Vous êtes sur la page 1sur 8

Multifunction IEDs 01

MiCOM C434
Bay unit for control and monitoring

MiCOM C434 is a cost-effective modular bay control unit


and designed for the control and monitoring of bays.

APPLICATION AND SCOPE


The scope of information handled by the MiCOM C434
is designed for the control and monitoring of up to 24
electrically operated switchgear units equipped with electrical
C434 40TE with graphic display
checkback signalling located in the bay of a medium-voltage
substation or a non-complex high-voltage station.

External auxiliary devices are largely obviated through the


integration of binary signal inputs and power outputs that are
independent of auxiliary voltages, by the direct connection
option for current and voltage transformers and by the
comprehensive interlocking capability. This simplifies handling
of the protection and control technology for a switchbay from
planning to commissioning.
C434 84TE with text display

During operation, the user-friendly interface facilitates setting


of the unit and promotes safe operation of the substation by
preventing nonpermissible switching operations.

Providing identical user interfaces as the combined protection


and control devices (One-Box Solutions) of the same range,
MiCOM C434 is ideal to complete protection and control
solutions in substations on bay level.

For the selection of the bay, the MiCOM C434 offers a wide
range of predefined bay types and allows loading a user-
defined bay type.

Customer Benefits The comprehensive set of integrated communication protocols


facilitates the connection to a substation control system and
User-friendly
a RTU, as well as the data transmission for serial connected
Easily configurable
devices (IEDs, Intelligent Eletronic Device).
Straightforward commissioning
Large selection of predefined bay types The modular design of MiCOM C434 with an application-
Open communication structure matched complementary fitting offers the user a flexible
Communication interface to the concept for an easy integration of the control device in the
substation control system substation. MiCOM C434 offers both flush-mounting case for
Remote access by operating program racks or control panels and surface-mounting case 40T and
84T for wall installation with text and graphic display.
02
Multifunction IEDs MiCOM C434

MAIN FUNCTIONS form of single-pole operating signals; they are


processed in accordance with their significance
Main functions are autonomous function groups
for the substation (circuit breaker readiness,
and can be individually configured or disabled
for example). Furthermore up to four multi-pole
to suit a particular application. Function groups
operating signals can be configured.
that are not required and have been disabled by
the user are masked completely (except for the For each switchgear input and each free input, a
configuration parameter) and functional support is separate debounce and chatter time may be set.
withdrawn from such groups.
The MiCOM C434 issues switching command
This concept permits an extensive scope of functions outputs with the integration of switching readiness
and universal application of the device in a single and permissibility tests; subsequently the C434
design version, while at the same time providing for monitors the intermediate position times of the
a clear and straight-forward setting procedure and switchgear units. If a switchgear malfunction is
adaptation to the control task under consideration. detected, this fact will be indicated, e.g. by an
appropriately configured LED indicator.
The Bay Unit for Control and Monitoring MiCOM
Before a switching command output is executed,
C434 is provided with a great number of control and
the interlocking logic of the MiCOM C434 will
monitoring functions.
check whether the new switchgear unit state
corresponds to a permissible bay or substation
Control functions
topology. The interlocking logic is set out for
For the acquisition of switchgear positions, the each bay in the default setting as bay interlock
MiCOM C434 uses up to 48 binary inputs for the with and without station interlock. By means of
signaling of up to 24 two-pole switching positions a straight-forward parameter setting procedure,
and up to 48 binary outputs for controlling of up to the interlocking equations can be adapted to
24 switchers or transformer tap changer positions. the prevailing bay and substation topology. The
presentation and functioning of the interlocking system
The acquisition of further binary inputs is in the
correspond to those of the programmable logic.

MiCOM C434 Functions Overview


Function ANSI General Description
DEV01..DEV24 3/6 Control and monitoring of up to 24 switchgear units
CMD_1 Single-pole commands
SIG_1 Single-pole signals
SIG_M Multi-pole signals
ILOCK Interlocking logic
ASC 25 Automatic synchronism control optional
TAPCH 2 Tap-Changer Control
COUNT Binary Count Inputs
LOGIC Programmable logic
LIMIT 71 Limit monitoring for analog measured values optional
LIM_x Limit monitoring for phase currents and voltages optional
AR_MVx Arithmetic-mean value acquisition optional
LT_RC Long-term recording optional
INP / OUTP Binary signal inputs / output relays (maximum number) 228 / 88
MEASI / MEASO Analog Input/Output (2 x 20 mA output, 20 mA input, resistance
optional
thermometer input)
COMMx Communication interfaces optional
IEC Communication IEC 61850 optional
IRIGB IRIG B input optional
MM_BC / MM_AC Feeder line MODBUS (binary commands, analog commands,
optional
/ MM_BS / MM_AS binary signals, analog signals)
DTI Deviation time integral optional
Other functions 2 / 74
03
Multifunction IEDs MiCOM C434

For integration of the MiCOM C434 into a control Tap-changer control


systems for substations, the equations for the bay
For the acquisition of signals from two transformer
interlock with station interlock form the basis of
tap position changers, up to two multi-pole operation
interlock checking.
signals may be configured. Acquisition may be
Without integration into the substation control carried out either in binary, BCD or Gray code.
system, the bay interlock without station interlock Both tap position changers could be controlled by
is used in interlock checking; external ring feeders relay outputs. The relay outputs are activated by
may be included in the interlocking logic. commands issued from an external voltage regulator
via binary signal inputs or via the serial link.
If the bay or station topology (as applicable) is
permissible then the switching command is issued. The operation of tap position changer is
If a non permissible state would result from the monitored by MiCOM C434.
switching operation then the switching command is
Binary counter inputs
rejected and a signal to this effect is issued.
For the acquisition of up to 24 binary counters,
If the bay type does not require all binary outputs
one binary input each may be configured.
then the remaining outputs are available for free
The contents of these high-speed counters (60Hz)
configuration.
is transmitted cyclically via the serial link.
In addition to the switching command output , a
In the event of loss of operating voltage, the
triggering of binary outputs by single-pole commands
count is stored. After a renewed startup of the
as continous or pulse commands is possible.
unit, counting is continued with the stored value
As part of its control functions, the MiCOM C434 as initial value. Initial values could be set for each
stores bay type definitions with their default counter separately.
settings. By setting the appropriate parameter,
Automatic synchronism check
the bay type is activated with its default settings.
This includes both the activation of the assigned In dual-feeder networks this ensures that
diagram and the setting of the communication reclosure will proceed only if the synchronism
interface. The user can adapt individual conditions are met.
parameters, such as the circuit breaker operation
time to the bays characteristics.

FUNCTION DIAGRAM

Control / Monitoring of Communication


COMM1 COMM2 IEC IRIGB Recording and acquisition
up to 24 switching devices
of measured values
to substation control system / by modem ...
via RS 485 or optical fibre connection
DEVxx ILOCK
per IEC 60870-5-101/-103,
MODBUS, DNP 3.0, Courier
MM_BC MM_AC MM_BS MM_AS AR_MVx Meas.
values
LT_RC

V ref

LIM_x
Self 25
LOGIC SIG_M LIMIT
monitoring ASC

DTI
I

TAPCH COUNT SIG_1 CMD_1 MEASI MEASO


Bay Unit for Control and
Monitoring MiCOM C434

Description of ANSI code nos. see Functions Overview


04
Multifunction IEDs MiCOM C434

Limit value monitoring The user-configurable logic function is then able to


influence the individual functions without external
A multitude of currents, voltages and the
wiring (block, reset, trigger, for example).
measured temperature are monitored to aid
operation of the protected line. This function is Via non-storable continuous signals, monostable
not intended to be used for protection purposes! trigger signals and bistable stored setting/resetting
signals, the Boolean equations can be controlled
E.g. for the 3-phase currents, the phase-to-ground
externally via any of the devices interfaces.
voltages and the phase-to-phase voltages the
highest and the lowest value is determined. Measured data input and output
These are evaluated using an operate value and
There are optionally a 20 mA input and two
time delay set by the user. Thereby, these currents
20 mA outputs available for the acquisition of
and voltages can be monitored for exceeding an
external measured variables and for the output
upper limit or falling below a lower limit.
of measured variables. A settable scaling allows
Deviation-time integral a straightforward adaptation of the measuring
range of the input variable or output variables
The filtering of the measured values via the
(for example 0 to 10 mA, 4 to 20 mA).
deviation-time integral is used for diminution of the
required band width on the serial communication There is optionally an input for a resistance
interfaces. In this operation the difference between thermometer (PT100) available for a direct
the last measured value transmitted and the temperature acquisition.
updated measured value (new-old-comparison) GLOBAL FUNCTIONS
is controlled and is added to a cumulated value
(integral). If the amount of the difference or the Functions operating globally allow the adaptation
amount of the integral exceed the set threshold, of the device s interfaces to the power system,
the updated measured value is transmitted. offer support during commissioning and testing
and provide continuously updated information on
Arithmetic-mean value acquisition the operation, as well as valuable analysis results
Arithmetic-mean values could be evaluated on following events in the system.
the RMS values, peak values and complex values Clock synchronization
of currents and voltages as well as on active and
reactive power and frequency. In conjunction with MiCOM C434 incorporates an internal clock with
the long-term recording the arithmeticmean value a resolution of 1 ms. All events are time-tagged
acquisition provides archive functionality. based on this clock, entered in the recording
memory appropriate to their significance and
Programmable logic signaled via the communication interface.
The efficient user-configurable logic enables Alternatively two synchronisation methods can
the user to set up logic operations on binary be used according to the configuration of MiCOM
signals within a framework of Boolean equations. C434: using one of the protocols IEC 60870-5-
By means of a straightforward configuration 103, IEC 60870-5-101, MODBUS, DNP3.0, the
procedure, any of the signals of the protection device will be synchronized by a time telegram
device can be linked by logic OR or AND from a higher-level substation control system or
operations with the possibility of additional in any other case it will be synchronized using the
negation operations. IRIG-B signal input.
The output signal of an equation can be fed into
The internal clock will then be adjusted
a further, higher ordinal number equation as an
accordingly and operate with an accuracy of
input signal thus leading to a set of interlinked
10 ms if synchronized via protocol and 1
Boolean equations.
ms if synchronized via IRIG-B signal.
The output signal of each equation is fed to a separate
timer stage with two timer elements and a choice
of operating modes, which offers the possibility of
assigning a freely configurable time characteristic to
the output signal of each Boolean equation. MiCOM C434 offers a multitude
The two output signals of each equation can be of control and monitoring functions
internally fed back into any available input function.
05
Multifunction IEDs MiCOM C434

Operating data recording Local control and display


For the continuous recording of processes All data required for operation of the device are
in system operation as well as of events, entered from the integrated local control panel,
a non-volatile memory is provided the data important for system management are
(cyclic buffer). The relevant signals, each read out and the local control of switching devices
fully tagged with date and time at signal start is realized (for the graphics display only).
and signal end, are entered in chronological
With the help of the display panels, the user is
order. Included are control actions such as the
able to carry out a quick and up-to-date check of
enabling or disabling of functions as well as
the state of the bay.
local control triggering for testing and resetting.
On the bay panel the selected bay is displayed as
Long-term recording
a single-pole equivalent network with the updated
While long-term recording is in progress, the switchgear states, as well as ancillary information
sampled values of analog input variables or such as the position of the remote/local switch or
measured operating data and signals the operating state of the interlock functions.
(time-tagged) are recorded. The recording
period can be adjusted via the size of the Selected measured values are displayed on the
sampling interval. measured value panels.
For the transmission of the long-term recording, Up to 28 state signals are displayed on the signal
the user may select the triggered mode or the panels which are automatically enabled when the
cyclic mode. state changes.
Moreover, different kinds of presentation can be
Self-monitoring
selected for the display of states and state changes.
Comprehensive self-monitoring procedures within The event panel displays events like the opening
the devices ensure that faulty condition is detected of a switchgear unit with timetagging.
and prevent malfunction of the MiCOM C434.
As the auxiliary voltage is turned on, a functional
test is carried out. Cyclic self-monitoring tests
are run during operation. If test results deviate
from the default value then the corresponding
signal is entered into the nonvolatile monitoring
signal memory. The result of the fault diagnosis
determines whether a blocking of the protection
device will occur or whether a warning only is
issued.

Selection of the bay

Definition of the interlocking conditions Creation of the bay with the bay type editor
06
Multifunction IEDs MiCOM C434

SWITCHGEAR CONTROL INFORMATION INTERFACE


The control of switching devices from the local Information is exchanged via the local
control panel is only possible if the version with control panel, the PC link, or two optional
graphics display has been chosen. In this case, communications interfaces.
switchgear units can be controlled via the Bay A communication interface is designed to conform
Panel provided that the unit has been set to local either to international standard IEC 61850, IEC
control. This setting may be selected either via 60870-5-103 or to IEC 60870-5-101, DNP 3.0,
the password-protected Local/Remote Key L/R MODBUS or Courier. Using this interface, the
or via an external switch. Once the intended MiCOM C434 can be integrated into a substation
switching device has been selected with the help control system or connected to a RTU.
of the Selection Key , the switching device
may then be controlled via the Close Key I or The second communication interface
Open Key O (per IEC 60870-5-103) is used as a parameter
setting interface in remote access.
Before the switching command is executed, the
interlock equations are tested. If the switching The MiCOM C434 can be set completely via the
command is permissible, it will be executed. If not, local control panel or the setting software MiCOM
an appropriate signal can be issued by an LED S1. This includes all setting parameters as well as
indicator. The switching command is not executed the selection of the bay type.
in this case. Pressing the Page Key results in The operating data logs and monitoring signal logs
leaving the display of the bayor the menu tree and as well as the measured operating values can be
switching to the panel display mode. The panel read out through the operating program. Control and
type being displayed is switched by pressing the test functions can be triggered by the program.
Page Key . From the Panel display, the user
can return to the menu tree display at any time by For the selection of the bay type, the C434 has
pressing the Enter Key. more than 280 pre-defined bay types, that contain
the configuration of the binary inputs and outputs
The control of bay units via external binary signal for the Switchgear Control, the bay interlocking as
inputs is possible for both the graphics display well as the setting for the selected communication
version and the text display version. This external protocol. The settings of these bay types can be
control may be configured as Local Control and/or individually adapted.
Remote Control.

Local control panel COMM1 IEC 61850


- Display of the switching states Interface to the substation control system
- Local control of the switching devices
- Access to all settings, signals and
measured values

MODEM MODEM

COMM2
Remote parameter setting
PC
Local interface

Information interfaces
07
Multifunction IEDs MiCOM C434

USER-SPECIFIC BAY TYPES


User-specific bay types with up to 8 bay diagrams The interlocking equations take the operating mode
are designed by the bay type editor BTC (plug-in with and without station interlock into account and
into MiCOM S1 S&R-103). support interlocking through ring feeders.
The configuration of the bay with the graphic After a successful syntax check and the
editor as user-friendly interface includes the assignment of the switching devices and
presentation on the local control panel, the interlocking equations, the upload of the bay
assignment of the binary signal inputs and the types takes place in MiCOM C434.
output relays as well as the definition of
Further documentation is given in the report data
the interlocking equations.
in XML or HTML format.

Bay Panel(s) Signal Panel(s) Measured Value Panel Event Panel


Protocol View
C434 Page H 17:58:34 Signals 17:58:44
Signals 17:58:44
C434 Page B 17:58:34 Signals 17:58:44
C434 Page A 17:58:34 Signals 17:58:44 Meas. values 17:58:44 Events 17:58:54 Oper/Rec/OP_RC
BB 1 MAIN : Voltage A-B prim. 20.04.98 Operat. Data Record.
BB2 M.C.B. trip V EXT 20.7 kV 05:21:32.331 LIMIT
PSS : Voltage B-C prim. Enabled
Q1 Q2 20.6 kV
PS 1 active Start
PSS : Voltage C-A prim. 20.04.98
Q0 PS 2 active 20.8 kV 23:58:17.501 MAIN
MAIN : Current A prim. CB closed sig. EXT
Bay interlock. act. 416 A End
Locked Q8 Current B prim. 21.04.98
MAIN : 415 A
Remote Subst. interl. act. 05:21:32.331 DEV01
Current C prim. Switch.device closed
1088 A 417 A Start
Curr. IP,max prim.

Gertetyp
Control and Display Panels

Settings Operation Events

Device ID Cyclic values Fault & Event counters


Config. parameters Control and testing Event meas. values
Function parameters Operating data rec. Event recordings

Global Operat. meas. values


Mainl functions Physical state signals
Parameter subset 1 Logical state signals
Parameter subset ... Menu Tree
Control

Display Panels and Menu Tree

Proven control, forward-looking


communication, complete local
control panel, only one setting file
08
Multifunction IEDs MiCOM C434

Device Track Record


CFE: Modular Bay Unit for Control and
Monitoring, Market introduction 1988

CFEC: Compact Bay Unit for Control and


Monitoring, Market introduction 1992

CF 202: Compact Bay Unit for Control and


Monitoring with extended function range,
Market introduction 1998

CF 242: Modular Bay Unit for Control and


Monitoring, Market introduction 1999

C232: Take-over and extension of the CF


202 in the MiCOM family since 2001

C434: Take-over and extension of the CF


242 in the MiCOM family since 2001.

2011 Schneider Electric - All rights reserved

Schneider Electric
35, rue Joseph Monier As standards, specifications and designs change from time to time, please ask for confirmation
CS 30323 of the information given in this publication.
92506 Rueil-Malmaison Cedex, France
Tel: +33 (0) 1 41 29 70 00 This document has been printed
on ecological paper
RCS Nanterre 954 503 439
Capital social 896 313 776 Publishing: Schneider Electric
www.schneider-electric.com Design: Schneider Electric
Printing:

NRJED111019EN 03-2011

Vous aimerez peut-être aussi