
F-Frame
ED 100225 2, 3 240 125 N.I.T. 65 10 1
EDH 100225 2, 3 240 125 N.I.T. 100 10
EDC 100225 2, 3 240 125 N.I.T. 200 10 1
EHD 15100 1 277 125 N.I.T. 14 10
EHD 15100 2, 3 480 250 N.I.T. 18 14 10 1
FDB 15150 1 347 125 N.I.T. 14 10
FDB 15225 2, 3 600 250 N.I.T. 18 14 14 10 1
FDB 15225 4 600 250 N.I.T. 18 14 14 10
FD 15150 1 347 125 N.I.T. 35 18 10 1
FD 15225 2, 3 600 250 N.I.T. 65 35 18 10
FD 15225 4 600 250 N.I.T. 65 35 18 10 1
FDE 15225 3 600 N.I.T. 65 35 18
HFD 1530 1 347 125 N.I.T. 65 25 10 1
HFD 15225 2,3 600 250 N.I.T. 100 65 25 22
HFD 15225 4 600 250 N.I.T. 100 65 25 22
1
HFDE 15225 3 600 N.I.T. 100 65 25
FDC d 1530 1 347 125 N.I.T. 30 10
1
FDC d
FDC d
15225
15225
2, 3
4
600
600
250
250
N.I.T.
N.I.T.




200
200






100
100


35
35


22
22


1
FDCE d
FD-LFD
15225
15150
3
3
600
600


N.I.T.
N.I.T.




200
200





200
100



25
200






1
NNote
a Refer to catalogue no. PG01200001K for complete Series C Moulded-Case Circuit Breaker information.
1
b N.I.T. is non-interchangeable trip unit and I.T. is interchangeable trip unit.
c Two-pole circuit breaker, or two poles of three-pole circuit breaker at 250 Vdc.
1
d Current limiting.
1
1
1
Low Voltage Switchboards and SwitchgearCA015002ENAugust 2013www.eatoncanada.ca T8-47
8 Low Voltage Switchboards and Switchgear
Components

Quick ReferenceSeries C Circuit Breakers a, continued


1 CSA Listed Interrupting Ratings rms Symmetrical Amperes (kA)
Circuit Cont. Amp.
2 Breaker Rating No. of
Volts
Trip
Vac Ratings Vdc Ratings c

Type @ 40C Poles AC DC Type b 120 120/240 240 277 480 600 125 250 125/250
3 J-Frame
JD 70250 2, 3, 4 600 250 I.T. 65 35 18 10
4 HJD 70250 2, 3, 4 600 250 I.T. 100 65 25 22
JDC d 70250 2, 3, 4 600 250 I.T. 200 100 35 22
5 K-Frame
DK 250400 2, 3 240 250 I.T. 65 10
6 KD 100400 2, 3, 4 600 250 I.T. 65 35 25 10
CKD 100400 2, 3, 4 600 250 I.T. 65 35 25 10
7 HKD 100400 2, 3, 4 600 250 I.T. 100 65 35 22

8 CHKD
KDC d
100400
100400
2, 3, 4
2, 3, 4
600
600
250
250
I.T.
I.T.




100
200


65
100
35
65


22
22

9 L-Frame
LD 300600 2, 3, 4 600 250 I.T. 65 35 25 22

1 CLD
HLD
300600
300600
2, 3, 4
2, 3, 4
600
600
250
250
I.T.
I.T.




65
100


35
65
25
35


22
25

1 CHLD 300600 2, 3, 4 600 250 I.T. 100 65 35 25


LDC d 300600 2, 3, 4 600 250 I.T. 200 100 50 25

1 CLDC d 300600 2, 3, 4 600 250 I.T. 200 100 50 25


MDL-Frame
1 MDL 300800 2, 3 600 250 I.T. 65 50 25 22
CMDL 300800 2, 3 600 250 I.T. 65 50 25 22
1 HMDL 300800 2, 3 600 250 I.T. 100 65 35 25
CHMDL 300800 2, 3 600 250 I.T. 100 65 35 25
1 N-Frame
ND 4001200 3, 4 600 N.I.T. 65 50 25
1 CND 4001200 3, 4 600 N.I.T. 65 50 25
HND 4001200 3, 4 600 N.I.T. 100 65 35
1 CHND 4001200 3, 4 600 N.I.T. 100 65 35
NDC 4001200 3, 4 600 N.I.T. 200 100 65
1 CNDC 4001200 3, 4 600 N.I.T. 200 100 65
R-Frame
1 RD 1600 8001600 3, 4 600 N.I.T. 125 65 50
CRD 1600 8001600 3, 4 600 N.I.T. 125 65 50
1 RD 2000 10002000 3, 4 600 N.I.T. 125 65 50
CRD 2000 10002000 3, 4 600 N.I.T. 125 65 50
1 RD 2500 12002500 3, 4 600 N.I.T. 125 65 50

1 RDC 1600
CRDC 1600
8001600
8001600
3, 4
3, 4
600
600


N.I.T.
N.I.T.




200
200


100
100
65
65





1 RDC 2000
CRDC 2000
12002500
10002000
3, 4
3, 4
600
600


N.I.T.
N.I.T.




200
200


100
100
65
65





1 RDC 2500 12002500


HMCP Motor Circuit Protectors
3, 4 600 N.I.T. 200 100 65

1 Current Limit-RT Current Limiting Circuit BreakersNon-Fused Type


LCL 125400 2, 3 600 N.I.T. 200 200 100
1 Tri-PacT Current Limiting Circuit BreakersFused Type
FB 15100 2, 3 600 250 N.I.T. 200 200 200
1 LA 70400 2, 3 600 250 I.T. 200 200 200
NB 300800 2, 3 600 250 I.T. 200 200 200
1 NNote
a Refer to catalogue no. PG01200001K for complete Series C Moulded-Case Circuit Breaker information.
1 b N.I.T. is non-interchangeable trip unit and I.T. is interchangeable trip unit.
c Two-pole circuit breaker, or two poles of three-pole circuit breaker at 250 Vdc.
1 d Current limiting.

T8-48 Low Voltage Switchboards and SwitchgearCA015002ENAugust 2013www.eatoncanada.ca


Low Voltage Switchboards and Switchgear
Components
8
Quick ReferenceSeries GT Circuit Breakers a

Breaker Capacity (kA rms) Vac 5060 Hz


1
CSA
Vac Vdc
Trip Units c
FT-AM /AT-AM
2
Max.
Ratings Ratings Electronic (DigitripE RMS 310) Thermal-Magnetic Electronic RMS d
Circuit
Breaker
Rated
Current No. of Ampere Fixed Adjustable 3
Type (Amperes) Poles 240 480 600 125/250 b Range Interchangeable Built-In Thermal Thermal Magnetic LS LSI LSG LSIG
JG-Frame 4
E 250 2, 3, 4 65 25 18 10 20250 n n n n Adjustable n n n n
S 250 2, 3, 4 85 35 18 22 20250 n n n n Adjustable n n n n 5
H 250 2, 3, 4 100 65 25 22 20250 Adjustable
6
n n n n n n n n
C 250 3, 4 200 100 35 42 20250 n n n n Adjustable n n n n
U 250 3, 4 200 150 50 50 20250 Adjustable
7
n n n n n n n n
LG-Frame
E
S
600
600
3, 4
3, 4
65
85
35
50
18
25
22
22
100600
100600
n
n
n
n
n
n
n
n
Adjustable
Adjustable
nb
nb
nb
nb
nb
nb
nb
nb
8
H
C
600
600
3, 4
3, 4
100
200
65
100
35
50
42
42
100600
100600
n
n
n
n
n
n
n
n
Adjustable
Adjustable
nb
nb
nb
nb
nb
nb
nb
nb
9
U 600 3, 4 200 150 65 50 100600 n n n n Adjustable nb nb nb nb
1
Quick ReferenceSeries G Circuit Breakers, continued 1
Breaker Capacity (kA rms) Vac 5060 Hz
Trip Units 1
Electronic
Circuit
Max.
Rated
CSA
Vac Ratings
Electronic
(Digitrip RMS 310+)
(Digitrip RMS 310+,
610 and 910) Electronic d
1
Breaker Current No. of Ampere
Type (Amperes) Poles 240 480 600 Range Built-In Built-In LI LS LSI LIG LSG LSIG ALSI ALSIG 1
NG-Frame
S 800, 1200 2, 3, 4 85 50 25 3201200 n n n n n n n 1
H 800, 1200 2, 3, 4 100 65 35 3201200 n n n n n n n
C 800, 1200 2, 3, 4 200 100 65 3201200 n n n n n n n 1
RG-Frame
H 1600, 2000, 2500 3, 4 125 65 50 8002500 n ne n n ne n n n n 1
C 1600, 2000, 2500 3, 4 200 100 65 8002500 ne ne
1
n n n n n n n

NNote
a Refer to catalogue no. CA08100005E for complete Series G Moulded-Case Circuit Breaker information.
b Two poles in series.
1
c F = Fixed, A = Adjustable, T = Thermal, M = Magnetic.
d Not suitable for DC application. Four-pole ground fault not available.
1
e Available only on Digitrip 610 and 910 trip units.
1
1
1
1
1
1
1
1
1
1
Low Voltage Switchboards and SwitchgearCA015002ENAugust 2013www.eatoncanada.ca T8-49
8 Low Voltage Switchboards and Switchgear
Components

Magnum Power Circuit Breakers


1
Magnum DST Low Voltage Power Circuit Breaker Family ANSI Rated for Switchgear Applications
2
3
4
5
6
7
8
9
Magnum DS Switchgear Low Voltage Power Circuit Breakers
1
rms Symmetrical Current Ratings kA 50/60 Hz a

1 Frame Breaker Type Frame Interrupting Interrupting Interrupting Short-Time


Fixed Internal
Instantaneous
Available Current Sensor and Rating
Plugs for Digitrip RMS Trip Unit
Amperes Catalogue Number Type at 254 Vac at 508 Vac at 635 Vac Withstand Trip (Establishes Breaker In Rating)
1 800 MDS-408 Standard 42 42 42 42 200, 250, 300, 400, 600, 800
MDS-608 Standard 65 65 65 65
1 MDS-808 Standard 85 85 85 85
MDS-C08 Standard 100 100 100 85 85
1 MDS-L08 b Standard 200 200 200

1 1200 MDS-412
MDS-512
Standard
Standard
42
50
42
50
42
50
42
50


200, 250, 300, 400, 600, 800, 1000, 1200

1 MDS-612
MDS-812
Standard
Standard
65
85
65
85
65
85
65
85

1 1600
MDS-C12
MDS-616
Standard
Standard
100
65
100
65
100
65
85
65

200, 250, 300, 400, 600, 800, 1000,
1200, 1600
1 MDS-816
MDS-C16
Standard
Standard
85
100
85
100
85
100
85
85

85

1 2000
MDS-L16 b
MDS-620
Standard
Standard
200
65
200
65
200
65

65

200, 250, 300, 400, 600, 800, 1000, 1200,
1600, 2000
1 MDS-820 Standard 85 85 85 85
MDS-C20 Standard 100 100 100 85 85

1 MDS-L20 b Standard 200 200 200


3200 MDS-632 Standard 65 65 65 65 200, 250, 300, 400, 600, 800, 1000, 1200,

1 MDS-832 Standard 85 85 85 85 1600, 2000, 2500, 3000, 3200

MDS-C32 Standard 100 100 100 85 85


1 4000 MDS-840 Double 85 85 85 85 2000, 2500, 3200, 4000
MDS-C40 Double 100 100 100 100
1 5000 MDS-850 Double 85 85 85 85 2500, 3200, 4000, 5000
MDS-C50 Double 100 100 100 100
1 NNote
a Interrupting ratings shown based on breaker equipped with integral Digitrip RMS trip unit. Interruption ratings for non-automatic breakers are equal to the published short-time withstand rating.
1 These interruption ratings are based on the standard duty cycle consisting of an open operation, a 15-second interval and a close-open operation, in succession, with delayed tripping in case
of short-delay devices. The standard duty cycle for short-time ratings consists of maintaining the rated current for two periods of 1/2 seconds each, with a 15-second interval of zero current
between the two periods.
1 b Magnum MDSL current limiting power circuit breaker with integral current limiters. Current limiter selected determines short-time and fixed instantaneous trip rating. Maximum voltage rating
is 600 Vac.
1
1
1
T8-50 Low Voltage Switchboards and SwitchgearCA015002ENAugust 2013www.eatoncanada.ca
Low Voltage Switchboards and Switchgear
Components
8
Trip Units
1
Moulded-Case Digitrip Selection Guide 2
Trip Unit Digitrip Digitrip Digitrip Digitrip Digitrip Digitrip Digitrip Digitrip
Type RMS 310+ RMS 310 RMS 510 RMS 610 RMS 810 RMS 910 OPTIM 550 OPTIM 1050
3
rms sensing Yes Yes Yes Yes Yes Yes Yes Yes
Breaker Type 4
Frame FDE, JG, K, LG, NG, RG a K, L, M, N, R R R, RG R R, RG K, L, N K, L, N, R
Ampere range 152500 152500 8005000 8005000 8005000 8005000 701200 705000 5
Interrupting rating at 480V 35, 65, 100, 150 kA 35, 65, 100 kA 65, 100 kA 65, 100 kA 65, 100 kA 65, 100 kA 35, 65, 100 kA 35, 65, 100 kA
Protection 6
Ordering options LS, LSG LSI, LSIG LS, LSG LSI, LSIG LI, LS, LSI, LIG, LI, LS, LSI, LIG, LI, LS, LSI, LIG, LI, LS, LSI, LIG, LSI, LSI (A), LSI (A), LISG
LSG, LSIG LSG, LSIG LSG, LSIG LSG, LSIG LSIG 7
Arcflash Reduction No ALSI, ALSIG b No No No No No No No No
Maintenance SystemE 8
Fixed rated plug (In) No Yes Yes Yes Yes Yes Yes Yes Yes Yes
Overtemperature trip Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes 9
Long Delay Protection (L)
Adjustable rating plug (In) No Yes No No No No No No 1
Long delay pickup 40100% frame 0.51.0 (In) c 0.51.0 x (In) 0.51.0 x (In) 0.51.0 x (In) 0.51.0 x (In) 0.41.0 x (In) 0.41.0 x (In)
Long delay time I2t 224 seconds 10 seconds 224 seconds 224 seconds 224 seconds 224 seconds 224 seconds 224 seconds 1
Long delay time I4t No No No No No No 15 seconds 15 seconds
Long delay thermal memory Yes Yes Yes Yes Yes Yes Yes Yes 1
High load alarm Yes No No 0.85 x Ir 0.85 x Ir 0.85 x Ir 0.51.0 x Ir 0.51.0 x Ir
Short Delay Protection (S) 1
Short delay pickup Varies by frame d 200800% x (In) 200600% 200600% 200600% 200600% 150800% 150800%
S1 and S2 x (Ir) S1 and S2 x (Ir) S1 and S2 x (Ir) S1 and S2 x (Ir) x (Ir) x (Ir) 1
Short delay time I2t Yes No 100 ms No 100500 ms 100500 ms 100500 ms 100500 ms 100500 ms 100500 ms
Short delay time flat No Inst300 ms No Inst300 ms 100500 ms 100500 ms 100500 ms 100500 ms 100500 ms 100500 ms 1
Short delay time ZSI Yes No Yes Yes Yes Yes Optional Yes
Instantaneous Protection (I) 1
Instantaneous pickup No Varies by No 200800% 200600% 200600% 200600% 200600% 200800% x (In) 200800% x (In)
frame d x (In) M1 and M2 x (In) M1 and M2 x (In) M1 and M2 x (In) M1 and M2 x (In) 1
Discriminator No No Yes e Yes e Yes e Yes e Yes Yes
Instantaneous override Yes Yes Yes Yes Yes Yes Yes Yes 1
Ground Fault Protection (G)
Ground fault alarm Yes Yes No No No No 20/25100% f 20/25100% gh 1
Ground fault pickup 20100% frame f Var/frame f 25100% x In f 25100% x In f 25100% x In f 25100% x In f 20/25100% f 20/25100% gh
Ground fault delay I2t No No 100500 ms 100500 ms 100500 ms 100500 ms 100500 ms 100500 ms 1
Ground fault delay flat Inst300 ms Inst500 ms 100500 ms 100500 ms 100500 ms 100500 ms 100500 ms 100500 ms
Ground fault ZSI Yes No Yes Yes Yes Yes Optional Yes 1
Ground fault Yes Yes Yes Yes Yes Yes Yes Yes
thermal memory 1
System Diagnostics
Cause of trip LEDs No No Yes Yes Yes Yes Yes Yes 1
Magnitude of No No No Yes Yes Yes Yes Yes
trip information 1
Remote signal contacts No No No Yes Yes Yes No Yes
Legend NNote 1
BIM = Breaker Interface Module a No rating plugs necessary. e LS/LSG only.
Is
In
=
=
Sensor Rating
Rating Plug
b Only available on LG, NG and f Not to exceed 1200A. 1
RG breaker. g L- and N-Frames *20100% x Is.
Ir = LDPU Setting x In
c Adjust by rating plug.
d FDE and JG 2001200% x In
R-Frame *25100% x In. 1
h By OPTIMizer/BIM.
LG 2001200% x In
NG 200900% x In 1
RG 200800% x In
1
1
Low Voltage Switchboards and SwitchgearCA015002ENAugust 2013www.eatoncanada.ca T8-51
8 Low Voltage Switchboards and Switchgear
Components

Moulded-Case Digitrip Selection Guide, continued


1 Trip Unit Digitrip Digitrip Digitrip Digitrip Digitrip Digitrip Digitrip Digitrip
Type RMS 310+ RMS 310 RMS 510 RMS 610 RMS 810 RMS 910 OPTIM 550 OPTIM 1050
2 System Monitoring

3 Digital display
Current
No
No
No
No
No
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes a
Yes
Yes a
Yes

4 Voltage
Power and energy
No
No b
No
No c
No
No
No
No
No
Yes
Yes
Yes
No
No
No
Yes

5 Power quality harmonics


Power factor
No
No
No
No
No
No
No
No
No
Yes (over
Yes
Yes
No
No
Yes
Yes
PowerNet only)
6 Communications

7 PowerNetE
Testing
No No No No Yes Yes Optional Yes

8 Testing method Test kit Test set Integral Integral Integral Integral OPTIMizer, OPTIMizer, BIM,
BIM, PowerNet PowerNet
(optional)
9 Legend NNote
BIM = Breaker Interface Module a By OPTIMizer/BIM.
1 Is = Sensor Rating b Yes, with addition of Power Monitoring/
In = Rating Plug Metering Module (PM3).
1 Ir = LDPU Setting x In
c Yes, with addition of Energy Sentinel.

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
T8-52 Low Voltage Switchboards and SwitchgearCA015002ENAugust 2013www.eatoncanada.ca
Low Voltage Switchboards and Switchgear
Components
8
Digitrip Trip Units for Magnum DS Power Circuit Breakers
Digitrip 520 Digitrip 520M Digitrip 520MC Digitrip 1150+ a
1
2
3
Trip Unit Type 4
Ampere range 2006000A 2006000A 2006000A 2006000A
Interrupting rating at 480V 42200 kA 42200 kA 42200 kA 42200 kA 5
rms sensing Yes Yes Yes Yes
Protection and Coordination 6
Protection Ordering options LI, LSI, LSIG LSI, LSIG, LSIA LSI, LSIG, LSIA LSI, LSIG, LSIA
Fixed rating plug (In) Yes Yes Yes Yes
7
Long delay protection (L)
Overtemperature trip
Long delay pickup
Yes
0.41.0 x (In)
Yes
0.41.0 x (In)
Yes
0.41.0 x (In)
Yes
0.41.0 x (In)
8
Long delay time I t at 6 x Ir 224 seconds 224 seconds 224 seconds 224 seconds
9
2

Long delay time I4t No No No 15 seconds


IEEE curves
Long delay thermal memory
No
Yes
No
Yes
No
Yes
Yes
Yes
1
Short delay protection (S)
High load alarm
Short delay pickup
No
2001000% x (Ir) and M1
No
2001000% x (Ir) and M1
No
2001000% x (Ir) and M1
0.51.0 x (Ir)
2001000% x (Ir) and M1
1
Short delay time I2t at 8 x Ir
Short delay time flat
100500 ms
100500 ms
100500 ms
100500 ms
100500 ms
100500 ms
100500 ms
100500 ms
1
Short delay time ZSI Yes Yes Yes Yes
1
Instantaneous protection (I) Instantaneous pickup 2001000% x (In) and M1 2001000% x (In) and M1 2001000% x (In) and M1 2001000% x (In) and M1
Making current release Yes Yes Yes Yes 1
Off position LSI and LSIG Yes Yes Yes
Ground fault protection (G) b Ground fault alarm No Yes Yes Yes 1
Ground fault pickup 25100% x (In) 25100% x (In) 25100% x (In) 24100% x (In)
Ground fault delay I2t at 0.625 x In 100500 ms 100500 ms 100500 ms 100500 ms 1
Ground fault delay flat 100500 ms 100500 ms 100500 ms 100500 ms
Ground fault ZSI Yes Yes Yes Yes 1
Ground fault thermal memory Yes Yes Yes Yes
Disable ground fault protection No No No No 1
Neutral protection (N) Model LSI Model LSI Model LSI Model LSI
Legend NNote 1
In = Rating Plug and Sensor Rating a Over and undervoltage alarm or trip, b 1200A maximum ground fault setting
Ir = Long Delay Pickup Setting over and underfrequency alarm or trip,
voltage unbalance alarm or trip, reverse
per UL/NEC.T 1
power trip, and phase rotation alarm
are included. 1
1
1
1
1
1
1
1
1
1
Low Voltage Switchboards and SwitchgearCA015002ENAugust 2013www.eatoncanada.ca T8-53
8 Low Voltage Switchboards and Switchgear
Components

Digitrip Trip Units for Magnum DS Power Circuit Breakers, continued


1 Digitrip 520 Digitrip 520M Digitrip 520MC Digitrip 1150+ a

2
3
4 Trip Unit Type
System Diagnostics
5 Cause-of-trip LEDs Yes Yes Yes Yes
Magnitude of trip information No Yes Yes Yes
6 Remote signal contacts No Yes Yes Yes
Programmable contacts No No No Yes
7 System Monitoring

8 Digital display
Current (% ) full scale sensor
No
No
4-character LCD
Yes 2%
4-character LCD
Yes 2%
24-character LED
Yes 1%

9 Voltage (%) L to L
Power and energy (%)
No
No
No
No
No
No
Yes 1%
Yes 2%

1 Apparent power kVA and demand


Reactive power kVAR
No
No
No
No
No
No
Yes
Yes

1 Power factor No No No Yes


Crest factor No No No Yes

1 Power qualityharmonics No No No Yes


% THD, waveform capture No No No Yes
1 System Communications
Type No No INCOME INCOM/TripLink
1 Power supply in breaker Optional Standard Standard
Additional Features
1 Trip log (three events) No No No Yes
Electronic operations counter No No No Yes
1 Testing method b Test set Test set Test set Integral and test set
Waveform capture No No No Yes
1 Arcflash Reduction Maintenance System No No Yes Yes
Breaker health monitor No No No Yes
1 Protective relay functions No No No Yes a
Legend NNote
1 In = Rating Plug and Sensor Rating a Over and undervoltage alarm or trip, b Test set for secondary injection.
Ir = Long Delay Pickup Setting over and underfrequency alarm or trip,
1 voltage unbalance alarm or trip, reverse
power trip, and phase rotation alarm
are included.
1
1
1
1
1
1
1
1
1
1
T8-54 Low Voltage Switchboards and SwitchgearCA015002ENAugust 2013www.eatoncanada.ca
Low Voltage Switchboards and Switchgear
Components
8
Digitrip Trip Units for Magnum DS Power Circuit Breakers, continued
Digitrip 520i Digitrip 520Mi Digitrip 520MCi Digitrip 1150i+ a
1
2
3
Trip Unit Type 4
Ampere range 2006300A 2006300A 2006300A 2006300A
Interrupting rating at 690V 40100 kA 40100 kA 40100 kA 40100 kA 5
rms sensing Yes Yes Yes Yes
Protection and Coordination 6
Protection Ordering options LI, LSI, LSIG LSI, LSIG, LSIA LSI, LSIG, LSIA LSI, LSIG, LSIA
Fixed rating plug (In) Yes Yes Yes Yes
7
Long delay protection (L)
Overtemperature trip
Long delay setting
Yes
0.41.0 x (In)
Yes
0.41.0 x (In)
Yes
0.41.0 x (In)
Yes
0.41.0 x (In)
8
Long delay time I t at 6 x Ir 224 sec 224 sec 224 sec 224 sec
9
2

Long delay time I4t No No No 15 sec


IEC Type A, B, C curves
Long delay thermal memory
No
Yes
No
Yes
No
Yes
Yes
Yes
1
Short delay protection (S)
High load alarm
Short delay pickup
No
2001000% x (Ir) and M1
No
2001000% x (Ir) and M1
No
2001000% x (Ir) and M1
0.71.0 x Ir
1501000% x (Ir) and M1
1
Short delay time I2t at 8 x Ir
Short delay time flat
100500 ms
100500 ms
100500 ms
100500 ms
100500 ms
100500 ms
100500 ms
100500 ms
1
Short delay time ZSI Yes Yes Yes Yes
1
Instantaneous protection (I) Instantaneous pickup 2001000% x (In) and M1 2001000% x (In) and M1 2001000% x (In) and M1 2001000% x (In) and M1
Making current release Yes Yes Yes Yes 1
Off position Yes Yes Yes Yes
Earth fault protection (G) Earth fault alarm No Yes Yes Yes 1
Earth fault pickup 25100% x (In) 25100% x (In) 25100% x (In) 24100% x (In)
Earth fault delay I2t at 0.625 x In 100500 ms 100500 ms 100500 ms 100500 ms 1
Earth fault delay flat 100500 ms 100500 ms 100500 ms 100500 ms
Earth fault ZSI Yes Yes Yes Yes 1
Earth fault memory Yes Yes Yes Yes
Disable ground fault protection No No No Yes 1
Neutral protection (N) Model LSI Model LSI Model LSI Model LSI
Legend NNot 1
In = Rating Plug and Sensor Rating a Over and undervoltage alarm or trip,
Ir =
i =
Long Delay Pickup Setting
Trip units are only used on
over and underfrequency alarm or trip,
voltage unbalance alarm or trip, reverse
1
IEC breakers with earth fault power trip, and phase rotation alarm
are included. 1
1
1
1
1
1
1
1
1
1
Low Voltage Switchboards and SwitchgearCA015002ENAugust 2013www.eatoncanada.ca T8-55
8 Low Voltage Switchboards and Switchgear
Components

Digitrip Trip Units for Magnum DS Power Circuit Breakers, continued


1 Digitrip 520i Digitrip 520Mi Digitrip 520MCi Digitrip 1150i+ a

2
3
4 Trip Unit Type
System Diagnostics
5 Cause of trip LEDs Yes Yes Yes Yes
Magnitude of trip information No No No Yes
6 Remote signal contacts No Yes Yes Yes
Programmable contacts No No No 2
7 System Monitoring

8 Digital display
Current (%) full scale sensor
No
No
4-Character LCD
Yes 2%
4-Character LCD
Yes 2%
24-Character LED
Yes 1%

9 Voltage (%) L to L
Power and energy (%)
No
No
No
No
No
No
Yes 1%
Yes 2%

1 Apparent power kVA and demand


Reactive power kVAR
No
No
No
No
No
No
Yes
Yes

1 Power factor No No No Yes


Crest factor No No No Yes

1 Power qualityharmonics No No No Yes


% THD No No No Yes
1 System Communications
Type INCOM/PowerNet/Modbus b/ INCOM/PowerNet/TripLink/
1 Power supply in breaker N/A Optional
PROFIBUS b
Standard
Modbus b/PROFIBUS b
Standard

1 Additional Features
Trip log (three events) No No No Yes
1 Electronic operations counter No No No Yes
Testing method c Test set Test set Test set Integral and test set
1 Waveform capture No No No Yes
ARMs (Arcflash Reduction Maintenance System Mode) No No Yes Yes d
1 Breaker health monitor No No No Yes
Programmable relay functions No No No Yes a
1 Legend NNot
In = Rating Plug and Sensor Rating a Over and undervoltage alarm or trip,
1 Ir =
i =
Long Delay Pickup Setting
Trip units are only used on
over and underfrequency alarm or trip,
voltage unbalance alarm or trip, reverse
IEC breakers with earth fault power trip, and phase rotation alarm
1 are included
b Requires externally mounted MMINT
1 or PMINT module.
c Test set for secondary injection.

1 d Contact Eaton for availability.

1
1
1
1
1
1
1
T8-56 Low Voltage Switchboards and SwitchgearCA015002ENAugust 2013www.eatoncanada.ca
Low Voltage Switchboards and Switchgear
Components
8
Fusible Switches
1
Horizontally Mounted Fusible Switches Fusible Switch Ratings
Rating Horizontally
2
(Amperes/Voltage) Fuse Type Unit Size a Mounted
30 250 Ac or Dc R 4X Twin
3
30/60/100A
60
600 Ac
250 Ac or Dc
R, J
R
4X
4X
Twin
Twin
4
30/60/100A

100
600 Ac
250 Ac or Dc
R, J
R
4X
4X
Twin
Twin
5
200A

200
600 Ac
250 Ac or Dc
R, J
R, T
5X
6X
Twin
Single or twin
6
400A

400
600 Ac
250 Ac or Dc
R, J, T
R, T
6X
9X
Single or twin
Single
7
600/800A
600
600 Ac
250 Ac
R, J, T
R, T
9X
11X
Single
Single
8
600 Ac R, J, T 11X Single
9
800 250 Ac T 11X Single
1200A 600 Ac L, T 11X Single 1
1200 250 Ac T 15X Single
600 Ac L 15X Single 1
NNot
a 1X = 1-3/8 inch.
1
1
1
Horizontally Mounted Fusible SwitchesX Spacing a

1
3060 3060
4X
38.00
100A 100A
1
(965.2)
Wide 200A 6X
1
3060 3060 5X 1
100A 100A

200A 200A 6X 1
1
400A 9X
1
48.00
(1219.2)
Wide 600/800A 11X 1
Structure
1
1200A 15X
1
1
1
NNote: 200A, 600V with Class R fuses available as a single unit only.
1
1
1
1
Low Voltage Switchboards and SwitchgearCA015002ENAugust 2013www.eatoncanada.ca T8-57
8 Low Voltage Switchboards and Switchgear
Components

Fusible Switch Selection Guide


1 Dimensions in Inches (mm)

2 30/60/100A 400A
3 18.00 (457.2) Wide, 4X High, Twin Fusible Switch 22.00 (558.8) Wide, 9X High, Single Fusible Switch a

Ampere Rating Ampere Rating Fuse Type Catalogue Number


4 Unit 1 Unit 2 Fuse Type Catalogue Number 240 Vac or 250 Vac

5 240 Vac or 250 Vdc 400 R FDPW325R


30 30 R FDPWT3211R 400 (Main) R FDPW325MR
6 30 60 R FDPWT3212R 600 Vac
30 100 R FDPWT3213R 400 R FDPW365R
7 60 60 R FDPWT3222R 400 (Main) R FDPW365MR
60 100 R FDPWT3223R 400 J FDPW365J
8 100 100 R FDPWT3233R 400 (Main) J FDPW365MJ
600 Vac
9 30 30 R FDPWT3611R 18.00 (457.2) Wide, 16X HighTop Feed Main a

30 30 J FDPWT3611J Ampere Rating Fuse Type Catalogue Number


1 30 60 R FDPWT3612R
240 Vac or 250 Vac
30 60 J FDPWT3612J
400 R FDPW325TR
1 60 60 R FDPWT3622R
600 Vac
60 60 J FDPWT3622J
1 400
400
R
J
FDPW365TR
FDPW365TJ
22.00 (558.8) Wide, 5X High, Twin Fusible Switch
1 Ampere Rating 18.00 (457.2) Wide, 16X HighBottom Feed Main a
Unit 1 Unit 2 Fuse Type Catalogue Number
1 600 Vac
Ampere Rating Fuse Type Catalogue Number
240 Vac or 250 Vac
30 100 R FDPWT3613R
1 60 100 R FDPWT3623R
400 R FDPW325BR
600 Vac
1 100 100 R FDPWT3633R
400 R FDPW365BR
400 J FDPW365BJ
1 200A NNot
a For cable-in/cable-out application of a branch switch, additional terminals are required.
1 22.00 (558.8) Wide, 6X High, Twin Fusible Switch Order the terminal kit TA750FDPW. The kit contains three terminals and hardware.
Ampere Rating
1 Unit 1 Unit 2 Fuse Type Catalogue Number

1 240 Vac or 250 Vdc


200 200 R FDPBT3244R

1 200
600 Vac
200 R FDPBT3244RDS

1 200 200 J FDPBT3644J


200 200 J FDPBT3644JDS
1 18.00 (457.2) Wide, 6X High, Single Fusible Switch
1 Ampere Rating Fuse Type Catalogue Number
240 Vac or 250 Vac
1 200 T FDPBS324F
200 R FDPBS324R
1 600 Vac
200 R FDPBS364R
1 200 J FDPBS364J
200 T FDPBS364F
1
1
1
T8-58 Low Voltage Switchboards and SwitchgearCA015002ENAugust 2013www.eatoncanada.ca
Low Voltage Switchboards and Switchgear
Components
8
600A 1200A
1
22.00 (558.8) Wide, 11X High, Single Fusible Switch a 22.00 (558.8) Wide, 15X High, Single Fusible Switch c

Ampere Rating Fuse Type Catalogue Number Ampere Rating Fuse Type Catalogue Number 2
240 Vac or 250 Vac
600 R FDPW326R
240 Vac
1200 T FDPW328F
3
600 (Main)
600 Vac
R FDPW326MR 1200 (Main)
600 Vac
T FDPW328MF
4
600 R FDPW366R 1200 L FDPW368 5
600 (Main) R FDPW366MR 1200 (Main) L FDPW368M
600 J FDPW366J
22.00 (558.8) Wide, 16X HighTop Feed Main c
6
600 (Main) J FDPW366MJ

18.00 (457.2) Wide, 16X HighTop Feed Main a


Ampere Rating Fuse Type Catalogue Number 7
240 Vac
Ampere Rating Fuse Type Catalogue Number 1200 T FDPW328TF 8
240 Vac or 250 Vac 600 Vac
600 R FDPW326TR 1200 L FDPW368T 9
600 Vac
600 R FDPW366TR 22.00 (558.8) Wide, 16X HighBottom Feed Main c 1
600 J FDPW366TJ Ampere Rating
240 Vac
Fuse Type Catalogue Number
1
18.00 (457.2) Wide, 16X HighBottom Feed Main a

Ampere Rating Fuse Type Catalogue Number


1200 T FDPW328BF 1
600 Vac
240 Vac or 250 Vac 1200 L FDPW368B 1
600 R FDPW326BR NNote
600 Vac a For cable-in/cable-out application of a branch switch, additional terminals are required. 1
600 R FDPW366BR Order two of the terminal kit TA750FDPW. Each kit contains three terminals and hardware.
600 J FDPW366BJ b For cable-in/cable-out application of a branch switch, additional terminals are required.
Order three of the terminal kit TA750FDPW. Each kit contains three terminals and hardware.
1
c For cable-in/cable-out application of a branch switch, additional terminals are required.
Order four of the terminal kit TA750FDPW. Each kit contains three terminals and hardware. 1
800A

22.00 (558.8) Wide, 11X High, Single Fusible Switch b


1
Ampere Rating Fuse Type Catalogue Number 1
240 Vac
800 T FDPW327F 1
800 (Main) T FDPW327MF
600 Vac 1
800 L FDPW367
800 (Main) L FDPW367M
1
18.00 (457.2) Wide, 16X HighTop Feed Main b 1
Ampere Rating Fuse Type Catalogue Number
1
240 Vac
800 T FDPW327TF 1
600 Vac
800 L FDPW367T 1
18.00 (457.2) Wide, 16X HighBottom Feed Main b
1
Ampere Rating Fuse Type Catalogue Number
240 Vac 1
800 T FDPW327BF
600 Vac
1
800 L FDPW367B
1
1
Low Voltage Switchboards and SwitchgearCA015002ENAugust 2013www.eatoncanada.ca T8-59
8 Low Voltage Switchboards and Switchgear
Components

FDPW Switch Ratings


1 Horsepower Rating
Short-Circuit Size and Type of Cu/Al

2 Ampere Rating Voltage Rating kAIC Standard Maximum Fuse Type Conductor per Phase
30A switch 240 Vac 200 3 7.5 R #14 to 1/0

3 480 Vac 200 5 15 R, J #14 to 1/0


600 Vac 200 7.5 20 R, J #14 to 1/0
4 250 Vdc 10 5 5 a #14 to 1/0
60A switch 240 Vac 200 7.5 15 R #14 to 1/0
5 480 Vac 200 15 30 R, J #14 to 1/0
600 Vac 200 15 50 R, J #14 to 1/0
6 250 Vdc 10 10 10 a #14 to 1/0
100A switch 240 Vac 200 15 30 R #14 to 1/0
7 480 Vac 200 25 60 R, J #14 to 1/0
600 Vac 200 30 75 R, J #14 to 1/0
8 250 Vdc 10 20 20 a #14 to 1/0
200A switch b 240 Vac 200 25 60 R, T #4 to 300 kcmil
9 480 Vac 200 50 125 R, J, T #4 to 300 kcmil
600 Vac 200 60 150 R, J, T #4 to 300 kcmil
1 250 Vdc 10 40 40 a #4 to 300 kcmil
400A switch 240 Vac 200 50 125 R, T 250 to 750 kcmil or (2) 3/0 to 250 kcmil c
1 480 Vac 200 100 250 R, J, T 250 to 750 kcmil or (2) 3/0 to 250 kcmil c
600 Vac 200 125 350 R, J, T 250 to 750 kcmil or (2) 3/0 to 250 kcmil c
1 250 Vdc 10 50 50 a 250 to 750 kcmil or (2) 3/0 to 250 kcmil c
600A switch 240 Vac 200 75 200 R, T (2) #4 to 600 kcmil or (4) 3/0 to 250 kcmil
1 480 Vac 200 150 400 R, J, T (2) #4 to 600 kcmil or (4) 3/0 to 250 kcmil
600 Vac 200 200 500 R, J, T (2) #4 to 600 kcmil or (4) 3/0 to 250 kcmil
1 800A switch 240 Vac 200 N/A N/A T (3) 250 to 750 kcmil or (6) 3/0 to 250 kcmil
480 Vac 200 N/A N/A L, T (3) 250 to 750 kcmil or (6) 3/0 to 250 kcmil
1 600 Vac 200 N/A N/A L, T (3) 250 to 750 kcmil or (6) 3/0 to 250 kcmil
1200A switch 240 Vac 200 N/A N/A T (4) 250 to 750 kcmil or (8) 3/0 to 250 kcmil
1 480 Vac 200 N/A N/A L (4) 250 to 750 kcmil or (8) 3/0 to 250 kcmil
600 Vac 200 N/A N/A L (4) 250 to 750 kcmil or (8) 3/0 to 250 kcmil
1 NNote

1 a Contact fuse manufacturer for UL listed Dc fuses.


b Switch type FDPB (breaker based).

1 c Lug size conversion kit available for: 1 x 750 kcmil (600A FDP), 2 x 750 kcmil (600A FDPW), 3 x 350 kcmil (600A CFDOW SW).
N/A = Not Applicable

1
1
1
1
1
1
1
1
1
1
1
T8-60 Low Voltage Switchboards and SwitchgearCA015002ENAugust 2013www.eatoncanada.ca
Low Voltage Switchboards and Switchgear
Components
8
Surge Protection Devices
1
SPD Series Specifications 2
Description Specification
Surge capacity ratings available 50, 80, 100, 120, 160, 200, 250, 300, 400 kA per phase 3
Nominal discharge current (In) 20 kA
Short-circuit current rating (SCCR) 200 kA 4
SPD type Basic feature package = Type 1 (can also be used in Type 2 applications)
Standard and Standard with Surge Counter feature packages = Type 2 5
Single split-phase voltages available 120/240
Three-phase wye system voltages available 120/208, 127/220, 230/400, 277/480, 347/600 6
Three-phase delta system voltages available 240, 480, 600
Input power frequency 50/60 Hz 7
Power consumption (basic units):
208Y, 220Y, 240S, 240D and 240H voltage codes 0.5W 8
400Y, 480Y and 480D voltage codes 1.1W
600Y and 600D voltage codes 1.3W 9
Power consumption (standard and standard with surge counter units):
208Y, 220Y, 240S, 240D and 240H voltage codes 0.6W 1
400Y, 480Y and 480D basic voltage codes 1.7W
600Y and 600D voltage codes 2.1W 1
Protection modes Single split phase....................................... L-N, L-G, N-G, L-L
Three-phase wye........................................ L-N, L-G, N-G, L-L 1
Three-phase delta....................................... L-G, L-L

Maximum continuous operating voltage (MCOV):


Three-phase high-leg delta......................... L-N, L-G, N-G, L-L
1
240S, 208Y, 220Y and 240H MCOV
400Y and 480Y MCOV
150 L-N, 150 L-G, 150 N-G, 300 L-L
320 L-N, 320 L-G, 320 N-G, 640 L-L
1
600Y MCOV
240D MCOV
420 L-N, 420 L-G, 420 N-G, 840 L-L
320 L-G, 320 L-L
1
480D MCOV
600D MCOV
640 L-G, 640 L-L
840 L-G, 840 L-L
1
Ports 1
1
Operating temperature 4F through 122F (20C through 50C)
Operating humidity 5% through 95%, noncondensing 1
Operating altitude Up to 16,000 ft (5000m)
Seismic withstand capability Meets or exceeds the requirements specified in IBC 2006, CBC 2007 1
Weight 50200 kA units approximately 3.5 lbs (1.6 kg)

Form C relay contact ratings


250400 kA units approximately 7.0 lbs (3.2 kg)
150 Vdc or 125 Vac, 1A maximum
1
Form C relay contact logic Power ON, normal stateNO contact = open, NC contact = closed
Power OFF or fault stateNO contact = closed, NC contact = open 1
EMI/RFI filtering attenuation Up to 50 dB from 10 kHz to 100 MHz
Agency certifications and approvals UL 1449 3rd Edition recognized component for the U.S. and Canada 1
UL 1283 (Type 2 SPDs only)
Warranty 10 years 1
1
Feature Package Comparison
Standard with 1
Feature Basic Standard Surge Counter
Surge protection using thermally protected MOV technology n n n 1
Dual-coloured protection status indicators for each phase n n n
Dual-coloured protection status indicators for the neutral-ground protection mode n n n 1
Audible alarm with silence button n n
Form C relay contact n n 1
EMI/RFI filtering, providing up to 50 dB of noise attenuation from 10 kHz to 100 MHz n n
Surge counter with reset button n 1
1
Low Voltage Switchboards and SwitchgearCA015002ENAugust 2013www.eatoncanada.ca T8-61
8 Low Voltage Switchboards and Switchgear
Components

Metering
1
2 Metering Selection Chart
Power XpertT Meter 4000/6000/8000 Series Power Xpert Meter 2000 Series IQ 250/260 Series
3
4
5 Device Name

6 Electrical Parameters
Volts 0.1% of reading + 0.02% FS 0.1% of reading 0.1% of reading

7 Amperes
Current range (% of nominal)
0.05% of reading + 0.01% FS
0.00520A (400%)
0.1% of reading
0.1200%
0.1% of reading
0.1200%

8 Watts 0.1% of reading + 0.0025% FS 0.2% of reading 0.2% of reading


VARs 0.1% of reading + 0.0025% FS 0.2% of reading 0.2% of reading

9 VA 0.1% of reading + 0.0025% FS 0.2% of reading 0.2% of reading


PF-apparent 0.1% 0.2% of reading 0.2% of reading
1 PF-displacement 0.1%
Frequency 0.01 Hz 0.03 Hz 0.03 Hz
1 THD-voltage 127th 40th bcde 40th f
THD-current 127th 40th bcde 40th f
1 Watthours 0.2% per ANSI C12.20 0.2 Class a 0.2% per ANSI C12.20 0.2 Class 0.2% per ANSI C12.20 0.2 Class
VAR-hours 0.2% per ANSI C12.20 0.2 Class a 0.2% per ANSI C12.20 0.2 Class 0.2% per ANSI C12.20 0.2 Class
1 VA-hours 0.2% per ANSI C12.20 0.2 Class a 0.2% per ANSI C12.20 0.2 Class 0.2% per ANSI C12.20 0.2 Class
Ampere-demand 0.05% of reading + 0.01% FS 0.1% per ANSI C12.20 0.2 Class 0.1% per ANSI C12.20 0.2 Class
1 Watt-demand 0.2% per ANSI C12.20 0.2 Class a 0.2% per ANSI C12.20 0.2 Class 0.2% per ANSI C12.20 0.2 Class
VAR-demand 0.2% per ANSI C12.20 0.2 Class a 0.2% per ANSI C12.20 0.2 Class 0.2% per ANSI C12.20 0.2 Class
1 VA-demand 0.2% per ANSI C12.20 0.2 Class a 0.2% per ANSI C12.20 0.2 Class 0.2% per ANSI C12.20 0.2 Class
Revenue accuracy 0.2% per ANSI C12.20 0.2 Class a ANSI C12.20 (0.2%) ANSI C12.20 (0.2%)
1 Individual ampere harmonics 85th g 40th cde
Individual voltage harmonics 85th g 40th cde
1 Interharmonics Yes hi
Minimum and/or Maximum Values
1 Volts L-L, L-N, N-G, VAUX L-L L-L, L-N L-L, L-N
Current A, B, C, N, G A, B, C, N A, B, C
1 Power Watt, VAR, VA Watt, VAR, VA Watt, VAR, VA
Power Factor Apparent/displacement Apparent Apparent
1 Frequency Hz Hz Hz
THD Amperes/volts (L-L, L-N, AUX L-L) Amperes/volts bcde Amperes/volts f
1 Demand values kW, kVAR, kVA, amperes kW, kVAR, kVA, amperes kW, kVAR, kVA, amperes
Trend analysis 2 / 4 h / 8 i GB 256 / 512 b / 768 cde MB j
1 Event logging 2 / 4 h / 8 i GB 100,000 alarms/events with timestamp 128 KB k

1 Disturbance recording
Legend
2 / 4 h / 8 i GB, 60 cycles per event
NNote
768 MB up to 64 cycles per event de

1

PG = Programmable
FS = Full scale
a Under typical operating conditions.
b PXM 2260 only.
f IQ 260 only.
g Individual values reported to 85th
h PXM 6000 only.
i PXM 8000 only.
RV = Read value
1 Auxiliary Voltage
(Optional) = Provides three
c PXM 2270 only.
d PXM 2280 only.
harmonic; anti-alias filtering prevents
higher frequencies from distorting
j At computer only.
k Optional.
readings (see IEC 61000-4-7).
additional voltage
1 inputs to the meter:
e PXM 2290 only.

Va2, Vb2, Vc2


1 Interharmonics = Power Xpert Meter
6000/8000 supported

1
1
1
T8-62 Low Voltage Switchboards and SwitchgearCA015002ENAugust 2013www.eatoncanada.ca
Low Voltage Switchboards and Switchgear
Components
8
Metering Selection Chart, continued
Power Xpert Meter 4000/6000/8000 Series Power Xpert Meter 2000 Series IQ 250/260 Series
1
2
3
Device Name 4
Other Features
Storage 2 / 4 a / 8 b GB 256 / 512 c / 768 def MB Standard 128 KB for logging, up to 8 parameters every 5
15 minutes for 30 days g
PG output relays 5 maximum Optional (2) Form C, 5 A or (4) Form A, 120 mA Optional (2) Form C, 5 A or (4) Form A, 120 mA 6
PG analogue outputs Optional (4) 420 mA or (4) 01 mA Optional (4) 420 mA or (4) 01 mA
Discrete contact inputs 8 Optional (2) or (4) Optional (2) or (4) 7
Analogue inputs
Synch-input kW utility Via status input Via end of interval pulse with Via end of interval pulse with 8
optional digital inputs optional digital inputs
Auxiliary voltage Yes 9
kWh pulse initiator Yes Yes Yes
Waveform display Local/computer h 1
Waveform capture, samples/cycle Yes, 512 (4096 oversampling) Yes, up to 64 e, up to 512 f
Frequency distribution display 1
Display type LCD Red LED Red LED
Display lines/character Graphic (320 x 240 pixels) 3 lines, 4 characters 3 lines, 4 characters 1
Display character height 5.5 mm H x 4 mm W 0.56 (14.2) H 0.56 (14.2) H
Communications Serial: ModbusT RTU, Modbus ASCII Serial: Modbus RTU, Modbus ASCII, DNP 3.0 Serial: Modbus RTU, Modbus ASCII, DNP 3.0 1
Network: Modbus TCP, Ethernet TCP/IP, Network: Modbus TCP, BACnet/IP, Ethernet Network: Modbus TCP via Power Xpert
HTTP, SNMP, SMTP, FTP TCP/IP, HTTP, HTTPS, SNMP, SMTP,
Waveform FTP ef
Gateway
1
Setup configuration Via Web browser/display Via Web browser/display Via configuration software/display
Dimensions in inches (mm) Meter: 8.82 (224.0) H x 8.22 (208.8) W x 4.85 (123.2) H x 4.85 (123.2) W x 4.85 (123.2) H x 4.85 (123.2) W x
1
6.72 (170.7) D 4.97 (126.2) D 4.97 (126.2) D
Display:

9.02 (229.1) H x 7.80 (198.1) W x
2.49 (63.2) D
1
Operating temperature range 20 to 60C display unit
20 to 70C meter base unit i
20 to 70C 20 to 70C
1
Reference literature TD02601007E TD02601017E TD02601016E
Legend NNote
1


PG = Programmable
FS = Full scale
a PXM 6000 only.
b PXM 8000 only.
d PXM 2270 only.
e PXM 2280 only.
g Optional.
h At computer only.
1
RV = Read value
Auxiliary Voltage
(Optional) = Provides three
c PXM 2260 only. f PXM 2290 only. i Using <10 VA meter sourced 24V power.
1
additional voltage
inputs to the meter: 1
Va2, Vb2, Vc2
Interharmonics = Power Xpert Meter
6000/8000 supported 1
1
1
1
1
1
1
1
1
Low Voltage Switchboards and SwitchgearCA015002ENAugust 2013www.eatoncanada.ca T8-63
8 Low Voltage Switchboards and Switchgear
Components

Metering Selection Chart, continued


1 IQ Analyzer 6000 Series IQ DP-4000 Series IQ 230 Series

2
3
4 Device Name
Electrical Parameters
5 Volts 0.2% FS a 0.3% FS 0.5% FS
Amperes 0.2% FS a 0.3% FS 0.5% FS
6 Current range (% of nominal) 3800% 10250% 1200%
Watts 0.4% FS, 6 Reading b 0.6% FS 1.0% FS
7 VARs 0.4% FS, 6 Reading c 0.6% FS 1.0% FS
VA 0.4% FS, 6 Reading b 0.6% FS 1.0% FS
8 PF-apparent 0.8% FS a 1.0% FS 2.0% FS

9 PF-displacement
Frequency
0.8% FS a
0.04% a or 0.01 Hz
1.0% FS
0.17% FS
2.0% FS
0.1% Hz

1 THD-voltage
THD-current
50th
50th
31st
31st

1 Watthours
VAR-hours
0.5% reading b
1% reading c
0.6% FS
0.6% FS
1.0% per ANSI C12
1.0% per ANSI C12

1 VA-hours
Ampere-demand
0.5% reading b
0.2% FS a
0.6% FS
0.3%
1.0% per ANSI C12
0.5% per ANSI C12

1 Watt-demand
VAR-demand
0.4% FS a
0.4% FS a
0.6%
0.6%
1.0% per ANSI C12
1.0% per ANSI C12

1 VA-demand 0.4% FS a 0.6% 1.0% per ANSI C12


Revenue accuracy ANSI C12.20 (0.5%) ANSI C12.1 (1%)

1 Individual ampere harmonics 50th


Individual voltage harmonics 50th
1 Interharmonics
Minimum and/or Maximum Values
1 Volts L-L, L-N L-L, L-N L-L, L-N
Current A, B, C, N, G A, B, C A, B, C
1 Power Watt, VAR, VA Watt, VAR, VA Watt, VAR, VA
Power factor Apparent/displacement Apparent/displacement Apparent/displacement
1 Frequency Hz Hz Hz
THD Amperes/volts Amperes/volts
1 Demand values All All All
Trend analysis Time/date 2 alarms d
1 Event logging 504 events w/timestamp d d

Disturbance recording 10 waveform events


1 Legend NNote
PG = Programmable a From 3 to 300% of FS.
1 FS = Full scale b At unity power factory and
RV = Read value 5300% of FS.
1 Auxiliary Voltage
(Optional) = Provides three
c At a power factor <0.5 and

additional voltage 5300% of FS.


1 inputs to the meter:
Va2, Vb2, Vc2
d At computer only.

Interharmonics = Power Xpert Meter


1 6000/8000 supported

1
1
1
1
T8-64 Low Voltage Switchboards and SwitchgearCA015002ENAugust 2013www.eatoncanada.ca
Low Voltage Switchboards and Switchgear
Components
8
Metering Selection Chart, continued
IQ Analyzer 6000 Series IQ DP-4000 Series IQ 230 Series
1
2
3
Device Name 4
Other Features
Storage 90 KB 15 parameters 5
PG output relays (4) 10 A Form C a (3) 10 A Form C b (2) 100 mA Form A
PG analogue outputs (4) 010/420 mA
6
Discrete contact inputs (3) +30 Vdc differential (1) kW demand b (2) +30 Vdc differential
Analogue inputs (1) 020/420 mA (1) 420 mA
7
Synch-input kW Utility
Auxiliary voltage c
At device or via communications

At device or via communications b

Via communications only

8
kWh pulse initiator
Waveform display
Yes
Local b/computer
Yes b

Yes

9
Waveform capture, samples/cycle
Frequency distribution display
Yes, 128
Local b/computer




1
Display type
Display lines/character
Graphic LCD with LED backlight
7 lines, 147 characters
7 Segment LED
1 line, 7 characters
Backlit LCD
4 lines, 20 characters
1
Display character height
Communications
Up to 7 lines
Serial: INCOM d
1 line
Serial: INCOM d
1.60 (40.6) H x.09 (2.3) W
Serial: INCOM, Modbus RTU e
1
Network: via Power Xpert Gateway d Network: via Power Xpert Gateway d Network: via Power Xpert Gateway
Setup configuration Via configuration software/display Via configuration software/display Via configuration software/display
1
Dimensions in inches (mm)
Operating temperature range
6.70 (170.2) W x 10.30 (261.6) H x 5.40 (137.2) D f
20 to 70C
6.70 (170.2) W x 10.30 (261.6) H x 5.40 (137.2) D f
20 to 70C
Refer to TD.17.06.T.E
0 to 50C
1
Reference literature
NNote

1
Legend


PG = Programmable
FS = Full scale
a Relays programmable to operate on any
measured function.
d An IPONI is required.
e IQ 230M only.
1
RV = Read value b Optional.
Auxiliary Voltage
c The auxiliary voltage option adds three
f Dimensions in mm =
170.2 W x 261.6 H x 137.2 D.
1
(Optional) = Provides three
additional voltage additional voltage input channels to
inputs to the meter: Power Xpert Meters. 1
Va2, Vb2, Vc2
Interharmonics = Power Xpert Meter
6000/8000 supported
1
1
1
1
1
1
1
1
1
1
1
1
Low Voltage Switchboards and SwitchgearCA015002ENAugust 2013www.eatoncanada.ca T8-65
8 Low Voltage Switchboards and Switchgear
Components

Metering Selection Chart, continued


1
Power Monitoring /
2 IQ 130/140/150 Series IQ 35M IQ 150S/250S Series Metering Module (PM3)

3
4
Device Name
5 Electrical Parameters
Volts 0.25% of reading 0.4% +0.015% per C deviation from 25C 0.1% of reading 0.5% of reading
6 Amperes 0.25% of reading 0.4% (5100%), 0.8%(15%) +0.015% 0.1% of reading 0.5% of reading
per C from 25C
7 Current range (% of nominal) 0.1200% 1120% 0.1200%
Watts 0.5% of reading a 0.5% per ANSI C12.20 and 0.2% of reading 1.0% of reading
8 IEC 62053-22 Class 0.5S
VARs 0.5% of reading a 2.0% per IEC 62053-23 Class 2 0.2% of reading 1.0% of reading
9 VA 0.5% of reading a Calculated: vector sum of 0.2% of reading 1.0% of reading
watts and VARs

1 PF-apparent 0.5% of reading a Calculated: watts/VAs 0.2% of reading 2.0% of reading


PF-displacement
1 Frequency 0.03 Hz a 0.02 Hz 0.03 Hz 0.1 Hz
THD-voltage
1 THD-current
Watthours 0.5% per ANSI C12.20 0.5 Class b 0.5% per ANSI C12.20 and 0.2% per ANSI C12.20 0.2 Class 1.0% per ANSI C12.1
1 VAR-hours 0.5% per ANSI C12.20 0.5 Class b
IEC 62053-22 Class 0.5S
2.0% per IEC 62053-23 Class b 0.2% per ANSI C12.20 0.2 Class 1.0% of reading

1 VA-hours
Ampere-demand
0.5% per ANSI C12.20 0.5 Class b
0.25% per ANSI C12.20 0.5 Class a


0.2% per ANSI C12.20 0.2 Class
0.1% per ANSI C12.20 0.2 Class
1.0% of reading

1 Watt-demand 0.5% per ANSI C12.20 0.5 Class a 0.5% per ANSI C12.20 and
IEC 62053-22 Class 0.5S
0.2% per ANSI C12.20 0.2 Class

1 VAR-demand
VA-demand
0.5% per ANSI C12.20 0.5 Class a
0.5% per ANSI C12.20 0.5 Class a
2.0% per IEC 62053-23 Class 2
Calculated: vector sum of
0.2% per ANSI C12.20 0.2 Class
0.2% per ANSI C12.20 0.2 Class


watts and VARs
1 Revenue accuracy ANSI C12.20 (0.5%) 0.5% per ANSI C12.20 and ANSI C12.20 (0.2%) 1.0% per ANSI C12.1
IEC 62053-22 Class 0.5S
1 Individual ampere harmonics
Individual voltage harmonics
1 Interharmonics
Minimum and/or Maximum Values
1 Volts L-L, L-N L-L, L-N
Current A, B, C A, B, C,
1 Power Watt, VAR, VA a Watt, VAR, VA
Power factor Apparent a Apparent (low alert) Apparent
1 Frequency Hz a Hz (out of range alert) Hz
THD
1 Demand values kW, kVAR, kVA, amperes a kW, kVAR, kVA; kW, kVAR, kVA, amperes
maximum kW, kVAR, kVA
1 Trend analysis c 2 MB e
Event logging c Logging on demand interval or 2 MB e
1 Modbus command d
Disturbance recording
1 Legend NNote
PG = Programmable a IQ 140/150.
1

FS = Full scale
RV = Read value
b IQ 150 only.
c At computer only.
Auxiliary Voltage
1 (Optional) = Provides three d Optional.
additional voltage e IQ 250S only.
1 inputs to the meter:
Va2, Vb2, Vc2
Interharmonics = Power Xpert Meter
1 6000/8000 supported

T8-66 Low Voltage Switchboards and SwitchgearCA015002ENAugust 2013www.eatoncanada.ca


Low Voltage Switchboards and Switchgear
Components
8
Metering Selection Chart, continued
Power Monitoring / Metering
1
IQ 130/140/150 Series IQ 35M IQ 150S/250S Series Module (PM3)
2
3
4
Device Name
Other Features 5
Storage 10 registers (16 bit) by 5760 2 MB b
entries each (115 KB) a 6
PG output relays
PG analogue outputs 7
Discrete contact inputs 2-pulse inputs with BACnet Circuit breaker status
Analogue inputs 8
Synch-input kW utility Optional demand synchronization
via Modbus 9
Auxiliary voltage c
kWh pulse initiator a Yes Yes 1
Waveform display
Waveform capture 1
Frequency distribution display
Display type Red LED Backlit LCD Red LED 1
Display lines/character 3 lines, 4 characters 2 lines by 5 characters each 3 lines, 4 characters
(full alphanumeric top row)
1
Display character height 0.56 (14.2) H 7.5 mm 0.56 (14.2) H
Communications Serial: Modbus RTU,
Modbus ASCII a
Serial: Modbus RTU a,
BACnet MS/TP a
Serial: Modbus RTU, Modbus ASCII,
DNP 3.0
Serial: INCOM, Modbus RTU d
Network: via Power Xpert Gateway
1
Network: Modbus TCP a 4 Network: Modbus TCP via Network: Modbus TCP,
Power Xpert Gateway wired or wireless 1
Setup configuration Via configuration software/display Via display/configuration software Via configuration software/display
Dimensions in inches (mm) 4.85 (123.2) H x 4.85 (123.2) W 3.60 (91.4) H x 4.20 (106.7) W 7.90 (200.7) H x 7.50 (190.5) W Refer to IL01219085E 1
x 4.97 (126.2) D x 2.30 (58.4) D x 3.10 (78.7) D 25 to 70C
Operating temperature range 20 to 70C Meter: 30 to 70C
Display: 10 to 50C
20 to 70C 1
Reference literature TD02601016E
NNote
TD02601018E TD02601019E
1
Legend


PG = Programmable
FS = Full scale
a Optional.
b IQ 250S only.
1
RV = Read value
Auxiliary Voltage
c The auxiliary voltage option adds three
additional voltage input channels to
1
(Optional) = Provides three
additional voltage Power Xpert Meters.
inputs to the meter: d Contact Eaton for availability. 1
Va2, Vb2, Vc2
Interharmonics = Power Xpert Meter
6000/8000 supported
1
1
1
1
1
1
1
1
1
Low Voltage Switchboards and SwitchgearCA015002ENAugust 2013www.eatoncanada.ca T8-67
8 Low Voltage Switchboards and Switchgear
Components

This page intentionally left blank.


1
2
3
4
5
6
7
8
9
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
T8-68 Low Voltage Switchboards and SwitchgearCA015002ENAugust 2013www.eatoncanada.ca
Eaton is dedicated to ensuring that reliable, efficient and safe
power is available when its needed most. With unparalleled
knowledge of electrical power management across industries,
experts at Eaton deliver customized, integrated solutions to solve
our customers most critical challenges.

Our focus is on delivering the right solution for the application.


But, decision makers demand more than just innovative products.
They turn to Eaton for an unwavering commitment to personal
support that makes customer success a top priority. For more
information, visit www.eatoncanada.ca.

Eaton
1000 Eaton Blvd.
Cleveland, Ohio
44122
United States
877-ETN-CARE (877-386-2273)
www.eaton.com

Canadian Operations
5050 Mainway
Burlington, ON L7L 5Z1
Canada
1-800-268-3578
www.eatoncanada.ca

2013 Eaton Corporation Eaton is a registered trademark Follow us on social media to get the
All Rights Reserved of Eaton Corporation. latest product and support information.
Printed in Canada
Pub No. CA015002EN All trademarks are property of their
July 2013 respective owners.