I) Design Parametres:-
As per Table 1 of IS:2911(Part III)-1980,safe load carrying capacity 375mm dia DUR piles in medium compact
sandy soils or clayey soils of medium consistency is = 360.00KN
As per clause 5.2.7.2 of IS:2911(Part III)-1980,the minimum spacing between the centre to centre of bored DUR
piles should not be less than 1.5Du.
Further as per clause 5.2.8.1,the load carrying capacity of each individual pile should be reduced by 10% due to
group action.
Assuming water table in the pile bulb,the safe load carrying capacity is to be reduced by 25% as per the
clause B-1.6 of IS 2911(Part III)-1980.
Providing five piles,the load carrying capacity of the pile cap will be
Reducing 10% per each pile due group action,the net safe load carrying
capacity
Y
2.67
Y
2.67
375 DUR piles
2.67
x x
1.99
207.43mm
209.98mm
The critical section of one way shear is at a distance of 'd' from the face of the column
As per clause 40.5.1 of IS 456:2000,the shear strength can be increased by 2d/a v times for the sections located
at a distance closer than 2d from concentrated load or face of support,where a v is the shear span
2d/av = 2.36
0.677 >0.426
Though,the truss action is not pre-dominant,the tensile reinforcement should be checked for horizontal tensile force
resulting from truss action,because av/d ratio is not more than 2.
H = Pu/30Ld[3L2-b2] = 252.31KN
The tensile reinforcement provided is more than the above value.Hence O.K
d) Bursting steel:-
1465.24KN
146.52KN
1611.76KN
1.125
mm dia DUR piles in medium compact
270.00KN
1350.00KN
1215.00KN
Hence O.K
.67
.67
2.67
2.670m
2.670m
1.410m
0.650m
0.565m
0.480m
381.99KN-m
567.00mm
28.64mm
1582.31sqmm
7.87Nos
12Nos
2411.52sqmm
0.159
406.16KN-m
567.00mm
30.50mm
1684.80sqmm
8.38Nos
12Nos
2411.52sqmm
0.159
of the column
d by 2d/a v times for the sections located
he shear span
580.02sqmm
e value.Hence O.K
DESIGN OF PILE CAPS----PC2(1,4,5,6,7,8,9,12,22,31,33,34,35,36,37,38)
I) Design Parametres:-
As per Table 1 of IS:2911(Part III)-1980,safe load carrying capacity 375mm dia DUR piles in medium compact
sandy soils or clayey soils of medium consistency is = 360.00KN
As per clause 5.2.7.2 of IS:2911(Part III)-1980,the minimum spacing between the centre to centre of bored DUR
piles should not be less than 1.5Du.
Further as per clause 5.2.8.1,the load carrying capacity of each individual pile should be reduced by 10% due to
group action.
Assuming water table in the pile bulb,the safe load carrying capacity is to be reduced by 25% as per the
clause B-1.6 of IS 2911(Part III)-1980.
Providing four piles,the load carrying capacity of the pile cap will be
Reducing 10% per each pile due group action,the net safe load carrying
capacity
Y
Y
2.09
x x
1.41
2.09
232.87mm
243.57mm
The critical section of one way shear is at a distance of 'd' from the face of the column
As per clause 40.5.1 of IS 456:2000,the shear strength can be increased by 2d/a v times for the sections located
at a distance closer than 2d from concentrated load or face of support,where a v is the shear span
2d/av = 2.55
0.887 >0.503
Though,the truss action is not pre-dominant,the tensile reinforcement should be checked for horizontal tensile force
resulting from truss action,because av/d ratio is not more than 2.
H = Pu/24Ld[3L2-b2] = 242.31KN
The tensile reinforcement provided is more than the above value.Hence O.K
d) Bursting steel:-
1234.58KN
123.46KN
1358.04KN
270.00KN
1080.00KN
972.00KN
Hence O.K
2.09
2.090m
2.090m
1.410m
0.600m
0.515m
0.405m
376.86KN-m
517.00mm
40.06mm
1732.08sqmm
8.62Nos
12Nos
2411.52sqmm
0.223
427.78KN-m
517.00mm
45.68mm
1975.44sqmm
9.83Nos
12Nos
2411.52sqmm
0.223
of the column
d by 2d/a v times for the sections located
he shear span
557.03sqmm
e value.Hence O.K
DESIGN OF PILE CAPS----PC4(3,19,21,32)
I) Design Parametres:-
As per Table 1 of IS:2911(Part III)-1980,safe load carrying capacity 450mm dia DUR piles in medium compact
sandy soils or clayey soils of medium consistency for 4.50m depth is = 525.00KN
Assuming water table in the pile bulb,the safe load carrying capacity is to be reduced by 25% as per the
clause B-1.6 of IS 2911(Part III)-1980.
Providing two piles,the load carrying capacity of the pile cap will be 787.50KN
Reducing 10% per each pile due to group action,the net safe load carrying 708.75KN
capacity
Hence,ultimate load carrying capacity of the pile cap = 1063.13KN > Total load
Hence O.K
PC2
450mm DUR
2.44
1.69
1.6875
Column
0.3x0.375
0.75
As such,the dimensions of the pile cap of as given below:-
371.45mm
However assume 750mm overall depth,then the effective depth comes to 690.00mm
Hence No.of 20mm dia bars to be provided within pile diametre = 5Nos
The critical section of one way shear is at a distance of 'd' from the face of the column
The design shear strength of concrete for the above steel percentage from
As per clause 40.5.1 of IS 456:2000,the shear strength can be increased by 2d/a v times for the sections located
at a distance closer than 2d from concentrated load or face of support,where a v is the shear span
2d/av = 2.1
0.809 >0.805
Though,the truss action is not pre-dominant,the tensile reinforcement should be checked for horizontal tensile force ' H '
resulting from truss action,because av/d ratio is not more than 2.
Hd=(Pu/2)[L/2-a/4]
H = Pu/8d[2L-a] = 498.66KN
Area of steel required to resist the above above tensile force Ast = 1146.34sqmm
The tensile reinforcement provided is more than the above value.Hence O.K
d) Bursting steel:-
I) Design Parametres:-
As per Table 1 of IS:2911(Part III)-1980,safe load carrying capacity 375mm dia DUR piles in medium compact
sandy soils or clayey soils of medium consistency is = 360.00KN
As per clause 5.2.7.2 of IS:2911(Part III)-1980,the minimum spacing between the centre to centre of bored DUR
piles should not be less than 1.5Du.
Further as per clause 5.2.8.1,the load carrying capacity of each individual pile should be reduced by 10% due to
group action.
Assuming water table in the pile bulb,the safe load carrying capacity is to be reduced by 25% as per the
clause B-1.6 of IS 2911(Part III)-1980.
Providing THREE piles,the load carrying capacity of the pile cap will be
PC3
Y
PC3
Y
1.91
X X
0.70
2.09
199.03mm
212.58mm
The critical section of one way shear is at a distance of 'd' from the face of the column
The design shear strength of concrete for the above steel percentage from
As per clause 40.5.1 of IS 456:2000,the shear strength can be increased by 2d/a v times for the sections located
at a distance closer than 2d from concentrated load or face of support,where a v is the shear span
2d/av = 2
0.646 >0.359
Though,the truss action is not pre-dominant,the tensile reinforcement should be checked for horizontal tensile force
resulting from truss action,because av/d ratio is not more than 2.
H = Pu/24Ld[3L2-b2] = 189.65KN
The tensile reinforcement provided is more than the above value.Hence O.K
d) Bursting steel:-
966.29KN
96.63KN
1062.92KN
270.00KN
810.00KN
729.00KN
Hence O.K
5mm DUR
2.090m
1.910m
1.410m
0.600m
0.515m
0.518m
251.56KN-m
517.00mm
28.99mm
1145.55sqmm
5.70Nos
10Nos
2009.60sqmm
0.204
290.53KN-m
286.99KN-m
517.00mm
33.19mm
1311.47sqmm
6.53Nos
10Nos
2009.60sqmm
0.204
7 8.5 2.3495
of the column
10 12 1131.429
6 16 1206.857
1.75
0.55 1.125
-3.5 -4.5
0.55
435.98sqmm
e value.Hence O.K
DESIGN OF PILE CAPS----PC5(10,14,15,16,17,18,39)
I) Design Parametres:-
As per Table 1 of IS:2911(Part III)-1980,safe load carrying capacity 375mm dia DUR piles in medium compact
sandy soils or clayey soils of medium consistency for 3.75m depth is = 360.00KN
Assuming water table in the pile bulb,the safe load carrying capacity is to be reduced by 25% as per the
clause B-1.6 of IS 2911(Part III)-1980.
Providing two piles,the load carrying capacity of the pile cap will be
Reducing 10% per each pile due to group action,the net safe load carrying
capacity
375 DUR
2.09
2.09
0.70
As such,the dimensions of the pile cap of as given below:-
307.83mm
The critical section of one way shear is at a distance of 'd' from the face of the column
The design shear strength of concrete for the above steel percentage from
As per clause 40.5.1 of IS 456:2000,the shear strength can be increased by 2d/a v times for the sections locate
at a distance closer than 2d from concentrated load or face of support,where a v is the shear span
2d/av = 2.47
0.976 >0.732
Though,the truss action is not pre-dominant,the tensile reinforcement should be checked for horizontal tensile
resulting from truss action,because av/d ratio is not more than 2.
Hd=(Pu/2)[L/2-a/4]
H = Pu/8d[2L-a] = 344.60KN
The tensile reinforcement provided is more than the above value.Hence O.K
d) Bursting steel:-
656.02KN
65.60KN
721.62KN
540.00KN
486.00KN
Hence O.K
2.09m
0.70m
1.41m
0.518m
220.55KN-m
640.00mm
56.82mm
822.89sqmm
4.09Nos
5Nos
1004.80sqmm
0.224
v
times for the sections located
792.18sqmm
.Hence O.K
#DIV/0!
DESIGN OF TWO WAY SLAB:-
Design Parametres:-
Unit weight of RCC = 25KN/cum
Concrete mix : M20
Steel : Fe415
Cover to Reinforcement : 25mm
Characteristic compressive strength of concrete = 20N/sqmm
Yield strength of steel = 415N/sqmm
Item Slab panel Description
S1(End Panel)--Two S2(Portico Panel)-- S3(Interior S4(Interior
adjacent edges Three edges Panel)--One Panel)--One
discontinuous discontinuous(One short edge short edge
short edge discontinuous discontinuous
continuous)
8 16 1609.143
2 12 226.2857
6 16 1206.857
6 25 2946.429
2 12 226.2857
6 16 1206.857
12 12 1357.714
8 16 1609.143
4 20 1257.143
8 16 1609.143
26 12 2941.714
12 16 2413.714
10 20 3142.857
6 16 1206.857
10 12 1131.429