TIA Portal WinCC RT Advanced OPC DA Server (Sep 2015)

This option is only available on Panel PCs like IPC477D, on MP Panels,


but not on KTP Panels.
Im using OPC test-client from Rockwell Automation, but you can use
any other OPC Client
take a look here for OPC Clients
http://www.opcconnect.com/freecli.php
Here a short and simple how-to video:
https://www.youtube.com/watch?v=kgMBwj4EE0w
To activate TIA Portal WinCC RT Advanced OPC DA Server just follow
this steps:
1. Open TIA Portal
2. Navigate to Runtime Settings and open it

3. Select services
4. Select checkbox Operate as OPC Server and choose OPC DCOM
Server

5. Now just start the runtime (or transfer it to your Panel) and
connect to OPC Server via OPC Client.

OPC, Siemens OPC, OPC Client, OPC Communication, OPC


Server, TIA, TIA Portal, WinCC Advanced