WIND ANALYSIS.
Section Sheet no./rev.
1
CSEC (U) LTD
Calc. by Date Chk'd by Date App'd by Date
P.O BOX 21879, KAMPALA.
Ph. +256(0)392 947 199 W 7/12/2017
31820
10000
Building data
Type of roof Hipped
Length of building L = 30000 mm
Width of building W = 10000 mm
Height to eaves H = 30000 mm
Pitch of main slope 0 = 20.0 deg
Pitch of gable slope 90 = 20.0 deg
Total height h = 31820 mm
Basic values
Fundamental basic wind velocity vb,0 = 24.2 m/s
Season factor cseason = 1.00
Direction factor cdir = 1.00
Shape parameter K K = 0.2
Exponent n n = 0.5
Probability factor cprob = [(1 - K ln(-ln(1-p)))/(1 - K ln(-ln(0.98)))]n = 1.00
Basic wind velocity (Exp. 4.1) vb = cdir cseason vb,0 cprob = 24.2 m/s
Reference mean velocity pressure qb = 0.5 vb2 = 0.365 kN/m2
Orography
Orography factor not significant co = 1.0
Terrain category II
Displacement height (sheltering effect excluded) hdis = 0mm
Project Job Ref.
WIND ANALYSIS.
Section Sheet no./rev.
2
CSEC (U) LTD
Calc. by Date Chk'd by Date App'd by Date
P.O BOX 21879, KAMPALA.
Ph. +256(0)392 947 199 W 7/12/2017
The velocity pressure for the windward face of the building with a 0 degree wind is to be considered as 1 part as
the height h is less than b (cl.7.2.2)
The velocity pressure for the windward face of the building with a 90 degree wind is to be considered as 3 parts as
the height h is greater than 2b (cl.7.2.2)
Peak velocity pressure - windward wall - Wind 0 deg
Reference height (at which q is sought) z = 30000mm
Displacement height (sheltering effects excluded) hdis = 0 mm
Roughness length (Table 4.1) z0 = 50 mm
Roughness length (Category II) z0,II = 50 mm
Minimum height (Table 4.1) zmin = 2000 mm
Maximum height zmax = 200000 mm
Terrain factor kr = 0.19 (z0 / z0,II)0.07 = 0.19
Roughness factor cr = kr ln((z - hdis) / z0) = 1.22
Mean wind vm = cr co vb = 29.4 m/s
Turbulence factor kI = 1.0
Turbulence intensity Iv = kI / (co ln((z - hdis) / z0)) = 0.156
Peak velocity pressure qp = (1 + 7 Iv) 0.5 vm2 = 1.13 kN/m2
Structural factor
Structural factor csCd = 0.927
Peak velocity pressure - windward wall (lower part) - Wind 90 deg
Reference height (at which q is sought) z = 10000mm
Displacement height (sheltering effects excluded) hdis = 0 mm
Terrain factor kr = 0.19 (z0 / z0,II)0.07 = 0.19
Roughness factor cr = kr ln((z - hdis) / z0) = 1.01
Mean wind vm = cr co vb = 24.3 m/s
Turbulence factor kI = 1.0
Turbulence intensity Iv = kI / (co ln((z - hdis) / z0)) = 0.189
Peak velocity pressure qp = (1 + 7 Iv) 0.5 vm2 = 0.86 kN/m2
Peak velocity pressure - windward wall, (middle part) - Wind 90 deg
Reference height (at which q is sought) z = 20000mm
Displacement height (sheltering effects excluded) hdis = 0 mm
Terrain factor kr = 0.19 (z0 / z0,II)0.07 = 0.19
Roughness factor cr = kr ln((z - hdis) / z0) = 1.14
Mean wind vm = cr co vb = 27.5 m/s
Turbulence factor kI = 1.0
Turbulence intensity Iv = kI / (co ln((z - hdis) / z0)) = 0.167
Peak velocity pressure qp = (1 + 7 Iv) 0.5 vm2 = 1.03 kN/m2
Peak velocity pressure - windward wall (upper part), other walls - Wind 90 deg
Reference height (at which q is sought) z = 30000mm
Displacement height (sheltering effects excluded) hdis = 0 mm
Terrain factor kr = 0.19 (z0 / z0,II)0.07 = 0.19
Roughness factor cr = kr ln((z - hdis) / z0) = 1.22
Mean wind vm = cr co vb = 29.4 m/s
Turbulence factor kI = 1.0
Turbulence intensity Iv = kI / (co ln((z - hdis) / z0)) = 0.156
Peak velocity pressure qp = (1 + 7 Iv) 0.5 vm2 = 1.13 kN/m2
Project Job Ref.
WIND ANALYSIS.
Section Sheet no./rev.
3
CSEC (U) LTD
Calc. by Date Chk'd by Date App'd by Date
P.O BOX 21879, KAMPALA.
Ph. +256(0)392 947 199 W 7/12/2017
WIND ANALYSIS.
Section Sheet no./rev.
4
CSEC (U) LTD
Calc. by Date Chk'd by Date App'd by Date
P.O BOX 21879, KAMPALA.
Ph. +256(0)392 947 199 W 7/12/2017
WIND ANALYSIS.
Section Sheet no./rev.
5
CSEC (U) LTD
Calc. by Date Chk'd by Date App'd by Date
P.O BOX 21879, KAMPALA.
Ph. +256(0)392 947 199 W 7/12/2017
L
L
6000
D E
A B
J
2500
8000
2500
J
L
2500
F
1000
Project Job Ref.
WIND ANALYSIS.
Section Sheet no./rev.
6
CSEC (U) LTD
Calc. by Date Chk'd by Date App'd by Date
P.O BOX 21879, KAMPALA.
Ph. +256(0)392 947 199 W 7/12/2017