NT-Converter is an interface module for IG/IS-NT controllers. It allows to connect them into an existing
system consisting of IG/IS classic line controllers or to some third-party gen-set controllers
(Woodward, Barber-Colman, ...) via their analog Load Sharing lines. Connection via their CAN2 bus is
available from the 1.1 version of NT-Converter.
HW version Description
1.0 initial version
SW version Description
1.0 initial version
1.1 CAN extension
The module doesnt allow connect IM-NT controller into an other system !
The module doesnt support Power Management !
IG/IS-NT
COMC2
H2
L2
CAN2
LS
IG-NT IG-NT
Add. 5 Add. 4
CAN2 CAN2
Add. 32
Add. 32 Add. 32
Add. 32
LAN
NT- NT-
IG-IB
Converter Converter
Add.
Add. 55 Add. 4
Add. 4
LSM
CAN2
CAN2
CAN2 LSM CAN2 LSM CAN2 LSM
IG/IS-NT
COMC2
H2
L2
- Connect IG/IS-NT via its CAN2 bus interface (Intercontroller & monitoring).
- Extend the existing Load Sharing line among third-party controllers to NT-Converter terminals.
Use shielded wire. The shield can be connected to the appropriate terminal at NT-Converter
as well (if not connected to some other controller yet).
- Follow the documentation and/or terminal descriptions of the existing controllers to determine
which of the two Load Sharing line wires is positive and connect this one to LSM+ terminal at
NT-Converter.
- Select the appropriate NT-Converter mode according to the table below.
Jumper Meaning
MODE 1-5 Analog Load Sharing line mode selection
CAN R Terminating CAN resistors 120W
BOOT Switches to boot mode which allows
optional firmware upgrade
Hint:
All MODE jumpers are OPEN by default. This means ComAp mode is selected.
CAN R jumper is CLOSED by default at IG/IS-NT CAN bus side and OPEN at IG/IS classic side.
Operating conditions
Operating temperature -40 +70 C
Storage temperature -40 +80 C
Humidity 85% without condensation
Protection IP20
Standard conformity
Analog output
Load sharing output 5 / 10 V DC, impedance 10-50kW