SKM Air Cooled Condensing Units

ACUV-D Series - R-134a


R-134a

ACUV-D Series
Air Cooled Condesing Units

Range 8 TR to 142 TR
(27 kW to 501 kW)

Sharjah Economic Excellence

facebook.com/skmaircon
www.skmaircon.com @skmaircon
Award winner

1
SKM Air Cooled Condensing Units
ACUV-D Series - R-134a

Contents
Legend ............................................ 2 Selection Procedure ...................... 16
Nomenclature .................................. 2 Field Connections .......................... 17 Introduction
Introduction ...................................... 2 Typical Wiring Diagram ................. 18
General Features ............................ 3 Electrical Data ............................... 19
Component Features ....................... 3 SKM ACUV-D series Air cooled condensing unit
Dimensional Data .......................... 24
Control Panel ................................... 4 Loading Points ............................... 27 are designed for the use on systems with indoor
Unit Controller ................................. 4 Location & Space Requirements ... 29 units connected to remote condensing units
Optional Features ............................ 5 Unit Installation .............................. 29 located outside either on ground or on roof level.
Engineering Specifications ............... 7 Typical Refrigerant Piping ............. 31
Capacity Ratings ............................. 11 Recommended Line Sizes ............ 32
Compressor Starting ...................... 15 SKM ACUV-D units are manufactured to meet
Guide Specification ....................... 34
Capacity Control Steps ................... 16 the requirements of the gulf severe climatic
conditions.

The ACUV-D Air Cooled Condensing unit are


Legend ideal for warehouses, large halls, schools,
mosques, or wherever the requirement calls for a
The following abbreviations are used throughout this manual:
heavy duty unit with a semi-hermetic compressor.

BPF........... By-pass Factor MBh..........BTUH x 1000 ACUV-D series Air cooled condensing unit
cfm............ cubic feet per minute Ph............ Phase
( semi-hermetic reciprocating ) are available in
EER.......... Energy Efficiency Ratio Pa.............Pascals
50 models covering nominal capacity ranges
PD.......... .Pressure Drop
Hz............. Hertz from 8 TR - 142 TR (27 kW to 501 kW) in 50Hz
PI............ Power Input
inwg.......... inches of water gauge RPM........Revolutions per Minute and 60Hz.
kW............ kilowatts TR.......... Tons of Refrigeration
kg............. kilogram = 12 MBh ACUV-D Air Cooled Condensing unit are rated
lbs............ pounds weight (British units) V............. Volt in accordance with AHRI-365.
L/S........... liters per second
ACUV-D series provide efficient operation, wide
range of design flexibility coupled with packaged
concept requiring least on-site work.
Nomenclature
ACUV-D series Air Cooled Condensing units are
ACU V - 5 1 008 D Y
used for commercial and industrial applications
where high efficient condensing units are needed
Air cooled
Power Supply Code to match an indoor central station AHUs or coils
Condensing Unit
Y: 380V-415V/3Ph/50Hz to get maximum performance advantages of split
P: 440V/3Ph/50Hz
V-Shape Condenser sytem with reasonable initial cost.
R: 380V/3Ph/60Hz
Construction
E: 460V/3Ph/60Hz
T: 220V/3Ph/60Hz SKM provides qualified service and stock
Power Supply 5 : 50Hz
Frequency 6 : 60Hz of replacement parts in all major cities of the
Semi hermetic
Reciprocating Compressor
G.C.C. countries, Egypt, Jordan, and Pakistan.
No. of Refrigerant Circuits (R-134a) See back cover for details or call SKM.
Nominal Capacity (TR)

SKM Air Conditioning LLC

SKM reserves the right to change, in part or in


whole the specifications of its Air Conditioning
Equipment at any time in order to add the latest
technology. Therefore, the enclosed information
may change without any prior notice.
You name it.....We cool it

2
SKM Air Cooled Condensing Units
ACUV-D Series - R-134a
General Features Condensers
The ACUV-D series is a modern, diversified and environment Condenser coils are manufactured of seamless copper tubes
friendly series of air cooled condensing unit which uses R-134a mechanically bonded to aluminum fins to ensure optimum heat
as a refrigerant. transfer.

The complete ACUV-D condensing unit provides an extremely


rugged, heavy duty, long-life and energy efficient that will
provide higher efficiency over a long and extended life. What
makes ACUV-D series the pride of SKM products is the use of:

Semi Hermetic Reciprocating, heavy duty, energy efficient


compressors.
Totally enclosed, Class F insulated, IP55 protected condenser
fan motor.
Heavy duty condenser optimised in design for long-life
maintenance free operation.
Condenser Coil
Cabinet construction specifically designed for Gulf climates.
All coils are tested against leakage by air pressure of 450 psig
IP 54 Electrical panel. (3100 kPa) under water. All standard coils are 2,3 or 4 rows/
Factory installed, advanced and user friendly microprocessor 14 FPI, 3/8 (9.5 mm) O.D. tubes. An integral subcooling circuit
based control system. is provided to increase the cooling capacity, without additional
operating cost.
Interface capability with major BMS protocols (option).
For different application requirements, other optional condenser
The SKM ACUV-D series air cooled condensing units are durable, fin materials are available:
dependable, strong, reliable, versatile, quiet and energy efficient.
Wherever a heavy duty condensing unit is required, the ACUV-D Copper fins.
series should be an automatic choice.
Electrotinned Copper fins.
Copper finned coils with electro-tinned after manufacturing.
Precoated Aluminum fins.
Component Features The pre-coated is hydrophobic polyurethane resin. This
option provides substantial corrosion protection beyond
Compressor standard coil construction.
Aeris Guard Coil coating.
Compressors used in ACUV-D series are fully accessible,
The Aeris Guard Coil is a self etching high performance
semi-hermetic, reciprocating type. They are equipped with an
modified epoxy finish that is specifically designed to coat
oil sight glass, suction and discharge service valves and
and protect Aluminum and Copper surfaces. In addition,
crankcase heater. All compressors are refrigerant gas cooled
the coating is ideal for the protection of ferrous and non
and equipped with an oil pressure lubrication system. The oil
ferrous materials.
pump working in either direction is protected by an oil screen
and a valve provided for the fitting of an oil pressure gauge.
SKM ACUV-D series, all models, are restricted to a 14 FPI (1.8
mm) fin spacing condenser coil. Gulf dust storms and the general
For protection, all compressors are equipped with preset internal
level of available maintenance in Gulf countries ensures this
relief valve between suction and discharge sides.
condenser coil design shall provide long life and maintenance-free
operation with the least possibility of operational blockage on
The compressors are provided with vibration isolator springs
the condenser. Ample condenser surface and sensible air flow
underneath and therefore, external to ACUV-D series, AVMs
across the condenser ensures a low temperature differential
may be necessary only for critical applications.
between condensing temperature and the high Gulf ambients
making the ACUV-D condensing unit perform efficiently and
The compressor motors have inherent thermal protection. This
durably.
is in addition to other standard safety and protection controls.
Compressors conform to EN 12900 standards.

3
SKM Air Cooled Condensing Units
ACUV-D Series - R-134a
Condenser Fans Refrigerant Pipe work
Condenser fans are propeller type, aluminium alloy blades, SKM ACUV-D series Condensing units are provided with
directly driven by electric motors. Motors are Totally Enclosed all internal piping, using ACR grade copper tubing, between
Air Over (TEAO) six pole with class F insulation and minimum compressor and condenser.
IP55 protection.The TEAO and class F insulation features ensure
long life and are unique for SKM. Loose supplied liquid line refrigerant controls are available as an
option for field installation (Please specify CRSP). When this
The motors are factory wired, option is ordered, the unit will be supplied with a correctly sized
using wires specially selected thermostatic expansion valve, liquid line solenoid valve, liquid
for high ambients operation, line sight glass/moisture indicator and filter drier having flared
to unit control panel where the or soldered ends isolatable with one shut-off valve.
motor contactors are located
Shut-off valve for the other side of the filter drier can be supplied,
to control the operation of
if option CXFV is specified.
these motors.
Whether or not, these options are include, installation of solenoid
The condenser fans are valve in the liquid line near the evaporator is mandatory for proper
individually statically and operation of the unit since the unit will switch off only after a pump
dynamically balanced at the down cycle. Solenoid valve is to interlocked with controller as
factory. per terminals in the wiring diagram.
Condenser Fan Motor
Complete fan assembly is provided with suitable acrylic coated
fan guard. Control Panel
The unit mounted control panel enclosure is fabricated out of heavy
Casing/Structure gauge sheet steel in phosphatized powder coated baked finish.
The enclosure conforms to IP54 as per guidelines in IEC 529.
Designed for ease of handling and low cost to install. The
ACUV-D Air cooled condensing Units are factory assembled and A hinged access door and key-fastener is provided for easy access
mounted on a rigid base. The casing used in ACUV -D condensing and security. The panel is factory wired in accordance with NEC
units is made of zinc coated galvanized steel sheets conforming 430 & 440, labelled, tagged and features 220V / 240V controls.
to JIS-G3302 and ASTM A653 which is phosphatized then baked
after an electrostatic powder coat of approximately 60 microns. Compressors are with DOL or part winding starting,
depending on model .
This finish and coating passed a 1000 hours in 5 % salt spray Individual compressor & condenser fan motor contactors.
testing at 95F (35C) and 95% relative humidity as per ASTM Motor protector circuit breaker for condenser fan motors.
B117. Control circuit breaker.
Unit on/off Switch.
The entire assembly comes complete with lifting holes on the Microprocessor control boards.
base frame for rigging and installation. Access panels are Control Relays.
provided for easy service and maintainance Power and control terminal blocks.

Options available include hot dipped galvanized base frame


and structural members aluminium/stainless steel panels on Microprocessor Controller
request, as an option.

Refrigerant Charge
Condensing units are shipped with nitrogen holding charge only.
Microprocessor Controller

Piping connections All ACUV-D series condensing units are equipped with a full
function microprocessor based controller as a standard feature.
ACUV-D Air Cooled Condensing units piping connections come, The controller is factory programmed for the control of AHU fan
as standard, terminated with sealed and soldered copper pipe motor, compressors and condenser fans. The controller comes
ends. with a built in keypad and display for simple but meaningful man
machine interface.
Normal installation would require the cutting off (using roller-type
tube cutters) of the ends prior to connections being resoldered This controller provides complete operational control for the unit
and connected to the field supplied refrigerant pipework. and has built-in auto diagnostic capability that can signal normal
operation or alarm conditions as well as shutting down the unit
or system if necessary.

4
SKM Air Cooled Condensing Units
ACUV-D Series - R-134a
Low suction pressure.
High discharge pressure.
High compressor motor temperature. (For compressors
with electronic module).
Compressor short cycling.

Room Unit BMS Connectivity (Optional)


The controller comes with a loose supplied sleek and elegant Volt free contacts for run status, common fault status, auto
design room unit for installing in the conditioned space. mode status and provision for remote on/off shall be provided
Communication between unit controller and room unit is through as option if required.
two wire interface. The communication cable should be 2 In addition, the ACUV-D microprocessor can support the
core, twisted pair, unscreened with stranded conductors
major BMS protocols such as BACnet, Modbus & LON. Extra
(as per KNX specification) . Maximum distance between room
hardware may be required depending on the protocol.
unit and controller can be 700 meters. The room unit has a built
in sensor for measuring the room temperature. It transmits room
temperature, set point, unit operating mode, operating schedule
etc. to the unit controller. Control of the compressors is based on Optional Features
room temperature and the set point, as standard. If unit control
needs to be based on duct temperature, please specify during Alternative Condenser Material
time of order. Made of copper tubes and alternative fin material and/or protective
coating.
The Main Features of the controller are as follows: For Pre Coated aluminum fins, specify (FAP).
Built in LCD display with back light. For Aluminum Fins with Aeris Post Coat Protection, specify
Roll & push knob and 3 function buttons. (FAA).
Battery backed up built in real time clock. For Copper Fins, specify (FC).
Multiple authorization level to provide tight security for the For Copper Fins with Aeris Post Coat Protection,specify
control system. (FCA).
Capacity control based on room temperature or return air For electrotinned Copper Fins only, specify (CFT).
temperature. For Copper Finned Coils electrotinned post manufacturing,
Alarm history. specify (FCT).
A sleek & elegant design room unit.
Condenser Coil Guard (CGP)
Display Information Galvanized wire mesh guaid with painted finish for condenser
Coil.Recommended on ground level installations where coil
SKM ACUV-D series condensing units offer LCD display which needs to be protected against vandalism.
allows the operator to access different parameters of the unit.
Operator can view and change the unit parameters. The display Galvanized Frame And Base (GFB)
information includes: Steel frame and base which are hot dip galvanized
Status. after manufacturing process. This is recommended for highly
Outputs. corrosive environments.
Inputs. Pressure Gauges (SDG)
Alarms. Suction and discharge and oil pressure indication of each
Set points. refrigerant circuit. Gauges are mounted outside the Control Panel
Password.
Low noise Fan and motor assembly (LNF)
System Control Philosophy Can be provided for applications where minimal unit sound is
required.
Unit maybe enabled or disabled through the on/off switch in
the unit control panel. Control is based on room temperature Pressure Relief Valve (PRV)
sensed by room unit. Compressors will be staged based on the
To protect the unit from being over-pressurized.
set point and actual. room temperature. On an increase in room
temperature, cooling stages will be added and on a decrease in Marine Paint (MP)
room temperature, cooling stages will be removed from the system. To provide increased corrosion resistance coastal environments
and offshore locations.
System Protection Condenser Fans with polyglycoat coating (PGF)
The intelligent microprocessor based controller monitors To provide protection against corrosion for condenser fans.
all the safeties related to the unit and makes the necessary
protections, by shutting down the entire unit or the effected Capacity Control Steps (CRS1)
circuit. The protection includes: To provide additional capacity steps on the units. See Table 6
(Page 16) for optional steps available.

5
SKM Air Cooled Condensing Units
ACUV-D Series - R-134a
Isolated Condenser Fan Motors (CMS) Soft Starter (SFS)
For elimination of extraneous noise and vibration from condenser To reduce the starting current of compressors using reduced
fan motor, the motors are individually isolated from the frame. voltage starting method. Compressors will be started using
electronic solid state soft starters that will ramp up the speed of
Hot Gas Bypass System (GBP) the compressors to rated speed within few seconds thus reducing
With solenoid valve to enable operation of a large sized unit at low the mechanical & electrical stresses .
loads, like during low ambients due to application requirements.
(Highly recommended for 100% fresh air application). Suction Pressure read out Capability (SPC)
Additional transducer in suction line to display suction pressure
IP-55 Control Panel (ICP) in microprocessor.
Control Panel for special applications to meet IP 55 requirements.
BMS Interface Volt free Contacts (BMVF)
Manual Reset Type High Pressure Switch (MHP) Volt free contacts for run status, common fault status, auto mode
To replace standard auto reset, capsule type pressure switch. status and provision for remote on/off shall be provided as option
if required. For additional requirements, please contact SKM.
Low Ambient Operation Kit (LAO)
For unit operation down to lower than normal gulf ambient. Please BMS Interface thru protocol (BMSP)
specify during the time of order. For interfacing the units with major BMS protocols such as
BACNet, Modbus or LON. Extra hardware may be required
High Ambient Operation kit (HAO) depending on the protocol.
For operation at ambient temperature between 125F (52C)
and 131F (55C) maximum.
Condenser Fan motors with anti-condensation
heaters built-in (CFMA)
Main Isolator (Without door interlock) (ISO) Where application so requires.
For main power isolation. (consult SKM) Ammeter & Phase Selector switch (AMPC)
Control Transformer (CXT) To indicate running AMPS of each compressor.
This option is necessary and available for ACUV-D models Ammeter & Phase Selector switch (AMPI)
rated for 440V/3PH/50Hz or 460V/3PH/60Hz or power To indicate running AMPS on main incomer of the unit.
supplies without neutral. (When ordering for these voltages,
this option must be ordered). Voltmeter & Selector Switch (VSS)
For incoming line voltage.
Voltage Monitoring Module (VMM)
UL 1995 (UL-LISTED)
To prevent ACUV-D unit operation in the event of Phase
loss, Phase reversal, and Under / Over voltage on the incoming Unit construction are certified and in compliance of UL 1995
line voltage. safety standards. Consult SKM for availability of selected models .

Voltage Monitoring Module as per DEWA (DVM) Options for Field Installations
Under voltage relay as per DEWA regulations. This option is
available for Dubai, UAE only. Anti-vibration mounts (CAVM)
Recommended for roof mounted units or other locations in
Part Winding Start (PWS) the vicinity of occupied spaces, where noise/vibration may be
Where specifically required by local codes, compressors may objectionable.
be with Part Winding Start to reduce the high inrush current at Hi-Lo Gauges (CSDG)
starting.Some of the compressors are with part winding start as
Without piping or isolating pet cocks.
standard. Refer to page 15 for more details.
Liquid Line Controls (CRSP)
Unload Start Kit (USK) Comprises of correctly sized thermostatic expansion valve,
This option is required when the compressor needs a high starting suitable solenoid valve,filter drier,sight glass and one number
torque such as when the load is high. shut-off per circuit
Star Delta Starter (SDS) Extra Shut Off Valve (CXFV)
To reduce the starting current of compressors using reduced Extra Shut off valve in liquid line to fully isolate the filter drier.
voltage starting method. Compressors will be started in Star &
after few seconds it will be changed over to Delta. Duct Temperature Sensor (DTS)
In order to control the unit based on return / supply air duct
Circuit Breaker for Compressor (CBC) temperature.
For those electrical specification calls for additional over load Special custom built units incorporating specially required features
and short circuit protection. like units with anti-condensation resistance heaters embedded
in condenser motors and for off-shore application, special units
External Overload Protection (EOP) with stainless steel panels can be manufactured as per customer
For those electrical specification which require additional overload requirement.
protection for the compressors.
Contact SKM for all such applications or requirements.

6
SKM Air Cooled Condensing Units
ACUV-D Series - R-134a
ENGINEERING SPECIFICATIONS - 50 HZ
Model ACUV 51008-D 51010-D 51014-D 52015-D 52017-D 52019-D 51021-D 51022-D
BTUH 92000 106000 166000 180000 190000 210000 240000 270000
Cooling Capacity (1)
W 26964 31067 48652 52755 55686 61547 70340 79132
BTUH 78000 90000 142000 152000 160000 176000 206000 232000
Cooling Capacity (2)
W 22860 26377 41618 44549 46893 51583 60375 67995
Type - Semi-Hermetic Reciprocating 1450 RPM
Quantity - 1 1 1 2 2 2 1 1
Compressor
Oil Charge(Polyol Ester) US Gal 0.69 0.69 1.19 0.69/0.69 0.69/0.69 0.69/0.69 1.25 1.25
per Crkt (1/2/3/4) Liter 2.61 2.61 4.5 2.61/2.61 2.61/2.61 2.61/2.61 4.73 4.73
Type - Air cooled 2 & 3 or 4 rows 14 FPI (1.8 mm) fin spacing Cu tubes Al fins
Condenser Coil ft 19.4 19.4 24.4 24.4 24.4 29.3 31.5 31.5
Face Area
m 1.8 1.8 2.3 2.3 2.3 2.7 2.9 2.9
Type - Propeller direct drive 960 RPM
Code / Quantity - 628/2 628/2 723/2 723/2 723/2 823/2 823/2 823/2
Condenser Fan
cfm 9240 8920 13240 13240 13240 17880 18180 18180
Air Flow Rate
l/s 4361 4210 6248 6248 6248 8438 8580 8580
Type - Totally enclosed, air over Class F insulation, 6-pole, IP-55
Condenser Motor
Size / Quantity kW 0.37/2 0.37/2 0.75/2 0.75/2 0.75/2 1.5/2 1.5/2 1.5/2
Refrigerant (R - 134a) Operating Charge per Circuit lbs 9.5 14.1 18.5 9.3/9.3 12.1/8.8 11/11 24.3 25.6
(1/2/3/4) (3) kg 4.3 6.4 8.4 4.2/4.2 5.5/4 5/5 11 11.6
Number of Refrigerant Circuits - 1 1 1 2 2 2 1 1
lbs 878 915 1185 1362 1384 1467 1349 1367
Unit Operating Weight
kg 398 415 538 618 628 666 612 620

Model ACUV 52022-D 51028-D 52028-D 52030-D 51030-D 52034-D 52040-D 52045-D
BTUH 260000 328000 326000 340000 368000 400000 465000 540000
Cooling Capacity (1)
W 76202 96131 95545 99648 107855 117233 136284 158265
BTUH 222000 278000 278000 288000 314000 342000 400000 465000
Cooling Capacity (2)
W 65064 81477 81477 84408 92028 100234 117233 136284
Type - Semi-Hermetic Reciprocating 1450 RPM
Quantity - 2 1 2 2 1 2 2 2
Compressor
Oil Charge(Polyol Ester) US Gal 1.19/0.69 1.25 1.19/1.19 1.25/0.69 1.32 1.25/1.19 1.25/1.19 1.25/1.25
per Crkt (1/2/3/4) Liter 4.5/2.61 4.73 4.5/4.5 4.73/2.61 5 4.73/4.5 4.73/4.5 4.73/4.73
Type - Air cooled 2 & 3 or 4 rows 14 FPI (1.8 mm) fin spacing Cu tubes Al fins
Condenser Coil ft 31.5 40.0 40.0 40.0 40.0 53.3 53.3 64.0
Face Area
m 2.9 3.7 3.7 3.7 3.7 5.0 5.0 5.9
Type - Propeller direct drive 960 RPM
Code / Qty. - 823/2 823/3 823/3 823/3 823/3 823/3 829/3 823/4
Condenser Fan
cfm 18180 26160 26160 26160 26160 27900 32040 36480
Air Flow Rate
l/s 8580 12345 12345 12345 12345 13167 15120 17216
Type - Totally enclosed, air over Class F insulation, 6-pole, IP-55
Condenser Motor
Size / Qty. kW 1.5/2 1.5/3 1.5/3 1.5/3 1.5/3 1.5/3 1.5/3 1.5/4
Refrigerant (R - 134a) Operating Charge per Circuit lbs 15.7/11 31.5 14.7/14.7 22.1/11 31.5 24.7/16.8 20.4/20.4 24.4/24.4
(1/2/3/4) (3) kg 7.1/5 14.3 6.7/6.7 10/5 14.3 11.2/7.6 9.3/9.3 11.1/11.1
Number of Refrigerant Circuits - 2 1 2 2 1 2 2 2
lbs 1625 1745 2118 2069 2000 2418 2488 2984
Unit Operating Weight
kg 737 791 961 938 907 1096 1128 1353
Table 1

Notes:

1. Cooling capacity at 95F (35C) ambient temperature according to AHRI-365.


2. Cooling capacity at Gulf conditions : 115F (46.1C) condenser entering air temperature & 45F (7.2C) SST.
3. Operating charge is approximate for condensing unit only and does not include refrigerant lines and evaporator coil.
4. Condensing units are shipped with nitrogen holding charge only.

7
SKM Air Cooled Condensing Units
ACUV-D Series - R-134a
ENGINEERING SPECIFICATIONS - 50 HZ
M o de l ACUV 52049-D 52053-D 52058-D 52060-D 53064-D 53068-D 53070-D
BTUH 590000 635000 690000 730000 755000 815000 855000
Cooling Capacity (1)
W 172919 186108 202227 213951 221278 238863 250586
BTUH 500000 540000 590000 620000 645000 700000 730000
Cooling Capacity (2)
W 146542 158265 172919 181712 189039 205158 213951
Type - Semi-Hermetic Reciprocating 1450 RPM
Quantity - 2 2 2 2 3 3 3
Compressor
Oil Charge(Polyol Ester) US Gal 1.25/1.25 1.25/1.25 1.32/1.25 1.32/1.32 1.25/1.25/1.25 1.25/1.25/1.25 1.25/1.25/1.25
per Crkt (1/2/3/4) Liter 4.73/4.73 4.73/4.73 5/4.73 5/5 4.73/4.73/4.73 4.73/4.73/4.73 4.73/4.73/4.73
Type - Air cooled 2 & 3 or 4 rows 14 FPI (1.8 mm) fin spacing Cu tubes Al fins
Condenser Coil ft 72.0 72.0 72.0 72.0 97.5 97.5 97.5
Face Area
m 6.7 6.7 6.7 6.7 9.1 9.1 9.1
Type - Propeller direct drive 960 RPM
Code / Quantity - 823/4 829/4 829/4 829/4 823/6 823/6 823/6
Condenser Fan
cfm 37280 42880 40920 40920 54900 54900 54900
Air Flow Rate
l/s 17593 20236 19311 19311 25908 25908 25908
Type - Totally enclosed, air over Class F insulation, 6-pole, IP-55
Condenser Motor
Size / Quantity kW 1.5/4 1.5/4 1.5/4 1.5/4 1.5/6 1.5/6 1.5/6
Refrigerant (R - 134a) Operating Charge per Circuit lbs 30.4/24.5 26/26 38.1/31.5 33.2/33.2 27.1/27.1/27.1 28.5/28.5/28.5 28.5/28.5/28.5
(1/2/3/4) (3) kg 13.8/11.1 11.8/11.8 17.3/14.3 15.1/15.1 12.3/12.3/12.3 12.9/12.9/12.9 12.9/12.9/12.9
Number of Refrigerant Circuits - 2 2 2 2 3 3 3
lbs 3067 3063 3574 3816 5474 5506 5748
Unit Operating Weight
kg 1391 1389 1621 1731 2483 2497 2607

Model ACUV 53080-D 53084-D 53086-D 54095-D 54106-D 54114-D 54120-D


BTUH 965000 1005000 1045000 1180000 1285000 1365000 1440000
Cooling Capacity (1)
W 282825 294549 306272 345838 376612 400059 422040
BTUH 820000 855000 890000 1005000 1095000 1160000 1230000
Cooling Capacity (2)
W 240328 250586 260844 294549 320926 339977 360492
Type - Semi-Hermetic Reciprocating 1450 RPM
Quantity - 3 3 3 4 4 4 4
Compressor
Oil Charge(Polyol Ester) US Gal 1.25/1.25/1.25 1.32/1.25/1.25 1.32/1.32/1.25 1.25/1.25/1.25/1.25 1.25/1.25/1.25/1.25 1.32/1.32/1.25/1.25 1.32/1.32/1.32/1.32
per Crkt (1/2/3/4) Liter 4.73/4.73/4.73 5/4.73/4.73 5/5/4.73 4.73/4.73/4.73/4.73 4.73/4.73/4.73/4.73 5/5/4.73/4.73 5/5/5/5
Type - Air cooled 2 & 3 or 4 rows 14 FPI (1.8 mm) fin spacing Cu tubes Al fins
Condenser Coil ft 97.5 97.5 97.5 130.0 130.0 130.0 130.0
Face Area
m 9.1 9.1 9.1 12.1 12.1 12.1 12.1
Type - Propeller direct drive 960 RPM
Code / Qty. - 829/6 829/6 829/6 829/8 829/8 829/8 829/8
Condenser Fan
cfm 59340 59340 59340 83360 79120 79120 79120
Air Flow Rate
l/s 28004 28004 28004 39339 37338 37338 37338
Type - Totally enclosed, air over Class F insulation, 6-pole, IP-55
Condenser Motor
Size / Qty. kW 1.5/6 1.5/6 1.5/6 1.5/8 1.5/8 1.5/8 1.5/8
Refrigerant (R - 134a) Operating Charge per Circuit lbs 35.8/35.8/35.8 35.9/35.9/35.9 35.9/35.9/35.9 29.3/29.3/29.3/29.3 36.6/36.6/36.6/36.6 36.6/36.6/36.6/36.6 36.6/36.6/36.6/36.6
(1/2/3/4) (3) kg 16.2/16.2/16.2 16.3/16.3/16.3 16.3/16.3/16.3 13.3/13.3/13.3/13.3 16.6/16.6/16.6/16.6 16.6/16.6/16.6/16.6 16.6/16.6/16.6/16.6
Number of Refrigerant Circuits - 3 3 3 4 4 4 4
lbs 5970 6225 6479 6991 7282 7791 8299
Unit Operating Weight
kg 2707 2823 2938 3171 3303 3533 3764
Table 1 ends

Notes:

1. Cooling capacity at 95F (35C) ambient temperature according to AHRI-365.


2. Cooling capacity at Gulf conditions : 115F (46.1C) condenser entering air temperature & 45F (7.2C) SST.
3. Operating charge is approximate for condensing unit only and does not include refrigerant lines and evaporator coil.
4. Condensing units are shipped with nitrogen holding charge only.

8
SKM Air Cooled Condensing Units
ACUV-D Series - R-134a
ENGINEERING SPECIFICATIONS - 60 HZ
Model ACUV 61009-D 61011-D 61016-D 62018-D 62020-D 62022-D 61024-D 61026-D
BTUH 108000 126000 196000 212000 224000 248000 286000 320000
Cooling Capacity (1)
W 31653 36928 57444 62134 65651 72685 83822 93787
BTUH 92000 108000 168000 180000 190000 210000 244000 274000
Cooling Capacity (2)
W 26964 31653 49238 52755 55686 61547 71512 80305
Type - Semi-Hermetic Reciprocating 1750 RPM
Quantity - 1 1 1 2 2 2 1 1
Compressor
Oil Charge(Polyol Ester) US Gal 0.69 0.69 1.19 0.69/0.69 0.69/0.69 0.69/0.69 1.25 1.25
per Crkt (1/2/3/4) Liter 2.61 2.61 4.5 2.61/2.61 2.61/2.61 2.61/2.61 4.73 4.73
Type - Air cooled 2 & 3 or 4 rows 14 FPI (1.8 mm) fin spacing Cu tubes Al fins
Condenser Coil ft 19.4 19.4 24.4 24.4 24.4 29.3 31.5 31.5
Face Area
m 1.8 1.8 2.3 2.3 2.3 2.7 2.9 2.9
Type - Propeller direct drive 960 RPM
Code / Quantity - 628/2 628/2 723/2 723/2 723/2 823/2 823/2 823/2
Condenser Fan
cfm 11200 10820 15660 15660 15660 21760 22120 22120
Air Flow Rate
l/s 5286 5106 7390 7390 7390 10269 10439 10439
Type - Totally enclosed, air over Class F insulation, 6-pole, IP-55
Condenser Motor
Size / Quantity kW 0.55/2 0.55/2 1.1/2 1.1/2 1.1/2 2.2/2 2.2/2 2.2/2
Refrigerant (R - 134a) Operating Charge per Circuit lbs 9.5 14.3 18.7 9.4/9.4 12.1/8.8 11.1/11.1 25.8 26
(1/2/3/4) (3) kg 4.3 6.5 8.5 4.3/4.3 5.5/4 5/5 11.7 11.8
Number of Refrigerant Circuits - 1 1 1 2 2 2 1 1
lbs 884 923 1195 1372 1396 1495 1380 1387
Unit Operating Weight
kg 401 419 542 622 633 678 626 629

Model ACUV 62026-D 61032-D 62032-D 62034-D 61036-D 62040-D 62046-D 62052-D
BTUH 310000 388000 386000 400000 435000 475000 550000 640000
Cooling Capacity (1)
W 90856 113716 113130 117233 127491 139215 161196 187573
BTUH 262000 330000 330000 342000 370000 405000 470000 550000
Cooling Capacity (2)
W 76788 96717 96717 100234 108441 118699 137749 161196
Type - Semi-Hermetic Reciprocating 1750 RPM
Quantity - 2 1 2 2 1 2 2 2
Compressor
Oil Charge(Polyol Ester) US Gal 1.19/0.69 1.25 1.19/1.19 1.25/0.69 1.32 1.25/1.19 1.25/1.25 1.25/1.25
per Crkt (1/2/3/4) Liter 4.5/2.61 4.73 4.5/4.5 4.73/2.61 5 4.73/4.5 4.73/4.73 4.73/4.73
Type - Air cooled 2 & 3 or 4 rows 14 FPI (1.8 mm) fin spacing Cu tubes Al fins
Condenser Coil ft 31.5 40.0 40.0 40.0 40.0 53.3 53.3 64.0
Face Area
m 2.9 3.7 3.7 3.7 3.7 5.0 5.0 5.9
Type - Propeller direct drive 960 RPM
Code / Qty. - 823/2 823/3 823/3 823/3 823/3 823/3 829/3 823/4
Condenser Fan
cfm 22120 31860 31860 31860 31860 33990 38700 44400
Air Flow Rate
l/s 10439 15035 15035 15035 15035 16041 18263 20953
Type - Totally enclosed, air over Class F insulation, 6-pole, IP-55
Condenser Motor
Size / Qty. kW 2.2/2 2.2/3 2.2/3 2.2/3 2.2/3 2.2/3 2.2/3 2.2/4
Refrigerant (R - 134a) Operating Charge per Circuit lbs 15.7/11.1 31.9 16/16 23.2/11.9 31.9 26.9/16.8 21.8/21.8 24.4/24.4
(1/2/3/4) (3) kg 7.1/5 14.5 7.3/7.3 10.5/5.4 14.5 12.2/7.6 9.9/9.9 11.1/11.1
Number of Refrigerant Circuits - 2 1 2 2 1 2 2 2
lbs 1650 1780 2152 2110 2031 2457 2531 3032
Unit Operating Weight
kg 748 807 976 957 921 1114 1148 1375
Table 2

Notes:

1. Cooling capacity at 95F (35C) ambient temperature according to AHRI-365.


2. Cooling capacity at Gulf conditions : 115F (46.1C) condenser entering air temperature & 45F (7.2C) SST.
3. Operating charge is approximate for condensing unit only and does not include refrigerant lines and evaporator coil.
4. Condensing units are shipped with nitrogen holding charge only.

9
SKM Air Cooled Condensing Units
ACUV-D Series - R-134a
ENGINEERING SPECIFICATIONS - 60 HZ
Model ACUV 62058-D 62062-D 62067-D 62071-D 63074-D 63078-D 63082-D
BTUH 695000 750000 820000 865000 895000 965000 1010000
Cooling Capacity (1)
W 203693 219812 240328 253517 262309 282825 296014
BTUH 595000 635000 695000 735000 765000 830000 865000
Cooling Capacity (2)
W 174385 186108 203693 215416 224209 243259 253517
Type - Semi-Hermetic Reciprocating 1750 RPM
Quantity - 2 2 2 2 3 3 3
Compressor
Oil Charge(Polyol Ester) US Gal 1.25/1.25 1.25/1.25 1.32/1.25 1.32/1.32 1.25/1.25/1.25 1.25/1.25/1.25 1.25/1.25/1.25
per Crkt (1/2/3/4) Liter 4.73/4.73 4.73/4.73 5/4.73 5/5 4.73/4.73/4.73 4.73/4.73/4.73 4.73/4.73/4.73
Type - Air cooled 2 & 3 or 4 rows 14 FPI (1.8 mm) fin spacing Cu tubes Al fins
Condenser Coil ft 72.0 72.0 72.0 72.0 97.5 97.5 97.5
Face Area
m 6.7 6.7 6.7 6.7 9.1 9.1 9.1
Type - Propeller direct drive 960 RPM
Code / Quantity - 823/4 829/4 829/4 829/4 823/6 823/6 823/6
Condenser Fan
cfm 45400 51760 49560 49560 66840 66840 66840
Air Flow Rate
l/s 21425 24427 23388 23388 31543 31543 31543
Type - Totally enclosed, air over Class F insulation, 6-pole, IP-55
Condenser Motor
Size / Quantity kW 2.2/4 2.2/4 2.2/4 2.2/4 2.2/6 2.2/6 2.2/6
Refrigerant (R - 134a) Operating Charge per Circuit lbs 30.4/24.6 26.9/26.9 38.1/31.5 34/34 28.5/28.5/28.5 28.5/28.5/28.5 28.5/28.5/28.5
(1/2/3/4) (3) kg 13.8/11.2 12.2/12.2 17.3/14.3 15.4/15.4 12.9/12.9/12.9 12.9/12.9/12.9 12.9/12.9/12.9
Number of Refrigerant Circuits - 2 2 2 2 3 3 3
lbs 3113 3113 3619 3870 5555 5579 5821
Unit Operating Weight
kg 1412 1412 1641 1755 2519 2530 2640

Model ACUV 63094-D 63098-D 63100-D 64113-D 64124-D 64132-D 64140-D


BTUH 1145000 1190000 1235000 1395000 1525000 1620000 1705000
Cooling Capacity (1)
W 335580 348769 361958 408851 446952 474795 499707
BTUH 970000 1010000 1050000 1190000 1295000 1375000 1455000
Cooling Capacity (2)
W 284291 296014 307737 348769 379543 402989 426436
Type - Semi-Hermetic Reciprocating 1750 RPM
Quantity - 3 3 3 4 4 4 4
Compressor
Oil Charge(Polyol Ester) US Gal 1.25/1.25/1.25 1.32/1.25/1.25 1.32/1.32/1.25 1.25/1.25/1.25/1.25 1.25/1.25/1.25/1.25 1.32/1.32/1.25/1.25 1.32/1.32/1.32/1.32
per Crkt (1/2/3/4) Liter 4.73/4.73/4.73 5/4.73/4.73 5/5/4.73 4.73/4.73/4.73/4.73 4.73/4.73/4.73/4.73 5/5/4.73/4.73 5/5/5/5
Type - Air cooled 2 & 3 or 4 rows 14 FPI (1.8 mm) fin spacing Cu tubes Al fins
Condenser Coil ft 97.5 97.5 97.5 130.0 130.0 130.0 130.0
Face Area
m 9.1 9.1 9.1 12.1 12.1 12.1 12.1
Type - Propeller direct drive 960 RPM
Code / Qty. - 829/6 829/6 829/6 829/8 829/8 829/8 829/8
Condenser Fan
cfm 72000 72000 72000 100880 96000 96000 96000
Air Flow Rate
l/s 33978 33978 33978 47607 45304 45304 45304
Type - Totally enclosed, air over Class F insulation, 6-pole, IP-55
Condenser Motor
Size / Qty. kW 2.2/6 2.2/6 2.2/6 2.2/8 2.2/8 2.2/8 2.2/8
Refrigerant (R - 134a) Operating Charge per Circuit lbs 35.9/35.9/35.9 35.9/35.9/35.9 35.9/35.9/35.9 29.3/29.3/29.3/29.3 36.6/36.6/36.6/36.6 36.6/36.6/36.6/36.6 36.6/36.6/36.6/36.6
(1/2/3/4) (3) kg 16.3/16.3/16.3 16.3/16.3/16.3 16.3/16.3/16.3 13.3/13.3/13.3/13.3 16.6/16.6/16.6/16.6 16.6/16.6/16.6/16.6 16.6/16.6/16.6/16.6
Number of Refrigerant Circuits - 3 3 3 4 4 4 4
lbs 6043 6296 6548 7089 7380 7885 8389
Unit Operating Weight
kg 2741 2855 2970 3215 3347 3576 3805
Table 2 ends

Notes:

1. Cooling capacity at 95F (35C) ambient temperature according to AHRI-365.


2. Cooling capacity at Gulf conditions : 115F (46.1C) condenser entering air temperature & 45F (7.2C) SST.
3. Operating charge is approximate for condensing unit only and does not include refrigerant lines and evaporator coil.
4. Condensing units are shipped with nitrogen holding charge only.

10
SKM Air Cooled Condensing Units
ACUV-D Series - R-134a
CAPACITY RATINGS - 50 HZ
Condenser Entering Air Temperature F (C)
SST 95F (35C) 105F (40C) 115F (46C) 125 (52C)
Model
Total Capacity PI * Total Capacity PI * Total Capacity PI * Total Capacity PI *
ACUV
F C MBH kW kW MBH kW kW MBH kW kW MBH kW kW
35 1.7 74.6 21.9 6.1 68.8 20.2 6.4 63.0 18.5 6.7 57.2 16.8 7.0
40 4.4 83.2 24.4 6.4 76.8 22.5 6.8 70.5 20.7 7.1 64.3 18.8 7.5
51008-D
45 7.2 92.4 27.1 6.7 85.5 25.1 7.1 78.7 23.1 7.5 71.8 21.0 7.9
50 10.0 102.2 30.0 7.0 94.8 27.8 7.5 87.3 25.6 8.0 79.9 23.4 8.4
35 1.7 86.3 25.3 6.9 79.3 23.2 7.2 72.3 21.2 7.5 65.4 19.2 7.8
40 4.4 96.5 28.3 7.2 88.8 26.0 7.6 81.3 23.8 8.0 73.7 21.6 8.3
51010-D
45 7.2 107.4 31.5 7.6 99.1 29.0 8.0 90.9 26.6 8.4 82.6 24.2 8.8
50 10.0 119.0 34.9 7.9 110.1 32.3 8.4 101.2 29.7 8.9 92.3 27.0 9.3
35 1.7 135.5 39.7 10.9 125.3 36.7 11.5 115.1 33.7 12.0 104.9 30.7 12.6
40 4.4 150.4 44.1 11.4 139.3 40.8 12.1 128.3 37.6 12.7 117.2 34.3 13.4
51014-D
45 7.2 166.4 48.8 11.9 154.3 45.2 12.7 142.3 41.7 13.4 130.3 38.2 14.1
50 10.0 183.3 53.7 12.5 170.3 49.9 13.3 157.2 46.1 14.0 144.2 42.3 14.9
35 1.7 196.2 57.5 16.4 181.3 53.1 17.3 166.3 48.7 18.0 151.3 44.4 18.8
40 4.4 217.9 63.9 17.3 201.8 59.1 18.3 185.5 54.4 19.2 169.3 49.6 20.1
51021-D
45 7.2 241.1 70.7 18.2 223.6 65.5 19.3 206.0 60.4 20.3 188.5 55.3 21.4
50 10.0 265.8 77.9 19.1 246.9 72.4 20.3 227.9 66.8 21.5 209.1 61.3 22.7
35 1.7 222.5 65.2 20.0 206.3 60.5 21.0 189.9 55.7 21.9 173.7 50.9 22.9
40 4.4 246.3 72.2 21.1 228.6 67.0 22.2 210.9 61.8 23.2 193.4 56.7 24.4
51022-D
45 7.2 271.5 79.6 22.3 252.4 74.0 23.4 233.3 68.4 24.6 214.5 62.9 26.0
50 10.0 298.3 87.4 23.4 277.6 81.4 24.7 257.0 75.3 26.1 236.9 69.4 27.7
35 1.7 268.4 78.7 23.5 247.8 72.6 24.6 227.2 66.6 25.5 206.6 60.6 26.5
40 4.4 297.5 87.2 24.7 275.0 80.6 25.9 252.6 74.0 27.0 230.1 67.4 28.2
51028-D
45 7.2 328.5 96.3 25.9 304.0 89.1 27.2 279.6 81.9 28.4 255.0 74.8 29.8
50 10.0 361.2 105.9 27.3 334.7 98.1 28.6 308.1 90.3 30.0 281.5 82.5 31.5
35 1.7 302.4 88.6 29.6 279.3 81.9 30.6 256.2 75.1 31.6 233.1 68.3 32.7
40 4.4 334.7 98.1 31.4 309.7 90.8 32.6 284.7 83.4 33.8 259.7 76.1 35.1
51030-D
45 7.2 368.9 108.1 33.1 341.9 100.2 34.6 314.9 92.3 36.0 287.8 84.4 37.6
50 10.0 405.0 118.7 34.9 375.9 110.2 36.6 346.8 101.6 38.3 317.6 93.1 40.2
35 1.7 145.9 42.8 12.4 134.5 39.4 13.0 123.1 36.1 13.6 111.8 32.8 14.1
40 4.4 162.5 47.6 13.1 150.0 44.0 13.8 137.6 40.3 14.4 125.2 36.7 15.1
52015-D
45 7.2 180.1 52.8 13.8 166.6 48.8 14.5 153.2 44.9 15.3 139.7 40.9 16.1
50 10.0 198.9 58.3 14.4 184.3 54.0 15.3 169.8 49.8 16.2 155.1 45.5 17.2
35 1.7 154.6 45.3 13.3 142.2 41.7 13.9 129.8 38.1 14.4 117.5 34.4 15.0
40 4.4 172.1 50.5 14.1 158.6 46.5 14.8 145.2 42.6 15.4 131.7 38.6 16.1
52017-D
45 7.2 190.8 55.9 14.8 176.2 51.6 15.6 161.6 47.4 16.4 146.9 43.1 17.2
50 10.0 210.7 61.8 15.6 194.9 57.1 16.5 179.1 52.5 17.3 163.2 47.8 18.3
35 1.7 169.6 49.7 13.9 155.7 45.6 14.6 142.0 41.6 15.1 128.3 37.6 15.6
40 4.4 189.3 55.5 14.7 174.3 51.1 15.4 159.3 46.7 16.0 144.4 42.3 16.7
52019-D
45 7.2 210.4 61.7 15.4 194.1 56.9 16.2 177.9 52.2 17.0 161.7 47.4 17.8
50 10.0 233.0 68.3 16.1 215.4 63.1 17.1 197.8 58.0 18.0 180.2 52.8 18.9
35 1.7 213.4 62.6 18.2 196.7 57.7 19.1 180.0 52.8 19.9 163.3 47.9 20.7
40 4.4 236.9 69.4 19.2 218.8 64.1 20.2 200.6 58.8 21.1 182.5 53.5 22.1
52022-D
45 7.2 261.9 76.8 20.2 242.3 71.0 21.3 222.6 65.2 22.4 202.9 59.5 23.5
50 10.0 288.4 84.5 21.2 267.2 78.3 22.4 245.9 72.1 23.6 224.5 65.8 25.0
35 1.7 266.8 78.2 22.0 246.7 72.3 23.2 226.5 66.4 24.3 206.3 60.5 25.4
40 4.4 296.0 86.8 23.1 274.0 80.3 24.4 252.1 73.9 25.7 230.2 67.5 27.0
52028-D
45 7.2 327.0 95.8 24.2 303.1 88.9 25.7 279.4 81.9 27.1 255.5 74.9 28.5
50 10.0 359.8 105.5 25.4 334.0 97.9 26.9 308.3 90.4 28.5 282.5 82.8 30.1
35 1.7 277.0 81.2 23.6 255.5 74.9 24.7 233.8 68.5 25.7 212.2 62.2 26.8
40 4.4 307.9 90.2 24.9 284.5 83.4 26.2 261.0 76.5 27.4 237.5 69.6 28.7
52030-D
45 7.2 340.8 99.9 26.3 315.4 92.4 27.7 290.0 85.0 29.1 264.7 77.6 30.6
50 10.0 375.7 110.1 27.6 348.3 102.1 29.2 320.9 94.1 30.8 293.6 86.1 32.6
35 1.7 327.6 96.0 27.6 302.7 88.7 29.0 277.7 81.4 30.3 252.8 74.1 31.6
40 4.4 363.5 106.5 29.1 336.5 98.6 30.6 309.4 90.7 32.1 282.3 82.8 33.7
52034-D
45 7.2 401.8 117.8 30.5 372.5 109.2 32.3 343.1 100.6 34.0 313.9 92.0 35.8
50 10.0 442.3 129.6 32.0 410.7 120.4 34.0 379.0 111.1 35.9 347.5 101.8 38.0
35 1.7 383.3 112.3 33.4 353.9 103.7 35.0 324.4 95.1 36.5 295.0 86.5 38.1
40 4.4 425.0 124.6 35.3 393.1 115.2 37.1 361.2 105.9 38.9 329.4 96.5 40.8
52040-D
45 7.2 469.4 137.6 37.3 434.9 127.5 39.3 400.4 117.4 41.3 366.2 107.3 43.6
50 10.0 516.4 151.4 39.2 479.2 140.5 41.5 442.1 129.6 43.8 405.5 118.8 46.4
Table 3
Note:
* Power Input mentioned in these pages should not be used for Cable/Fuse selection.
MCA & MFA Values given in the electrical data (Pages 19 to 23) should be referred for the same.

Computer Print outs for matched ratings with SKM Air Handling Units are available.

11
SKM Air Cooled Condensing Units
ACUV-D Series - R-134a
CAPACITY RATINGS - 50 HZ
Condenser Entering Air Temperature F (C)
Model SST 95F (35C) 105F (40C) 115F (46C) 125 (52C)
ACUV Total Capacity PI * Total Capacity PI * Total Capacity PI * Total Capacity PI *
F C MBH kW kW MBH kW kW MBH kW kW MBH kW kW
35 1.7 445.7 130.6 39.9 413.2 121.1 41.9 380.4 111.5 43.8 347.9 102.0 45.8
40 4.4 493.3 144.6 42.2 458.0 134.2 44.4 422.5 123.8 46.5 387.4 113.6 48.8
52045-D
45 7.2 543.9 159.4 44.5 505.6 148.2 46.8 467.3 137.0 49.2 429.7 125.9 51.9
50 10.0 597.6 175.2 46.7 556.2 163.0 49.3 515.0 151.0 52.1 474.7 139.1 55.2
35 1.7 484.3 141.9 43.8 447.8 131.2 45.9 411.1 120.5 47.7 374.6 109.8 49.8
40 4.4 535.9 157.1 46.3 496.1 145.4 48.5 456.3 133.8 50.6 416.7 122.1 53.0
52049-D
45 7.2 590.6 173.1 48.7 547.5 160.5 51.1 504.3 147.8 53.5 461.5 135.3 56.3
50 10.0 648.4 190.1 51.2 601.8 176.4 53.9 555.1 162.7 56.6 508.9 149.2 59.7
35 1.7 523.6 153.5 47.7 483.1 141.6 49.7 442.6 129.7 51.6 402.1 117.8 53.7
40 4.4 579.3 169.8 50.3 535.2 156.9 52.5 491.1 143.9 54.6 446.8 131.0 57.1
52053-D
45 7.2 638.3 187.1 52.9 590.3 173.0 55.3 542.4 159.0 57.7 494.2 144.8 60.7
50 10.0 700.4 205.3 55.7 648.5 190.1 58.3 596.5 174.8 61.0 544.2 159.5 64.2
35 1.7 567.6 166.4 53.3 524.1 153.6 55.4 480.6 140.9 57.3 437.0 128.1 59.4
40 4.4 628.4 184.2 56.3 581.1 170.3 58.7 533.8 156.5 60.9 486.5 142.6 63.5
52058-D
45 7.2 692.8 203.0 59.3 641.5 188.0 62.0 590.3 173.0 64.6 539.0 158.0 67.7
50 10.0 760.8 223.0 62.4 705.4 206.8 65.4 650.1 190.5 68.5 594.5 174.3 71.9
35 1.7 600.7 176.1 59.4 554.7 162.6 61.4 508.8 149.1 63.4 462.8 135.6 65.6
40 4.4 664.5 194.8 63.0 614.8 180.2 65.4 565.0 165.6 67.8 515.2 151.0 70.5
52060-D
45 7.2 732.0 214.6 66.6 678.3 198.8 69.4 624.6 183.1 72.3 570.8 167.3 75.6
50 10.0 803.3 235.4 70.2 745.4 218.5 73.5 687.5 201.5 76.9 629.5 184.5 80.8
35 1.7 616.8 180.8 52.7 570.8 167.3 55.4 524.3 153.7 57.9 478.0 140.1 60.4
40 4.4 684.5 200.6 55.6 634.4 185.9 58.6 584.0 171.2 61.4 534.0 156.5 64.4
53064-D
45 7.2 756.5 221.7 58.5 702.3 205.8 61.9 647.8 189.9 65.1 593.9 174.1 68.6
50 10.0 833.2 244.2 61.4 774.5 227.0 65.1 715.8 209.8 68.8 657.9 192.8 72.9
35 1.7 669.5 196.2 59.8 620.7 181.9 62.8 571.5 167.5 65.6 522.7 153.2 68.6
40 4.4 741.1 217.2 63.2 688.1 201.7 66.5 634.8 186.1 69.6 582.2 170.6 73.1
53068-D
45 7.2 817.3 239.6 66.6 759.8 222.7 70.2 702.3 205.8 73.7 645.7 189.3 77.7
50 10.0 898.1 263.2 69.9 835.9 245.0 73.9 774.0 226.9 78.0 713.5 209.1 82.7
35 1.7 702.8 206.0 64.1 650.2 190.6 67.0 597.4 175.1 69.8 544.9 159.7 72.9
40 4.4 777.4 227.8 67.7 720.2 211.1 70.9 662.9 194.3 74.1 606.0 177.6 77.7
53070-D
45 7.2 856.5 251.0 71.3 794.4 232.9 74.8 732.5 214.7 78.4 671.1 196.7 82.7
50 10.0 940.1 275.5 75.0 873.0 255.9 78.9 806.2 236.3 83.1 740.2 216.9 87.9
35 1.7 792.1 232.2 71.2 731.0 214.3 74.3 670.0 196.4 77.2 608.8 178.4 80.2
40 4.4 877.0 257.0 74.9 810.4 237.5 78.4 743.8 218.0 81.6 677.1 198.4 85.2
53080-D
45 7.2 966.9 283.4 78.9 894.5 262.2 82.5 822.1 241.0 86.1 749.4 219.7 90.4
50 10.0 1061.9 311.2 82.9 983.4 288.2 86.9 904.8 265.2 90.9 826.0 242.1 95.6
35 1.7 825.5 242.0 77.3 761.9 223.3 80.4 698.4 204.7 83.3 634.8 186.1 86.4
40 4.4 913.4 267.7 81.7 844.3 247.5 85.1 775.2 227.2 88.4 706.0 206.9 92.3
53084-D
45 7.2 1006.5 295.0 86.1 931.5 273.0 89.9 856.6 251.1 93.8 781.4 229.0 98.3
50 10.0 1104.6 323.8 90.6 1023.6 300.0 94.9 942.5 276.2 99.3 861.2 252.4 104.4
35 1.7 858.3 251.6 83.5 792.3 232.2 86.5 726.3 212.9 89.4 660.2 193.5 92.6
40 4.4 949.1 278.2 88.4 877.6 257.2 91.9 806.0 236.2 95.4 734.3 215.2 99.3
53086-D
45 7.2 1045.2 306.3 93.4 967.8 283.7 97.4 890.4 261.0 101.5 812.7 238.2 106.3
50 10.0 1146.5 336.0 98.4 1063.0 311.6 103.0 979.4 287.1 107.8 895.6 262.5 113.3
35 1.7 969.5 284.1 87.6 896.4 262.7 91.7 823.1 241.3 95.4 750.1 219.8 99.5
40 4.4 1072.8 314.4 92.5 993.3 291.1 96.9 913.7 267.8 101.1 834.4 244.6 105.9
54095-D
45 7.2 1182.5 346.6 97.4 1096.2 321.3 102.1 1009.9 296.0 106.9 924.0 270.8 112.5
50 10.0 1298.4 380.6 102.4 1205.0 353.2 107.6 1111.7 325.8 113.1 1019.1 298.7 119.4
35 1.7 1056.2 309.6 94.9 974.7 285.7 99.1 893.3 261.8 102.9 811.8 237.9 107.0
40 4.4 1169.3 342.7 99.9 1080.5 316.7 104.5 991.7 290.7 108.8 902.7 264.6 113.7
54106-D
45 7.2 1289.3 377.9 105.1 1192.7 349.6 110.0 1096.1 321.3 114.8 999.2 292.9 120.6
50 10.0 1415.9 415.0 110.6 1311.2 384.3 115.8 1206.4 353.6 121.2 1101.3 322.8 127.5
35 1.7 1122.7 329.1 107.2 1036.2 303.7 111.3 949.9 278.4 115.1 863.4 253.1 119.4
40 4.4 1241.8 364.0 113.3 1148.0 336.5 118.0 1054.3 309.0 122.5 960.3 281.5 127.7
54114-D
45 7.2 1367.9 400.9 119.6 1266.4 371.2 124.8 1164.8 341.4 130.2 1062.9 311.5 136.4
50 10.0 1500.9 439.9 126.0 1391.2 407.8 131.9 1281.4 375.6 138.0 1171.3 343.3 145.1
35 1.7 1187.3 348.0 119.4 1096.1 321.3 123.5 1004.9 294.5 127.4 913.5 267.7 131.7
40 4.4 1312.2 384.6 126.8 1213.6 355.7 131.6 1114.9 326.8 136.4 1016.1 297.8 141.8
54120-D
45 7.2 1444.3 423.3 134.3 1337.8 392.1 139.8 1231.3 360.9 145.7 1124.6 329.6 152.3
50 10.0 1583.4 464.1 141.7 1468.7 430.5 148.2 1354.0 396.8 155.2 1239.0 363.1 163.1
Table 3 ends
Note:
* Power Input mentioned in these pages should not be used for Cable/Fuse selection.
MCA & MFA Values given in the electrical data (Pages 19 to 23) should be referred for the same.

Computer Print outs for matched ratings with SKM Air Handling Units are available.

12
SKM Air Cooled Condensing Units
ACUV-D Series - R-134a
CAPACITY RATINGS - 60 HZ
Condenser Entering Air Temperature F (C)
Model SST 95F (35C) 105F (40C) 115F (46C) 125 (52C)
ACUV Total Capacity PI* Total Capacity PI* Total Capacity PI* Total Capacity PI*
F C MBH kW kW MBH kW kW MBH kW kW MBH kW kW
35 1.7 88.8 26.0 7.4 81.9 24.0 7.8 75.0 22.0 8.2 68.1 20.0 8.5
40 4.4 99.0 29.0 7.8 91.4 26.8 8.3 83.9 24.6 8.7 76.3 22.4 9.1
61009-D
45 7.2 109.8 32.2 8.2 101.6 29.8 8.7 93.4 27.4 9.2 85.2 25.0 9.7
50 10.0 121.4 35.6 8.6 112.5 33.0 9.2 103.6 30.4 9.7 94.7 27.8 10.3
35 1.7 103.0 30.2 8.4 94.6 27.7 8.8 86.3 25.3 9.1 78.0 22.9 9.4
40 4.4 115.1 33.7 8.8 105.9 31.1 9.3 96.9 28.4 9.7 87.8 25.7 10.1
61011-D
45 7.2 128.0 37.5 9.2 118.1 34.6 9.8 108.3 31.7 10.2 98.4 28.8 10.7
50 10.0 141.8 41.6 9.6 131.1 38.4 10.2 120.4 35.3 10.8 109.7 32.2 11.4
35 1.7 161.1 47.2 13.3 148.9 43.6 14.0 136.7 40.1 14.7 124.6 36.5 15.3
40 4.4 178.7 52.4 14.0 165.4 48.5 14.7 152.2 44.6 15.5 139.0 40.7 16.3
61016-D
45 7.2 197.4 57.9 14.6 183.0 53.6 15.5 168.7 49.4 16.3 154.3 45.2 17.2
50 10.0 217.2 63.7 15.3 201.7 59.1 16.2 186.1 54.6 17.2 170.6 50.0 18.2
35 1.7 233.3 68.4 20.0 215.5 63.2 21.0 197.6 57.9 21.9 179.7 52.7 22.9
40 4.4 258.9 75.9 21.1 239.5 70.2 22.3 220.1 64.5 23.3 200.8 58.8 24.5
61024-D
45 7.2 286.1 83.9 22.3 265.1 77.7 23.6 244.1 71.6 24.8 223.3 65.5 26.2
50 10.0 315.0 92.3 23.5 292.4 85.7 24.8 269.8 79.1 26.3 247.5 72.5 27.8
35 1.7 264.2 77.4 24.3 244.8 71.7 25.5 225.2 66.0 26.7 205.9 60.3 28.0
40 4.4 292.1 85.6 25.8 270.9 79.4 27.1 249.8 73.2 28.4 229.0 67.1 29.9
61026-D
45 7.2 321.6 94.3 27.2 298.7 87.5 28.7 275.9 80.9 30.2 253.7 74.3 31.9
50 10.0 352.8 103.4 28.6 328.1 96.2 30.3 303.7 89.0 32.0 279.9 82.0 34.0
35 1.7 318.7 93.4 28.7 294.1 86.2 29.9 269.5 79.0 31.0 244.9 71.8 32.2
40 4.4 352.8 103.4 30.2 326.0 95.5 31.5 299.2 87.7 32.8 272.4 79.8 34.3
61032-D
45 7.2 389.0 114.0 31.7 359.8 105.5 33.2 330.7 96.9 34.7 301.5 88.4 36.3
50 10.0 427.2 125.2 33.3 395.6 116.0 34.9 364.0 106.7 36.5 332.3 97.4 38.4
35 1.7 358.2 105.0 36.0 330.7 96.9 37.2 303.2 88.9 38.4 275.7 80.8 39.7
40 4.4 395.9 116.0 38.3 366.2 107.3 39.7 336.4 98.6 41.1 306.6 89.9 42.7
61036-D
45 7.2 435.7 127.7 40.5 403.6 118.3 42.2 371.5 108.9 43.9 339.3 99.4 45.9
50 10.0 477.7 140.0 42.8 443.1 129.9 44.7 408.5 119.7 46.8 373.8 109.6 49.3
35 1.7 173.2 50.8 15.1 159.6 46.8 15.8 146.0 42.8 16.5 132.4 38.8 17.2
40 4.4 192.6 56.4 16.0 177.7 52.1 16.8 163.0 47.8 17.6 148.2 43.4 18.4
62018-D
45 7.2 213.2 62.5 16.8 197.2 57.8 17.8 181.1 53.1 18.7 165.0 48.4 19.7
50 10.0 235.2 68.9 17.7 217.8 63.8 18.8 200.4 58.7 19.8 182.9 53.6 21.0
35 1.7 183.2 53.7 16.3 168.4 49.4 16.9 153.7 45.1 17.6 138.9 40.7 18.2
40 4.4 203.7 59.7 17.2 187.7 55.0 18.0 171.6 50.3 18.7 155.5 45.6 19.6
62020-D
45 7.2 225.5 66.1 18.2 208.1 61.0 19.1 190.7 55.9 20.0 173.2 50.8 21.0
50 10.0 248.6 72.9 19.1 229.9 67.4 20.2 211.0 61.9 21.2 192.0 56.3 22.5
35 1.7 201.6 59.1 17.0 185.1 54.3 17.7 168.8 49.5 18.3 152.4 44.7 19.0
40 4.4 224.8 65.9 17.9 206.9 60.6 18.8 189.1 55.4 19.5 171.3 50.2 20.3
62022-D
45 7.2 249.6 73.2 18.8 230.3 67.5 19.8 210.9 61.8 20.7 191.5 56.1 21.7
50 10.0 276.1 80.9 19.7 255.1 74.8 20.8 234.2 68.6 21.9 213.2 62.5 23.1
35 1.7 253.3 74.2 22.2 233.4 68.4 23.2 213.5 62.6 24.2 193.5 56.7 25.2
40 4.4 280.9 82.3 23.5 259.2 76.0 24.6 237.6 69.6 25.7 215.9 63.3 26.9
62026-D
45 7.2 310.1 90.9 24.7 286.7 84.0 26.0 263.2 77.2 27.3 239.7 70.2 28.7
50 10.0 341.0 99.9 26.0 315.7 92.5 27.4 290.3 85.1 28.9 264.8 77.6 30.6
35 1.7 317.0 92.9 26.9 292.9 85.9 28.3 268.8 78.8 29.6 244.7 71.7 30.9
40 4.4 351.2 102.9 28.3 325.0 95.3 29.8 298.9 87.6 31.3 272.7 79.9 32.8
62032-D
45 7.2 387.5 113.6 29.7 359.1 105.3 31.4 330.7 96.9 33.0 302.3 88.6 34.8
50 10.0 425.9 124.8 31.1 395.2 115.8 33.0 364.5 106.8 34.8 333.7 97.8 36.8
35 1.7 328.8 96.4 28.7 303.0 88.8 30.0 277.2 81.2 31.3 251.4 73.7 32.6
40 4.4 364.9 107.0 30.4 336.9 98.8 31.9 308.9 90.5 33.4 281.0 82.4 35.0
62034-D
45 7.2 403.3 118.2 32.2 373.1 109.3 33.8 342.8 100.5 35.5 312.7 91.6 37.4
50 10.0 444.1 130.2 33.8 411.4 120.6 35.7 378.8 111.0 37.7 346.4 101.5 39.9
35 1.7 389.8 114.3 33.5 360.0 105.5 35.2 330.1 96.8 36.8 300.3 88.0 38.4
40 4.4 432.1 126.6 35.4 399.7 117.2 37.3 367.3 107.7 39.1 335.1 98.2 41.1
62040-D
45 7.2 477.0 139.8 37.3 442.0 129.5 39.4 406.9 119.3 41.5 372.1 109.1 43.8
50 10.0 524.5 153.7 39.2 486.7 142.7 41.5 449.0 131.6 43.9 411.5 120.6 46.5
35 1.7 454.4 133.2 40.7 419.3 122.9 42.5 384.0 112.6 44.4 349.0 102.3 46.3
40 4.4 503.2 147.5 43.2 465.1 136.3 45.3 427.0 125.1 47.5 389.2 114.1 49.8
62046-D
45 7.2 554.9 162.6 45.7 513.7 150.6 48.1 472.7 138.5 50.6 432.1 126.7 53.4
50 10.0 609.6 178.7 48.2 565.3 165.7 50.9 521.2 152.8 53.7 477.9 140.1 57.0
35 1.7 529.4 155.2 48.6 490.4 143.7 51.0 451.2 132.2 53.4 412.5 120.9 55.9
Table 4
40 4.4 585.2 171.5 51.4 542.9 159.1 54.1 500.5 146.7 56.8 458.9 134.5 59.7
Note:
62052-D
45 7.2 644.5 188.9 54.3 598.6 175.5 57.3 553.0 162.1 60.3 508.4 149.0 63.6
50 10.0 707.1 207.3 57.2 657.7 192.8 60.5 608.7 178.4 64.0 561.1 164.5 67.9
* Power Input
35
mentioned
1.7
in these
575.4
pages
168.6
should not
53.4
be used
531.7
for Cable/Fuse
155.8
selection.
55.8 488.0 143.0 58.0 444.4 130.3 60.5
MCA & MFA
40 Values
4.4 given in the electrical
635.9 186.4 data
56.4(Pages588.4
19 to 23) 172.5
should be referred
59.0 for the same.
540.9 158.5 61.7 493.7 144.7 64.6
62058-D
45 7.2 700.0 205.2 59.5 648.5 190.1 62.4 597.0 175.0 65.4 546.0 160.0 68.8
Computer50
Print
10.0
outs767.5
for matched
225.0
ratings
62.6
with711.8
SKM Air208.6
Handling Units are
65.8 656.4
available.
192.4 69.2 601.4 176.3 73.1
35 1.7 620.2 181.8 58.2 571.9 167.6 60.5 523.7 153.5 62.7 475.4 139.3 65.3
40 4.4 685.2 200.8 61.4 632.6 185.4 64.0 580.1 170.0 66.6 527.4 154.6 69.6
62062-D
45 7.2 753.8 220.9 64.7 696.7 204.2 67.6 639.6 187.5 70.6 582.3 170.7 74.0
50 10.0 825.9 242.1 68.1 764.2 224.0 71.2 702.3 205.9 74.5 640.2 187.6 78.5
35
40
1.7
4.4
675.1
746.6
197.9
218.8
64.8
68.5
623.1
690.1
182.6
202.3
67.2
71.3
571.2
633.7
167.4
185.7
69.5
74.0
519.1
577.2
152.2
169.2
13
72.0
77.1
62067-D
45 7.2 822.2 241.0 72.4 761.0 223.1 75.5 699.9 205.1 78.7 638.6 187.2 82.4
35 1.7 317.0 92.9 26.9 292.9 85.9 28.3 268.8 78.8 29.6 244.7 71.7 30.9

SKM Air Cooled Condensing Units


40 4.4 351.2 102.9 28.3 325.0 95.3 29.8 298.9 87.6 31.3 272.7 79.9 32.8
62032-D
45 7.2 387.5 113.6 29.7 359.1 105.3 31.4 330.7 96.9 33.0 302.3 88.6 34.8
50 10.0 425.9 124.8 31.1 395.2 115.8 33.0 364.5 106.8 34.8 333.7 97.8 36.8

62034-D
35
40
45
1.7
4.4
7.2
328.8
364.9
403.3
ACUV-D Series - R-134a
96.4
107.0
118.2
28.7
30.4
32.2
303.0
336.9
373.1
88.8
98.8
109.3
30.0
31.9
33.8
277.2
308.9
342.8
81.2
90.5
100.5
31.3
33.4
35.5
251.4
281.0
312.7
73.7
82.4
91.6
32.6
35.0
37.4
50 10.0 444.1 130.2 33.8 411.4 120.6 35.7 378.8 111.0 37.7 346.4 101.5 39.9
35 1.7 389.8 114.3 33.5 360.0 105.5 35.2 330.1 96.8 36.8 300.3 88.0 38.4

CAPACITY RATINGS - 60 HZ
62040-D
40
45
4.4
7.2
432.1
477.0
126.6
139.8
35.4
37.3
399.7
442.0
117.2
129.5
37.3
39.4
367.3
406.9
107.7
119.3
39.1
41.5
335.1
372.1
98.2
109.1
41.1
43.8
50 10.0 524.5 153.7 39.2 486.7 142.7 41.5 449.0 131.6 43.9 411.5 120.6 46.5
35 1.7 454.4 133.2 40.7 419.3 Condenser
122.9 Entering
42.5 Air Temperature
384.0 F (C)
112.6 44.4 349.0 102.3 46.3
Model 40 SST 4.4 503.2 95F (35C) 43.2
147.5 465.1 105F (40C) 45.3
136.3 427.0 115F (46C)
125.1 47.5 389.2 125 (52C)
114.1 49.8
62046-D
ACUV 45 7.2 Total Capacity
554.9 162.6 PI*
45.7 Total Capacity
513.7 150.6 PI*
48.1 Total Capacity
472.7 138.5 PI*
50.6 Total Capacity
432.1 126.7 PI*
53.4
F
50 C
10.0 MBH
609.6 kW
178.7 kW
48.2 MBH
565.3 kW
165.7 kW
50.9 MBH
521.2 kW
152.8 kW
53.7 MBH
477.9 kW
140.1 kW
57.0
35 1.7 88.8
529.4 26.0
155.2 7.4
48.6 81.9
490.4 24.0
143.7 7.8
51.0 75.0
451.2 22.0
132.2 8.2
53.4 68.1
412.5 20.0
120.9 8.5
55.9
40 4.4 99.0
585.2 29.0
171.5 7.8
51.4 91.4
542.9 26.8
159.1 8.3
54.1 83.9
500.5 24.6
146.7 8.7
56.8 76.3
458.9 22.4
134.5 9.1
59.7
61009-D
62052-D
45 7.2 109.8
644.5 32.2
188.9 8.2
54.3 101.6
598.6 29.8
175.5 8.7
57.3 93.4
553.0 27.4
162.1 9.2
60.3 85.2
508.4 25.0
149.0 9.7
63.6
50 10.0 121.4
707.1 35.6
207.3 8.6
57.2 112.5
657.7 33.0
192.8 9.2
60.5 103.6
608.7 30.4
178.4 9.7
64.0 94.7
561.1 27.8
164.5 10.3
67.9
35 1.7 103.0
575.4 30.2
168.6 8.4
53.4 94.6
531.7 27.7
155.8 8.8
55.8 86.3
488.0 25.3
143.0 9.1
58.0 78.0
444.4 22.9
130.3 9.4
60.5
40 4.4 115.1
635.9 33.7
186.4 8.8
56.4 105.9
588.4 31.1
172.5 9.3
59.0 96.9
540.9 28.4
158.5 9.7
61.7 87.8
493.7 25.7
144.7 10.1
64.6
61011-D
62058-D
45 7.2 128.0
700.0 37.5
205.2 9.2
59.5 118.1
648.5 34.6
190.1 9.8
62.4 108.3
597.0 31.7
175.0 10.2
65.4 98.4
546.0 28.8
160.0 10.7
68.8
50 10.0 141.8
767.5 41.6
225.0 9.6
62.6 131.1
711.8 38.4
208.6 10.2
65.8 120.4
656.4 35.3
192.4 10.8
69.2 109.7
601.4 32.2
176.3 11.4
73.1
35 1.7 161.1
620.2 47.2
181.8 13.3
58.2 148.9
571.9 43.6
167.6 14.0
60.5 136.7
523.7 40.1
153.5 14.7
62.7 124.6
475.4 36.5
139.3 15.3
65.3
40 4.4 178.7
685.2 52.4
200.8 14.0
61.4 165.4
632.6 48.5
185.4 14.7
64.0 152.2
580.1 44.6
170.0 15.5
66.6 139.0
527.4 40.7
154.6 16.3
69.6
61016-D
62062-D
45 7.2 197.4
753.8 57.9
220.9 14.6
64.7 183.0
696.7 53.6
204.2 15.5
67.6 168.7
639.6 49.4
187.5 16.3
70.6 154.3
582.3 45.2
170.7 17.2
74.0
50 10.0 217.2
825.9 63.7
242.1 15.3
68.1 201.7
764.2 59.1
224.0 16.2
71.2 186.1
702.3 54.6
205.9 17.2
74.5 170.6
640.2 50.0
187.6 18.2
78.5
35 1.7 233.3
675.1 68.4
197.9 20.0
64.8 215.5
623.1 63.2
182.6 21.0
67.2 197.6
571.2 57.9
167.4 21.9
69.5 179.7
519.1 52.7
152.2 22.9
72.0
40 4.4 258.9
746.6 75.9
218.8 21.1
68.5 239.5
690.1 70.2
202.3 22.3
71.3 220.1
633.7 64.5
185.7 23.3
74.0 200.8
577.2 58.8
169.2 24.5
77.1
61024-D
62067-D
45 7.2 286.1
822.2 83.9
241.0 22.3
72.4 265.1
761.0 77.7
223.1 23.6
75.5 244.1
699.9 71.6
205.1 24.8
78.7 223.3
638.6 65.5
187.2 26.2
82.4
50 10.0 315.0
901.8 92.3
264.3 23.5
76.3 292.4
835.9 85.7
245.0 24.8
79.7 269.8
769.8 79.1
225.6 26.3
83.4 247.5
703.5 72.5
206.2 27.8
87.8
35 1.7 264.2
713.8 77.4
209.2 24.3
72.2 244.8
658.9 71.7
193.1 25.5
74.5 225.2
604.1 66.0
177.1 26.7
76.8 205.9
549.1 60.3
160.9 28.0
79.4
40 4.4 292.1
788.7 85.6
231.2 25.8
76.7 270.9
729.4 79.4
213.8 27.1
79.5 249.8
670.0 73.2
196.4 28.4
82.4 229.0
610.5 67.1
178.9 29.9
85.6
61026-D
62071-D
45 7.2 321.6
867.8 94.3
254.4 27.2
81.3 298.7
803.8 87.5
235.6 28.7
84.6 275.9
739.7 80.9
216.8 30.2
88.1 253.7
675.4 74.3
198.0 31.9
92.1
50 10.0 352.8
951.1 103.4
278.8 28.6
85.9 328.1
882.2 96.2
258.6 30.3
89.7 303.7
813.2 89.0
238.3 32.0
93.8 279.9
743.9 82.0
218.0 34.0
98.8
35 1.7 318.7
733.7 93.4
215.0 28.7
64.1 294.1
678.5 86.2
198.9 29.9
67.3 269.5
622.9 79.0
182.6 31.0
70.3 244.9
567.6 71.8
166.4 32.2
73.5
40 4.4 352.8
813.2 103.4
238.3 30.2
67.8 326.0
753.2 95.5
220.8 31.5
71.4 299.2
693.0 87.7
203.1 32.8
74.9 272.4
633.3 79.8
185.6 34.3
78.6
61032-D
63074-D
45 7.2 389.0
897.7 114.0
263.1 31.7
71.5 359.8
832.8 105.5
244.1 33.2
75.6 330.7
767.8 96.9
225.0 34.7
79.5 301.5
703.6 88.4
206.2 36.3
83.9
50 10.0 427.2
987.4 125.2
289.4 33.3
75.2 395.6
917.3 116.0
268.9 34.9
79.7 364.0
847.4 106.7
248.4 36.5
84.2 332.3
778.6 97.4
228.2 38.4
89.3
35 1.7 358.2
795.5 105.0
233.2 36.0
72.8 330.7
737.0 96.9
216.0 37.2
76.5 303.2
678.1 88.9
198.8 38.4
80.0 275.7
620.0 80.8
181.7 39.7
83.7
40 4.4 395.9
879.6 116.0
257.8 38.3
77.1 366.2
816.0 107.3
239.2 39.7
81.1 336.4
752.3 98.6
220.5 41.1
85.1 306.6
689.8 89.9
202.2 42.7
89.4
61036-D
63078-D
45 7.2 435.7
968.7 127.7
283.9 40.5
81.3 403.6
899.9 118.3
263.8 42.2
85.8 371.5
831.3 108.9
243.7 43.9
90.3 339.3
764.3 99.4
224.0 45.9
95.3
50 10.0 477.7
1063.0 140.0
311.6 42.8
85.6 443.1
988.8 129.9
289.8 44.7
90.6 408.5
915.2 119.7
268.2 46.8
95.8 373.8
843.6 109.6
247.3 49.3
101.6
35 1.7 173.2
833.9 50.8
244.4 15.1
78.1 159.6
771.0 46.8
226.0 15.8
81.6 146.0
708.0 42.8
207.5 16.5
85.0 132.4
645.4 38.8
189.2 17.2
88.8
40 4.4 192.6
921.2 56.4
270.0 16.0
82.6 177.7
852.8 52.1
250.0 16.8
86.5 163.0
784.5 47.8
229.9 17.6
90.5 148.2
716.9 43.4
210.1 18.4
94.9
62018-D
63082-D
45 7.2 213.2
1013.5 62.5
297.1 16.8
87.2 197.2
939.5 57.8
275.4 17.8
91.5 181.1
865.7 53.1
253.7 18.7
96.0 165.0
792.9 48.4
232.4 19.7
101.2
50 10.0 235.2
1110.8 68.9
325.6 17.7
91.8 217.8
1030.9 63.8
302.2 18.8
96.6 200.4
951.5 58.7
278.9 19.8
101.8 182.9
873.3 53.6
256.0 21.0
107.8
35 1.7 183.2
941.8 53.7
276.0 16.3
86.8 168.4
868.8 49.4
254.6 16.9
90.3 153.7
795.9 45.1
233.3 17.6
93.6 138.9
722.8 40.7
211.9 18.2
97.3
40 4.4 203.7
1041.5 59.7
305.3 17.2
91.4 187.7
961.9 55.0
281.9 18.0
95.4 171.6
882.5 50.3
258.6 18.7
99.3 155.5
802.8 45.6
235.3 19.6
103.7
62020-D
63094-D
45 7.2 225.5
1146.9 66.1
336.2 18.2
96.2 208.1
1060.5 61.0
310.8 19.1
100.6 190.7
974.1 55.9
285.5 20.0
105.0 173.2
887.4 50.8
260.1 21.0
110.1
50 10.0 248.6
1258.0 72.9
368.7 19.1
101.1 229.9
1164.5 67.4
341.3 20.2
105.8 211.0
1070.8 61.9
313.8 21.2
110.8 192.0
976.7 56.3
286.3 22.5
116.6
35 1.7 201.6
980.8 59.1
287.5 17.0
94.1 185.1
904.9 54.3
265.2 17.7
97.6 168.8
829.1 49.5
243.0 18.3
101.0 152.4
753.0 44.7
220.7 19.0
104.8
40 4.4 224.8
1083.9 65.9
317.7 17.9
99.5 206.9
1001.5 60.6
293.5 18.8
103.6 189.1
919.0 55.4
269.4 19.5
107.6 171.3
836.4 50.2
245.1 20.3
112.2
62022-D
63098-D
45 7.2 249.6
1192.8 73.2
349.6 18.8
105.1 230.3
1103.5 67.5
323.4 19.8
109.6 210.9
1014.1 61.8
297.2 20.7
114.3 191.5
924.4 56.1
271.0 21.7
119.8
50 10.0 276.1
1307.5 80.9
383.2 19.7
110.7 255.1
1211.0 74.8
355.0 20.8
115.7 234.2
1114.4 68.6
326.6 21.9
121.1 213.2
1017.3 62.5
298.2 23.1
127.5
35 1.7 253.3
1019.0 74.2
298.7 22.2
101.5 233.4
940.2 68.4
275.6 23.2
105.0 213.5
861.5 62.6
252.5 24.2
108.4 193.5
782.6 56.7
229.4 25.2
112.3
40 4.4 280.9
1125.5 82.3
329.9 23.5
107.7 259.2
1040.1 76.0
304.9 24.6
111.8 237.6
954.8 69.6
279.8 25.7
115.9 215.9
869.2 63.3
254.8 26.9
120.8
62026-D
63100-D
45 7.2 310.1
1237.8 90.9
362.8 24.7
114.0 286.7
1145.6 84.0
335.8 26.0
118.7 263.2
1053.3 77.2
308.7 27.3
123.7 239.7
960.6 70.2
281.6 28.7
129.5
50 10.0 341.0
1356.0 99.9
397.4 26.0
120.4 315.7
1256.6 92.5
368.3 27.4
125.7 290.3
1157.0 85.1
339.1 28.9
131.5 264.8
1056.9 77.6
309.8 30.6
138.6
35 1.7 317.0
1148.8 92.9
336.7 26.9
106.9 292.9
1061.5 85.9
311.1 28.3
111.6 268.8
974.1 78.8
285.5 29.6
116.2 244.7
887.2 71.7
260.0 30.9
121.2
40 4.4 351.2
1269.4 102.9
372.1 28.3
112.9 325.0
1174.6 95.3
344.3 29.8
118.2 298.9
1079.7 87.6
316.5 31.3
123.5 272.7
985.4 79.9
288.8 32.8
129.4
62032-D
64113-D
45 7.2 387.5
1397.1 113.6
409.5 29.7
119.1 359.1
1294.2 105.3
379.3 31.4
124.9 330.7
1191.5 96.9
349.2 33.0
130.9 302.3
1089.6 88.6
319.4 34.8
137.8
50 10.0 425.9
1531.7 124.8
448.9 31.1
125.4 395.2
1420.5 115.8
416.4 33.0
131.8 364.5
1309.7 106.8
383.9 34.8
138.6 333.7
1200.0 97.8
351.7 36.8
146.5
35 1.7 328.8
1255.7 96.4
368.1 28.7
115.7 303.0
1158.4 88.8
339.5 30.0
120.4 277.2
1061.2 81.2
311.0 31.3
124.8 251.4
963.8 73.7
282.5 32.6
129.8
40 4.4 364.9
1388.6 107.0
407.0 30.4
121.9 336.9
1282.6 98.8
375.9 31.9
127.2 308.9
1176.6 90.5
344.9 33.4
132.4 281.0
1070.3 82.4
313.7 35.0
138.2
62034-D
64124-D
45 7.2 403.3
1529.2 118.2
448.2 32.2
128.3 373.1
1414.0 109.3
414.4 33.8
134.1 342.8
1298.8 100.5
380.7 35.5
140.0 312.7
1183.2 91.6
346.8 37.4
146.8
50 10.0 444.1
1677.4 130.2
491.6 33.8
134.8 411.4
1552.6 120.6
455.1 35.7
141.1 378.8
1427.7 111.0
418.5 37.7
147.7 346.4
1302.3 101.5
381.7 39.9
155.4
35 1.7 389.8
1333.3 114.3
390.8 33.5
130.4 360.0
1230.2 105.5
360.6 35.2
135.1 330.1
1127.2 96.8
330.4 36.8
139.6 300.3
1023.9 88.0
300.1 38.4
144.7
40 4.4 432.1
1473.1 126.6
431.8 35.4
138.1 399.7
1361.2 117.2
399.0 37.3
143.5 367.3
1249.3 107.7
366.2 39.1
149.0 335.1
1137.2 98.2
333.3 41.1
155.3
62040-D
64132-D
45 7.2 477.0
1620.6 139.8
475.0 37.3
146.0 442.0
1499.5 129.5
439.5 39.4
152.2 406.9
1378.4 119.3
404.0 41.5
158.7 372.1
1256.9 109.1
368.4 43.8
166.2
50 10.0 524.5
1775.9 153.7
520.5 39.2
154.0 486.7
1645.2 142.7
482.2 41.5
160.9 449.0
1514.4 131.6
443.9 43.9
168.4 411.5
1383.0 120.6
405.3 46.5
177.3
35 1.7 454.4
1408.6 133.2
412.9 40.7
145.2 419.3
1299.8 122.9
381.0 42.5
149.8 384.0
1191.0 112.6
349.1 44.4
154.4 349.0
1081.9 102.3
317.1 46.3
159.7
40 4.4 503.2
1554.9 147.5
455.7 43.2
154.4 465.1
1437.3 136.3
421.3 45.3
160.0 427.0
1319.6 125.1
386.8 47.5
165.8 389.2
1201.7 114.1
352.2 49.8
172.5
62046-D
64140-D
45 7.2 554.9
1709.1 162.6
500.9 45.7
163.9 513.7
1582.3 150.6
463.8 48.1
170.5 472.7
1455.3 138.5
426.6 50.6
177.5 432.1
1328.0 126.7
389.2 53.4
185.9
50 10.0 609.6
1871.2 178.7
548.4 48.2
173.5 565.3
1734.8 165.7
508.5 50.9
181.1 521.2
1598.0 152.8
468.4 53.7
189.5 477.9
1460.7 140.1
428.1 57.0
199.9
35 1.7 529.4 155.2 48.6 490.4 143.7 51.0 451.2 132.2 53.4 412.5 120.9 Table 55.9
4 ends
Note: 40 4.4 585.2 171.5 51.4 542.9 159.1 54.1 500.5 146.7 56.8 458.9 134.5 59.7
62052-D
45 7.2 644.5 188.9 54.3 598.6 175.5 57.3 553.0 162.1 60.3 508.4 149.0 63.6
50 10.0 707.1 207.3 57.2 657.7 192.8 60.5 608.7 178.4 64.0 561.1 164.5 67.9
* Power Input mentioned in these pages should not be used for Cable/Fuse selection.
35 1.7 575.4 168.6 53.4 531.7 155.8 55.8 488.0 143.0 58.0 444.4 130.3 60.5
MCA & MFA Values given in the electrical data (Pages 19 to 23) should be referred for the same.
40 4.4 635.9 186.4 56.4 588.4 172.5 59.0 540.9 158.5 61.7 493.7 144.7 64.6
62058-D
45 7.2
Computer Print outs700.0 205.2
for matched 59.5
ratings with648.5
SKM Air190.1Handling 62.4 597.0
Units are 175.0
available. 65.4 546.0 160.0 68.8
50 10.0 767.5 225.0 62.6 711.8 208.6 65.8 656.4 192.4 69.2 601.4 176.3 73.1
35 1.7 620.2 181.8 58.2 571.9 167.6 60.5 523.7 153.5 62.7 475.4 139.3 65.3
40 4.4 685.2 200.8 61.4 632.6 185.4 64.0 580.1 170.0 66.6 527.4 154.6 69.6
62062-D
45 7.2 753.8 220.9 64.7 696.7 204.2 67.6 639.6 187.5 70.6 582.3 170.7 74.0
50 10.0 825.9 242.1 68.1 764.2 224.0 71.2 702.3 205.9 74.5 640.2 187.6 78.5

14 35
40
1.7
4.4
675.1
746.6
197.9
218.8
64.8
68.5
623.1
690.1
182.6
202.3
67.2
71.3
571.2
633.7
167.4
185.7
69.5
74.0
519.1
577.2
152.2
169.2
72.0
77.1
62067-D
45 7.2 822.2 241.0 72.4 761.0 223.1 75.5 699.9 205.1 78.7 638.6 187.2 82.4
50 10.0 901.8 264.3 76.3 835.9 245.0 79.7 769.8 225.6 83.4 703.5 206.2 87.8
SKM Air Cooled Condensing Units
ACUV-D Series - R-134a
Compressor Starting
The ACUV-D Units standard mode of compressor starting is given as per Table No. 5.
Maximum Instantaneous Current Flow (ICF) as shown in Electrical Specifications, Pages 19 - 23, must be used in determining the
need for part winding start for models with DOL as standard.
Compressor Starting
If part winding start is required, please specify option PWS at enquiry/order, available only for the models shown with PWS as
option in Table 5.

Power Supply ( V/Ph/Hz )

Model 380~415/3/50,
440/3/50 220/3/60
ACUV 380/3/60 , 460/3/60

Standard Option Standard Option Standard Option


51008-D 61009-D
51010-D 61011-D
51014-D 61016-D
DOL PWS
52015-D 62018-D
52017-D 62020-D DOL PWS DOL -
52019-D 62022-D
51021-D 61024-D
PWS -
51022-D 61026-D
52022-D 62026-D DOL PWS
51028-D 61032-D PWS - PWS - PWS -
52028-D 62032-D
DOL PWS DOL - DOL PWS
52030-D 62034-D
51030-D 61036-D PWS - ** - PWS -
52034-D 62040-D DOL PWS
52040-D 62046-D
DOL PWS DOL -
52045-D 62052-D
52049-D 62058-D
52053-D 62062-D PWS -
52058-D 62067-D PWS -
** -
52060-D 62071-D
53064-D 63074-D
53068-D 63078-D DOL PWS DOL -
PWS -
53070-D 63082-D
53080-D 63094-D PWS -
53084-D 63098-D PWS -
** -
53086-D 63100-D
54095-D 64113-D DOL PWS DOL -
54106-D 64124-D PWS -
54114-D 64132-D PWS -
** -
54120-D 64140-D
Table 5
** For Details, Please consult SKM

15
SKM Air Cooled Condensing Units
ACUV-D Series - R-134a
Capacity Control Steps
The Standard Capacity Control Steps are shown below.

Number of Number
ACUV Standard Optional
Steps of Steps
51008-D 61009-D 100-0 1 100-50-0 2
51010-D 61011-D 100-0 1 100-50-0 2
51014-D 61016-D 100-0 1 100-50-0 2
52015-D 62018-D 100-50-0 2 100-75-50-25-0 4
52017-D 62020-D 100-53-0 2 100-77-53-27-0 4
52019-D 62022-D 100-50-0 2 100-75-50-25-0 4
51021-D 61024-D 100-0 1 100-67-0 2
51022-D 61026-D 100-0 1 100-67-0 2
52022-D 62026-D 100-61-0 2 100-81-61-31-0 4
51028-D 61032-D 100-0 1 100-67-0 2
52028-D 62032-D 100-50-0 2 100-75-50-25-0 4
52030-D 62034-D 100-70-0 2 100-85-70-46-0 4
51030-D 61036-D 100-0 1 100-75-0 2
52034-D 62040-D 100-59-0 2 100-80-59-39-0 4
52040-D 62046-D 100-50-0 2 100-83-50-33-0 4
52045-D 62052-D 100-50-0 2 100-83-50-33-0 4
52049-D 62058-D 100-54-0 2 100-84-54-36-0 4
52053-D 62062-D 100-50-0 2 100-83-50-33-0 4
52058-D 62067-D 100-54-0 2 100-84-54-40-0 4
52060-D 62071-D 100-50-0 2 100-88-50-38-0 4
53064-D 63074-D 100-68-37-0 3 100-89-68-58-37-24-0 6
53068-D 63078-D 100-66-33-0 3 100-89-67-55-33-22-0 6
53070-D 63082-D 100-69-37-0 3 100-89-69-58-37-25-0 6
53080-D 63094-D 100-66-33-0 3 100-89-67-55-33-22-0 6
53084-D 63098-D 100-68-37-0 3 100-89-68-58-37-27-0 6
53086-D 63100-D 100-70-35-0 3 100-90-70-61-35-26-0 6
54095-D 64113-D 100-77-54-27-0 4 100-92-77-69-54-45-27-18-0 8
54106-D 64124-D 100-75-50-25-0 4 100-92-75-67-50-42-25-17-0 8
54114-D 64132-D 100-77-54-27-0 4 100-92-77-69-54-47-27-20-0 8
54120-D 64140-D 100-75-50-25-0 4 100-94-75-69-50-44-25-19-0 8
Table 6

Selection Procedure Altitude Correction Factors


Example The unit ratings are based on sea level. Above sea level apply
the following correction factors:
The following information should be determined:
1. Required total capacity = 430 MBh (126 kW)
2. Saturated suction temperature = 50F (10C)
Altitude Capacity Power
3. Condenser entering air temperature = 115F (46C) feet meter Multiplier Multiplier
4. Power Supply (V/Ph/Hz) = 380/3/50 0 0 1 1
Enter capacity ratings from Table 3 at 115F (46C) condenser 2000 610 0.99 1.01
entering air temperature and select model ACUV 52040-D
4000 1219 0.98 1.02
having a cooling capacity of 442.1 MBh (129.6 kW) at 50F
(10C) saturated suction temperature, compressor motor power 6000 1829 0.97 1.03
input is 43.8 kW. For further details refer to physical data and 8000 2438 0.96 1.04
specifications sheets.
10000 3048 0.95 1.05
Capacity ratings are based on sea level operation. Above sea
Table 7
level, apply the following corrections method.
Actual capacity (at level) = Sea level capacity x altitude correction
factor (from Table 7).

16
SKM Air Cooled Condensing Units
ACUV-D Series - R-134a
Field Connections
ACUV-D series self-contained heavy duty air cooled condensing units are designed for minimum field interaction.
Power hook-ups for AHU starter and fan interlock and control wiring of room unit as per Electrical hook-up diagram is all that is
required to electrically connect any model of ACUV-D series.
Every ACUV-D series condensing unit requires, at most, field installed fused disconnect switches or circuit breakers, and room unit.
Refer below for a schematic representation of required field electrical hook-ups for a standard ACUV-D series condensing unit.
All field wiring must be done in accordance with applicable local and national codes.
For maximum recommended fuse sizes and minimum circuit amps for cable sizing, see Page 19 - 23 of this bulletin.

The ACUV-D series is then ready to provide cooling, on demand.

Field Wiring Requirement Schematic

L1 L2 L3 N
**
L N L1 L2 L3 N

3 PHASE,
3 WIRE SYSTEM
440V/3PH/50Hz CIRCUIT BREAKER
220V/3PH/60Hz OR FUSED CIRCUIT BREAKER
460V/3PH/60Hz DISCONNECT SWITCH OR FUSED
(NOT BY SKM) DISCONNECT SWITCH
(NOT BY SKM)

3 PHASE,
4 WIRE SYSTEM
380-415V/3PH/50Hz
L1
L2
380V/3PH/60Hz
L3
N

GROUND 3 PHASE,
4 WIRE SYSTEM
E
380-415V/3PH/50Hz
L1 380V/3PH/60Hz
L2

CUSTOMER SUPPLIED
EFM STARTER INTERLOCK TO AHU AND INSTALLED
AHU STARTER BOX
(BY OTHERS) FIELD ACCESSORY
(CONTACTOR, OVERLOAD
RELAY & ON/OFF CONTROL etc.)

DOL/STAR DELTA
FAN INTERLOCK FROM AHU

ROOM UNIT
(LOOSESUPPLY) U
V M
W 3~

+ -
E
CE+ CE-

AIR HANDLING UNIT

2 CORE UNSCREENED TWISTED PAIR CABLE (BY OTHERS)


LINE VOLTAGE
FIELD WIRING
ACUV-D SERIES
CONTROL PANEL LOW VOLTAGE
FIELD WIRING
REFER ACTUAL WIRING DIAGRAM
FURNISHED WITH THE UNIT FOR
EXACT IDENTIFICATION OF WIRE NUMBERS.

** ACUV-D SERIES UNITS RATED FOR 440V/3PH/50Hz, 460V/3PH/60Hz, OR POWER SUPPLIES WITH OUT NEUTRAL
REQUIRE SEPARATE SOURCE OF CONTROL POWER SUPPLY THRU FIELD SUPPLIED & INSTALLED 15A/220V FUSED
CONTROL DISCONNECT SWITCH OR ORDER WITH FACTORY BUILT IN OPTION ' CXT '.

17
18
POWER SUPPLY
L1
** L2
L3
N

MPCB1 MPCB2 MPCB3 MPCB4

I> I> I> I> I> I> I> I> I> I> I> I>
N L1
C1 C2
C3 C4 C5 C6

MCB1 CM1 CM2 CFM1 CFM2 CFM3 CFM4


PROVIDE OVERCURRENT, EARTH FAULT PROTECTION, SHORT CIRCUITAND
** DISCONNECT MEANS AS REQUIRED BYLOCAL & NATIONAL ELECTRIC CODE.

NOTE:-
ROOM UNIT
(LOOSE SUPPLY) * Typical wiring diagram given here is for units with 380~ 415/3/50 or
380/3/60, 4 wire power supplies.
Typical Wiring Diagram

* Wiring diagrams for 440/3/50, 220/3/60 or 460/3/60


power supplies are available on request.

* For 440/3/50 or 460/3/60 or power supplies without neutral,


G G + - CXT option is a must.
I I CR6 CR7 CR4 CR5 CS CR8

MP-1
MP-2
L EGEND

LPS-1
LPS-2

OPS-1
OPS-2
P PRESSURE ACTIVATED SWITCH OFH OIL FAILURE HEATER

RUN/STOP
TFR TRANSFORMER OPS OIL PRESSURESWITCH

FAN INTERLOCK
(BY OTHERS)
CS CONTROL SWITCH MP MOTOR PROTECTOR

DISC. PRESSURE-1
DISC. PRESSURE-2
TWISTED PAIR CABLE
2CORE UNSCREENED
C CONTACTOR MPCB MOTOR PROTECTOR CIRCUT BREAKER
CCH CRANK CASE HEATER OL OVERLOADRELAY
MCB MINIATURECIRCUIT BREAKER LSV LIQUID LINE SOLENOID VALVE
CFM CONDENSER FAN MOTOR EFM EVAPORATORFANMOTOR
CM COMPRESSOR MOTOR CR CONTROL RELAY
LPS LOW PRESSURE SWITCH
FIELD WIRING
HPS HIGH PRESSURESWITCH

24~_ RS485 PB
VOLTFREECONTACTTO

M
M
M
M
M
M
M
B-
MCB2

X1
X2
X3
X4
X5
X6
X7
X8

B1
B2
B3
A+

D1
D2
DG
MATCHINGAHUFOR

CE-

REF
CE+

5V=
5V=
DU1
DU2

T1
T2
T3
T4
T5
T6
T7

24V=
24V=
CR3

INFO

MICROPROCESSOR EFMSTARTER
CONTROLLER OK INTERLOCK
TFR

24V

220~ 240V
ESC
ACUV-D Series - R-134a

C1 C2 CR1 CR2

T8
T9

24~_
G0
Q12
Q11
Q14
Q22
Q21
Q24
Q33
Q34
Q43
Q44
Q53
Q54
Q64
Q73
Q74
Q84
C
D01
D02
DL1
DN
DL2

T10
T11
T12
T13
T-IP
T-HI

MP1 MP2 L L
11 11 OPS1 OPS2
L 1 2 L 1 2 M M

N 12 14 N 12 14
M M

LSV-1 LSV-2
(BY OTHERS)

CCH1
CCH2
FAN INTERLOCK FROM AHU

HPS-1
HPS-2

R
R
E

OFH-1
OFH-2

COMP.-1
LSV-1
COMP.-2
LSV-2
CFM1
CFM2
CFM3
CFM4
EFM
SKM Air Cooled Condensing Units

P C1 CR1 P C2 CR2 C3 C4 C5 C6 CR3 CR4 CR5 CR6 CR7 CR8


SKM Air Cooled Condensing Units
ACUV-D Series - R-134a
ELECTRICAL DATA
ELECTRICAL DATA
Power Supply: 380~415V/3PH/50Hz
Unit Characteristic
Model Compressor Condenser Fan Motor
ICF
ACUV MFA MCA
DOL PWS QTY RLA LRA QTY FLA LRA
51008-D 50 25 118 73 1 17 113 2 1.1 3.9
51010-D 50 28 137 84 1 19 132 2 1.1 3.9
51014-D 80 43 222 138 1 29 211 2 2.4 8.9
52015-D 63 45 141 96 2 17 113 2 2.4 8.9
52017-D 80 48 160 108 1+1 19 + 17 132 + 113 2 2.4 8.9
52019-D 80 53 172 119 2 19 132 2 3.9 17.2
51021-D 125 65 296 186 1 44 275 2 3.9 17.2
51022-D 160 77 383 238 1 54 362 2 3.9 17.2
52022-D 100 65 251 167 1+1 29 + 19 211 + 132 2 3.9 17.2
51028-D 200 102 - 267 1 71 404 3 3.9 17.2
52028-D 125 79 265 181 2 29 211 3 3.9 17.2
52030-D 160 88 319 209 1+1 44 + 19 275 + 132 3 3.9 17.2
51030-D 200 117 - 384 1 83 513 3 3.9 17.2
52034-D 160 98 329 219 1+1 44 + 29 275 + 211 3 3.9 17.2
52040-D 160 113 344 234 2 44 275 3 3.9 17.2
52045-D 200 139 445 300 2 54 362 4 3.9 17.2
52049-D 250 160 487 325 1+1 71 + 54 404 + 362 4 3.9 17.2
52053-D 250 177 - 342 2 71 404 4 3.9 17.2
52058-D 315 192 - 459 1+1 83 + 71 513 + 404 4 3.9 17.2
52060-D 315 204 - 471 2 83 513 4 3.9 17.2
53064-D 250 181 487 342 1+2 54 + 44 362 + 275 6 3.9 17.2
53068-D 315 201 507 362 3 54 362 6 3.9 17.2
53070-D 315 222 549 387 1+2 71 + 54 404 + 362 6 3.9 17.2
53080-D 400 256 - 421 3 71 404 6 3.9 17.2
53084-D 400 271 - 538 1+2 83 + 71 513 + 404 6 3.9 17.2
53086-D 400 283 - 550 2+1 83 + 71 513 + 404 6 3.9 17.2
54095-D 400 301 628 466 2+2 71 + 54 404 + 362 8 3.9 17.2
54106-D 500 335 - 500 4 71 404 8 3.9 17.2
54114-D 500 362 - 629 2+2 83 + 71 513 + 404 8 3.9 17.2
54120-D 500 386 - 653 4 83 513 8 3.9 17.2
Table 8
LEGEND:

MFA Maximum Fuse Ampere (For Fuse/ circuit breaker sizing DOL Direct On Line Start
complies with NEC Article 440-22 & 430-52.
PWS Part Winding Start
MCA Minimum Circuit Amps (For Wire sizing), complies with NEC
Article 440-33. LRA Locked Rotor Amps

RLA Rated Load Amps (at Worst operating Condition). FLA Full Load Amps

ICF Maximum Instantaneous Current Flow.

Note :
Voltage imbalance not to exceed 2 % of the rated voltage

19
SKM Air Cooled Condensing Units
ACUV-D Series - R-134a
ELECTRICALDATA
ELECTRICAL DATA
Power Supply: 440V/3PH/50Hz
Unit Characteristic
Model Compressor Condenser Fan Motor
ICF
ACUV MFA MCA
DOL PWS QTY RLA LRA QTY FLA LRA
51008-D 50 29 109 - 1 20 105 2 0.95 3.42
51010-D 63 33 127 - 1 23 123 2 0.95 3.42
51014-D 100 51 206 - 1 36 196 2 2.1 7.6
52015-D 80 51 135 - 2 20 105 2 2.1 7.6
52017-D 80 55 153 - 1+1 23 + 20 123 + 105 2 2.1 7.6
52019-D 100 61 164 - 2 23 123 2 3.5 14.7
51021-D 125 62 274 - 1 42 256 2 3.5 14.7
51022-D 160 74 355 - 1 52 337 2 3.5 14.7
52022-D 125 77 237 - 1+1 36 + 23 196 + 123 2 3.5 14.7
51028-D 200 98 - 341 1 68 376 3 3.5 14.7
52028-D 160 94 254 - 2 36 196 3 3.5 14.7
52030-D 160 88 301 - 1+1 42 + 23 256 + 123 3 3.5 14.7
51030-D For Details, Please consult SKM
52034-D 160 101 314 - 1+1 42 + 36 256 + 196 3 3.5 14.7
52040-D 160 107 320 - 2 42 256 3 3.5 14.7
52045-D 200 133 414 - 2 52 337 4 3.5 14.7
52049-D 250 153 453 - 1+1 68 + 52 376 + 337 4 3.5 14.7
52053-D 250 169 - 413 2 68 376 4 3.5 14.7
52058-D
For Details, Please consult SKM
52060-D
53064-D 250 172 453 - 1+2 52 + 42 337 + 256 6 3.5 14.7
53068-D 250 192 473 - 3 52 337 6 3.5 14.7
53070-D 315 212 512 - 1+2 68 + 52 376 + 337 6 3.5 14.7
53080-D 315 244 - 488 3 68 376 6 3.5 14.7
53084-D
For Details, Please consult SKM
53086-D
54095-D 400 287 587 - 2+2 68 + 52 376 + 337 8 3.5 14.7
54106-D 400 319 - 563 4 68 376 8 3.5 14.7
54114-D
For Details, Please consult SKM
54120-D
Table 9
LEGEND:

MFA Maximum Fuse Ampere (For Fuse/ circuit breaker sizing DOL Direct On Line Start
complies with NEC Article 440-22 & 430-52.
PWS Part Winding Start
MCA Minimum Circuit Amps (For Wire sizing), complies with NEC
Article 440-33. LRA Locked Rotor Amps

RLA Rated Load Amps (at Worst operating Condition). FLA Full Load Amps

ICF Maximum Instantaneous Current Flow.

Note :
Voltage imbalance not to exceed 2 % of the rated voltage

20
SKM Air Cooled Condensing Units
ACUV-D Series - R-134a
ELECTRICALDATA
ELECTRICAL DATA
Power Supply: 380V/3PH/60Hz
Unit Characteristic
Model Compressor Condenser Fan Motor
ICF
ACUV MFA MCA
DOL PWS QTY RLA LRA QTY FLA LRA
61009-D 50 30 149 92 1 20 143 2 1.5 4.5
61011-D 63 34 174 107 1 23 168 2 1.5 4.5
61016-D 100 53 281 174 1 36 268 2 3.1 9.6
62018-D 80 53 176 119 2 20 143 2 3.1 9.6
62020-D 80 57 201 134 1+1 23 + 20 168 + 143 2 3.1 9.6
62022-D 100 64 214 147 2 23 168 2 5.3 17.5
61024-D 160 80 372 232 1 54 349 2 5.3 17.5
61026-D 200 95 483 299 1 66 460 2 5.3 17.5
62026-D 125 81 314 207 1+1 36 + 23 268 + 168 2 5.3 17.5
61032-D 250 127 - 336 1 87 513 3 5.3 17.5
62032-D 160 99 332 225 2 36 268 3 5.3 17.5
62034-D 200 108 400 261 1+1 54 + 23 349 + 168 3 5.3 17.5
61036-D 250 144 - 462 1 101 620 3 5.3 17.5
62040-D 200 121 413 274 1+1 54 + 36 349 + 268 3 5.3 17.5
62046-D 200 139 431 292 2 54 349 3 5.3 17.5
62052-D 250 172 559 375 2 66 460 4 5.3 17.5
62058-D 315 198 612 407 1+1 87 + 66 513 + 460 4 5.3 17.5
62062-D 315 219 - 428 2 87 513 4 5.3 17.5
62067-D 400 236 - 554 1+1 101 + 87 620 + 513 4 5.3 17.5
62071-D 400 250 - 568 2 101 620 4 5.3 17.5
63074-D 315 224 612 428 1+2 66 + 54 460 + 349 6 5.3 17.5
63078-D 315 248 636 452 3 66 460 6 5.3 17.5
63082-D 400 275 689 484 1+2 87 + 66 513 + 460 6 5.3 17.5
63094-D 500 317 - 526 3 87 513 6 5.3 17.5
63098-D 500 334 - 652 1+2 101 + 87 620 + 513 6 5.3 17.5
63100-D 500 348 - 666 2+1 101 + 87 620 + 513 6 5.3 17.5
64113-D 500 372 787 581 2+2 87 + 66 513 + 460 8 5.3 17.5
64124-D 630 414 - 623 4 87 513 8 5.3 17.5
64132-D 630 446 - 764 2+2 101 + 87 620 + 513 8 5.3 17.5
64140-D 630 474 - 792 4 101 620 8 5.3 17.5
Table 10
LEGEND:

MFA Maximum Fuse Ampere (For Fuse/ circuit breaker sizing DOL Direct On Line Start
complies with NEC Article 440-22 & 430-52.
PWS Part Winding Start
MCA Minimum Circuit Amps (For Wire sizing), complies with NEC
Article 440-33. LRA Locked Rotor Amps

RLA Rated Load Amps (at Worst operating Condition). FLA Full Load Amps

ICF Maximum Instantaneous Current Flow.

Note :
Voltage imbalance not to exceed 2 % of the rated voltage

21
SKM Air Cooled Condensing Units
ACUV-D Series - R-134a
ELECTRICAL DATA
ELECTRICAL DATA
Power Supply: 460V/3PH/60Hz
Unit Characteristic
Model Compressor Condenser Fan Motor
ICF
ACUV MFA MCA
DOL PWS QTY RLA LRA QTY FLA LRA
61009-D 50 26 120 74 1 17 113 2 1.3 5.2
61011-D 50 28 139 86 1 19 132 2 1.3 5.2
61016-D 80 46 226 142 1 30 211 2 3.1 11.8
62018-D 63 46 145 100 2 17 113 2 3.1 11.8
62020-D 80 49 164 111 1+1 19 + 17 132 + 113 2 3.1 11.8
62022-D 80 55 177 124 2 19 132 2 5 21
61024-D 125 68 301 191 1 45 275 2 5 21
61026-D 160 81 388 243 1 55 362 2 5 21
62026-D 125 69 256 172 1+1 30 + 19 211 + 132 2 5 21
61032-D 200 106 - 273 1 71 404 3 5 21
62032-D 125 85 272 188 2 30 211 3 5 21
62034-D 160 92 325 215 1+1 45 + 19 275 + 132 3 5 21
61036-D 250 122 - 390 1 84 513 3 5 21
62040-D 160 103 336 226 1+1 45 + 30 275 + 211 3 5 21
62046-D 200 118 351 241 2 45 275 3 5 21
62052-D 250 146 453 308 2 55 362 4 5 21
62058-D 250 166 495 333 1+1 71 + 55 404 + 362 4 5 21
62062-D 315 182 - 349 2 71 404 4 5 21
62067-D 315 198 - 466 1+1 84 + 71 513 + 404 4 5 21
62071-D 315 184 - 361 2 72 362 4 5 21
63074-D 250 191 498 353 1+2 55 + 45 362 + 275 6 5 21
63078-D 315 211 518 373 3 55 362 6 5 21
63082-D 315 231 560 398 1+2 71 + 55 404 + 362 6 5 21
63094-D 400 263 - 430 3 71 404 6 5 21
63098-D 400 279 - 547 1+2 84 + 71 513 + 404 6 5 21
63100-D 400 292 - 560 2+1 84 + 71 513 + 404 6 5 21
64113-D 400 312 641 479 2+2 71 + 55 404 + 362 8 5 21
64124-D 500 344 - 511 4 71 404 8 5 21
64132-D 500 373 - 641 2+2 84 + 71 513 + 404 8 5 21
64140-D 500 399 - 667 4 84 513 8 5 21
Table 11
LEGEND:

MFA Maximum Fuse Ampere (For Fuse/ circuit breaker sizing DOL Direct On Line Start
complies with NEC Article 440-22 & 430-52.
PWS Part Winding Start
MCA Minimum Circuit Amps (For Wire sizing), complies with NEC
Article 440-33. LRA Locked Rotor Amps

RLA Rated Load Amps (at Worst operating Condition). FLA Full Load Amps

ICF Maximum Instantaneous Current Flow.

Note :
Voltage imbalance not to exceed 2 % of the rated voltage

22
SKM Air Cooled Condensing Units
ACUV-D Series - R-134a
ELECTRICALDATA
ELECTRICAL DATA
Power Supply: 220V/3PH/60Hz
Unit Characteristic
Model Compressor Condenser Fan Motor
ICF
ACUV MFA MCA
DOL PWS QTY RLA LRA QTY FLA LRA
61009-D 100 48 248 153 1 33 238 2 2.5 7.5
61011-D 100 55 288 177 1 38 278 2 2.5 7.5
61016-D 160 85 466 289 1 58 444 2 5.4 16.7
62018-D 125 87 293 198 2 33 238 2 5.4 16.7
62020-D 160 93 333 222 1+1 38 + 33 278 + 238 2 5.4 16.7
62022-D 160 106 355 244 2 38 278 2 9 29.7
61024-D 250 131 - 386 1 89 579 2 9 29.7
61026-D 315 156 - 496 1 109 762 2 9 29.7
62026-D 200 131 521 343 1+1 58 + 38 444 + 278 2 9 29.7
61032-D 400 208 - 533 1 143 808 3 9 29.7
62032-D 250 160 550 372 2 58 444 3 9 29.7
62034-D 315 178 665 433 1+1 89 + 38 579 + 278 3 9 29.7
61036-D 500 238 - 909 1 167 1230 3 9 29.7
62040-D 315 198 685 453 1+1 89 + 58 579 + 444 3 9 29.7
62046-D 400 229 - 484 2 89 579 3 9 29.7
62052-D 400 283 - 623 2 109 762 4 9 29.7
62058-D 500 326 - 651 1+1 143 + 109 808 + 762 4 9 29.7
62062-D 630 360 - 685 2 143 808 4 9 29.7
62067-D 630 390 - 1061 1+1 167 + 143 1230 + 808 4 9 29.7
62071-D 630 414 - 1085 2 167 1230 4 9 29.7
63074-D 500 370 - 710 1+2 109 + 89 762 + 579 6 9 29.7
63078-D 630 410 - 750 3 109 762 6 9 29.7
63082-D 630 453 - 778 1+2 143 + 109 808 + 762 6 9 29.7
63094-D 800 521 - 846 3 143 808 6 9 29.7
63098-D 800 551 - 1222 1+2 167 + 143 1230 + 808 6 9 29.7
63100-D 800 575 - 1246 2+1 167 + 143 1230 + 808 6 9 29.7
64113-D 800 614 - 939 2+2 143 + 109 808 + 762 8 9 29.7
64124-D 1000 682 - 1007 4 143 808 8 9 29.7
64132-D 1000 736 - 1407 2+2 167 + 143 1230 + 808 8 9 29.7
64140-D 1000 784 - 1455 4 167 1230 8 9 29.7
Table 12
LEGEND:

MFA Maximum Fuse Ampere (For Fuse/ circuit breaker sizing DOL Direct On Line Start
complies with NEC Article 440-22 & 430-52.
PWS Part Winding Start
MCA Minimum Circuit Amps (For Wire sizing), complies with NEC
Article 440-33. LRA Locked Rotor Amps

RLA Rated Load Amps (at Worst operating Condition). FLA Full Load Amps

ICF Maximum Instantaneous Current Flow.

Note :
Voltage imbalance not to exceed 2 % of the rated voltage

23
SKM Air Cooled Condensing Units
ACUV-D Series - R-134a
ACUV Models - 51008D-51010D & 61009D-61011D
10 10
LEGEND [254] [254]
Dimensional Data 1 CONDENSER FAN
2 CONDENSER COIL A1
ACUV Models:
ACUV Models51008-D-51010-D CONTROL& 61009-D-61011-D
- 51008D-51010D 3& 61009D-61011D
PANEL A3
4 COMPRESSOR
10 10
ALL DIMENSIONS ARE IN INCHES [mm]
LEGEND [254] [254]
1 CONDENSER FAN
2 CONDENSER COIL A1
3 CONTROL PANEL A3
4 COMPRESSOR
ALL DIMENSIONS ARE IN INCHES [mm] A2 A4

45 68
[1143] [1727]
3
A2 A4

45 68
[1143] [1727]
VENTILATION
3
ON BOTH SIDES
SUCTION

[1312]
51.6
LIQUID
DETACHABLE
VENTILATION
PLATE FOR
[457]

ON BOTH SIDESENTRY RIGGING HOLES


18

CABLE SUCTION

[1312]
0.79 [20] 4 Nos.

51.6
LIQUID ACCESS
DETACHABLE
PLATE FOR
[178]

[100]
[457]

RIGGING HOLES 8

3.9
18

CABLE ENTRY 0.79 [20] 4 Nos.


[203]
ACCESS
[178]

[100]
8

3.9
7

[203]

ACUV Models - 51014D to 52022D & 61016D to 62026D


ACUV Models: 51014D - 52022D & 61016D - 62026D
ACUV Models - 51014D to 52022D & 61016D to 62026D
LEGEND 10 10
1 CONDENSER FAN [254] [254]

LEGEND2 CONDENSER COIL 10 10


3 CONTROL
1 CONDENSER FAN PANEL [254] A1 [254]
4 COMPRESSOR
2 CONDENSER COIL A3
ALL DIMENSIONS
3 CONTROL PANEL ARE IN INCHES [mm] A1
4 COMPRESSOR
MODEL DIMENSIONS A3
ALL DIMENSIONS
ACUV ARE LIN INCHES
W [mm] H A B
*51014D 56 74 51.65 20.67 -
*61016D [1422] [1880] [1312] [525] -
52015D 56 74 51.65 18 18
62018D [1422] [1880] [1312] [457] [457]
52017D 56 76 51.65 18 18
62020D [1422] [1930] [1312] [457] [457]
52019D 56 84 59.65 18 18
62022D [1422] [2134] [1515] [457] [457]
*51021D 58 84 59.65 20.67 -
A2 A4
*61024D [1473] [2134] [1515] [525] -
*51022D 58 84 59.65 22.72 - A2 A4
*61026D [1473] [2134] [1515] [577] -
52022D 58 84 59.65 20.67 18
62026D [1473] [2134] [1515] [525] [457]
*MODEL WITH ONE COMPRESSOR Table 13
DIM.12" INSTEAD OF 10" & 4" FOR ONE COMPRESSOR MODEL
ALL DIMENSIONS ARE IN INCHES [mm]
L W
3 L W
3
1 1

SUCTION #1 SUCTION #1 SUCTION #2 SUCTION #2


VENTILATION
VENTILATION LIQUID #2 LIQUID #2
ON BOTH SIDESSIDES
ON BOTH LIQUID #1 LIQUID #1 RIGGING HOLES
2 RIGGING HOLES
H

2 0.79 [20] 4 Nos.


H

0.79 [20] 4 Nos.


[100]
3.94

DETACHABLE
[100]
A3.94

DETACHABLE
PLATE FOR
CABLEPLATE
ENTRYFOR
B

B
A

CABLE ENTRY

4 ACCESS 4*
4*
4 4*
[178]

[178]

ACCESS
4* [101]
7

7
[178]

[178]

[101]
[101]
7

10 * [101] 10*
[254] 10 * [254] 10*
[254] [254]

24
SKM Air Cooled Condensing Units
ACUV-D Series - R-134a
Dimensional Data
ACUV Models - 51028D to 52040D & 61032D to 62046D

ACUV Models: 51028D - 52040D & 61032D- 62046D


10 10 LEGEND
[254] [254] 1 CONDENSER FAN
A1 A3
ACUV Models - 51028D to 52040D & 61032D to 62046D 2 CONDENSER COIL
3 CONTROL PANEL
4 COMPRESSOR
10 10 LEGEND
ALL DIMENSIONS ARE IN INCHES [mm]
[254] [254] 1 CONDENSER FAN
A1 A3 MODEL COIL DIMENSIONS
2 CONDENSER
ACUV- H A B
3 CONTROL PANEL
*51028D 60.63 24.8 -
4 COMPRESSOR
*61032D [1540] [630] -
ALL DIMENSIONS ARE IN INCHES [mm]
52028D 60.63 20.67 20.67
62032D [1540] [525] [525]
52030D 60.63 20.67 18
62034D [1540] [525] [457]
*51030D 60.63 24.8 -
*61036D [1540] [630] -
A2 A4 52034D 76.65 20.67 20.67
62040D [1947] [525] [525]
52040D 76.65 20.67 20.67
62046D [1947] [525] [525]
A2 A4 *MODEL WITH ONE COMPRESSOR
DIM.12" INSTEAD OF 10" & 4" FOR ONE COMPRESSOR MODOL
Table 14
ALL DIMENSIONS ARE IN INCHES [mm]

76 88
[1930] [2235]
76 1 88
3 [1930] [2235]
SUCTION #1
1 SUCTION #2
3
SUCTION #1
SUCTION #2
2 LIQUID #1 LIQUID #2
VENTILATION
ON BOTH SIDES VENTILATION 2 LIQUID #1 LIQUID #2
H

ON BOTH SIDES
H
[100]
3.9

AA
[100]

B
3.9

DETACHABLE DETACHABLE

B
PLATE FOR PLATE FOR
CABLE ENTRY CABLE ENTRY
4 *4 * ACCESS
ACCESS 4* 4*
[178]

[178]
[178]

[178]
4 4 [102]
[102] [102] [102]
77

7
10* 10 *
10* 10 *
[254] [254]
[254] [254]

ACUV Models: ACUV


52045D - 52060D
Models - 52045D & 62052D
to 52060D & 62052D to 62071D - 62071D
ACUV Models - 52045D10to 52060D & 62052D to 62071D 10 LEGEND
[254] [254] 1 LEGEND
CONDENSER FAN
10 10
A1 A3 [254] 2 CONDENSER COIL
[254] 1 CONDENSER FAN
3 CONTROL PANEL
A1 A3 2 CONDENSER COIL
4 COMPRESSOR
3 CONTROL
ALL DIMENSIONS AREPANEL
IN INCHES [mm]
4 COMPRESSOR DIMENSIONS
MODEL
ACUV- H ARE IN INCHES
A
ALL DIMENSIONS [mm]B
52045D 77.63 23.7 23.7
62052D [1972] [602] [602]
52049D 85.63 25.79 23.7
62058D [2175] [655] [602]
52053D 85.63 25.79 25.79
62062D [2175] [655] [655]
52058D 85.63 25.79 25.79
62067D [2175] [655] [655]
A2 A4 52060D 85.63 25.79 25.79
62071D [2175] [655] [655]
ALL DIMENSIONS ARE IN INCHES [mm] Table 15
84 88
[2134] [2235]
A2 A4 1
3

84 88
FILTERED SUCTION #1 SUCTION #2
VENTILATION [2134] 2 [2235]
ON BOTH SIDES 1
3
H

LIQUID #1 LIQUID #2
DETACHABLE
[125]

PLATE FOR
4.92

FILTERED CABLE ENTRY SUCTION #1 SUCTION #2


A

2
B

VENTILATION
ON BOTH SIDES
ACCESS
H

4
LIQUID #1 LIQUID #2
[203]

[203]
8

RIGGING HOLES 4 4
DETACHABLE .79 [20] 4 Nos.
[102] [102]
[125]

PLATE FOR
4.92

10 10
CABLE ENTRY [254] [254]
A

ACCESS
25
4
[203]

[203]
8

8
SKM Air Cooled Condensing Units
ACUV-D Series - R-134a
Dimensional Data
ACUV Models - 53064D to 53086D & 63074D to 63100D
ACUV Models: 53064D - 53086D & 63074 - 63100D
LEGEND 10 10
[254] [254]
1 CONDENSER FAN A1 A3 A5
ACUV Models - 53064D to 53086D & 63074D to 63100D
2 CONDENSER COIL
3 CONTROL PANEL 10 10
LEGEND
4 COMPRESSOR [254] [254]
1 CONDENSER FAN A1 A3 A5
ALL
2 DIMENSIONS
CONDENSER ARE
COILIN INCHES [mm] CIRCUIT-A
3 CONTROL PANEL CIRCUIT-B
4 COMPRESSOR CIRCUIT-C
ALL DIMENSIONS ARE IN INCHES [mm] CIRCUIT-A
CIRCUIT-B
CIRCUIT-C

A2 A4 A6

135.6
A2 A4 [3445] A6
47 88.6 12
88 [1195] 135.6
[2250] [305]
[2235] [3445]
47 2 1
88.6 PARTITION 12
88 [1195] [2250] [305]
[2235]
2 1 PARTITION

FILTERED
VENTILATION
105.92
[2690]

[2420][2420]
95.2995.29

LIQUID x3Nos. FILTERED


ON BOTH SIDES
VENTILATION
105.92
[2690]

LIQUID x3Nos. ON BOTH SIDES

DETACHABLE
[125][125]
4.924.92

PLATE FOR
[750][750]
29.529.5

DETACHABLE
CABLE
PLATE FOR ENTRY
CABLE ENTRY

4
SUCTION x3Nos. RIGGING HOLES 4
SUCTION x3Nos. RIGGING HOLES
8/7 [22] x 4 Nos.
8/7 [22] x 4 Nos.

ACUV Models:
ACUV 54095D
ACUVModels
Models 54095D to-54120D
-- 54095D 54120D
54120D &toto64113
&& 64113D
64113D 64140D - 64140D
64140D

LEGEND 1010 20 20 10 10
LEGEND
[254]
[254] [508][508] [254] [254]
1 CONDENSER FAN
1 CONDENSER FAN A1 A3 A5 A7
2 CONDENSER COIL A1 A3 A5 A7
2 CONDENSER COIL
3 CONTROL PANEL
3 CONTROL PANEL
4 COMPRESSOR
4 COMPRESSOR
ALL DIMENSIONS ARE IN INCHES [mm] CIRCUIT-A
ALL DIMENSIONS ARE IN INCHES [mm] CIRCUIT-A
CIRCUIT-B
CIRCUIT-C
CIRCUIT-B
CIRCUIT-D
CIRCUIT-C
CIRCUIT-D

A2 A4 A6 A8
177.2
A2 A4 A6 A8
[4500]
88.6 88.6 12
88 177.2
[2250] [2250] [305]
[2235] [4500]
PARTITION 88.6 2 1 88.6
PARTITION 12
88 [2250] [2250] [305]
[2235]
PARTITION 2 1 PARTITION 3

3
FILTERED
VENTILATION
106.92

[2420]
[2715]
95.29

LIQUID x4Nos. ON BOTH SIDES

FILTERED
VENTILATION
DETACHABLE
106.92

[2420]
[2715]
95.29

LIQUID x4Nos. PLATEON BOTH SIDES


FOR
[150]
5.92

[750]
29.5

CABLE ENTRY

DETACHABLE
PLATE FOR
[150]
5.92

[750]

4 4
29.5

SUCTION x4Nos. RIGGING HOLES CABLE ENTRY


8/7 [22] x 4 Nos.

4 4
SUCTION x4Nos. RIGGING HOLES
26 8/7 [22] x 4 Nos.
SKM Air Cooled Condensing Units
ACUV-D Series - R-134a

LOADING POINTS
50 Hz
LOADING POINTS TOTAL
ACUV UNIT
A1 A2 A3 A4 A5 A6 A7 A8 WEIGHT
Ib. 221 209 236 209 - - - - 876
51008-D
Kg. 100 95 107 95 - - - - 397
Ib. 232 221 245 221 - - - - 917
51010-D
Kg. 105 100 111 100 - - - - 416
Ib. 300 280 324 280 - - - - 1184
51014-D
Kg. 136 127 147 127 - - - - 537
Ib. 342 329 364 329 - - - - 1363
52015-D
Kg. 155 149 165 149 - - - - 618
Ib. 348 337 368 333 - - - - 1387
52017-D
Kg. 158 153 167 151 - - - - 629
Ib. 368 355 392 355 - - - - 1471
52019-D
Kg. 167 161 178 161 - - - - 667
Ib. 355 254 485 254 - - - - 1347
51021-D
Kg. 161 115 220 115 - - - - 611
Ib. 346 326 368 326 - - - - 1367
51022-D
Kg. 157 148 167 148 - - - - 620
Ib. 426 417 410 373 - - - - 1625
52022-D
Kg. 193 189 186 169 - - - - 737
Ib. 448 410 443 445 - - - - 1746
51028-D
Kg. 203 186 201 202 - - - - 792
Ib. 529 492 549 549 - - - - 2119
52028-D
Kg. 240 223 249 249 - - - - 961
Ib. 505 496 507 558 - - - - 2066
52030-D
Kg. 229 225 230 253 - - - - 937
Ib. 487 450 531 533 - - - - 2001
51030-D
Kg. 221 204 241 242 - - - - 908
Ib. 593 567 620 637 - - - - 2417
52034-D
Kg. 269 257 281 289 - - - - 1096
Ib. 613 576 650 650 - - - - 2489
52040-D
Kg. 278 261 295 295 - - - - 1129
Ib. 655 617 858 858 - - - - 2988
52045-D
Kg. 297 280 389 389 - - - - 1355
Ib. 675 639 875 878 - - - - 3067
52049-D
Kg. 306 290 397 398 - - - - 1391
Ib. 675 637 878 878 - - - - 3067
52053-D
Kg. 306 289 398 398 - - - - 1391
Ib. 800 750 975 1050 - - - - 3574
52058-D
Kg. 363 340 442 476 - - - - 1621
Ib. 840 765 1107 1107 - - - - 3819
52060-D
Kg. 381 347 502 502 - - - - 1732
Ib. 690 902 1054 904 856 1069 - - 5475
53064-D
Kg. 313 409 478 410 388 485 - - 2483
Ib. 692 904 1063 908 860 1076 - - 5504
53068-D
Kg. 314 410 482 412 390 488 - - 2496
Ib. 734 948 1103 950 900 1116 - - 5751
53070-D
Kg. 333 430 500 431 408 506 - - 2608
Ib. 770 983 1142 988 935 1155 - - 5973
53080-D
Kg. 349 446 518 448 424 524 - - 2709
Ib. 817 1127 1158 1032 935 1155 - - 6224
53084-D
Kg. 371 511 525 468 424 524 - - 2823
Ib. 817 1128 1347 1096 935 1155 - - 6479
53086-D
Kg. 371 512 611 497 424 524 - - 2938
Ib. 926 745 745 924 922 743 904 1083 6992
54095-D
Kg. 420 338 338 419 418 337 410 491 3171
Ib. 959 781 778 959 959 781 942 1122 7281
54106-D
Kg. 435 354 353 435 435 354 427 509 3302
Ib. 1127 867 864 1127 961 781 942 1122 7790
54114-D
Kg. 511 393 392 511 436 354 427 509 3533
Ib. 1129 867 864 1127 1129 867 1028 1290 8300
54120-D
Kg. 512 393 392 511 512 393 466 585 3764
Table 16

27
SKM Air Cooled Condensing Units
ACUV-D Series - R-134a
LOADING POINTS
60 Hz
LOADING POINTS TOTAL
ACUV UNIT
A1 A2 A3 A4 A5 A6 A7 A8 WEIGHT
Ib. 222 212 238 212 - - - - 884
61009-D
Kg. 101 96 108 96 - - - - 401
Ib. 232 221 247 221 - - - - 920
61011-D
Kg. 105 100 112 100 - - - - 417
Ib. 302 284 326 284 - - - - 1197
61016-D
Kg. 137 129 148 129 - - - - 543
Ib. 344 331 366 331 - - - - 1372
62018-D
Kg. 156 150 166 150 - - - - 622
Ib. 351 340 370 335 - - - - 1396
62020-D
Kg. 159 154 168 152 - - - - 633
Ib. 375 362 399 362 - - - - 1497
62022-D
Kg. 170 164 181 164 - - - - 679
Ib. 348 329 373 329 - - - - 1378
61024-D
Kg. 158 149 169 149 - - - - 625
Ib. 351 331 373 331 - - - - 1385
61026-D
Kg. 159 150 169 150 - - - - 628
Ib. 432 423 417 379 - - - - 1652
62026-D
Kg. 196 192 189 172 - - - - 749
Ib. 459 421 450 452 - - - - 1782
61032-D
Kg. 208 191 204 205 - - - - 808
Ib. 538 503 556 556 - - - - 2152
62032-D
Kg. 244 228 252 252 - - - - 976
Ib. 518 509 516 567 - - - - 2110
62034-D
Kg. 235 231 234 257 - - - - 957
Ib. 498 459 538 540 - - - - 2035
61036-D
Kg. 226 208 244 245 - - - - 923
Ib. 606 580 626 644 - - - - 2456
62040-D
Kg. 275 263 284 292 - - - - 1114
Ib. 626 589 659 659 - - - - 2534
62046-D
Kg. 284 267 299 299 - - - - 1149
Ib. 668 631 869 869 - - - - 3036
62052-D
Kg. 303 286 394 394 - - - - 1377
Ib. 688 650 886 889 - - - - 3113
62058-D
Kg. 312 295 402 403 - - - - 1412
Ib. 688 650 889 889 - - - - 3116
62062-D
Kg. 312 295 403 403 - - - - 1413
Ib. 814 763 986 1061 - - - - 3623
62067-D
Kg. 369 346 447 481 - - - - 1643
Ib. 853 781 1120 1120 - - - - 3874
62071-D
Kg. 387 354 508 508 - - - - 1757
Ib. 703 915 1067 917 869 1083 - - 5554
63074-D
Kg. 319 415 484 416 394 491 - - 2519
Ib. 706 917 1074 922 871 1089 - - 5579
63078-D
Kg. 320 416 487 418 395 494 - - 2530
Ib. 745 959 1114 961 911 1129 - - 5819
63082-D
Kg. 338 435 505 436 413 512 - - 2639
Ib. 781 994 1155 999 946 1166 - - 6042
63094-D
Kg. 354 451 524 453 429 529 - - 2740
Ib. 829 1140 1169 1045 946 1166 - - 6295
63098-D
Kg. 376 517 530 474 429 529 - - 2855
Ib. 829 1140 1358 1107 946 1166 - - 6546
63100-D
Kg. 376 517 616 502 429 529 - - 2969
Ib. 937 756 756 937 933 754 917 1094 7085
64113-D
Kg. 425 343 343 425 423 342 416 496 3213
Ib. 972 792 792 972 972 792 953 1133 7378
64124-D
Kg. 441 359 359 441 441 359 432 514 3346
Ib. 1140 878 878 1138 972 792 953 1133 7883
64132-D
Kg. 517 398 398 516 441 359 432 514 3575
Ib. 1140 878 878 1138 1140 878 1039 1301 8390
64140-D
Kg. 517 398 398 516 517 398 471 590 3805
Table 17

28
SKM Air Cooled Condensing Units
ACUV-D Series - R-134a
Location and Space Requirements

ACUV A B C
Due to the vertical air flow discharge condenser design, it is 51008-D 61009-D
recommended that certain precautions are to be taken before 51010-D 61011-D
42

installation. There should be no obstruction on the air flow. 51014-D 61016-D 40 60


52015-D 62018-D
50
Orient the unit so that prevailing winds blow parallel to the unit 52017-D 62020-D
52019-D 62022-D
length thus minimizing the effects on condensing pressure.
51021-D 61024-D
If it is not practical to orient the unit in this manner, a wind 51022-D 61026-D 56
deflecting shield should be considered. 52022-D 62026-D
48 72
51028-D 61032-D
It is also necessary to provide adequate clearance on all sides 52028-D 62032-D

of the unit for service access and satisfactory performance. 52030-D 62034-D
66
51030-D 61036-D
This will prevent excessive condensing temperatures and
52034-D 62040-D
enhance system performance and operating economy. 52040-D 62046-D 64 96
52045-D 62052-D
A flat concrete foundation or floor which can support the 52049-D 62058-D
weight of the equipment must be provided as the unit must be 52053-D 62062-D
72
78
108
52058-D 62067-D
level for proper operation and functioning of controls.
52060-D 62071-D
53064-D 63074-D
Under certain critical conditions it is recommended that 53068-D 63078-D
vibration isolators of rubber-in-shear or spring type be installed 53070-D 63082-D
under the base. 53080-D 63094-D
53084-D 63098-D
84 46 90
The isolators must be designed for the operating weight of the 53086-D 63100-D
54095-D 64113-D
unit. For operating load points refer to Loading Points Data
54106-D 64124-D
(page 27 & 28).Correct selection of types of isolators depends 54114-D 64132-D
upon application and structure. 54120-D 64140-D

ALL DIMENSIONS ARE IN INCHES [mm] Table 18

Single Unit Installation


SPACING FOR SERVICE DUCT

SPACING FOR AIR FLOW A

DUCT
A

B
A

78
[1981]
PACV- 52060-D & 52065-D
DUCT

PACV- 62070-D & 62076-D

DUCT
A*
A

PACV- 51008-D TO 52055-D


PACV- 61009-D TO 62064-D

DUCT
46
A*

[1165]

SPACING FOR BOTH AIR FLOW AND SERVICE PACV- 53070-D TO 54125-D
*

PACV- 63082-D TO 64145-D

29
SKM Air Cooled Condensing Units
ACUV-D Series - R-134a
Multiple Units Installation

SPACING FOR SERVICE AND ACCESS


B

A*
SPACING FOR AIR FLOW
B

C*
C
A

A*
B

ACUV - 51008D to 52060D ACUV - 53064D to 54120D


ACUV - 61009D to 62071D ACUV - 63074D to 64140D

*
SPACING FOR AIRFLOW & SERVICE

30
SKM Air Cooled Condensing Units
ACUV-D Series - R-134a
Typical Refrigeration Piping

Legend
1

1. Expansion Valve. 3
2

AIR
2. Sight Glass. 4
FLOW

5
3. Solenoid Valve. AHU

4. Filter Drier.
5. Shut Off Valve. CONDENSING UNIT
6. Liquid Line. 6

7. Suction Line.
1

6
2 7
3
AIR
4 FLOW
5

AHU

CONDENSING UNIT

Single Circuit Unit Shown.


For unit with multiple circuits, DOTTED IN CASE OF
DOUBLE SUCTION RISER

piping will be identical.

Refrigerant Piping
Correct design and size of refrigerant piping is necessary for c. Pressure drop due to vertical lift of liquid line for R-134a
proper operation. The refrigerant piping generally should be 1F (0.55C) sub cooling must be allowed for each 5.5 ft
designed to accomplish the following: (1.7m) vertical rise in order to avoid flash gas forming due
to the weight of the column of liquid refrigerant.
a. To ensure proper refrigerant feed to the evaporator.
b. To provide practical refrigerant line sizes without excessive
SKM ACUV-D Series units are designed with a sub cooling
pressure drop.
circuit enough to sub cool the liquid 12F (6.6 C), which gives
c. To maintain uniform return of lubricating oil to the compressor. the liquid maximum 66 ft. (20m) lift without additional sub cooling.
d. To prevent liquid refrigerant from entering the compressor Liquid suction heat exchanger can be used for additional sub
cooling in order to avoid flash gas forming.
and causing compressor damage due to "slugging".

Field Expansion Valve Selection


Matching DX Coil Selection
The following recommendations should be taken into consideration
when selecting expansion valves in field. For single circuit ACUV-D Series, the DX coil selection in a
MAH or other air handler from SKM should be based on total
1. Expansion valves should be installed as close to the capacity. For multiple circuit ACUV-D Series, extra care should
evaporator as possible, mounted directly to the distributor. be exercised and correspondingly split, by face area or number
of rows to correspond and match the capacity split available in
2. The following possible sources of pressure drop to be the multiple circuited ACUV-D Series selected. For optimum
considered: matching the DX coil should be ordered from SKM as well.

a. Friction losses through refrigerant lines. SKM provides correct no. of feeds and circuits and properly
sized distribution to ensure the correct split on the DX coil is made
b. Pressure drop across valves and controls. available to match the particular selected ACUV-D Series model.

31
SKM Air Cooled Condensing Units
ACUV-D Series - R-134a
Recommended Refrigerant Line Sizes - 50 Hz
Liquid Line, Inches Suction Line, Inches
Model
Circuit 1 Circuit 2 Circuit 3 Circuit 4 Circuit 1 Circuit 2 Circuit 3 Circuit 4
ACUV
25ft 50ft 75ft 100ft 25ft 50ft 75ft 100ft 25ft 50ft 75ft 100ft 25ft 50ft 75ft 100ft 25ft 50ft 75ft 100ft 25ft 50ft 75ft 100ft 25ft 50ft 75ft 100ft 25ft 50ft 75ft 100ft
51008-D 1/2 5/8 5/8 5/8 - - - - - - - - - - - - 1 3/8 1 3/8 1 5/8 1 5/8 - - - - - - - - - - - -
51010-D 5/8 5/8 7/8 7/8 - - - - - - - - - - - - 1 3/8 1 3/8 1 5/8 1 5/8 - - - - - - - - - - - -
51014-D 5/8 7/8 7/8 7/8 - - - - - - - - - - - - 1 3/8 1 5/8 2 1/8 2 1/8 - - - - - - - - - - - -
52015-D 1/2 5/8 5/8 5/8 1/2 5/8 5/8 5/8 - - - - - - - - 1 3/8 1 3/8 1 5/8 1 5/8 1 3/8 1 5/8 1 5/8 1 5/8 - - - - - - - -
52017-D 5/8 5/8 7/8 7/8 1/2 5/8 5/8 5/8 - - - - - - - - 1 3/8 1 3/8 1 5/8 1 5/8 1 3/8 1 5/8 1 5/8 1 5/8 - - - - - - - -
52019-D 5/8 5/8 7/8 7/8 5/8 5/8 7/8 7/8 - - - - - - - - 1 3/8 1 3/8 1 5/8 1 5/8 1 3/8 1 5/8 1 5/8 1 5/8 - - - - - - - -
51021-D 7/8 7/8 7/8 7/8 - - - - - - - - - - - - 1 5/8 2 1/8 2 1/8 2 1/8 - - - - - - - - - - - -
51022-D 7/8 7/8 7/8 1 1/8 - - - - - - - - - - - - 2 1/8 2 1/8 2 1/8 2 5/8 - - - - - - - - - - - -
52022-D 5/8 7/8 7/8 7/8 5/8 5/8 7/8 7/8 - - - - - - - - 1 3/8 1 5/8 2 1/8 2 1/8 1 3/8 1 5/8 1 5/8 1 5/8 - - - - - - - -
51028-D 7/8 7/8 1 1/8 1 1/8 - - - - - - - - - - - - 2 1/8 2 1/8 2 5/8 2 5/8 - - - - - - - - - - - -
52028-D 5/8 7/8 7/8 7/8 5/8 7/8 7/8 7/8 - - - - - - - - 1 3/8 1 5/8 2 1/8 2 1/8 1 3/8 2 1/8 2 1/8 2 1/8 - - - - - - - -
52030-D 7/8 7/8 7/8 7/8 5/8 5/8 7/8 7/8 - - - - - - - - 1 5/8 2 1/8 2 1/8 2 1/8 1 3/8 1 5/8 1 5/8 1 5/8 - - - - - - - -
51030-D 7/8 1 1/8 1 1/8 1 1/8 - - - - - - - - - - - - 2 1/8 2 1/8 2 5/8 2 5/8 - - - - - - - - - - - -
52034-D 7/8 7/8 7/8 7/8 5/8 7/8 7/8 7/8 - - - - - - - - 1 5/8 2 1/8 2 1/8 2 1/8 1 3/8 2 1/8 2 1/8 2 1/8 - - - - - - - -
52040-D 7/8 7/8 7/8 7/8 7/8 7/8 7/8 7/8 - - - - - - - - 1 5/8 2 1/8 2 1/8 2 1/8 1 5/8 2 1/8 2 1/8 2 1/8 - - - - - - - -
52045-D 7/8 7/8 7/8 1 1/8 7/8 7/8 7/8 1 1/8 - - - - - - - - 2 1/8 2 1/8 2 1/8 2 5/8 2 1/8 2 1/8 2 1/8 2 5/8 - - - - - - - -
52049-D 7/8 7/8 1 1/8 1 1/8 7/8 7/8 7/8 1 1/8 - - - - - - - - 2 1/8 2 1/8 2 5/8 2 5/8 2 1/8 2 1/8 2 1/8 2 5/8 - - - - - - - -
52053-D 7/8 7/8 1 1/8 1 1/8 7/8 7/8 1 1/8 1 1/8 - - - - - - - - 2 1/8 2 1/8 2 5/8 2 5/8 2 1/8 2 5/8 2 5/8 2 5/8 - - - - - - - -
52058-D 7/8 1 1/8 1 1/8 1 1/8 7/8 7/8 1 1/8 1 1/8 - - - - - - - - 2 1/8 2 1/8 2 5/8 2 5/8 2 1/8 2 5/8 2 5/8 2 5/8 - - - - - - - -
52060-D 7/8 1 1/8 1 1/8 1 1/8 7/8 1 1/8 1 1/8 1 1/8 - - - - - - - - 2 1/8 2 1/8 2 5/8 2 5/8 2 1/8 2 5/8 2 5/8 2 5/8 - - - - - - - -
53064-D 7/8 7/8 7/8 1 1/8 7/8 7/8 7/8 7/8 7/8 7/8 7/8 7/8 - - - - 2 1/8 2 1/8 2 1/8 2 5/8 1 5/8 2 1/8 2 1/8 2 1/8 1 5/8 2 1/8 2 1/8 2 1/8 - - - -
53068-D 7/8 7/8 7/8 1 1/8 7/8 7/8 7/8 1 1/8 7/8 7/8 7/8 1 1/8 - - - - 2 1/8 2 1/8 2 1/8 2 5/8 2 1/8 2 1/8 2 1/8 2 5/8 2 1/8 2 1/8 2 1/8 2 5/8 - - - -
53070-D 7/8 7/8 1 1/8 1 1/8 7/8 7/8 7/8 1 1/8 7/8 7/8 7/8 1 1/8 - - - - 2 1/8 2 1/8 2 5/8 2 5/8 2 1/8 2 1/8 2 1/8 2 5/8 2 1/8 2 1/8 2 1/8 2 5/8 - - - -
53080-D 7/8 7/8 1 1/8 1 1/8 7/8 7/8 1 1/8 1 1/8 7/8 7/8 1 1/8 1 1/8 - - - - 2 1/8 2 1/8 2 5/8 2 5/8 2 1/8 2 5/8 2 5/8 2 5/8 2 1/8 2 1/8 2 5/8 2 5/8 - - - -
53084-D 7/8 1 1/8 1 1/8 1 1/8 7/8 7/8 1 1/8 1 1/8 7/8 7/8 1 1/8 1 1/8 - - - - 2 1/8 2 1/8 2 5/8 2 5/8 2 1/8 2 5/8 2 5/8 2 5/8 2 1/8 2 1/8 2 5/8 2 5/8 - - - -
53086-D 7/8 1 1/8 1 1/8 1 1/8 7/8 1 1/8 1 1/8 1 1/8 7/8 7/8 1 1/8 1 1/8 - - - - 2 1/8 2 1/8 2 5/8 2 5/8 2 1/8 2 5/8 2 5/8 2 5/8 2 1/8 2 1/8 2 5/8 2 5/8 - - - -
54095-D 7/8 7/8 1 1/8 1 1/8 7/8 7/8 1 1/8 1 1/8 7/8 7/8 7/8 1 1/8 7/8 7/8 7/8 1 1/8 2 1/8 2 1/8 2 5/8 2 5/8 2 1/8 2 5/8 2 5/8 2 5/8 2 1/8 2 1/8 2 1/8 2 5/8 2 1/8 2 1/8 2 1/8 2 5/8
54106-D 7/8 7/8 1 1/8 1 1/8 7/8 7/8 1 1/8 1 1/8 7/8 7/8 1 1/8 1 1/8 7/8 1 1/8 1 1/8 1 1/8 2 1/8 2 1/8 2 5/8 2 5/8 2 1/8 2 5/8 2 5/8 2 5/8 2 1/8 2 1/8 2 5/8 2 5/8 2 1/8 2 1/8 2 5/8 2 5/8
54114-D 7/8 1 1/8 1 1/8 1 1/8 7/8 1 1/8 1 1/8 1 1/8 7/8 7/8 1 1/8 1 1/8 7/8 1 1/8 1 1/8 1 1/8 2 1/8 2 1/8 2 5/8 2 5/8 2 1/8 2 5/8 2 5/8 2 5/8 2 1/8 2 1/8 2 5/8 2 5/8 2 1/8 2 1/8 2 5/8 2 5/8
54120-D 7/8 1 1/8 1 1/8 1 1/8 7/8 1 1/8 1 1/8 1 1/8 7/8 1 1/8 1 1/8 1 1/8 7/8 1 1/8 1 1/8 1 1/8 2 1/8 2 1/8 2 5/8 2 5/8 2 1/8 2 5/8 2 5/8 2 5/8 2 1/8 2 1/8 2 5/8 2 5/8 2 1/8 2 1/8 2 5/8 2 5/8
Table 19

SKM ACUV-D Series Condensing Units are designed for satisfactory operation with single suction line.

1. Suction Line sizing selection recommendation in Table 19 is based on 2F temperature drop.

2. Double suction risers, for applications with systems having large variations in capacity , are recommended to ensure
proper oil flow up and return to compressor.

3. Liquid line sizing selection recommendation in Table 19 is based on 2F temperature drop.

4. Recommended line sizes in Table 19 are for guidance only. For detailed proper piping, consult recognized piping
references like ASHRAE Guide and Data Book for assistance.

5. Equivalent suction and liquid line lengths are shown in Table 19.

SKM is not responsible for faulty or improper design or sizing of refrigerant lines. The above recommendations do not
incorporate necessary slopes, etc. that may be required on horizontal risers, etc.

32
SKM Air Cooled Condensing Units
ACUV-D Series - R-134a
Recommended Refrigerant Line Sizes - 60 Hz
Liquid Line, Inches Suction Line, Inches
Model
Circuit 1 Circuit 2 Circuit 3 Circuit 4 Circuit 1 Circuit 2 Circuit 3 Circuit 4
ACUV
25ft 50ft 75ft 100ft 25ft 50ft 75ft 100ft 25ft 50ft 75ft 100ft 25ft 50ft 75ft 100ft 25ft 50ft 75ft 100ft 25ft 50ft 75ft 100ft 25ft 50ft 75ft 100ft 25ft 50ft 75ft 100ft
61009-D 1/2 5/8 5/8 7/8 - - - - - - - - - - - - 1 3/8 1 3/8 1 5/8 1 5/8 - - - - - - - - - - - -

61011-D 5/8 5/8 7/8 7/8 - - - - - - - - - - - - 1 3/8 1 5/8 1 5/8 2 1/8 - - - - - - - - - - - -

61016-D 5/8 7/8 7/8 7/8 - - - - - - - - - - - - 1 5/8 2 1/8 2 1/8 2 1/8 - - - - - - - - - - - -

62018-D 1/2 5/8 5/8 7/8 1/2 5/8 5/8 7/8 - - - - - - - - 1 3/8 1 3/8 1 5/8 1 5/8 1 3/8 1 5/8 1 5/8 1 5/8 - - - - - - - -

62020-D 5/8 5/8 7/8 7/8 1/2 5/8 5/8 7/8 - - - - - - - - 1 3/8 1 5/8 1 5/8 2 1/8 1 3/8 1 5/8 1 5/8 1 5/8 - - - - - - - -

62022-D 5/8 5/8 7/8 7/8 5/8 5/8 7/8 7/8 - - - - - - - - 1 3/8 1 5/8 1 5/8 2 1/8 1 3/8 1 5/8 1 5/8 2 1/8 - - - - - - - -

61024-D 7/8 7/8 7/8 1 1/8 - - - - - - - - - - - - 2 1/8 2 1/8 2 1/8 2 5/8 - - - - - - - - - - - -

61026-D 7/8 7/8 1 1/8 1 1/8 - - - - - - - - - - - - 2 1/8 2 1/8 2 5/8 2 5/8 - - - - - - - - - - - -

62026-D 5/8 7/8 7/8 7/8 5/8 5/8 7/8 7/8 - - - - - - - - 1 5/8 2 1/8 2 1/8 2 1/8 1 3/8 1 5/8 1 5/8 2 1/8 - - - - - - - -

61032-D 7/8 1 1/8 1 1/8 1 1/8 - - - - - - - - - - - - 2 1/8 2 5/8 2 5/8 2 5/8 - - - - - - - - - - - -

62032-D 5/8 7/8 7/8 7/8 5/8 7/8 7/8 7/8 - - - - - - - - 1 5/8 2 1/8 2 1/8 2 1/8 1 5/8 2 1/8 2 1/8 2 1/8 - - - - - - - -

62034-D 7/8 7/8 7/8 1 1/8 5/8 5/8 7/8 7/8 - - - - - - - - 2 1/8 2 1/8 2 1/8 2 5/8 1 3/8 1 5/8 1 5/8 2 1/8 - - - - - - - -

61036-D 7/8 1 1/8 1 1/8 1 1/8 - - - - - - - - - - - - 2 1/8 2 5/8 2 5/8 2 5/8 - - - - - - - - - - - -

62040-D 7/8 7/8 7/8 1 1/8 5/8 7/8 7/8 7/8 - - - - - - - - 2 1/8 2 1/8 2 1/8 2 5/8 1 5/8 2 1/8 2 1/8 2 1/8 - - - - - - - -

62046-D 7/8 7/8 7/8 1 1/8 7/8 7/8 7/8 1 1/8 - - - - - - - - 2 1/8 2 1/8 2 1/8 2 5/8 2 1/8 2 1/8 2 1/8 2 5/8 - - - - - - - -

62052-D 7/8 7/8 1 1/8 1 1/8 7/8 7/8 1 1/8 1 1/8 - - - - - - - - 2 1/8 2 1/8 2 5/8 2 5/8 2 1/8 2 5/8 2 5/8 2 5/8 - - - - - - - -

62058-D 7/8 1 1/8 1 1/8 1 1/8 7/8 7/8 1 1/8 1 1/8 - - - - - - - - 2 1/8 2 5/8 2 5/8 2 5/8 2 1/8 2 5/8 2 5/8 2 5/8 - - - - - - - -

62062-D 7/8 1 1/8 1 1/8 1 1/8 7/8 1 1/8 1 1/8 1 1/8 - - - - - - - - 2 1/8 2 5/8 2 5/8 2 5/8 2 1/8 2 5/8 2 5/8 2 5/8 - - - - - - - -

62067-D 7/8 1 1/8 1 1/8 1 1/8 7/8 1 1/8 1 1/8 1 1/8 - - - - - - - - 2 1/8 2 5/8 2 5/8 2 5/8 2 1/8 2 5/8 2 5/8 2 5/8 - - - - - - - -

62071-D 7/8 1 1/8 1 1/8 1 1/8 7/8 1 1/8 1 1/8 1 1/8 - - - - - - - - 2 1/8 2 5/8 2 5/8 2 5/8 2 1/8 2 5/8 2 5/8 2 5/8 - - - - - - - -

63074-D 7/8 7/8 1 1/8 1 1/8 7/8 7/8 7/8 1 1/8 7/8 7/8 7/8 1 1/8 - - - - 2 1/8 2 1/8 2 5/8 2 5/8 2 1/8 2 1/8 2 1/8 2 5/8 2 1/8 2 1/8 2 1/8 2 5/8 - - - -

63078-D 7/8 7/8 1 1/8 1 1/8 7/8 7/8 1 1/8 1 1/8 7/8 7/8 1 1/8 1 1/8 - - - - 2 1/8 2 1/8 2 5/8 2 5/8 2 1/8 2 5/8 2 5/8 2 5/8 2 1/8 2 1/8 2 5/8 2 5/8 - - - -

63082-D 7/8 1 1/8 1 1/8 1 1/8 7/8 7/8 1 1/8 1 1/8 7/8 7/8 1 1/8 1 1/8 - - - - 2 1/8 2 5/8 2 5/8 2 5/8 2 1/8 2 5/8 2 5/8 2 5/8 2 1/8 2 1/8 2 5/8 2 5/8 - - - -

63094-D 7/8 1 1/8 1 1/8 1 1/8 7/8 1 1/8 1 1/8 1 1/8 7/8 1 1/8 1 1/8 1 1/8 - - - - 2 1/8 2 5/8 2 5/8 2 5/8 2 1/8 2 5/8 2 5/8 2 5/8 2 1/8 2 5/8 2 5/8 2 5/8 - - - -

63098-D 7/8 1 1/8 1 1/8 1 1/8 7/8 1 1/8 1 1/8 1 1/8 7/8 1 1/8 1 1/8 1 1/8 - - - - 2 1/8 2 5/8 2 5/8 2 5/8 2 1/8 2 5/8 2 5/8 2 5/8 2 1/8 2 5/8 2 5/8 2 5/8 - - - -

63100-D 7/8 1 1/8 1 1/8 1 1/8 7/8 1 1/8 1 1/8 1 1/8 7/8 1 1/8 1 1/8 1 1/8 - - - - 2 1/8 2 5/8 2 5/8 2 5/8 2 1/8 2 5/8 2 5/8 2 5/8 2 1/8 2 5/8 2 5/8 2 5/8 - - - -

64113-D 7/8 1 1/8 1 1/8 1 1/8 7/8 1 1/8 1 1/8 1 1/8 7/8 7/8 1 1/8 1 1/8 7/8 1 1/8 1 1/8 1 1/8 2 1/8 2 5/8 2 5/8 2 5/8 2 1/8 2 5/8 2 5/8 2 5/8 2 1/8 2 1/8 2 5/8 2 5/8 2 1/8 2 1/8 2 5/8 2 5/8

64124-D 7/8 1 1/8 1 1/8 1 1/8 7/8 1 1/8 1 1/8 1 1/8 7/8 1 1/8 1 1/8 1 1/8 7/8 1 1/8 1 1/8 1 1/8 2 1/8 2 5/8 2 5/8 2 5/8 2 1/8 2 5/8 2 5/8 2 5/8 2 1/8 2 5/8 2 5/8 2 5/8 2 1/8 2 5/8 2 5/8 2 5/8

64132-D 7/8 1 1/8 1 1/8 1 1/8 7/8 1 1/8 1 1/8 1 1/8 7/8 1 1/8 1 1/8 1 1/8 7/8 1 1/8 1 1/8 1 1/8 2 1/8 2 5/8 2 5/8 2 5/8 2 1/8 2 5/8 2 5/8 2 5/8 2 1/8 2 5/8 2 5/8 2 5/8 2 1/8 2 5/8 2 5/8 2 5/8

64140-D 7/8 1 1/8 1 1/8 1 1/8 7/8 1 1/8 1 1/8 1 1/8 7/8 1 1/8 1 1/8 1 1/8 7/8 1 1/8 1 1/8 1 1/8 2 1/8 2 5/8 2 5/8 2 5/8 2 1/8 2 5/8 2 5/8 2 5/8 2 1/8 2 5/8 2 5/8 2 5/8 2 1/8 2 5/8 2 5/8 2 5/8

Table 20
SKM ACUV-D Series Condensing Units are designed for satisfactory operation with single suction line.

1. Suction Line sizing selection recommendation in Table 20 is based on 2F temperature drop.

2. Double suction risers, for applications with systems having large variations in capacity , are recommended to ensure
proper oil flow up and return to compressor.

3. Liquid line sizing selection recommendation in Table 20 is based on 2F temperature drop.

4. Recommended line sizes in Table 19 are for guidance only. For detailed proper piping, consult recognized piping
references like ASHRAE Guide and Data Book for assistance.

5. Equivalent suction and liquid line lengths are shown in Table 19.

SKM is not responsible for faulty or improper design or sizing of refrigerant lines. The above recommendations do not
incorporate necessary slopes, etc. that may be required on horizontal risers, etc.

33
SKM Air Cooled Condensing Units
ACUV-D Series - R-134a

GUIDE SPECIFICATIONS
GENERAL FEATURES REFRIGERANT PIPING
Condensing units shall be composed of compressor(s), fan(s), The refrigerant circuit piping shall be fabricated from ACR grade
Coil(s), refrigerant piping, electrical components & enclosing copper piping, with 1, 2, 3, or 4 refrigeration circuits.The piping
cabinet in one piece. connections shall be terminated with sealed & soldered copper
pipe ends,which give much simplicity & ease to the installation.
Unit shall be factory assembled, internally wired, piping
connections terminated with sealed and soldered copper pipe
ends. Unit shall be shipped with nitrogen holding charge (actual
charging with refrigerant R-134a should be done at site). Unit CASING
shall be capable to operate from 50F (10C) to 125F (52C)
ambient temperature and shall be rated in accordance with Unit casing shall be made of zinc coated galvanized steel
AHRI-365 standard. sheets conforming to JIS-G3302 and ASTM A653 which shall
be phosphatized and then electrostatically dry powder coated
of approx.60 microns to provide an extremely tough, scratch
resistance, excellent anti-corrosive protection that can pass
COIL(S) 1000 hrs in 5% salt spray testing at 95F (35C) and 95% relative
humidity as per ASTM B117.
Coil shall be air cooled with integral sub-cooling circuit,
constructed of seamless copper tubes 3/8" OD mechanically Unit casing shall be provided with access panels for easy service
bonded to wavy Aluminium (Copper) fins with maximum 14 and maintenance of all units parts.
FPI (1.8mm) spacing. Coil shall be tested against leakage by
pressurizing air at 450 psig (3100 kPa) in coil, under water,
cleaned and dehydrated at the factory.
CONTROL PANEL
The unit mounted control panel enclosure shall be fabricated
COMPRESSOR(S) out of heavy gauge sheet steel in phosphatized powder coated
baked finish. The enclosure shall conform to IP54 as per
Compressor shall be of high energy efficiency ratio, fully guidelines in IEC 529. A hinged access door and key-fastener
accessible, semi hermetic reciprocating type equipped with shall be provided for easy access and security. The panel shall
crankcase heater, oil pump, refrigerant gas cooled electric be factory wired in accordance with NEC 430 & 440, labeled,
motor, preset internal relief valve, inherent thermistor motor tagged and features 220V / 240V controls and shall include the
protection, suction and discharge service valves, oil sight following as minimum.
glass and shall be mounted on spring anti vibration mounts to
minimize vibration transmissions. Compressors shall conform All compressors shall be with DOL/part winding starting.
to EN 12900 standards.
Individual compressor and condenser fan motor contactors.
Motor protector circuit breaker for condenser fan motors.
Control circuit breaker.
CONDENSER FAN(S) & MOTOR(S) Unit on/off switch.
The machine shall be furnished with direct driven propeller type Microprocessor control boards.
discharging air upward condenser fans. Fans shall be constructed Control Relays.
of corrosion resistant blades such as heavy gauge aluminum. The Power and control terminal blocks.
fan and drive shall be held in proper alignment. Fan assemblies
shall be provided with heavy gauge, rust resistant steel wire fan
guard. All condenser fans shall be individually, statically, and
dynamically balanced for vibration free operation.

Motors shall be Totally Enclosed Air Over (TEAO), 6 poles, with


class F insulation, minimum IP-55 protection and factory wired
to unit control panel.

34
SKM Air Cooled Condensing Units
ACUV-D Series - R-134a

GUIDE SPECIFICATIONS

MICROPROCESSOR CONTROLLER DISPLAY INFORMATION


Condensing units shall be equipped with a full function Condensing units shall offer an LCD display which will allow the
microprocessor based controller as a standard feature. The operator to access different parameters of the unit. Operator shall
controller shall be factory programmed for the control of AHU be able to view and change the unit parameters. The display
fan motor, compressors and condenser fans. The controller information shall include:
shall come with a built in keypad and display for simple but
meaningful man machine interface. This controller shall provide Status.
complete operational control for the unit and shall have built-in
Outputs.
auto diagnostic capability that can signal normal operation or
alarm conditions as well as shutting down the unit or system if Inputs.
necessary. Alarms.
Set points.
The controller shall come with a loose supplied sleek and
elegant design room unit for installing in the conditioned space. Password.
Communication between unit controller and room unit shall
be through two wire interface. The communication cable shall The intelligent microprocessor based controller shall monitor
be 2 core, twisted pair, unscreened with stranded conductors. all the safeties related to the unit and makes the necessary
Maximum distance between room unit and controller shall be 700 protections, by shutting down the entire unit or the effected circuit.
meters. The room unit shall have a built in sensor for measuring The protections shall include:
the room temperature. It shall transmit room temperature, set
point, unit operating mode, operating schedule etc. to the unit Low suction pressure.
controller. Control of the compressors shall be based on room High discharge pressure.
temperature and the set point, as standard. Control based on Low oil pressure.
duct temperature shall be available if required.
High compressor motor temperature.
Compressor short cycling.
The Main Features of the controller shall be as follows:
Volt free contacts for run status, common fault status, auto mode
Built in LCD display with back light. status and provision for remote on/off shall be available as option.
Built in keypad. In addition, the unit microprocessor shall be able to support the
Battery backed up built in real time clock. major BMS protocols such as BACnet, Modbus & LON as option.
Multiple authorization level to provide tight security for the
control system.
Capacity control based on room temperature or return air
temperature.
Alarm history.
A sleek & elegant design room unit.

35
SKM Air Cooled Condensing Units
ACUV-D Series - R-134a
HEAD OFFICE
P.O Box: 6004
Sharjah, United Arab Emirates
Tel: +971 6 514 3333
Fax: +971 6 514 3300
Email: sales@skmaircon.com
Email: info@skmaircon.com

Spare Parts Division


Email: spareparts.skm@skmaircon.com

Service Centre
Email: aftersales.skm@skmaircon.com

REGIONAL OFFICES
United Arab Emirates
Abu Dhabi Dubai
P.O Box: 27788 P.O Box: 98822
Tel: +971 2 6445223 Tel: +971 4 2940900
Fax: +971 2 6445145 Fax: +971 4 2940029
Email: abudhabisales.skm@skmaircon.com Email: dubaisales.skm@skmaircon.com
Al Ain
Tel: +971 3 7619921 Kuwait
Fax: +971 3 7619941 Dasman
Email: alainsales.skm@skmaircon.com P.O Box: 1215-PC 15463
Tel: +965 2 2492200
Saudi Arabia (Production Facility) Fax: +965 2 2494400
Email: kuwaitsales.skm@skmaircon.com
SKM Air Conditioning Factory
Eastern province
AD Dammam Algeria
2nd industrial city Aissat Idir ( EX-ENMA) City
Abqiq main road Hail Street Bldg1, Flat 2, Dar El Beida Algiers
Tel: +966 3 8123332 / 4 / 5 Tel: +213 21 508197
Fax: +966 3 8123337 / +966 3 8123092 Fax: +213 21 508197
Email: saudifactory.skm@skmaircon.com Email: algeriasales.skm@skmaircon.com

For SKM Distributors visit: 068/2015


Supersedes Bulletin # 068/2014A
068/2015
Supersedes Bulletin # 068/2014A
www.skmaircon.com