Modbus parameterize
- The Modbus can be activated over the coordinate Z01.
- The Modbus - ID is adjusted over the coordinate Z07
- The Modbus - Register - Offset (MRO) is adjusted over the coordinate Z08 (default is 0)
The MRO applies with reading and write operations.
The EC-24 has a passive RS485 interface, i.e. the interface must be supplied externally.
(see manual)
01 Illegal Function
02 Illegal Data Address (Register not available)
03 Illegal Data Value (Register not recordable or Value wrong)
Data type Register Value Byte Byte Byte Byte Byte Byte Byte Byte Byte Byte
1 2 3 4 5 6 7 8 9 10
Data type (float, text ...) can be read or rather written only completely
float : 2 Register
long integer : 2 Register
integer : 1 Register
Text : 5 Register
Monthly Storage : 15 Register
Maximally 100 registers (in an instruction) can be read and/or rather written.
Counts are supplied as long - value (without comma), the valency of the counter can be sampled
over the Terz mode (register 2310).