DESIGN OF R.C.C. OPEN DRAIN ( clear height= 1.80 m, overall width=2.

46m)

f f

a
b

e
TYPICAL CROSS-SECTION

1.0 Design Data

1.1 Preliminary Dimensions :

Clear Span 'b' = 2.00 m


Clear Height 'a' = 1.80 m
Wall Thickness 'f' = 0.230 m
Base Thickness 'e' = 0.230 m
Overall height 'H' = 2.03 m
Overall width 'W' = 2.46 m

1.2 Material Properties

Density of backfill soil s = 20 kN/m3


Density of Concrete c = 25 kN/m3
S.B.C. of Soil qs = 50 kN/m2
Angle of Internal friction for back fill = 30 degree
friction angle between wall & backfill = 20 degree
Angle of Inclination of back of wall = 0 degree
Slope of backfill with horizontal i 0 degree
Permissible Settlement = 40.00 mm
Height of surcharge = 1.20 m

1.3 Design Parameters

Grade of Concrete = M25


Grade of Steel = Fe500
Clear Cover for earth face structural component = 50 mm
Clear Cover for inside face structural component = 50 mm
Clear Cover for bottom slab = 50 mm
Characteristic comp. strength of Concrete (fck) = 25.00 N/mm2
Yield strength of Steel ( fy ) = 500 N/mm2

2.0 Load Calculation

2.10 Dead Load of the Structure 'DL'

U.D.L on vertical wall = 10.35 kN/m


U.D.L on base slab = 5.75 kN/m

2.20 Dead Load on Bottom Slab due to Soil Silting

Thickness of earth fill due to silting = 0.3 m


Load (UDL) on bottom slab = 0.3 * 20 = 6 KN/m

2.30 Horizontal Earth Pressure

Critical loading condition will be the situation when box will be subjected to earth pressure
due to saturated backfill and there will be no water inside the box.
cos2 ( )
Co-efficient of Active Earth Pressure= (Ka)static 2
sin( )sin( i)
cos cos( )1
2

cos( )cos( i)
= 0.297

Earth-pressure at a depth 'h' from the top of vertical wall=Ka. s.h kN/sq.m

Horizontal force on wall due to Earth pressure at variuos level is shown in the load diagram below.

2.40 Live Load Surcharge


Equivalent height = 1.20 m
Uniform Intensity of loading = = 7.13 KN/m2

3.0 Structural Analysis


The structure is analysed for variuos load acting on it using structural-design software ''STAAD.ProV8i "
modelling it along the center lines of walls and slab. Spring type supports are adopted which are applied
various nodes along bottom slab. Stiffness of the support are calculated based on modulus of subgra
reaction.
10.35 10.35

2.23

11.75

10.69 10.69
11.38 7.13 7.13 11.38
LOAD DIAGRAM

4 3

8 7
5 9 10 11 12 13 14 6
1 2

Figure: STADD Discretisation of BOX Geometry.

Spring Constant= 1250 kN/m2 per m width


Nos. of springs provided= 10

Spring constant at end supports 1,2= 71.875 kN/m per m width


Spring constant at penultimate supports 5,6= 250.4464286 kN/m per m width
Spring constant atintermediate supports 9 to 14= 357.1428571 kN/m per m width

4. Design of Drain

a) Design of Vertical wall


Factored bending moment Mu(From analysis) = 30.1KN-m

Effective depth required d = Mu/0.133fckb = 95.15mm

Over all depth provided = 230.00mm


Effective depth provided(Assuming 50mm cover) d = 172.0mm

Mu/bd2 = 1.017

From table 3 of SP 16,percentage of steel required = 0.255

Area of steel required = 439sqmm

Hence provide 10mm dia HYSD bars@ 150mm c/c spacing

Hence Ast provided = 523sqmm

Check for shear:-

The critical section for beam shear is at distance of 'd' from the face of the support

Hence,the factored design shear force V Fd = 36.80KN


at a distance 'd' from the face of the support

Nominal shear stress Tv = 0.210N/sqmm <2.8 N/sqmm


(As per Table 20 of 1S 456)

Hence,the section is safe from shear point of view

Assumed percentage area of the steel reinforcement = 0.30%

The design shear strength of concrete for the above steel percentage from
Table 19 of IS 456 is
0.328

0.328>0.21

Hence,the depth provided is safe from beam shear point of view

Hence,no shear reinforcement is required.

Provide temperature re inforcement @ 0.12%

Area required = 276.00sqmm

Provide 1/3rd of above reinforcement on earthen side = 92.00sqmm


Provide 8mm dia @ 200mm c/c on earthen side

Provide 2/3rd of above reinforcement on other side = 184.00sqmm

Provide 8mm dia @ 150mm c/c on other side

Provide 10mm bars at 300mm c/c vertically on the inner face to support horizontal rods

b) Design of base slab


Factored bending moment Mu(From analysis) = 30.5KN-m

Effective depth required d = Mu/0.133fckb = 95.78mm

Over all depth provided = 230.00mm

Effective depth provided(Assuming 50mm cover) d = 172.0mm

Mu/bd2 = 1.031

From table 3 of SP 16,percentage of steel required = 0.255

Area of steel required = 439sqmm

Hence provide 10mm dia HYSD bars@ 150mm c/c spacing at bottom

Hence Ast provided = 523sqmm

Check for shear:-

The critical section for beam shear is at distance of 'd' from the face of the support

Hence,the factored design shear force V Fd = 13.00KN


at a distance 'd' from the face of the support

Nominal shear stress Tv = 0.080N/sqmm <2.8 N/sqmm


(As per Table 20 of 1S 456)

Hence,the section is safe from shear point of view

Assumed percentage area of the steel reinforcement = 0.30%


The design shear strength of concrete for the above steel percentage from
Table 19 of IS 456 is
0.328

0.328>0.08

Hence,the depth provided is safe from beam shear point of view

Hence,no shear reinforcement is required.

Provide temperature re inforcement @ 0.12%

Area required = 276.00sqmm

Provide 10mm dia @ 250mm c/c on top

Hence Ast provided = 314sqmm

Provide distribution steel of 10mm @ 300mm c/c in other direction both top and bottom

Design dimensions and reinforcments :

Clear Reinforcemnt
thick. in
(span x Member
mm earth face water face distribution bar. b
height)
wall 230 T10 @ 150 c/c T10 @300 c/c T8 @ 200 & 150
2.00 x 1.80
base-slab 230 T10 @ 150 c/c T10 @ 250 c/c T10 @300 c/c
=2.46m)
e

2
sin( i)

cos( i)

m below.

STAAD.ProV8i " by
hich are applied at
dulus of subgrade
distribution bar. b/f

8 @ 200 & 150 c/c


T10 @300 c/c